Download as pdf or txt
Download as pdf or txt
You are on page 1of 40

GIRISH HIRANANDANI

RESIDENTIAL VILLA FOR MR.


GIRISH HIRANANDANI
B+G+1

PRINTING DATE/TIME 12/25/2016 11:57:14 AM architects engineers designers planners

SUBMISSION : 100 % CD SUBMISSION

SUBMISSION DATE: 27/12/2016

LOCATION : DM PLOT 6316407, EMAAR PLOT PA-02 R.074,


DUBAI HILLS ESTATE
SHEET NO. : M0-GE-000
1 2 3 4 5 6 7
KEYPLAN

100% DD LOD
REVISION
SHEET NUMBER SHEET NAME NO. DATE
M0-GE-000 COVER SHEET B 27/12/2016
M0-GE-001 MECHANICAL LIST OF DRAWINGS B 27/12/2016
M0-GE-002 MECHANICAL ABBREVIATIONS B 27/12/2016
M0-GE-003 MECHANICAL LEGENDS B 27/12/2016

D
M0-GE-004 HVAC NOTES B 27/12/2016
D

M0-GE-005 WATER SUPPLY NOTES B 27/12/2016


M0-GE-006 DRAINAGE NOTES B 27/12/2016
M0-GE-101 HVAC DETAILS 1 B 27/12/2016
M0-GE-102 HVAC DETAILS 2 B 27/12/2016
M0-GE-103 HVAC DETAILS 3 B 27/12/2016
M0-GE-104 HVAC DETAILS 4 B 27/12/2016
M0-GE-105 HVAC DETAILS 5 B 27/12/2016
M0-GE-106 HVAC DETAILS 6 B 27/12/2016
M0-GE-107 DRAINAGE DETAILS 1 B 27/12/2016
M0-GE-108 DRAINAGE DETAILS 2 B 27/12/2016
M0-GE-109 DRAINAGE DETAILS 3 B 27/12/2016
M0-GE-110 WATER SUPPLY DETAILS 1 B 27/12/2016
M0-GE-111 WATER SUPPLY DETAILS 2 B 27/12/2016
M0-GE-112 WATER SUPPLY DETAILS 3 B 27/12/2016
M0-GE-113 FIREFIGHTING DETAILS B 27/12/2016
M1-AC-101 AC LAYOUT - BASEMENT FLOOR PLAN B 27/12/2016 CONSULTANT
M1-AC-102 AC LAYOUT - GROUND FLOOR PLAN B 27/12/2016
M1-AC-103 AC LAYOUT - FIRST FLOOR PLAN B 27/12/2016
M1-AC-104 AC LAYOUT - ROOF PLAN B 27/12/2016
M1-AC-105 HVAC EQUIPMENT SCHEDULE B 27/12/2016 architects engineers designers planners
M3-DR-101 DRAINAGE LAYOUT - BASEMENT FLOOR PLAN B 27/12/2016 TEL +971 4 332 4455 FAX +971 4 332 2113
M4-WS-101 WATER SUPPLY LAYOUT - BASEMENT FLOOR PLAN B 27/12/2016 po box 73033 dubai web site www.naga.ae
M6-FP-101 FIRE PROTECTION LAYOUT - BASEMENT FLOOR PLAN B 27/12/2016
M6-FP-102 FIRE PROTECTION LAYOUT - GROUND FLOOR PLAN B 27/12/2016
M6-FP-103 FIRE PROTECTION LAYOUT - FIRST FLOOR B 27/12/2016

C
C

RESIDENTIAL VILLA FOR


MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE

''ISSUE FOR'' ''DESCRIPTION''


RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
R FOR RECORD DOCUMENTS
P PRELIMINARY TD TENDER DOCUMENTS
M MUNICIPALITY REVIEW

B
B

B 27/12/2016 100 % CD FA NAGA


SUBMISSION
A 12/05/2016 100 % DD FA NAGA
SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED

ISSUE

PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE
DRAWN BY M.K.

CHECKED BY I.S.
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:57:17 AM

A
A

M0-GE-001

SHEET TITLE

MECHANICAL LIST OF
DRAWINGS
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

SYMBOLS ABBREVIATIONS SYMBOLS ABBREVIATIONS PLUMBING SYMBOLS FIREFIGHTING SYMBOLS PIPING FITTINGS & VALVES SYMBOLS
SYMBOLS ABBREVIATIONS SYMBOLS ABBREVIATIONS SYMBOLS ABBREVIATIONS
EXHAUST CEILING DIFFUSER
BACK DRAFT DAMPER
EXPANSION TANK -VERTICAL DRY CHEMICAL FIRE EXTINGUISHER BALANCE VALVE

SUPPLY SQUARE DIFFUSER VOLUME DAMPER EXPANSION TANK -INLINE CO2 FIRE EXTINGUISHER BALL VALVE

WATER EXTINGUISHER CHECK VALVE


RETURN SQUARE DIFFUSER BELL MOUTH PUMP-INLINE VERTICAL FB FIRE BLANKET LEVEL VALVE

SUPPLY FLOW BAR DIFFUSER GATE VALVE


DUCT END CAP

D
D

GLOBE VALVE
SOLAR PANEL
SUPPLY REGISTER T
THERMOSTAT MULTI PURPOSE VALVE

PRESSURE REGULATING VALVE


EXHAUST/RETURNSIDE REGISTER DOOR UNDER CUT
GULLY TRAP
HOSE BIBE
FLEXIBLE DUCT BELL MOUTH PRESSURE GAUGE
MANHOLE
WATER HAMER ARRESTOR
LOUVER DUCT TRANSITION
GAS CYLINDER WATER METER

CONCEALED INDOOR UNIT DUCT RISER

CONDENSING UNIT RECTANGULAR DUCT ELBOW


CONSULTANT
RETURN FLOW BAR DIFFUSER

EXHAUST FLOW BAR DIFFUSER architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

C
C

RESIDENTIAL VILLA FOR


MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE

''ISSUE FOR'' ''DESCRIPTION''


RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
R FOR RECORD DOCUMENTS
P PRELIMINARY TD TENDER DOCUMENTS
M MUNICIPALITY REVIEW

B
B

B 27/12/2016 100 % CD FA NAGA


SUBMISSION
A 12/05/2016 100 % DD FA NAGA
SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED

ISSUE

PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE N.T.S.
DRAWN BY MF

CHECKED BY EM
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:57:19 AM

A
A

M0-GE-002

SHEET TITLE

MECHANICAL
ABBREVIATIONS
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

LEGENDS DESCRIPTIONS LEGENDS DESCRIPTIONS (CONT.) FIRE & PLUMBING LEGENDS FIRE & PLUMBING LEGENDS (CONT.)

LEGENDS DESCRIPTION LEGENDS DESCRIPTION


SAD SUPPLY AIR DUCT RR RETURN REGISTER
LPG LIQUEFIED PETROLEUM GAS WS WATER SUPPLY

RAD RETURN AIR DUCT ER EXHAUST REGISTER

D
lb POUND DR DRAIN
D

FAD FRESH AIR DUCT HVAC HEATING, VENTILATING, AND gm/hr GRAMS/HOUR BD BIDET
AIR
CONDITIONING
PRS PRESSURE REGULATING STATION BP BOOSTER PUMP
EAD EXHAUST AIR DUCT RCD RETURN CEILING DIFFUSER

CNDS CONDENSATE DRAIN CWS COLD WATER SUPPLY


DX DIRECT EXPANSION
L/S LITER PER SECOND
CE CLEANING EYE HWS HOT WATER SUPPLY
T THERMOSTAT
°C DEGREE CELSIUS
CI CAST IRON DW DISH WASHER
F/A FROM ABOVE
F DEGREE FAHRENHEIT CO CLEAN OUT GV GATE VALVE
CONSULTANT
T/B TO BELOW
PT PRESSURE TANK DC DRAIN COCK CV CHECK VALVE

C/W COMPLETE WITH FD FLOOR DRAIN HWR HOT WATER RISER


BV BALANCE VALVE architects engineers designers planners
TEL +971 4 332 4455 FAX +971 4 332 2113
RD ROOF DRAIN HWRR HOT WATER RETURN RISER po box 73033 dubai web site www.naga.ae
FCU FAN COIL UNIT UC DOOR UNDER CUT

GT GULLY TRAP PRV PRESSURE REDUCING VALVE


RC REMOTE CONTROL
OU OUTDOOR CONDENSING UNIT
IL INVERT LEVEL UR URINAL
G.V. GATE VALVE
DG DOOR GRILL

C
LR LOW RISE WC WATER CLOSET
C

ECD EXHAUST CEILING DIFFUSER HR HIGH RISE CWP COLD WATER PIPE
IU INDOOR UNIT

DBT DRY BULB TEMPERATURE MH MANHOLE HWP HOT WATER PIPE

RWP RAIN WATER PIPE LAV LAVATORY


WBT WET BULB TEMPERATURE

CNDSP CONDENSATE PIPE HB HOSE BIB


CNDP CONDENSER WATER PIPES RESIDENTIAL VILLA FOR
SP SOIL PIPE FE FIRE EXTINGUISHER
MR. GIRISH HIRANANDANI
EQPM EQUIPMENT
G GAS DETECTOR DM PLOT 6316407, EMAAR PLOT PA-02
WP WASTE PIPE
R.074, DUBAI HILLS ESTATE

VD VOLUME DAMPER SV SOLONOID VALVE


VP VENT PIPE

IV ISOLATING VALVE ''ISSUE FOR'' ''DESCRIPTION''


RWS RAIN WATER STACK RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
SCD SUPPLY CEILING DIFFUSER
FA FOR APPROVAL DD DESIGN DEVELOPMENT
PRV PRESSURE REGULATING VALVE PS PROGRESS SET CD CONSTRUCTION
WAS WASTE STACK
R FOR RECORD DOCUMENTS
SR SUPPLY REGISTER P PRELIMINARY TD TENDER DOCUMENTS
NC NORMALLY CLOSE M MUNICIPALITY REVIEW
SS SOIL STACK

SFBD SUPPLY FLOW BAR DIFFUSER


VS VENT STACK F/A FROM ABOVE

RFBD RETURN FLOW BAR DIFFUSER F/B FROM BELOW


RVC ROOF VENT COWL

B
B

EFBD EXHAUST FLOW BAR DIFFUSER T/A TO ABOVE


IC INSPECTION CHAMBER

T/B TO BELOW
W/O WALL OPENING BD BALCONY DRAIN

H/L HIGH LEVEL


HL HIGH LEVEL

B 27/12/2016 100 % CD FA NAGA


PG PRESSURE GAUGE
LL LOW LEVEL SUBMISSION
A 12/05/2016 100 % DD FA NAGA
IV ISOLATING VALVE WITH LOCK SUBMISSION
FMP FORCED MAIN PIPE REV. DATE DESCRIPTION FOR BY
ISSUED
BRV BALANCE REGULATING VALVE
DN DOWN
ISSUE
WHA WATER HAMMER ARRESTOR
AAV AUTOMATIC AIR VENT PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE N.T.S.
DRAWN BY MF

CHECKED BY EM
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:57:22 AM

A
A

M0-GE-003

SHEET TITLE

MECHANICAL LEGENDS

1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
GENERAL HVAC NOTES:

1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE CO-ORDINATION OF ALL SERVICES.

2. All DUCT, GRILLE AND PIPES SIZES ARE IN MM.

3. ALL WORKMANSHIP AND MATERIAL SHALL COMPLY TO THE RELEVANT B.S STANDARDS, ASHRAE, NFPA AND THE SPECIFICATION.

4. ALL DUCT AND PIPE SUPPORTS TO BE DESIGNED TO WITHSTAND LATERAL MOVEMENTS AND LONGITUDINAL MOVEMENTS.

5. ALL EQUIPMENT, DUCT WORK, DAMPERS, SWITCHES, WIRES ETC. SHALL BE IDENTIFIED BY MARKERS/TAGS AS REQUIRED BY ENGINEER AND SPECIFICATION.

6. ALL THERMOSTAT IN PUBLIC AND COMMON AREA SHALL BE HOUSED IN LOCKABLE TRANSPARENT ENCLOSURE.

7. ANY DISCREPANCY ARE TO BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND RESOLVED PRIOR TO FINALIZATION OF CONTRACT. ANY VARIATION DUE TO NOT DOING SO WILL NOT BE ENTERTAINED.

D
D

8. SHOWN LOCATION OF THERMOSTATS ARE TENTATIVE, FINAL LOCATION SHALL BE COORDINATED WITH ARCHITECT DURING CONSTRUCTION STAGE.

9. WHERE MORE THAN ONE SERVICE (ELECTRICAL CABLES, DUCTS, PIPES) IS ROUTED THROUGH THE SAME AREA, THEY SHALL BE SUPPORTED BY STRUCTURAL FRAME SUPPORT WITH SERVICES STACKED ONE ABOVE THE OTHER.

10. CONTRACTOR TO COORDINATE WITH STRUCTURAL DRAWINGS FOR OPENINGS AND PENETRATORS. SUBMIT BUILDING WORK SHOP DRAWING FOR STRUCTURAL ENGINEER APPROVAL. ANY OPENING REQUIRED OTHER THAN THAT SHOWN ON STRUCTURAL DRAWING SHALL BE APPROVED BY STRUCTURAL ENGINEER.

11. ALL ELECTRICAL LOADS SHOWN ON ELECTRICAL TENDER DRAWINGS/SPECIFICATION TO BE CHECKED AND CONFIRMED AND ADJUSTED AS DEEMED NECESSARY.

12. SUITABLE APPROVED SLEEVES SHALL BE PROVIDED WHERE BOTH INSULATED AND NON INSULATED SERVICES PASS THROUGH WALLS AND FLOORS ETC.

13. PROVIDE STEEL PLATFORMS AND RAISED WALKWAYS TO CROSSOVER SERVICES ON ROOF/MECHANICAL FLOORS AND TO ACHIEVE ADEQUATE MAINTENANCE ACCESS TO THE APPROVAL OF ENGINEER.

14. ALL EXPOSED ANGLE SUPPORTS FOR DUCTS SHALL BE PAINTED AS SPECIFIED.

15. ALL EXPOSED DUCTS ON ROOF SHALL BE ALUMINUM CLADDED ON TOP OF THE INSULATION.

16. HEATING, VENTILATION AND AIR CONDITIONING (HVAC) SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS MANUAL AND OTHER APPROVED SUBMITTAL DATA.

17. VENTILATION AND AIR CONDITIONING DRAWINGS SHALL BE READ IN CONJUNCTION WITH GENERAL NOTES, SPECIFICATIONS, MISCELLANEOUS DETAILS, ARCHITECTURAL, ELECTRICAL, MECHANICAL AND STRUCTURAL DRAWINGS.
CONSULTANT
18. ANY MISSING DAMPERS (V.D,F.D.,...........ETC) TO BE PROVIDED BY CONTRACTOR.
HVAC EQUIPMENT NOTES

1. ALL CONDENSATE DRAINS FROM AHU/FCU/DX WHETHER SHOWN ON THE DRAWINGS OR NOT SHALL RUN WITH A FALL TO THE NEAREST WASTE STACK OR FLOOR DRAIN.
architects engineers designers planners

2. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING THE NOISE LEVELS IN VARIOUS AREAS WITHIN SPECIFIED LIMITS. CONTRACTOR SHALL INCLUDE IN HIS TENDER FOR ALL ATTENUATION MEANS WHETHER SPECIFIED OR NOT. TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae
3. ALL THE FAN COIL UNIT SHALL HAVE 25MM THICK WASHABLE FILTER AT 75 % EFFICIENCY.

4. CONTRACTOR SHALL SUBMIT PERFORMANCE TEST CERTIFICATE FOR EACH EQUIPMENT TO CONFIRM THAT IT CAN PRODUCE THE SCHEDULE DUTY AT THE SPECIFIED CONDITIONS.

5. POWER FACTOR CAPACITIES SHALL BE PROVIDED TO ALL MECHANICAL EQUIPMENTS.

6. CONTRACTOR SHALL FORWARD ACTUAL PHYSICAL DIMENSIONS, WEIGHTS OF EQUIPMENT FOR APPROVAL FROM STRUCTURAL ENGINEER.

C
7. EVERY HVAC EQUIPMENT SHALL BE PROVIDED WITH DISCONNECT SWITCH NEAR TO IT FOR EMERGENCY SHUT DOWN OF EQUIPMENT.
C

8. EXTERNAL STATIC PRESSURE FOR AHUs, FAHUs, FCUs, DX, FANs AND PUMP HEAD GIVEN IN SCHEDULE OF EQUIPMENT ARE ESTIMATED VALUES. THE CONTRACTOR SHALL BE RESPONSIBLE TO CALCULATE THE SAME AS PER ACTUAL CONDITIONS AND SUBMIT FOR ENGINEER'S APPROVAL.

9. COOLING LOAD CALCULATION SHALL BE DONE TO VERIFY THE SCHEDULE OF EQUIPMENT DATA AND SUBMIT FOR ENGINEERS APPROVAL.

DUCTWORK NOTES:

1. ALL DUCTWORK TO BE INSULATED IN ACCORDANCE WITH THE SPECIFICATIONS.


RESIDENTIAL VILLA FOR
2. ALL DUCTWORK SHALL BE AS PER SMACNA .
MR. GIRISH HIRANANDANI
3. ALL DUCT CONNECTIONS TO AHUs, FAHUs, DX AND FCUs SHALL BE OF FLEXIBLE TYPE. DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE
4. ALL DUCTWORK WITHIN 3.0 M OF FCU/DX/AHU/FAHU OR VAV SHALL BE ACOUSTICALLY LINED.

5. WHERE DUCT SIZES ARE NOT INDICATED, THE FOLLOWING CRITERIA SHALL BE FOLLOWED:
- MAIN AHU DUCTS ------------6.5M/S
-BRANCHES-----------------------3 M/S ''ISSUE FOR'' ''DESCRIPTION''
RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
6. PROVIDE PARTITION WITHIN CEILING VOIDS AS REQUIRED TO PREVENT MIXING OF RETURN AIR - WHEN TWO OR MORE UNITS ARE CONNECTED TO A COMMON CEILING VOID FOR RETURN AIR. SUCH PARTITIONS SHALL BE OF DRY WALL CONSTRUCTION. FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
7. UNLESS OTHERWISE INDICATED ALL OPEN END OF RETURN & EXTRACT AIR DUCT SHALL BE PROVIDED WITH STAINLESS STEEL WIRE MESH AS PER THE INSTRUCTIONS OF THE ENGINEER IN CHARGE. R FOR RECORD DOCUMENTS
P PRELIMINARY TD TENDER DOCUMENTS
8. FINAL DISTRIBUTION OF SUPPLY AIR, RETURN AIR, FRESH AIR & EXTRACT AIR DUCTWORK SHALL BE AS PER INTERIOR DESIGN LAYOUT, CONTRACTOR SHALL BE FULLY RESPONSIBLE TO COORDINATE ALL SERVICES, AS PER ENGINEER IN CHARGE.
M MUNICIPALITY REVIEW
9. FLEXIBLE DUCT TO ANY AIR OUTLET SHALL NOT EXCEED A LENGTH OF 1.5 METER AND SHOULD BE INSTALLED AS PER SMACNA STANDARDS.

10. RETURN AIR OPENING/DUCT OR PROPER SIZE WITH FRAME AND WIRE MESH SHALL BE PROVIDED ABOVE FALSE CEILING WHERE NECESSARY.

11. ALL FRESH AND EXTRACT AIR DUCT BRANCH OUTLET SHALL BE TERMINATED ADJACENT TO EACH FCU (UNLESS SHOWN ON DRAWINGS OTHERWISE) WITH VCD AND STAINLESS STEEL WIRE MESH.

B
B

12. ALL SUPPLY/RETURN AIR PLENUM SHALL BE INTERNALLY LINED AND PAINTED BLACK INTERNALLY.

13. PROVIDE SUFFICIENT TEST HOLES ON THE DUCT WORK AND PROTECT WITH PLUGS TO CHECK AIR FLOW AND PRESSURE.

14. ALL DUCT BENDS, BRANCHES AND TEES SHALL BE PROVIDED WITH TURNING VANES.

15. THE DUCT MAINS AND RISERS SHALL BE REINFORCED TO PREVENT DRUMMING.

16. CONTRACTOR IS RESPONSIBLE FOR ACHIEVING THE SYSTEM AIR BALANCE AND TO MAINTAIN THE PRESSURE RELATIONSHIP BETWEEN DIFFERENT AREAS. CONTRACTOR TO INCLUDE IN HIS TENDER FOR REGULATING DAMPERS AND OTHER ACCESSORIES AS REQUIRED, WHETHER INDICATED ON DRAWINGS OR NOT.
B 27/12/2016 100 % CD FA NAGA
SUBMISSION
DUCTWORK ACCESSORIES NOTES: A 12/05/2016 100 % DD FA NAGA
SUBMISSION
1. ACCESS PANELS TO BE PROVIDED WITHIN FALSE CEILING AT ALL LOCATIONS OF FCUs, VALVES, VCD, NRD & SPD. CONTRACTOR SHALL COORDINATE WITH ALL MEP SERVICES AND FALSE CEILING LAYOUT TO ENSURE THAT COMMON ACCESS PANELS ARE PROVIDED FOR MAINTENANCE. REV. DATE DESCRIPTION FOR BY
ISSUED
2. NON RETURN DAMPERS SHALL BE PROVIDED AFTER EACH DUCTED EXTRACT FAN.
ISSUE
3. VOLUME CONTROL DAMPER SHALL BE PROVIDED AT ALL A/C DUCT BRANCHES, WHETHER SHOWN ON DRAWINGS OR NOT FOR PROPER AIR BALANCING.
PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE
AIR TERMINALS NOTES:
SCALE
1. AIR OUTLET SHALL BE ALUMINUM ANODIZED EXTRUDED CONSTRUCTION WITH POWDER COATED OVEN BAKED ENAMEL FINISH. THE COLOR SHALL BE AS PER APPROVED MATERIAL SUBMITTAL. DRAWN BY MF
2. FINAL LOCATION AND TYPE OF AIR DEVICES SHALL BE COORDINATED WITH INTERIOR DESIGN LAYOUT AND THE CONTRACTOR SHALL REVISE IF REQUIRED WITHOUT ANY EXTRA COST. CHECKED BY EM
3. ALL SUPPLY AND EXTRACT DIFFUSERS/GRILLS SHALL HAVE BUILT IN VCD FOR FINAL FINE TUNING. MANAGEMENT M.SHAFY

4. FINAL LOCATION OF FRESH AIR LOVER AND EXTRACT AIR LOUVER TO BE CO-ORDINATE WITH ARCHITECT AT SITE AND COLOR IS SUBJECT TO ARCHITECTS APPROVAL. PRINTING DATE/TIME 12/25/2016 11:57:24 AM

A
A

5. ALL FRESH AIR LOUVER SHALL HAVE SAND TRAP.

M0-GE-004

SHEET TITLE

HVAC NOTES

1 2 3 4 5 6 7
1 2 3 4 5 6 7
STAMPS

WATER SUPPLY NOTES

1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE CO-ORDINATION OF ALL SERVICES.

2. PIPES SIZES SHOWN IN DRAWING ARE IN MM DN.

3. ALL COLD AND HOT WATER PIPE WORK TO BE AS PER SPECIFICATION.

4. ALL FINAL OUTLETS SHALL INCORPORATE ANGLE VALVES.

D
D

5. UNLESS OTHERWISE INDICATED ALL PIPE WORK IN TOILETS/BATH ROOMS ETC SHALL BE 20MM DIA DN WITH REDUCTIONS TO 15MM DIA DN ONLY AT FINAL OUTLETS AS APPROPRIATE.

6. BRANCH SUPPLY PIPES TO ALL AREAS WILL HAVE ISOLATING VALVES MOUNTED AT ACCESSIBLE HEIGHTS ABOVE FALSE CEILING.

7. FINAL LOCATION OF SOLAR WATER HEATER SHALL BE COORDINATED WITH OTHER SERVICE AND FALSE CEILING HEIGHTS AT SHOP DRAWINGS STAGE.

8. CONTRACTOR TO INCLUDE FOR PRESSURE REDUCING VALVES, ISOLATING VALVES AND NON RETURN VALVES AS REQUIRED BY THE SYSTEM.

9. WATER HAMMER ARRESTOR TO BE PROVIDED FOR EACH TOILET/KITCHEN .

10. ALL HIGH POINTS OF THE WATER SYSTEM SHALL BE PROVIDED WITH AUTOMATIC AIR VENT AND THE LOW POINT SHALL BE PROVIDED WITH DRAIN POINT WHETHER SHOWN ON LAYOUT OR NOT.

11. CONTRACTOR TO ENSURE ALL PUMPS ARE INSTALLED ON MINIMUM 150MM CONCRETE BASE.

12. ALL BURIED PIPES SHALL BE LAID ON COMPACT AND LEVEL SURFACE.

13. FINAL BIB TAP LOCATION/HEIGHT SHALL BE APPROVED BY ARCH.

14. FOR ALL THE PUMPS THE ACTUAL HEAD/FLOW TO BE ESTABLISHED BY CONTRACTOR AND CALCULATIONS TO BE FORWARDED TO CONSULTANT FOR APPROVAL. CONSULTANT

architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

C
C

RESIDENTIAL VILLA FOR


MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE

''ISSUE FOR'' ''DESCRIPTION''


RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
R FOR RECORD DOCUMENTS
P PRELIMINARY TD TENDER DOCUMENTS
M MUNICIPALITY REVIEW

B
B

B 27/12/20 100 % CD FA NAGA


16 SUBMISSION
A 12/05/20 100 % DD FA NAGA
16 SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED

ISSUE

PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE
DRAWN BY Author

CHECKED BY Checker
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:57:25 AM

A
A

M0-GE-005

SHEET TITLE

WATER SUPPLY NOTES

1 2 3 4 5 6 7
1 2 3 4 5 6 7
STAMPS

STANDARD NOTES FOR DRAINAGE


A)DOCUMENTATION F I C (THE LASTMANHOLE)
A-1 DM DRAINAGE DEPARTMENT N O C NO: - 1- F I C SHALL BE CONSTRUCTED IN CLOSE PROXIMITY WITH THE COMPOUND WALL AND OPPOSITE TO DM CHAMBER/MANHOLE AND THE
A-2 DM DRAINAGE DEPARTMENT 'F I C - COVER SHOULD 'BE DUCTILE IRON WITH 6MM THICK G.R.P PUSH FIT SEALING PLATE, THIS MANHOLE SHALL HAVE ONLY ONE
A-3 RECEIPT NO FOR SEW CONNECTION - TOTAL BUILT UP AREA = 298.0 SqM INCOMING CONNECTION AND WORK BY GRAVITY ONLY
A-4 RECEIPT NO FOR STORM WATER CONNECTION - N.A. TOTAL BUILT UP AREA = 3206 Sqft 2- IN CASE OF THERE ARE NO PROPOSAL OF FUTURE CONNECTION FROM DM DRAINAGE DEP. THE FUTURE CONNECTION SHALL BE IN
A-5 TOTAL NO OF SEPTIC TANK - NIL LESS WIDTH ROAD AND THE MAX DEPTH SHALL BE 1200 MM.
A-6 TOTAL NO OF DM SEWERAGE . CONNECTION - ONE D) MISCELLANEOUS

D
A-7 TOTAL NO OF DM STORM WATER . CONNECTION - NIL
D

RAIN WATER DRAINAGE


A-8 LAST BUILDING PERMIT NO:
B)PIPING 1- THE DRAINAGE OF ROOFS AND PAVED AREAS SHALL BE ACCORDING TO BS 6367
1- MATERIALS SHALL BE TO DM APPROVAL AND THE INSTALLATION SHALL BE ACCORDING TO BS 5572 2- RAIN WATER PIPES ARE NOT TO BE CONNECTED TO SEWER LINES. THEY SHALL FREE DISCHARGE ABOVE GROUND
2- ALL INTERNAL PIPING SHALL BE UPVC TO BS 4514 EXCEPT WASTE PIPING WHICH SHALL BE TO BS 5255. ALL U/G PIPING SHALL BE TO BS 4660 3- ALL O.T.S, S ( 4X4 M & LESS ) SHOULD HAVE FLOOR TRAPS FOR RAINWATER CONNECTED TO THE NEAREST GULLY TRAP OR WASTE
3- NO BENDS SHALL BE ALLOWED IN HORIZONTAL PIPES RUNNING UNDERGROUND. STACK. OTHER O.T.S,S SHALL HAVE RW DRAIN FOR RAIN WATER WHICH IS FREE DISCHARGE TO OUTSIDE.
RODDING EYES 4- FOR ALL AIR WELLS, ACCESS DOORS SHOULD BE PROVIDED AT THE LOWER LEVEL OF THE WELL .
1- ACCESS POINTS SHOULD BE CAREFULLY SITED TO ALLOW THE SERVICE ENTRY FOR CLEANING AND TESTING . 5- FOR PROJECT HAVING LARGE RAIN CATCHMENT AREAS, RAIN WATER SCHEME SHALL BE DESIGNED TO BS 6367 AND DM APPROVAL.
2- ALL VERTICAL STACKS SHALL BE PROVIDED WITH RODDING EYES AT JUNCTIONS ON EVERY FLOOR. GREASE TRAPS AND OIL INTERCEPTORS
3- ALL HORIZONTAL DRAINAGE PIPES SHALL HAVE RODDING EYES AT POINTS OF CHANGE OF DIRECTION IN PIPES AS REQUIRED FOR EFFECTIVE MAINTENANCE 1- ALL COMMERCIAL KITCHENS AND COMMUNAL ACCOMMODATION KITCHENS SHALL HAVE HEAVY DUTY GREASE TRAPS PROVIDED
4- RODDING EYES SHALL BE PROVIDED WHERE MORE THAN ONE WC IS CONNECTED TO A HORIZONTAL SOIL PIPE ACCORDING TO DM REGULATIONS.
5- RODDING EYE IS TO BE PROVIDED WHERE THE DISTANCE BETWEEN ONE WC AND STACK OR MANHOLE IS MORE THAN 5 METERS. 2- FOR VEHICLE WASHING AND SERVICE STATIONS, OIL INTERCEPTORS MUST BE PROVIDED AS PER DM REGULATIONS.
STACKS. SWIMMING POOLS
1- THE UPPER LIMIT OF STACK LOADING SHALL NOT BE MORE THAN A QUARTER FULL 1- DRAINAGE FOR THE SWIMMING POOLS AND BACKWASH PUMPS SHALL BE SHOWN ON SEPARATE DRAINAGE LAYOUTS PLAN.
2- FOR BUILDINGS OF LESS THAN 20 STORIES HEIGHT, APPLIANCES LOCATED ON GR. FLOOR SHALL NOT BE CONNECTED TO VERTICAL AND THE DRAINAGE LINE SHALL BE SHOWN ON THE RELEVANT DRAINAGE PLAN
STACK DISCHARGING AT GR. LEVEL 2- FOR SWIMMING POOLS ON THE ROOF OR UPPER FLOORS PROVIDE SEPARATE 2" DIA... PIPE ( AFTER PROVIDING REGULATING VALVE)TO.
3- FOR BUILDINGS GREATER THAN 20 STORIES APPLIANCES LOCATED AT GR. FLOOR AND FIRST FLOOR SHALL NOT BE CONNECTED TO THE GROUND FLOOR MANHOLE CONNECTION .CONNECTION TO BASEMENT SUMP PUMP SHALL NOT BE ALLOWED
VERTICAL STACK DISCHARGING AT GR. LEVEL PROVISION FOR FUTURE CONNECTION
4- CONNECTION FROM THE APPLIANCES LINES ON ANY FLOOR AND THE MAIN PIPE SHALL BE IN VERTICAL STAKES ONLY. 1- SHOP FACILITIES IN BUILDINGS SHALL HAVE WP. & VP CONNECTION PROVISIONS FOR FUTURE WITH APPROVED GRATING AS PER DM CONSULTANT
5- FOR ALL BENDS THAT ARE AT BASE OF STACKS, PROVIDE A 45 OR 90 DEGREES LONG RADIUS TYPE ELBOW DETAILS
VENT PIPES SAFETY AND HEALTH CONSIDERATIONS:
1- IN SINGLE STACK SYSTEM, PROVIDE A SEPARATE VENTILATION FOR INDIVIDUAL CONNECTIONS FROM THE WC, FLOOR TRAP, SINK, ETC. 1- WINDOW A/C SHALL BE PROVIDED WITH G.R.P. TRAYS HAVING DRAINAGE FACILITY
ANY HORIZONTAL PIPE LONGER THAN 1.5 METERS FROM SUCH FIXTURES SHALL BE VENTED ON THE HIGH SIDE 2- ALL A/C & BALCONY DRAINS SHALL BE CONNECTED TO WASTE PIPE SYSTEM VIA THE NEAREST FLOOR TRAP OR WASTE STACK.
architects engineers designers planners
2- VENT PIPES FROM MANHOLES AND VERTICAL STACKS SHALL BE EXTENDED 2 METERS ABOVE THE ROOF, THE END OF WHICH SHALL BE FITTED WITH VENT COWLS. 3- FLEXIBLE POLYETHYLENE DRAIN PIPES SHALL NOT BE USED FOR A/C CONDENSED DRAIN PIPING
4- COMMUNAL AND PUBLIC TOILETS IN INDUSTRIAL AND COMMERCIAL ESTABLISHMENT DORMITORIES AND EDUCATION INSTITUTES TEL +971 4 332 4455 FAX +971 4 332 2113
RESTRICTIONS po box 73033 dubai web site www.naga.ae
1- THE DRAINAGE PIPES SHALL BE MADE NOT TO RUN THROUGH ELECTRIC ROOMS OR ELECTRIC SUB-STATIONS SHALL BE FURNISHED WITH ASIAN TYPE WC IN PROPORTION NOT LESS THAN 75% OF TOTAL NIMBER OF WC REQUIRED
2- DIRECT CONNECTION OF WASTE SYSTEM FROM A FLOOR TRAP TO A FLOOR TRAP SHALL NOT BE PERMITTED. IN ADDITION ,PUBLIC BUILDING SHALL HAVE PROVISION FOR TOILET FACILITIES FOR DISABLED PERSONS
3- NO DRAIN PIPES SHALL BE CAST INTO AN RCC STRUCTURAL ELEMENT WITHOUT PRIOR APPROVAL FROM DM STRUCTURAL ENGINEER 5- ALL FLOOR DRAIN SHALL HAVE MINIMUM 75 MM DEEP SEAL
4- TO ALLOW THE DRAIN PIPES TO PASS THROUGH ANY STRUCTURAL ELEMENT IN BUILDING A CAST IRON SLEEVE IS FIRST FITTED WITHIN 6- FLOOR DRAINS SHALL BE PROVIDED IN ALL GARBAGE ROOMS IN ALL FLOORS AND PUMP ROOMS AND ALL GARAGE ROOMS
THE STRUCTURAL ELEMENT SUCH A BY PASS, THE SLEEVE SHALL OFFER A TOLERANCE OF AT LEAST 50 MM FOR EASE OF 7- ALL WATER SUPPLY PIPES SHALL BE INSTALLED AT LEST 1.0 M AWAY FROM THE SEWER PIPE LINE SEPTIC TANK OR SOAKAWAY.
INSTALLATION OF THE PIPE. THE GAP BETWEEN THE PIPE AND THE SLEEVE SHALL THEN BE FILLED WITH SUITABLE SEALANT. 8- URINALS SHALL BE CONNECTED TO SOIL PIPES.
5- NOT TO PLACE UNDERGROUND PIPE LINE WITH TOP OF PIPE LESS THAN 600 MM BELOW FFL UNLESS CONCRETE STYLE 150 MM THICK SYSTEM TEST
SHALL BE PROVIDED AROUND TO PROTECT THE PIPE 1- WATER AND AIR TESTS SHALL BE CARRIED OUT AFTER THE PIPES ARE INSTALLED AND CONSULTANT CERTIFICATE SHALL BE

C
6- TYPICAL OUTLET SIZE (MM) 7- STACK SIZES SHALL BE AS FOLLOWS: - 8- STACK SIZES SHALL BE AS FOLLOWS: - SUBMITED TO DM ENGINEERS.
C

WC 100 UP TO GROUND PLUS SEVEN STORY ABOVE SEVEN STORY E) SEPTIC TANKS, SOAKAWAY AND HOLDING TANKS
W . BASIN 32 SOIL PIPE 100 SOIL PIPE 150 D-1 SEPTIC TANK AND SOAKAWAY SHALL BE CONSTRUCTED AND SELECTED TO DM DETAILS AND SHALL BE ACCORDING TO BS 6297
KITCHEN SINK 40 WASTE PIPE 100 WASTE PIPE 150 D-2 THE FOUNDATION LEVEL OF THE BASE OF THE SOAKAWAY SHALL BE KEPT AT LEAST 1 M ABOVE THE WINTER WATER TABLE.
FLOOR DRAIN 75 VENT PIPE 75 VENT PIPE 100 D-3 THE FLOOR AREA OF THE SOAKAWAY SHALL BE DETERMINED ACCORDING TO THE 'PERCOLATION RATE IN ACCORDANCE WITH
BATH TUB/SHOWER 40 RAIN WATER PIPE 100 RAIN WATER PIPE 100 APPROPRIATE TEST IN THE BS 6297
WASHING M/C 40 BALCONY DRAIN PIPE 50 BALCONY DRAIN PIPE 50 D-4 LOCATIONS OF SEPTIC TANK AND SOAKAWAY SHOULD SHOWN ON SETTING OUT PLANS AND ON A GENERAL FOUNDATION LAYOUT PLANS.
BALCONY DRAIN 50 A/C DRAIN PIPE 32 A/C DRAIN PIPE 32 D-5 SOAKAWAY SHALL BE 1000 MM AWAY FROM THE SEPTIC TANK PLACED AT LEAST.
C)MANHOLES D-6 SEPTIC TANK & SOAK AWAY SHOULD BE CONSTRUCTED AT LEAST 3 MS AWAY FROM ANY FOOTING FOR A BUILDING OR A BOUNDARY WALL
1- THE MANHOLE SCHEDULE SHALL BE ARRANGED IN THE MANNER SHOWN BELOW ,THE MANHOLE INVERT LEVEL (I L) , COVER LEVEL (C L) AND SHOULD BE CONSTRUCTED FROM SOLID BLOCK WITH A PROVISION OF PROPER INSULATION FOR THE SEPTIC TANK.
DEPTH AND DISTANCE BETWEEN MANHOLES SHALL BE REFERENCED FROM D.M C , F.I.C USING DM'S DATUM D-7 IN CASE THERE IS A NEED TO CONSTRUCT THESE TANKS AT A DISTANCE LESS THAN 3. MS AND MORE THAN 1 MS FROM ADJACENT
AND ALL UNITS SHALL BE IN SYSTEM IS FOOTINGS. THE SEPTIC TANK SHOULD BE STRUCTURES FROM REINFORCED CONCRETE WITH A PROVISION OF PROPER INSULATION TO
MH NO
DMC
CL IL DISTANCE TO NEXT MH DEPTH COVER TYPE REMARK PREVENT ANY LEAKAGE FROM THE TANK
D-8 IF THE SEPTIC TANK & SOAK AWAY ARE TO BE FOUNDED AT A LOWER LEVEL THAN THAT OF ADJACENT FOOTING THEY SHOULD
RESIDENTIAL VILLA FOR
FIC
MH NO
BE CONSTRUCTED FIRST.
D-9 IF SEPTIC TANK CONSTRUCTED FROM FIBERGLASS MATERIAL THE DIMENSION SHALL BE THE SAME ,THE THICKNESS SHALL NOT LESS
MR. GIRISH HIRANANDANI
2- A SKETCH SHOWING THE RELATIVE LEVEL BETWEEN F.I.C AND BUILDING MANHOLES SHALL BE PROVIDED THAN 6 MM AND IT SHOULD BE INCASED WITH PROPER PROTECTION SOLID BLOCKS . DM PLOT 6316407, EMAAR PLOT PA-02
3- THE INVERT LEVEL OF THE EXTERNAL DRAINAGE SYSTEM SHALL BE DETERMINED BY THE CONSULTANT TAKING INTO CONSIDERATION D-10 PROPER INSULATION SHOULD BE PROVIDED FOR FOUNDATIONS OF BUILDINGS IN SUCH CIRCUMSTANCES FOR PROTECTION R.074, DUBAI HILLS ESTATE
THE DRAINAGE CONNECTION LEVEL TO MATCH THAT OF F.I.C, IN CASE OF N.O.C THE DEEP OF LAST MANHOLE SHALL BE LESS THAN 1200 MM. AGAINST SULFATES .
4- THE DEPTH OF FIRST MANHOLE SHALL BE AT LEAST 450 MM D-11 SOAKAWAY SHOULD BE FILLED WITH BOULDERS OF SIZE 75 MM TO 100 MM
5- SLOPES FOR HORIZONTAL RUNS SHALL BE AS FOLLOWS: FOR 100 MM - 1:60 FOR 150 MM - 1:90 FOR 200 MM - 1:120 D-12 GRP SEALING PLATE SHALL BE PROVIDED FOR THE LAST MANHOLE BEFORE THE SEPTIC TANK AND THE MANHOLE FOR
6- MANHOLES AND ACCESS CHAMBERS SHALL BE LAY OUT ACCORDING TO CONSULTANT'S SCHEME., COVERS PROVIDED SHALL BE ''ISSUE FOR'' ''DESCRIPTION''
THE FUTURE CONNECTION BEFORE THE DM SEWER LINE
SUITABLE FOR THE LOADS THEY ARE SUBJECTED TO, AND IN ACCORDANCE WITH BS 497 RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
7- ACUTE ANGLE CONNECTIONS SHALL NOT BE ALLOWED WITHIN JUNCTION MANHOLES. D-13 SIDE LEAKAGE FROM SOAK AWAY SHOULD BE PREVENTED OF CONSTRUCTED AT THE SAME LEVEL OF ADJACENT FOOTING OF
A BUILDING OR A BOUNDARY WALL FA FOR APPROVAL DD DESIGN DEVELOPMENT
8- AT A MH THE TOPS OF ALL SEWERS SHOULD BE AT THE SAME LEVEL SO THAT THE PIPES OF SMALLER DIAMETER ARE NOT PS PROGRESS SET CD CONSTRUCTION
FLOODED WHEN THE BIGGER PIPES ARE RUNNING FULL R FOR RECORD DOCUMENTS
9- BACKDROP SHALL BE PROVIDED WHEN THE LEVEL DIFFERENCE BETWEEN INCOMING AND MAIN SEWER IS CONSIDERABLE P PRELIMINARY TD TENDER DOCUMENTS
10- AN INSPECTION CHAMBER / MANHOLE / GULLY TRAP CONSTRUCTED IN COVERED AREA SHALL BE DRY TYPE AND PROVIDED WITH RECESSED M MUNICIPALITY REVIEW
DOUBLE SEAL TYPE COVER.
11- ANY MANHOLE LOCATED IN GARAGE, DRIVEWAY OR OTHER TRAFFIC AREAS SHALL BE PROVIDED WITH HEAVY DUTY COVERS.
12- IF INSPECTION CHAMBERS / MANHOLES ARE IN AGRICULTURAL LAND, MANHOLE COVERS SHOULD BE RAISED 75 MM ABOVE THE
THE NATURAL GROUND LEVEL.
13- DISTANCE BETWEEN MH TO MH SHALL NOT EXCEED 15 METERS IN VILLAS AND BUILDINGS
14- MINIMUM REQUIREMENT FOR MANHOLE VENTING SHALL BE THE PROVISION OF VENT PIPE TO FIRST AND LAST MANHOLES OF DRAINAGE LINE.

B
B

THESE VENT PIPES SHALL BE 100 MM BELOW COVER LEVEL.


15- THE SITING OF ANY MANHOLE SHALL BE KEPT AWAY FROM UNDERGROUND WATER TANK BY A DISTANCE NOT LESS THAN THE DEPTH OF THE
WATER TANK.
SUMP PUMP
1- IN BASEMENT, SAND TRAP WITH PVC BUCKET SHALL BE PROVIDED JUST BEFORE END CONNECTION OF CAR PARK DRAIN TO THE SUMP PUMP PIT
AND THE RAMP DRAIN CHANNEL
2- IF A BASEMENT SUMP PUMP IS FOR RAIN WATER COLLECTION ONLY FROM BASEMENT, CONNECT ONE WASTE PIPE FROM THE NEAREST TOILET .
TO THE BASEMENT DRAINAGE LINE TO MAKE IT ALWAYS WET.
3- SUMP PUMP SERVICE ONLY THE BASEMENT DRAIN AND SEWERAGE
MANHOLES CONSTRUCTION B 27/12/20 100 % CD FA NAGA
1- ALL INSPECTION CHAMBERS/MANHOLES SHOULD BE BUILT ON BED OF CEMENT CONCRETE 1:4:6 THE THICKNESS OF THE CONCRETE 16 SUBMISSION
SHALL BE 150 MM FOR MANHOLES UP TO 1000 MM DEEP AND 200 MM FOR DEPTHS ABOVE 1000 MM A 12/05/20 100 % DD FA NAGA
2- WHERE MANHOLE / INSPECTION CHAMBERS ARE CONSTRUCTED BELOW GROUND WATER TABLE , COMPLETE CONSTRUCTION SHALL BE EITHER 16 SUBMISSION
IN WATERPROOFED RCC. OR IN G.R.P REV. DATE DESCRIPTION FOR BY
3- ALL MAIN LINE CHANNELS SHALL BE LOCATED IN THE CENTER OF THE MANHOLES ISSUED
4- BENCHING OF INCOMING BRANCHES SHOULD BE INCLINED TOWARDS THE MAIN DIRECTION OF FLOW .
5- DIAMETER OF SEMI-CIRCULAR CHANNEL IN THE BOTTOM OF MANHOLE SHALL BE EQUAL TO THAT OF THE INCOMING SEWER DIAMETER.. ISSUE
6- THE SIDES OF CHANNELS IN MANHOLE SHALL BE EXTENDED VERTICALLY TO THE SAME LEVEL OF THE SOFFIT OF THE PIPE
7- THE BENCHING IN INSPECTION CHAMBER/ MANHOLES SHOULD HAVE SMOOTH SURFACE CEMENT PLASTER PROJECT NO. PROJECT NUMBER
8- MANHOLES SIZES SHALL BE AS FOLLOWS:-
PROJECT ARCHITECT H.S.
MANHOLES DEEP MM MANHOLES SIZE MM MANHOLES COVER MM
C:\Users\mhegazy\Documents\15-030
UP TO 1300 600X600 600X600 FOR SEW FOR SWD M-VILLA_mhegazy.rvt
FROM 1301 TO 1700 800X800 600X600 FOR SEW FOR SWD
FROM 1701 TO 2500 1000 600X600 FOR SEW FOR SWD REVIT FILE
FROM 2501 TO 4000 1500 600X600 FOR SEW FOR SWD
ALL 1000 & 1500 MANHOLE SHALL HAVE G.R.P. LININGS SCALE 1 : 100
DRAWN BY Author

CHECKED BY Checker
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:57:29 AM

A
A

DRAINAGE NOTES M0-GE-006


1 1 : 100

SHEET TITLE

DRAINAGE NOTES

1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

LIQUID LINE

SIGHT GLASS ELEC. WIRE


LIQUIDVALVE SOLENOID SUCTION LINE
VALVE RUBBER INSULATION
ISOLATING VALVES LIQUID VALVE SOLENOID
A/C COPPER PIPES, SUCTION LINE WITH RUBBER
INSULATION &CANVAS CLOTH & FOSTER 30-36
32mm MULTI LAYER ANTI-VIBRATION
RUBBER PADS

D
OU - VRF SIGHT GLASS
D

PITCH 1/2 % ISOLATING VALVES


CU
FILTER DRIER CONCRETE PLINTH 150mm
FILTER DRYER

D6 REFRIGERANT PIPE INSULATION 50mm THK. CORK UNDER


N.T.S. CONCRETE PLINTH
OIL TRAP
(REQUIRED AT EACH 8 m
NTERVAL OF SUCTION)
R.F.L.
SUCTION LINE LIQUID LINE

THERMAL EXPANSION VALVE CONSULTANT

RAWL PLUG
IU - VRF
4700 architects engineers designers planners
VIBRATION KIT TEL +971 4 332 4455 FAX +971 4 332 2113
4380 TRAP FOR LOWER UNITS
TWO ELBOWS OIL TRAP 3000 po box 73033 dubai web site www.naga.ae
(CAN BE DELETED IF
SUCTION LIFT IS < 2.4 m)
FAN COIL UNIT

THERMAL EXPANSION VALVE

4300
4140

C
C

IU - VRF

TWO ELBOWS OIL TRAP


(CAN BE DELETED IF
SUCTION LIFT IS < 2.4 m)
FRONT VIEW SIDE VIEW

2 WALL MOUNTED FAN OUTDOOR UNIT FOUNDATION


N.T.S.

C3 AND SPLIT UNIT HANGING DETAIL RESIDENTIAL VILLA FOR


1 VRF INDOOR/OUTDOOR UNIT CONNECTION DETAIL N.T.S.
MR. GIRISH HIRANANDANI
N.T.S.
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE

''ISSUE FOR'' ''DESCRIPTION''

NOTES: NOTES: RC REVIEW & COMMENTS SD SCHEMATIC DESIGN


FA FOR APPROVAL DD DESIGN DEVELOPMENT
1- FRESH AIR ENTERS THE UNIT AT AMBIENT CONDITIONS OF 46.1 °C/29.4 °C
1. FOR FAN DETAILS AND OTHER ACCESSORIES REQUIRED, PS PROGRESS SET CD CONSTRUCTION
2- FRESH AIR LEAVING PRE-COOL WRAP AROUND HEAT PIPE SECTION AND DOCUMENTS
SEE EQUIPMENT SCHEDULES AND SPECIFICATIONS. R FOR RECORD
ENTERING COOLING COIL.
P PRELIMINARY TD TENDER DOCUMENTS
3- FRESH AIR LEAVING COOLING COIL AFTER DEHUMIDIFICATION
2. FOR REQUIRED ROOF OPENING, REFER TO EQUIPMENT CLOSED CELL RUBBER M MUNICIPALITY REVIEW
AT 13.0 °C/12.6 °C OR AS SET AND ENTERING REHEAT COIL.
MANUFACTURER'S CATALOG. INSULATION SIMILAR TO
4- FRESH AIR LEAVING THE REHEAT WRAP AROUND HEAT PIPE SECTION
EUROFLEX
5- FRESH AIR SUPPLIED TO ALL VRF INDOOR FCU'S 3. FOR ROOF CONSTRUCTION, FLASHING AND
COUNTERFLASHING DETAIL, SEE ARCHITECTURAL DRAWING.
NON-FLAMMABLE ADHESIVE
4. PROVIDE SAFETY DISCONNECT SWITCH INSTALLED ON MOTOR COPPER

B
MOUNTING PLATE UNDER MOTOR DOME. PIPE
B

TYPE "L"
5. FOR KITCHEN EXHAUST FAN, THE BACKDRAFT DAMPER AND
FLEXIBLE DUCT CONNECTOR SHALL BE DISREGARDED.

ISOMETRIC VIEW DETAIL

B 27/12/2016 100 % CD FA NAGA


EXTERNAL SUBMISSION
PROTECTION:- A 12/05/2016 100 % DD FA NAGA
1COAT 30-36 G.I.FRAME WITH COVER SUBMISSION
1COAT 60-95 BOLTED TO TRAY 1.2mm THICKNESS
REV. DATE DESCRIPTION FOR BY
RUBBER GASKET FAN MOTOR ALUMINUM
CLADDING 0.9mm REFRIGERANT PIPE ISSUED
HOUSING REFRIGERANT PIPE
W/P CLAMP (SUCTION & LIQUID (SUCTION & LIQUID LINE) FIXED
LINE) FIXED BY TIE ALONG WITH PROTECTION ISSUE
WRAP TYP.
A PROJECT NO. PROJECT NUMBER
WIDE CABLE TRAY WITH MIN.
50mm DEEP+COVER ROOF F.F.L. PROJECT ARCHITECT H.S.
(WIDTH TO SUIT NOS. OF PIPES) C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

BRASS SECTION-A
SCREWED PLAN REVIT FILE
F/A IN @ 6 F/A OUT TO CABLE
1 2 3 4 5 SCALE As indicated
VARIES

46.1 °C DBT MANUFACTURER


TRAY
29.4 °C WBT STANDARD
STEEL CURBS 40 mm STANDING SEAM RIVETED OR DRAWN BY MF
BOLTED ON 300 mm CENTERS AND
CHECKED BY EM
WATERPROOFING WITH SUITABLE MASTIC SEALANT ISOMETRIC VIEW DETAIL
FLASHING MANAGEMENT M.SHAFY
FLASHING STEEL FRAME
(AS PER FAN SIZE) PRINTING DATE/TIME 12/25/2016 11:57:33 AM
25 THICK RIGID

A
A

DUCT INSULATION ALL AROUND


PLENUM WRAP AROUND SUPPLY AIR FAN
HEAT PIPE
PRE-FILTER SLOPE SLOPE
T.O.S.S.

BAG FILTER COOLING COIL SLAB OPENING M0-GE-101

A4 REFRIGERANT
N.T.S.
PIPE IN GALVANIZED TRUNK ON ROOF SHEET TITLE

3 TOTAL FRESH AIR HANDLING UNIT WITH WRAP AROUND HEAT PIPE 4 EXHAUST FAN INSTALLATION DETAIL
N.T.S. N.T.S.
HVAC DETAILS 1

1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

TYP. CONDENSER UNIT INSTALLED ON ROOF. MAINTAIN


ALL REQ'D CLEARANCES AS REQ'D BY MANUFACTURER.

To CDU-1
FR CDU-1
U-1 REFRIGERANT LINES TO BE INSULATED WITH 20mm
CD ARMAFLEX AND PROTECTIVE ALUMINUM JACKETING
TYP. MIN 6"x6" PRESSURE TREATED SLEEPERS; FASTEN TO REFRIGERANT LINES TO BE INSULATED WITH 20mm
CONDENSER BASE. COORDINATE INSTALLATION WITH ROOFING SEAL WATERTIGHT AT PENETRATIONS THRU ROOF - ARMAFLEX
CONTRACTOR AND w ARCH. DIV. TYPICAL

TYP. WALL MTD. EVAP./FAN COIL (FC-1 & 2); INSTALLATION HGT. TO

CD
MANUFACT. GUIDELINES. COORD. ON-SITE. UNIT MAY NOT BE

D
EXACTLY AS ILLUSTRATED; REFER TO MANUFACTURER'S LITERATURE. NES
D

TYP. FLEX. CONNECTION IDELI


U
F. G
C.P.
-1
ECU TO M ANU
P.
TYP. ROOF DECKING; TY TALL
MAY NOT BE EXACTLY AS INS
SHOWN. C.O.S. PIPING TO ROUTE INTO WALL CAVITY; INSTALL ESCUTCHEONS ON FIN.
TYP. UNION AS REQ'D SIDE OF WALL; COORD ON-SITE. TYPICAL.
19mm  CONDENSATE DRAIN & CONDENSATE PUMP: SEE
PLUMBING DRAWINGS FOR
CONTINUATION & NOTE #3.

TYP. RUBBER ISOLATOR


CONDENSER UNIT

TYP. 6"x6" (140/140mm) PRESSURE TREATED UPPER


SLEEPER - MIN. 2-REQ'D; LENGTH TO SUIT TYP. 50x50x3mm GALV, STEEL ANGLE IRON @ 100mm (L). SEAL ALL PENETRATIONS
SECURELY FASTEN SLEEPERS TO CONDENSER REQ'D BOTH SIDES; Min. WATERTIGHT w APPROVED
UNIT BASE; COORD. ON-SITE AND MANUFACTURER 8-SUCH SILICON SEALANT; COORD.
SEE BLOW-UP DETAIL AT RIGHT
ON-SITE
CONSULTANT
TYP. 6"x6" (140/140mm) PRESSURE TREATED LOWER ROOFING MEMBRANE TO ENCASE LOWER SUPPORT
SLEEPERS; COORD w ARCH DIV. TYP. FASTEN ANGLE IRON TO UPPER & LOWER SLEEPERS w
SUPPEORT SLEEPERS - MIN. 4-REQ'D; LENGTH TO Min. 6mm  x 75mm (L) GALV. LAG SCREWS. Min. 2
SUIT PER ANGLE IRON. COORD. ON-SITE
ROOFING INSULATION; C.O.S.
SECURELY FASTEN SLEEPERS TO ROOF STRUCTURE & ANGLE IRON architects engineers designers planners
w GALV. STEEL COUNTERSUNK CARRIAGE BOLTS; COORD. ON-SITE TEL +971 4 332 4455 FAX +971 4 332 2113
ROOF DECKING; C.O.S. BLOW-UP DETAIL po box 73033 dubai web site www.naga.ae

MIN. 50x50x3mm ANGLE IRON;


LENGTH TO SUIT NOTES -

1.) THESE DETAILS ARE SCHEMATIC ONLY. EXACT CONFIGURATION AND


ROUTING OF ALL REFRIGERANT AND CONDENSATE PIPING TO BE
DETERMINED ON-SITE AND COORDINATED WORK OF OTHER TRADES.
INSTALL TO MANUFACTURER'S GUIDELINES.

C
C

2.) INSTALL ALL COMPONENTS TO MANUFACTURER'S RECOMMENDATIONS


AND GUIDELINES; COORDINATE w WORK OF OTHER TRADES.

3.) INDIRECTLY CONNECT CONDENSATE DRAIN FROM CONDENSATE PUMP


TO NEW FUNNEL TRAP ABOVE FIN. CEILING; REFER TO PLAN LAYOUT
FOR ADDITIONAL INFORMATION. COORD. ON-SITE. CONDENSATE PUMP
TO BE ENCLOSED WITHIN WALL CAVITY OR IN DEDICATED WALL MTD.
ENCLOSURE AS REQ'D. TO BE c/w ACCESS DOOR. COORD. w ARCH.
DIVISION. WIRE CONDENSATE PUMP TO EVAPORATOR COIL UNIT PER.
MANUF. INSTRUCTIONS.

RESIDENTIAL VILLA FOR


C2 AC SPLIT SYTEM FIXATION
N.T.S.
4.) CAREFULLY COORDINATE THE INSTALLATION OF CONDENSER UNIT ON
ROOF WITH ARCHITECTURAL AND STRUCTURAL DIVISIONS. INTEGRITY
OF ROOFING MEMBRANE TO BE MAINTAINED WATERTIGHT.
MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE

''ISSUE FOR'' ''DESCRIPTION''


INSTRUMENT TEST
PORT BODY RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
FA FOR APPROVAL DD DESIGN DEVELOPMENT
RIVET OR SCREW PS PROGRESS SET CD CONSTRUCTION
R FOR RECORD DOCUMENTS
P PRELIMINARY TD TENDER DOCUMENTS
RUBBER GASKET WITH M MUNICIPALITY REVIEW
SELF SEALING FEATURE

5 10

B
INSULATION AND LAGGING DETAIL
B

22 mm Ø HOLE
ITEM DESCRIPTION

1 G.S.S. DUCTING
2 INSULATION / LINER ADHESIVE
2a SELF ADHESIVE PIN / HANGER
3 ACCOUSTIC LINER
1 4 F.G. FLEX. BLANKET
TYPICAL INSTRUMENT TEST PORT DETAIL 2 4a F.G. FLEX. BLANKET B 27/12/2016 100 % CD FA NAGA
4b F.G. RIGID BOARD SUBMISSION
2a
5 ALUMINIUM FOIL SELF ADHESIVE TAPE A 12/05/2016 100 % DD FA NAGA
6 VAPOUR BARRIER FIRST COAT SUBMISSION
7 CANVAS CLOTH REV. DATE DESCRIPTION FOR BY
3
9 ISSUED
8 6 SECOND COAT
SAME AS ITEM BUT
ALUMINUM CLADDING 8 9 ALUMINIUM CLADDING ISSUE
OVER INSULATION FOR 7 10 50X50X0.6 mm G.I. ANGLE
EXPOSED DUCTS 1 PROJECT NO. PROJECT NUMBER
2a 4 6
2 4a
FLASHING 4b PROJECT ARCHITECT H.S.
DUCT ATTENUATOR
INSULATED C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt
ACCESS DOOR
SLOPE
REVIT FILE
AT GRILLE'S
ACOUSTIC APPLICATION SCALE As indicated
PLENUM BOX
LINING 3
DRAWN BY MF
FA FAHU A. INDOOR A/C S & R DUCT
1 2 2a 4 5 6 7 8 10
IN COND SPACES CHECKED BY EM
B. A/C DUCT S & R DUCTS IN
SHAFTS & NON COND. SPACES
1 2 2a 4b 5 6 7 8 10
10 MANAGEMENT M.SHAFY
INSTRUMENT TEST PORTS
C. ROOF EXPOSED S & R DUCTS 1 2 2a 3 4b 5 6 7 8 9
ROOF SLAB FIRE DAMPER PRINTING DATE/TIME 12/25/2016 11:57:36 AM

A
A

CONC. SLAB

DUCT INSULATION AND LAGGING M0-GE-102


2 N.T.S.

1 FRESH AIR DUCT PASSING THROUGH WALL SHEET TITLE


N.T.S.

HVAC DETAILS 2

1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

DUCT CONSTRUCTION LOW PRESSURE UP TO 500 Pa

REINFORCEMENT SUPPORT
4 Nos, 15Ø HOLES LONGEST SIZE OF DUCT ROD SIZE GAL. SPACING

25
LONGITUDINAL CLASS TYPE
FOR M-12 (mm) ANGLE (m)
ANCHOR BOLTS DUCT (mm) GAUGE CONNECTIONS

50
150
LAPPED AND BUTTED CORNER 0-300 G 26 PITTSBURGH - 6 25x25 2.4
-

50
M.S PLATE 325 - 450 G 24 PITTSBURGH * T1 8 25x25 2.4
4mm THICK A 24 *T12 - 1"X26ga

25
LINER INTERIOR THE VELOCITY RATED
No. * T1

D
SIDE OF LINER MUST 475 - 750 G 24 PITTSBURGH C 24 8 25x25 2
*T12 - 1"x26ga
D

PINS WIDTH FACE THE AIR FLOW

C
800 - 900 G 22 PITTSBURGH * T1 10 25x25 2
MS ANGLE 3 0 8" dn D 22 *T12 - 1"x24ga
(FOR SIZE SEE TABLE-2) SECTION A-A 2 9"-16" * T1
950 - 1050 G 22 PITTSBURGH 10 40x40 2

B
3 17"-28" E 22 *T12 - 1 1/8"x18ga
M-10 NUT AND BOLT ALTERNATE FOLDED
4 29"-40" CORNER * T1

C
DUCT INSULATION 5 41"-52" A 1100 - 1350 G 20 PITTSBURGH F 20 10 40x40 1.8
*T12 - 1½"x24ga
(AS PER DETAIL) 6 53"-64" E
C

DUCT SECTION B *T14 ANGLE REIF.


7 65"-76" ALL TRANSVERSE H 18
HARDWOOD PAD TYPICALLY B
1400 - 1800 G 18 PITTSBURGH H= 1½" x 20 GA 12 40x40 1.8
8 77"-88" E
EDGES TO BE COATED F+ROD
100x100x50 4ft. OR 5ft. +1½"x1½"x 3/16"
DUCT 9 89"-100" A
WITH ADHESIVE
MS ANGLE J 18 *T14 ANGLE REIF.
40*40*4 1800 - 2130 G 18 PITTSBURGH F+ROD H= 2" x 20 GA 12 40x40 1.8
MAXIMUM SPACING FOR FASTENERS INTREVALS LINER ADHERED TO THE +2" x2" x 3/16"
DUCT WITH 90% MIN. AREA
DIMENSIONS
M-10 NUT AND BOLT VELOCITY * COVERAGE OF ADHESIVE
A B C E
- TABLE BASED ON SMACNA DUCST CONSTRUCTION STANDARD
MS ANGLE CONSULTANT
(FOR SIZE SEE TABLE-2) 0-2500 FPM 3" 12" 4" 18" - CROSS BREAK OR CROSS BEAD DUCTSIDES 480 mm AND LARGER
M-12 NUT FOR
ANCHOR BOLT 2501- 6000 FPM 3" 6" 4" 16"
A A
4mm THICK H H architects engineers designers planners
MS PLATE CONCRETE PLINTH
* UNLESS A LOWER LEVEL IS SET BY MANUFACTURER OR LISTING AGENCY TEL +971 4 332 4455 FAX +971 4 332 2113

100
300x300x100 HIGH po box 73033 dubai web site www.naga.ae
ROOF INSULATION T-1
T-12 T-14
STANDING ANGLE REIFORCED DRIVE SLIP

C6 TYPI. DETAIL OF DUCT LINER INSTALLATION


C4 HORIZONTAL
N.T.S.
DUCT SUPPORT RECTANGULAR DUCT N.T.S.
B6 RECTANGULAR
N.T.S.
GALVANIZED STEEL DUCT CONSTRUCTION

C
C

DUCT SHOULD EXTEND


STRAIGHT FOR SEVERAL
USE THIS METEHOD WHENEVER DUCTS CAN BE GROUPED TOGETHER INCHES FROM A CONNECTION
BEFORE BENDING.
300 m
m MA
XIMIU
WASHER M 25mm MINIMUM

BOTTOM CHORD OF RESIDENTIAL VILLA FOR


STEEL JOIST. SEE PROJECT DRAWINGS FOR 25mm BAND CLAMP
NUMBER & SIZE WITH WIRE IS OPTINAL. MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
5/8" ALL THREAD ROD R.074, DUBAI HILLS ESTATE
MAX. SAG 1/2"
PER FOOT OF
SUPPORT SPACING
FIG. A ''ISSUE FOR'' ''DESCRIPTION''
LOCKING NUT
RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
FA FOR APPROVAL DD DESIGN DEVELOPMENT
MAX. SAG 1/2" PS PROGRESS SET CD CONSTRUCTION
25mm MINIMUM
PER FOOT OF R FOR RECORD DOCUMENTS
SUPPORT NUT SUPPORT SPACING P PRELIMINARY TD TENDER DOCUMENTS
2.1/2"x2.1/2"x1/4" ANGLE (WHERE LENGTH OF M MUNICIPALITY REVIEW
ANGLE EXCEEDS GFT. USE INTERMEDIATE SUPPORT)

B
B

FIG. B

B1 LOW PRESSURE DUCT RUNS ON TRAPEZE HANGERS


B3 FLEXIBLE DUCT SUPPORTS
N.T.S.

N.T.S.

B 27/12/2016 100 % CD FA NAGA


SUBMISSION
A 12/05/2016 100 % DD FA NAGA
SUBMISSION
REV. DATE DESCRIPTION FOR BY
10mm SQUARE ROD VOLUME DAMPER WITH ISSUED
W LOCKING TYPE INDICATOR
QUADRANT AND SADDLE ISSUE
TO CLEAR INSULATION
BRANCH DUCT PROJECT NO. PROJECT NUMBER

1/4W' , 100mm MINIMUM PROJECT ARCHITECT H.S.


SQUARE OR RECTANGULAR DIFFUSER END BEARING
C:\Users\mhegazy\Documents\15-030
1.1/2" POCKET M-VILLA_mhegazy.rvt
1" FLANGE AND HEM. SLIP
MAIN DUCT CLINCH COLLAR REVIT FILE
ALTERNATE POSITION BOLT ON 4" CENTERS
OF BOLT RUBBER IMPREGNATED DUCT SCALE N.T.S.
1"x1/8" BAND IRON FABRIC
DRAWN BY MF
45°
20 U.S GAGE STEEL CHECKED BY EM
SUPPLY
MANAGEMENT M.SHAFY
AIR FLOW
W PRINTING DATE/TIME 12/25/2016 11:57:39 AM

A
RETURN/EXHAUST
A

AIR FLOW

A1 FLEXIBLE
N.T.S.
CONNECTION DETAIL RECT DUCT ANGULAR TAP WITH VOLUME DAMPER

M0-GE-103
RECT DUCT ANGULAR TAP WITH VOLUME DAMPER
A4 AND
N.T.S.
SPLIT UNIT HANGING DETAIL SHEET TITLE

HVAC DETAILS 3

1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

DUCT JOINT
BW2

R=1-1/2BW

T
2"
T
T=1/4W

D
W
T
D

W
3" MAX DISTANCE
ANGLE TO SUPPORT

W
SUGGESTED SIZING FOR
SUPPORT OF 12 FT. OF DUCT
R=1-1/2W
DUCT SIZE ANGLE
R=1-1/2BW

T
36" x 18" 1 1/2" x 1 1/2" x 1/8"

T
W

T
48" x 24" 1 1/2" x 1 1/2" x 1/8" R=1-1/2W
W BW
60" x 30" 1 1/2" x 1 1/2" x 3/16"

60" x 60" 1 1/2" x 1 1/2" x 1/4"


or 2" x 2" x 1/8" LONG RADIUS 45° ELBOW LONG ROUND TEE LONG RADIUS 90° ELBOW
OVER 60" - INCREASE ANGLE SIZE AS
REQUIRED FOR SPACE & DUCT SIZE.
BW

C1 RISER
N.T.S.
SUPPORTS-FROM FLOOR
TURN VANES
TURN VANES CONSULTANT

W
BW+2

W
architects engineers designers planners
TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

W
BW
BW

BRANCH TAKE-OFF TEE SQUARE TURN TEE SQUARE TURN 90° ELBOW

C
C

DUCT INSULATION

DUCT SECTION

87mm (TYP)
22 GAGE
TURN VANE
R2
DUCT INSULATION DETAIL (INSIDE THE BUILDING)

ALUMINIUM CLADDING WITH


HAMMER CLAD ALUMINIUM R1
DUCT INSULATION
SHEET 0.9mm THICK
DUCTS UP THRU 550mm
RESIDENTIAL VILLA FOR
POLYTHENE SHEET
DUCT SECTION COVERING SEALED WITH 45° R1 = 50mm MR. GIRISH HIRANANDANI
POLYTHENE TAPE R2 = 25mm
DM PLOT 6316407, EMAAR PLOT PA-02
8 oz SILK CLOTH DIPPED IN DUCT OVER 550mm R.074, DUBAI HILLS ESTATE
SEALFAS 30-36 AND R1 = 65mm
COATED WITH 2 COATS OF R2 = 57mm
SEALFAS 60-95 TURN VANE DETAIL
DUCT INSULATION DETAIL (EXTERNAL/EXPOSED TO AMBIENT) ''ISSUE FOR'' ''DESCRIPTION''
RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION

B3 RECTANGULAR DUCT FITTING R FOR RECORD DOCUMENTS


P PRELIMINARY TD TENDER DOCUMENTS

B1 DUCT INSULATION N.T.S. M MUNICIPALITY REVIEW

N.T.S.

B
B

B 27/12/2016 100 % CD FA NAGA


SLAB OPENING SUBMISSION
A 12/05/2016 100 % DD FA NAGA
AIR DUCT SUBMISSION
OVERALL WIDTH
REGLET 25mm DEEP W/ OR W/OUT REV. DATE DESCRIPTION FOR BY
CONCRETE/ 50
BLOCKWORKS TO BE FILLED WITH INSULATION ISSUED
SILICON SEALANT MIN. CUT/FIT ON SITE
SILICON
SEALANT 6mm.STAINLESS STEEL S 100 x 50 x 3 ALL ISSUE
SCREW WITH MATCHING NYLON AROUND MOUNT BY SELF
ARCHITRAVE TAPPING METAL SCREW #6 W/ 25 CLEARANCE ALL AROUND PROJECT NO. PROJECT NUMBER
PLUG SPACED @ EVERY 150mm
ALL AROUND LOCK WASHERS
PROJECT ARCHITECT H.S.
0.9mm.THK. ALUMINUM
PLASTER BOARD CLADDING/FLASHING C:\Users\mhegazy\Documents\15-030
AIR DUCT
M-VILLA_mhegazy.rvt
DUCT INSULATION VAPOUR
SEAL + SHEATH AS SPEC. REVIT FILE
50

DUCTWORK VAPOUR SEAL


SCALE N.T.S.
CURB
MIN.

DENSE FIBERGLASS
50

FIN. FLR. LEV. DRAWN BY MF


FILLER
CHECKED BY EM
BOTTOM OF SLAB MANAGEMENT M.SHAFY
50

PRINTING DATE/TIME 12/25/2016 11:57:42 AM

A
MASTIC FILLER ALL AROUND
A

A1 DUCT
N.T.S.
PASSING THRU WALL A3 TYPI.
N.T.S.
DUCT THRU SLAB DETAIL M0-GE-104

SHEET TITLE

HVAC DETAILS 4

1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

MIN. SIZE OF RECTANGULAR DUCT HANGERS - COMMERCIAL SYSTEMS


HALF OF GALV. STRAPS WXT.(mm) ROD DIAMETER .(mm)
DUCT MAXIMUM HANGER SPACING (m)
PERIMETER
(P/2),in 3.00 2.40 1.50 1.20 3.00 2.40 1.50 1.20
UP THROUGH 72 25X0.75 25X0.75 25X0.75 25X0.75 6 6 6 6
96 25X1.18 25X0.91 25X0.75 25X0.75 10 6 6 6
120 25X1.46 25X1.18 25X0.75 25X0.75 10 10 6 6
168 40X1.46 25X1.46 25X1.18 25X1.18 13 10 10 10
192 40X1.46 25X1.46 25X1.46 13 13 10 10
OVER 192 b
SPECIAL ANALYSIS REQUIRED

D
D

a: TABLE BASED ON SQUARE DUCTS, 1.46 mm.THICK, AND ALLOWS FOR DUCT WT. NORMAL
REINFORCEMENTS AND TRAPEZE WEIGHTS, AND FOR INSULATION WT. NO. EXTERNAL LOADS.
b: SEE AISC MANUAL FOR HANGER DESIGN CRITERIA.

ALLOWABLE LOADS FOR TRAPEZE ANGLES (kg)


ANGLE DUCT JOINT
SIZE

25X25X1.46

40X40X1.46
(mm)

25X25X3

40X40X4

40X40X5

40X40X6

50X50X5

50X50X6

70X70X6
WIDTH
OF HANGER 50
(d)IN mm
UP THROUGH 750 30 70 80 160 230 295 425 560 890
1050 15 50 65 145 220 275 410 540 875
1200 - 35 50 130 205 260 395 525 860 ANGLE
1500 - - - 85 160 220 355 480 815
50
1650 - - - 45 120 180 320 445 780
FASTENERS
1800 - - - - 85 145 280 410 745 CONSULTANT
2000 - - - - 35 95 230 360 695
2100 - - - - - 35 170 300 635
3 NOS SANDWICH RUBBER PADS
2400 - - - - - - - 145 480 OF SIZE 100x100x32mm THICK
2750 - - - - - - - - 275
architects engineers designers planners
TEL +971 4 332 4455 FAX +971 4 332 2113
STRAP (WXT(min)mm LOAD, kg po box 73033 dubai web site www.naga.ae
ALTERNATE STRAP 25X0.75 120
OR ANGLE ROD 25X0.91 145 RISER SUPPORT FROM FLOOR
STRAP (TYP.) UPPER 25X1.18 190
ATTACHMENTS 25X1.46 320
40X1.46 500

300mm ROD (DIA.)mm LOAD, kg


MAX. SPACING 6 120

C
76 mm 10 310
C

13 570
(150 mm) 25mm MIN. 16 910
SCREWS
BOLT d MAX (TYP)
MAXIMUM ALLOWABLE
TRAPEZE HANGER STRAP HANGER STRAP AND ROD LOADS

ALTERNATE
GALVANIZED SUPPORTS (TYP)

HANGER HANGER
STRAP COUPLING STRAP

WASHER
HANGER ROD SUGGESTED SIZING RESIDENTIAL VILLA FOR
NUT X
DUCT SIZE BAND
MR. GIRISH HIRANANDANI
Y
EXPANSION SHIELDS EXPANSION NAIL POWER ACTUATED
DM PLOT 6316407, EMAAR PLOT PA-02
450 x 300 40 x 16 Ga. R.074, DUBAI HILLS ESTATE
STUDS INTO STEEL WELDED STUDS
CONCRETE ANCHORS 600 x 500 25 x 3.2

R ALLOWABLE
HO ''ISSUE FOR'' ''DESCRIPTION''
ANC LOAD PER
UPPER ATTACHMENTS RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
DUCT GAGE FASTENER* FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION

B3 DUCT HANGING & ALLOWABLE LOADS 28,26 12 Kg R FOR RECORD DOCUMENTS


24,22,20 16 Kg P PRELIMINARY TD TENDER DOCUMENTS
N.T.S. M MUNICIPALITY REVIEW
18,16 23 Kg

* WELD , BOLT OR NO.8 SCREW (MIN).


DEVIATION PERMITTED BY OTHER
ANALYSIS. X=25mm ,Y=50mm , ADD OTHERS TO
ACCOMMODATE LOAD. MIMIMUM OF 3 ON 600 mm

B
WIDTH AND UP. ADD ALONG SIDES NEAREST ANCHORS.
B

NO REDUCTION IN
FULL RADIUS ELBOW TAKE-OFF WITH MAIN DUCT SIZE
REDUCTION IN MAIN DUCT SIZE.
CURVED FOR 45 33/64
SPLITTER B 27/12/2016 100 % CD FA NAGA
SPLITTER AIR FLOW STRAIGHT
DAMPER SUBMISSION
DAMPER SLOPE 1"IN 7"
A 12/05/2016 100 % DD FA NAGA
AIR FLOW SUBMISSION
AIR FLOW D1
REV. DATE DESCRIPTION FOR BY
D1 D ISSUED
SPLITTER 3/4
4D
3/4D D+ HEEL RADIUS
ROD
D +3/ STRAIGHT ISSUE
HEEL RADIUS D SUGGESTED SIZING
SPLITTER THROAT RADIUS
ROD D 3/4 D DUCT SIZE BAND PROJECT NO. PROJECT NUMBER
THROAT RADIUS 750 x 300 25 x 25 x 3.2 PROJECT ARCHITECT H.S.
3/4 D DOUBLE THICKNESS VANES 900 x 450 25 x 25 x 3.2 C:\Users\mhegazy\Documents\15-030
1050 x 600 32 x 32 x 3.2 M-VILLA_mhegazy.rvt

1200 x 750 32 x 32 x 3.2 REVIT FILE


SPLITTER
NOTES: SCALE N.T.S.
DAMPER
AIR FLOW
DRAWN BY MF
SPLITTER 1- BRACKETS ARE SIZED FOR 3600mm OF DUCT, MAXIMUM.
ROD 2- LOCATE DUCTS AGAINST WALL OR MAXIMUM OF 50mm CHECKED BY EM
D ONLY USED WHEN SPACE
STRAIGHT D+3/4 LIMITATION DOES NOT
MANAGEMENT M.SHAFY
HEEL REDIUS AWAY FROM WALL.
SPLITTER ALLOW FULL RADIUS ELBOW PRINTING DATE/TIME 12/25/2016 11:57:45 AM
THROAT RADIUS A- TENSILE LOAD = 3/8 x DUCT WEIGHT, SAFETY FACTOR OF 4.

A
CURVED FOR DAMPER
A

45 33/64 B- SHEAR LOAD x 1/2 x DUCT WEIGHT, SAFETY FACTOR OF 4.


FOR SMALL CFM
DRANCHING
SPLITTER ROD

AIR FLOW AIR FLOW 1 VERTICAL DUCT SUPPORT M0-GE-105


N.T.S.

A1 DUCT
N.T.S.
TAKE OFFS SHEET TITLE

HVAC DETAILS 5

1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

AIR RETURN DUCT

AIR AIR
FLOW FLOW

OPPOSED BLADE - KEY


DUCT OPERATED DAMPER SECTION
EXTENSION DUCT COOLAR

D
FRAME WITH CLINCH LOCK
D

RUBBER GASKET ALL AROUND


AIR RETURN REGISTER WALL OR CEILING-SEE ARCH. PLAN GALVANIZED MOTORIZED
2" GASKET 3/4" GALVANIZED MANUAL
SHEET FOR DETAILS OF CONSTRUCTION SHEET METAL VOLUME DAMPER
SHEET METAL VOLUME DAMPER
AIR METAL DUCT WORK (SLIP-ON TYPE)
DOOR DUCT WORK (SLIP-ON TYPE)
FLOW SCREW
SPACER SPACER FIXING
SCREWS FIXING
RETURN AIR REGISTER
SCREWS
25mm THK. 25mm THK.
HINGES INSULATION
SASH LOCK INSULATION
SECTION
SECTION
25mm THK, INSULATION
(IN CONDITIONED 25mm THK, INSULATION
AIR SUPPLY DUCT SPACE) (IN CONDITIONED
SPACE)
QUADRANT
BUTT HINGE SASH LOCK CONSULTANT
WHERE DIFFUSER IS LAST ON
AIR DISTRIBUTING LINE OR BRANCH EXTEND DUCT MOTOR DRIVE
GRID QUADRANT
FLOW 2" NECK DIAMETERS EXTEND GALVANIZED SHEET
DEAD ENDING. METAL DUCT WORK GALVANIZED SHEET
MOTORIZED METAL DUCT WORK architects engineers designers planners
GALV. SHEET
NOTE: EXTENSION DUCT COLLAR VOLUME DAMPER MANUAL TEL +971 4 332 4455 FAX +971 4 332 2113
METAL EDGE GALV. SHEET
VOLUME DAMPER (SLIP-ON TYPE) VOLUME DAMPER po box 73033 dubai web site www.naga.ae
1) PRE INSULATED ACCESS DOORS TO BE MOUNED ON INSULATED DUCTS METAL EDGE
DAMPER OPERATOR END VIEW (SLIP-ON TYPE)
DUCT ANGLE END VIEW
2) BARE/NON- INSULATED ACCESS DOORS TO BE MOUNTED ON REMOVABLE
NON-INSULATED DUCTS. SPONGE RUBBER GASKET ALL AROUND TYPICAL MANUAL VOLUME DAMPER
OUTER CONE TYPICAL MOTORIZED VOLUME DAMPER
INSTALLATION DETAIL
INSTALLATION DETAIL

ACCESS DOOR IN DUCT CEILING

C
2
C

N.T.S.
SPONGE RUBBER GASKET ALL AROUND

SQUARE OR RECTANGULAR DIFFUSER

1 TYPI. MOTORIZED & MANUAL VOLUME DAMPER


N.T.S.

A3 AIR
N.T.S.
REGISTERS
RESIDENTIAL VILLA FOR
MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE

''ISSUE FOR'' ''DESCRIPTION''


RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
R FOR RECORD DOCUMENTS
P PRELIMINARY TD TENDER DOCUMENTS
M MUNICIPALITY REVIEW
15° DEFLECTION EXPANSION ANCHOR
GRILLE SOCKET (TYP.)
EYE BOLT (TYP.) UNDERSIDE OF SLAB
AIR SUPPLY DUCT
STEEL HANGING WIRE (8G) STEEL HANGING ROD
OR WIRE

B
(TYP.)
B

AIR FLOW AIR FLOW


DROP ROD (TYP) THERMAL INSULATION
INSULATED FLEXIBLE DUCT
(MAX. LENGTH 1200mm) DUCT
CT HEAVY FELT GASKET-CEMENT
Y DU U OPPOSED BLADE-KEY INTERNALLY INSULATED
PL FC TO SIDE OF DUCTS ANGLE IRON SUPPORT
SUP ROM AIR DISTRIBUTING GRID
OPERATED DAMPER DIFFUSER ADAPTER 25 MM BAND
F SECTION WOOD PIECE TO REST ON
CLAMP
EXTENSION DUCT COLLER ANGLE IRON SUPPORT
SUPPLY DUCT
FROM FCU MANUAL VOLUME CONTROL
RUBBER GASKET ALL AROUND WALL OR CEILING OPPOSED BLADE DAMPER DAMPER B 27/12/2016 100 % CD FA NAGA
SUBMISSION
CONCEALED FIXING ACOUSTIC CEILING STAINLESS STEEL
REAR BARS WORM DRIVE CLAMP FOR DUCTS UP TO 150mm A 12/05/2016 100 % DD FA NAGA
AIR SUPPLY REGISTER FACE SIZE DIAMETER AND BAND CLIP FOR LARGER SIZE SUBMISSION
AIR FLOW

REV. DATE DESCRIPTION FOR BY


NOTES: ISSUED
1.UNLESS OTHERWISE SPECIFIED THE SIZE OF DIFFUSER ADAPTER SHALL BE
AS PER MANUFACTURERS RECOMMENDATIONS. ISSUE

B6 SUPPLY AIR REGISTER 2 PROJECT NO. PROJECT NUMBER

B1 TYPICAL
N.T.S.
DETAIL OF FACE GRILLE N.T.S.
A6 SQUARE
N.T.S.
SUPPLY CEILING DIFFUSER PROJECT ARCHITECT H.S.
C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE N.T.S.
DRAWN BY MF

CHECKED BY EM
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:57:49 AM

A
A

M0-GE-106

SHEET TITLE

HVAC DETAILS 6

1 2 3 4 5 6 7
1 2 3 4 5 6 7
STAMPS
1000
1150
100 100 300 300 100 100
100mm CONCRETE 350 350
MAKEUP COVER GRADE 2 200mm PLASTER
200mm SOLID CONCRETE BLOCK
BENCHING RENDERED AND
PLASTIC OR STEEL RENTENTION STRAPS 100 TROWLLED TO 1:6 SIDE SLOPE
TO BE USED AT 300mm MIN CENTERS 150mm CONCRETE BASE
CLASS- C
BARRIER MATERIAL
(2mm THICK) BUTT JOINTS ARE ALWAYS TO BE 75mm CONCRETE BLINDING 70 350 350 70
200 300 300 200
COVERED WITH RETENTION STRAPS CLASS- D 1290
1140

VENT COWL NOTE: SHOWN DETAILS ARE FOR MANHOLES LOCATED IN FINISHED/PAVED AREA. FOR MANHOLES LOCATED IN
FIBER GLASS BATTING (25mm THICK) NON FINISHED AREA SHALL BE PROVIDED WITH CORBELLING FOR FUTURE ADJUSTMENT AT OF MANHOLE TOP.
WASTE PIPE SOIL PIPE

D
600x600 / 750x750 I.C DETAILS (FOR DEPTHS UP TO 1200 DEPTH)
D

A
ACOUSTIC LAGGING OF DRAINAGE PIPING BENCHING

200 600 200


WASH BASIN 600 600 CHANNELS
B

750
ALL HORIZONTAL uPVC SOIL AND WASTE PIPES EXCEPT THOSE AT H/L OF CAR PARKING AREAS SHALL BE PROVIDED
WITH ACOUSTIC LAGGING AS DETAILED BELOW. FLEX. COUPLINGS
60
THE BARRIER SHALL BE CONSTRUCTED OF A 2mm THICK BARIUM SULPHATE LOADED LIMP VINYL SHEET BONDED TO A THIN LAYER OF REINFORCED ALUMINIUM FOIL ON ONE SIDE. B 0
THE BARRIER SHALL HAVE A NOMINAL DENSITY OF 4.8 kg/m3 AND SHALL HAVE MINIMUM STC RATING OF 28. BATH TUB W.C. A 750
BIDET (TO NEXT JOINT) 200 600 200
THE BARRIER SHALL BE CONSTRUCTED OF A 2mm THICK BARIUM SULPHATE LOADED LIMP VINYL SHEET BONDED TO A THIN LAYER OF REINFORCED ALUMINIUM FOIL ON ONE SIDE. Ø50 TYP
THE BARRIER SHALL HAVE A NOMINAL DENSITY OF 4.8 kg/m3 AND SHALL HAVE MINIMUM STC RATING OF 28. Ø50 Ø50
THE BARRIER SHALL EXHIBIT MINIUM FLAMMABILITY RATINGS OF 0.0 SECONDS FOR FLAME OUT AND AFTERGLOW AND 0.2 INCHES FOR CHAR LENGTH WHEN TESTED IN ACCORDANCE WITH FEDERAL TEST STD NO. 191-5903. TYPICAL CONNECTION DETAIL (FOR 600x600m MANHOLE)
THE BARRIER SHALL HAVE A MINIMUM THERMAL CONDUCTIVITY "K" VALUE OF 0.29 AND A RATED SERVICE TEMPERATURE RANGE OF 40F (-40C) TO 220F(105C). WHEN TESTED FOR SURFACE BUMING CHARACTERISTICS PER ASTM E84. NOTE : PURPOSE OF ABOVE DETAIL IS TO BE SHOW LOCATION OF FLEXIBLE COUPLINGS. SAME PRINCIPAL
THE BARRIER WILL HAVE A FLAME SPREAD INDEX OF NO MORE THAN 10 AND A SMOKE DEVELOPMENT INDEX OF NO MORE THAN 40. SHALL BE FOLLOWED FOR MUTIPLE CONNECTION MANHOLES.
SYPHON FLOOR GULLY
INSPECTION EYE INSPECTION EYE
Ø110 mm WASTE PIPE
SOUND TRANSMISSION LOSS CHARACHTERISTIES FOR BARRIER SHALL BE AS FOLLOWS : CLASS-C = GRADE M:40
WASH BASIN Ø110 mm SOIL PIPE
CLASS-D =PCC 1:3:6
TESTED AS A FREE HANGING BARRIER (ASTM E-90-90) CONSULTANT
FREQENCY, Hz
PRODUCT 125 250 500 1000 2000 4000 STC BATH TUB W.C. BIDET
KNM 100 ALQ-1 16 24 33 43 49 28 NOTES FOR MANHOLES CONSTRUCTION (RCC MANHOLE)
13
Ø50 Ø50 Ø50
BARRIER SHALL BE TYPE KNM100 ALQ-1 BY 'KINETICS NOISE CONTROL INC.' OR EQUAL APPROVED. 1. FOR CONCRETE CLASS DETAILS, REFER CIVIL WORKS SPECIFICATIONS. architects engineers designers planners
2. FOR EXTERNAL SURFACES OF MANHOLE WALLS, 3 COATS OF COLD APPLIED BITUMINIOUS POINT ARE REQUIRED.
TEL +971 4 332 4455 FAX +971 4 332 2113
THE DECOUPLING LAYER SHALL BE 25mm THICK FIBER GLASS BATTING, NON WOVEN POROUS SCRIM 3. FOR INTERNAL SURFACES AND BENCHING, PROVIDE 2 COAT OF EPOXY PAINT. po box 73033 dubai web site www.naga.ae
COATED GLASS CLOTH, QUILTED TOGETHER IN A MARTIX OF 100mm DIAMOND STITCH PATTERN WHICH SYPHON FLOOR GULLY 4. PROVIDE BLINDING ON POLYTHENE SHEET, 2000 GUAGE.
ENCAPSULATES THE GLASS FIBERS. THE COMPOSITE MATERIAL SHALL BE FABRICATED TO INCULDE A INSPECTION EYE 5. PROVIDE EPOXY COATED C. I. STEPS AT 300 MM INTERNAL, STAGGEREAD, FOR ALL MANHOLES DEEPER THAN 1200 MM.
INSPECTION EYE
NOMINAL 152mm WIDE BARRIER OVERLAP TAB EXTENDING BEYOND THE QUILTED FIBER GLASS TO
FACILITATE A LEAK-TIGHT SEAL AROUND FIELD JOINTS. TO GULLY TRAP
NOTE: SHOWN DETAILS ARE FOR MANHOLES LOCATED IN FINISHED/PAVED AREA.
THE DECOUPLING LAYER SHALL BE TYPE KFA BY 'KINETICS NOISE CONTROL INC' OR EQUAL APPROVED. FOR MANHOLES LOCATED IN NON FINISHED AREA SHALL BE PROVIDED WITH CORBELLING FOR FUTURE ADJUSTMENT AT OF MANHOLE TO
TO MANHOLE

C
C

D1 ACOUSTIC
N.T.S.
LAGGING OF DRAIN PIPES C4 TYPICAL
N.T.S.
DRAIN CONNECTION DETAIL C6 TYPICAL
N.T.S.
MANHOLE CONNECTION DETAIL

RESIDENTIAL VILLA FOR


UTILITY BOX U/B TYPICAL CLEANOUT FOR MR. GIRISH HIRANANDANI
ROOF DRAIN 300X300mm DRAINAGE STACKS ABOVE DM PLOT 6316407, EMAAR PLOT PA-02

300
(REFER TO MECH. DRWGS.) F.CEILING AT EVERY FLOOR. R.074, DUBAI HILLS ESTATE
PROPRIETARY METAL ROOF OUTLET
ADJUSTABLE TO REQUIRED LEVEL
LOOSE GRAVEL AROUND DRAIN WASHING MACHINE
NO CUT SLABS HOSE ''ISSUE FOR'' ''DESCRIPTION''
2" MAIN VENT
400x400x40 LOOSELY LAID 7cm seal PIPE RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
CONCRETE TILES ON P.V.C PAD min FA FOR APPROVAL DD DESIGN DEVELOPMENT
2"
SQ. GRATING 50 EXTRUDED POLYSTYRENE F.F.L PS PROGRESS SET CD CONSTRUCTION
INSULATION DOUBLE SEALED Ø 50 mm SEALED CHROME
ACCESS PLUG F.F.L. R FOR RECORD DOCUMENTS
RECESSED COVER PLATED COVER F.F.L
WATERPROOFING MEMBRANE P PRELIMINARY TD TENDER DOCUMENTS
1000 MM

4 TORCH APPLIED
(3'-3")

100mm THICK FT M MUNICIPALITY REVIEW


VARIES

FOAM CONCRETE LAID TO FALLS ACCES PLUG DOOR-(To Architect's Detail)


SOLID BLOCK ABOVE F.CEILING FOR
50 AT OUTLET 80 AT PERIMETER Ø50 mm
FFL INLET PIPE Ø110 OUTLET ACCESS TO DRAINAGE
ROOF SLAB TO Ø80 mm TO WASTE STACK STACKS CLEANOUTS.
ENGINEER' S DETAIL
CONCRETE BENCHING 2"

B
Ø100 R.W.P.
B

ACCESS PLUG IN WASHING MACHINE CONNECTION WASHING MACHINE


B1 RAIN
N.T.S.
WATER OUTLET DOME TYPE B2 VERTICAL
N.T.S.
RISER B3 TYPICAL
N.T.S.
DRY GULLY TRAP DETAILS DETAIL (CONCEALED)
B4 N.T.S. B5 CONNECTION
N.T.S.
DETAIL (EXPOSED) B6 ACCESS
N.T.S.
DOOR
B 27/12/20 100 % CD FA NAGA
16 SUBMISSION
A 12/05/20 100 % DD FA NAGA
16 SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED

ISSUE

PROJECT NO. PROJECT NUMBER


FLOOR SLAB
FCU SLEEVE PROJECT ARCHITECT H.S.
CEILING C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt
UPVC SEALED COVER "U" TRAP SIZE TO BE AS PER
RODDING EYE
FLOOR SLAB A/C EQUIPMENT. REVIT FILE
FLOOR FINISHES THICKNESS FLOOR SLABS
SLEEVE
FLOOR TRAP COVER SCALE N.T.S.
CONDENSATE DRAIN PIPE F.F.L. / S.S.L.
SUBJECT TO APPROVAL
DRAWN BY Author

150
200MM
(MIN)
VARIES

INSPECTION CHAMBER CHECKED BY Checker


300x300(12"x12") MIN CLEAN OUT
FLOOR DRAIN HEPSEAL ACCESS CAP MANAGEMENT M.SHAFY
CLEAN OUT Ø50 (2") INLET Ø82 (3") OUTLET

150
FFL Ø82 OUTLET
FFL PRINTING DATE/TIME 12/25/2016 11:57:53 AM

A
PIPE SUPPORT(TYP)
A

SHORT RADIUS BEND


150 150
FLOOR TRAP
SUBJECT TO APPROVAL

M0-GE-107
FCU/AHU CONDENSATE CONCRETE PROTECTION
A1 FLOOR
N.T.S.
CLEAN OUT A2 DRAIN
N.T.S.
CONNECTION A3 PIPE
N.T.S.
BEND IN STACKS A4 PIPE
N.T.S.
BEND AND CLEAN OUT A5 TYPICAL
N.T.S.
FLOOR TRAP DETAIL A7 OF PIPES UNDER BUILDINGS
N.T.S.
SHEET TITLE

DRAINAGE DETAILS 1

1 2 3 4 5 6 7
1 2 3 4 5 6 7
STAMPS

WASH BASIN

WB
15Ø FLEXIBLE BLOCK WALL
BOTTLE TRAP CONNECTOR
SINK COUNTER

4100
KITCHEN
40Ø TRAPPED WASTE

550
KITCHEN SINK

2250
1260
F.F.L F.F.L

32Ø WP

D
FT
D

110Ø EXTENSION PIPE


FLOOR BEAM 50Ø WP FROM
200Ø SLEEVE IN BEAM KITCHEN SINK BOTTLE TRAP
F.F.L S.S.L

32ØWP

140
82Ø WP 75Ø SLEEVE IN BEAM 2ND FL. FT

FLOOR DRAIN PIPE SUPPORT FLOOR SLAB

82Ø WP

TYPICAL DETAIL FOR WASH BASIN

CONNECTED TO FLOOR DRAIN CONSULTANT


TYPICAL KITCHEN SINK CONNECTION DETAIL TO FT

C1 TYPICAL
N.T.S.
DETAIL FOR WASH BASIN CONNECTED TO FLOOR DRAIN architects engineers designers planners
TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

110 VENT
160 WASTE

C
STACK
STACK
C

160 SOIL
ACCESS PANEL FOR STACK
DRAINAGE CLEANOUT
AT EVERY FLOOR (TO
ARCHITECT'S DETAIL
BY OTHERS) ACCESS PLUG

PIPE CLAMP
VENT CONNECTION
3000

@ EACH FLOOR

FLOOR OPENING
RESIDENTIAL VILLA FOR
FLOOR SLAB MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE
CONNECTION FROM CONNECTION FROM
INDIVIDUAL FLOOR INDIVIDUAL FLOOR

''ISSUE FOR'' ''DESCRIPTION''


SHAFT FOR
DRAINAGE PIPES RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
PIPE CLAMP R FOR RECORD DOCUMENTS
P PRELIMINARY TD TENDER DOCUMENTS
M MUNICIPALITY REVIEW

B
B

TYPICAL VENT STACK CONNECTION


B1 AND
N.T.S.
ACCESS PANEL DETAIL B3 ROODING
N.T.S.
EYE DETAILS & EXTENSIONS

B 27/12/20 100 % CD FA NAGA


16 SUBMISSION
A 12/05/20 100 % DD FA NAGA
16 SUBMISSION
REV. DATE DESCRIPTION FOR BY
GRADE ISSUED
LEVEL
ISSUE
TOP SOIL/ROAD SUB- 20 SCHEDULE OF DRAIN PIPE SLOPE PIPE SIZES:
BASE 0 PROJECT NO. PROJECT NUMBER
PIPE SIZE MINIMUM SLOPE(UNO)
PIPE SIZES FOR CONNECTIONS FROM SANITARY
WARNING TAPE Ø200 1:120 PROJECT ARCHITECT H.S.
FIXTURES / APPLIANCES SHALL BE AS FOLLOWS. (UNO)
Ø160 1:90 C:\Users\mhegazy\Documents\15-030
SELECTED MATERIAL 400 FOR WATER DRAIN M-VILLA_mhegazy.rvt
BACKFILL FREE OF CLAY, SR. NO. SANITARY FIXTURE mm
MAIN (VARIES FOR Ø110 1:60
LUMPS OF 75mm or LARGE DRAINAGE PIPE) REVIT FILE
Ø82 1:50 1 WATER CLOSET (WC) 110
DIA, STONES OF 40mm or
LARGE DIA, TIMBER PIECES, Ø50 1:40 2 WASH BASIN 32 SCALE N.T.S.
ROOTS OF TREES ETC.
100 Ø40 1:30 3 SHOWER 40 DRAWN BY Author

PIPE Ø32 1:30 4 BATH TUB 40


IMPORTED GRANULAR CHECKED BY Checker
MATERIAL 5 TO 10mm 5 WASHING MACHINE 40
SIZE 100 MANAGEMENT M.SHAFY
6 BIDET 32
PRINTING DATE/TIME 12/25/2016 11:57:54 AM
SHEDULE OF DRAIN PIPE SLOPES 7 KITCHEN SINK 40

A
150 PIPE 150
A

8 URINAL 32
9 CLEANERS SINK 40
10 FLOOR TRAP OUTLET 80
M0-GE-108
BEDDING & BACKFILL DETAIL SHEDULE OF PIPE SIZES

IN ACCORDANCE WITH BS-8301 SHEET TITLE


FOR EXTERNAL PIPES
A4 N.T.S. A1 SCHEDULE
N.T.S.
OF PIPE SLOPES AND SIZES
DRAINAGE DETAILS 2

1 2 3 4 5 6 7
1 2 3 4 5 6 7
STAMPS

φ75 VENT

COLOURED SEALANT TO MATCH


600X600mm GROUT WITH BACKING ROD
FLOOR LEVEL LD C.L. COVER
PRE FIXED TILES,
INSULATION, WATER
PROOFING MEMBRANE, &
ACCESS
SCREED AS DETAILED IN
PLUG
ARCH./STRUCTURAL
INLET DRAWING
OUTLET

D
D

ALUMINIUM PERFORATED
BUCKET FOR FILTRATION
R.C. SLAB

RWP

D3 SAND TRAP DETAIL


N.T.S.

1 TYPICAL RAIN WATER OUTLET DETAIL


N.T.S.

CONSULTANT

architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

Manhole Cover Slab 600X600 Inspection Chamber


(Slag Concrete) with C.I Cover and Frame
Finished Ground Level

C
φ100mm
C

A A
3mm Thick G.R.P Lining
Applied in Concrete
two coats TOILET TOILET
200mm Thick solid concrete To receiving Manhole slope 1%
blocks or concrete with 'X' IS SUBJECT TO THE
normal steel IL depends upon the
WC APPROVAL OF SAN. FIXTURE.
150mm Concrete (Slag cement) base receiving manhole IL
100mm Concrete Blinding 110Ø SP @
-600 from F.G.L L/L INSIDE WC
FFL SSL F.F.L S.S.L
THE CAVITY X

X
Incoming Pipe from
Lifting Section FLOOR BEAM
PLAN SECTION A-A FLOOR BEAM 300x200 CUTOUT 110Ø SP
RESIDENTIAL VILLA FOR

600
(max)
IN BEAM
Ø110 SP FROM WC
MR. GIRISH HIRANANDANI
110 SP TO 'X' IS SUBJECT TO THE DM PLOT 6316407, EMAAR PLOT PA-02
MAIN PIPE APPROVAL OF SAN. FIXTURE. PIPE SUPPORT R.074, DUBAI HILLS ESTATE

''ISSUE FOR'' ''DESCRIPTION''

D6 PRESSURE
N.T.S
BREAK MANHOLE RC
FA
REVIEW & COMMENTS
FOR APPROVAL
SD SCHEMATIC DESIGN
DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
R FOR RECORD DOCUMENTS

2 TYPICAL DETAIL FOR WATER CLOEST IN TOILET P


M
PRELIMINARY
MUNICIPALITY REVIEW
TD TENDER DOCUMENTS
N.T.S.

B
B

EPOXY COATED PROPRIETARY 100 mm THICK MEDIUM


PLANTER DRAIN WITH MESH SIZE GRAVEL LAYER
COVERED DOME (REFER TO 100 mm THICK FINE
THE DRAINAGE DRAWINGS) GRAVEL LAYER B 27/12/20 100 % CD FA NAGA
ORGANIC FIBRE 16 SUBMISSION
FILTER LAYER A 12/05/20 100 % DD FA NAGA
16 SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED

ISSUE

PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


SSL
C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE
COLD APPLIED GALVANIZED STEEL PIPE SCALE As indicated
WATERPROOFING MEMBRANE SLEEVE WITH NON-LEAK
PUDDLE FLANGE DRAWN BY Author
LIGHT WEIGHT CONCRETE
LAID TO SLOPE (MINIMUM CHECKED BY Checker
RC SLAB (REFER TO THE
THICKNESS 50 mm)
STRUCTURAL DRAWINGS)
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:57:57 AM

A
A

M0-GE-109
D7 PLANTER
N.T.S.
DRAIN DETAIL
SHEET TITLE

DRAINAGE DETAILS 3

1 2 3 4 5 6 7
1 2 3 4 5 6 7
STAMPS

15mm PIPE
1) SHOULD BE HEAVY DUTY FOR
R.C.C. BLOCK PARKING AREA AND DRIVE WAY.
2) MEDIUM DUTY FOR OTHER AREAS.

BIB TAP
RCC SLAB
RCC SLAB REDHEAD FIXING INTO CONCRETE

D
REDHEAD FIXING
D

BINDER ADJUSTABLE ASSEMBLY

VARIES

0'-10"
INTO CONCRETE P.P.R PIPE

VARIES
GALVANISED DROP STANDARD BINDER EYEBOLT
800mm

ROD 6.3mm DIA


STANDARD BRASS STANDARD BINDER PIPE CLIP ALL U/G. PIPES SHOULD BE
HOLDERBAT INSIDE OF THE CHANNELS

(UP TO 50mm DIA) WIDTH=SUM DIAMETERS OF PIPE +6"


(ABOVE 50mm DIA)
WATER SUPPLY PIPE CHANNEL DETAIL

BIB TAP CONNECTION DETAIL


D4 PIPE SUPPORT 1
D5 PIPE SUPPORT 2
B6 WATER SUPPLY PIPE CHANNEL DETAIL
N.T.S.
N.T.S.

D1 BIB TAP CONNECTION DETAIL N.T.S.

N.T.S.

CONSULTANT

architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

COLD WATER MAIN LINE


(INDICATIVELY SHOWN)

FALSE CEILING

C
C

PIPE
M.S GALV FLAT CHROME PLATED IV IV
ANGLE VALVE
15
CLOSING VALVE
FORK SUPPORT

50mm x 50mm MS GALVANISED INSULATED


CHANNEL FRAME BOLTED ON WALL HANDLE FLUSH TANK
(ABLUTION FAUCET)
10mm FLEXIBLE
ST.ST. HOSE RESIDENTIAL VILLA FOR
1000mm LONG 32
OUT SIDE WALL OF CONCRETE WATER
MR. GIRISH HIRANANDANI
BASE MOUNTED TANK DM PLOT 6316407, EMAAR PLOT PA-02
646.12

F.F.L R.074, DUBAI HILLS ESTATE


646.12

50 150

150
CONCRETE BLOCK WALL ''ISSUE FOR'' ''DESCRIPTION''
RC REVIEW & COMMENTS SD SCHEMATIC DESIGN

A5 TYPICAL W.C WATER SUPPLY CONNECTION DETAILS FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
N.T.S.
50 CWS PIPE FOR TANK INLET OR SUCTION PIPE R FOR RECORD DOCUMENTS

B2 PIPE SUPPORT 3 P PRELIMINARY TD TENDER DOCUMENTS


N.T.S. M MUNICIPALITY REVIEW

CONTINUOUS WELD

150
S.STEEL (4MM THICK)

B
B

EXPANSION
5 ANCHOR (TYP.) THREADED ROD
20 CWS 20 CWS (TYP.)
4 22 HWS

3 B 27/12/20 100 % CD FA NAGA


ADAPTOR 16 SUBMISSION
A 12/05/20 100 % DD FA NAGA
16 SUBMISSION
2 FALSE CEILING
REV. DATE DESCRIPTION FOR BY
ISSUED
16 CWS PEX CONDUIT 16 CWS PEX CONDUIT
1
IN WALL CHASE CAST IN CONCRETE WALL

1 PIPE THROUGH WATER TANK ISSUE


3500

TOILET
N.T.S
PROJECT NO. PROJECT NUMBER

RIGID FLEXIBLE CONNECTION PROJECT ARCHITECT H.S.


FLUSH CISTERN C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt
2400

ABLUTION HOSE
300 FLEXIBLE CONNECTION REVIT FILE
120

CHROME PLATED 300


1. R.C/SOLID BLOCK SUPPORT WITH PLASTER & EPOXY ANGLE VALVE SCALE As indicated
2. RUBBER PAD TO APPROVAL CHROME PLATED
3. ROOF WATER SUPPLY PIPE TO SPEC. FLEXIBLE CONNECTION DRAWN BY Author
4. PIPE INSULATION TO SPEC. CHECKED BY Checker
16 PEX PIPE TERMINATED WITH
5. FIXING CLAMP TO APPROVAL
850

WALL BOX & FEMALE ELBOW MANAGEMENT M.SHAFY


650
550

TO CONNECT ANGLE VALVE/STOP COCK ESCUTCHEON


100

PRINTING DATE/TIME 12/25/2016 11:58:01 AM


350

(TYP.) PLATE

A
A

A1 TYPICAL
N.T.S.
ROOF WATER SUPPLY INSTALLATION M0-GE-110

SHEET TITLE

A3 TYPICAL
N.T.S.
PEX PIPE INSTALLATION
WATER SUPPLY DETAILS 1

1 2 3 4 5 6 7
1 2 3 4 5 6 7
STAMPS

C A
D
10
G
E OUTLET
9
8 7 6
B 5
4

D
3
D

2
F 1

PRESSURE REDUCING VALVE I


WITH BUILT IN STRAINER AND UNION (FOR
SINGLE END UNION
J
MAINTENANCE OF PRV) H
ISOLATING VALVE ISOLATING VALVE
NORMALLY OPEN NORMALLY OPEN

PRESSURE GAUGE PRESSURE GAUGE

CONSULTANT

architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

Dimension in CM
A B C D E F G H I J
40 60 20 20 20 25 10 80 (Min:) 120 (Max:) 7.5 (dia:)

1 2 3 4 5 6 7 8 9 10
REGULATING VALVE

C
G.M.P.F G.M Inlet Nozzel Pad Locking Water Meter Viewing Protection Cover Outlet Gate Valve Union ( Threaded
NORMALLY CLOSED Adaptor Stop Meter Nozzle (Consumer side) Type )
C

Arrangement ( Perspex (size : with Hinges on Top


(1" x 1/2") Cock Hole Size 10mm 12.5 cm x12.5 cm) (Size 15cm x15cm)
(1/2") dia.)
Note:
1- Meter Viewing Perspex (Min : 5mm thickness) with Hinged Type Protection Cover .
2- Threaded type union is proposed for the purpose of replacing the meter with different meter lengths
3- Minimum 2 mtr. clearance shall be maintained between electricity and water service points.

C1 PRESSURE
N.T.S.
REDUCING VALVE ASSEMBLY (PRV) 1 ARRANGEMENT OF WATER METERING CABINET ON WALL
N.T.S

RESIDENTIAL VILLA FOR


MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE

6 5

6 5 ''ISSUE FOR'' ''DESCRIPTION''


RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
COVER 600 X 600MM R FOR RECORD DOCUMENTS
P PRELIMINARY TD TENDER DOCUMENTS
FLOAT VALVE TANK VENT M MUNICIPALITY REVIEW
WITH INSECT
GATE VALVE
SCREEN VALVE BOX COVER
VALVE BOX COVER GROUND FLOOR +0.15
SITE +0.00

B
B

SCHEDULE OF PIPE SIZE PIPE HANGER SCHEDULE FOR uPVC / PPR


NOMINAL SIZE uPVC PIPE uPVC/PPR PIPE HANGER ROD uPVC PIPE SUCTIONLINE

500
FLOOR SLAB
(INCH) SIZE (DIA mm) SIZE (DIA mm) (DIA mm) HORIZONTAL (m) FILL LINE 25mm (MIN.) 50mm
GALVANISED ANGLE 40x40mm (MIN.)
1/2" 15 15 8 1.050 FRAME ALL AROUND
3/4" 20 20 8 1.050 GAL. CHEQUERED PLATE RCC WATER TANK
HIGH LEVEL ALARM
4mm THICK HOT DIPPED 9 M3

1500
1" 25 25 8 1.050 GALVANISED.
HANGER ROD OFF FOR TRANSFER PUMP
1 1/4" 32 32 8 1.050
B 27/12/20 100 % CD FA NAGA
1 1/2" 40 40 8 1.050 GAL. ANGLE 40x40 ON FOR TRANSFER PUMP 16 SUBMISSION
2" 50 50 8 1.050 PIPES AT LOWER LEV. LOW LEVEL. A 12/05/20 100 % DD FA NAGA
DOMESTIC FOOT VALVE 16 SUBMISSION
2 1/2" 65 65 8 1.020 PIPE CLAMP
WATER REV. DATE DESCRIPTION FOR BY
3" 80 80 10 1.350 ISSUED
4" 100 100 10 1.750 40x40mm FRAME
ISSUE
1. HANGER WITHIN 600mm OF EACH SIDE OF VALVE, ELBOW & TEE TO BE PROVIDED.
PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

B1 SCHEDULE OF PIPE SIZE AND PIPE HANGER DETAIL FOR uPVC/PPR REVIT FILE
N.T.S.

B4 FOOT BRIDGE DETAIL A6 TYPICAL


N.T.S
DETAIL OF WATER TANK SCALE As indicated
N.T.S. DRAWN BY Author

CHECKED BY Checker
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:58:04 AM

A
A

M0-GE-111

SHEET TITLE

WATER SUPPLY DETAILS 2

1 2 3 4 5 6 7
1 2 3 4 5 6 7
STAMPS

D
D

PRESSURE VESSELS (AS


SPECIFIED)

I.V

RECIRCULATION PUMP SOLAR PANEL


I.V. N.R.V. I.V.
CONTROL
PANEL
SUCTION HEADER DISCHARGE HEADER

EXPANSION VESSEL
I.V. N.R.V. I.V. AND DRAIN
P
STRAINER

PRESSURE GAUGE CONSULTANT


DUTY/ ELECTRIC
STANDBY DISCHARGE PIPE I.V
I.V.

HEATER
P PUMPS P.R.V
PRESSURE TEST POINTS. COIL FOR I.V
I.V. I.V. (TYPICAL) SOLAR
FORM SCW architects engineers designers planners
PRESSURE TEST POINTS. TEL +971 4 332 4455 FAX +971 4 332 2113
SUCTION PIPE (TYPICAL)
DRV po box 73033 dubai web site www.naga.ae
FROM TANK(S)
PRESSURE REGULATING
I.V I.V. VALVE (TYPICAL) SOLAR SYSTEM
SCHEMATIC DIAGRAM

A1 TYPICAL
N.T.S.
DETAIL OF DOMESTIC BOOSTER WATER PUMP SET 1 SOLAR SYSTEM
N.T.S.

C
C

RESIDENTIAL VILLA FOR


MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE

''ISSUE FOR'' ''DESCRIPTION''


RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
R FOR RECORD DOCUMENTS
P PRELIMINARY TD TENDER DOCUMENTS
M MUNICIPALITY REVIEW

CONTROL PANEL
CONTROL PANEL

B
B

MOTOR
MOTOR B 27/12/20 100 % CD FA NAGA
16 SUBMISSION
18 LIT PRESSURE VESSEL (P.V.)
A 12/05/20 100 % DD FA NAGA
FLEXIBLE PIPE 16 SUBMISSION
PRESSURE GUAGE REV. DATE DESCRIPTION FOR BY
18 LIT PRESSURE VESSEL (P.V.) ISSUED
NON-RETURN VALVE
REGULATING VALVE ISSUE
REGULATING VALVE
PROJECT NO. PROJECT NUMBER

T P P PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE As indicated
DRAWN BY Author

B1 TYPICAL DETAIL OF DOMESTIC BOOSTER WATER PUMP SET CHECKED BY Checker

N.T.S. MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:58:06 AM

A
A

M0-GE-112

SHEET TITLE

WATER SUPPLY DETAILS 3

1 2 3 4 5 6 7
1 2 3 4 5 6 7
STAMPS
HOOK
REFER BRACKET
ENLARGED
VIEW SCREW

FB
670
4.5 Kg
CO2 FIRE PROTECTION EQUIPMENTS NOTES SCREW
1. ALL FIRE SERVICES EQUIPMENT SHALL BE MANUFACTURED BY ONE OF THE CIVIL DEFENSE APPROVED MAKE. BRACKET
4.5 Kg.
CO2

1200

1200
2.ALL FIXED AND PORTABLE FIRE FIGHTING EQUIPMENTS SHALL BE TESTED BY INTERNATIONALLY RECOGNIZED FIRE

1160

1160

D
TESTING LABORATORIES & SAFETY ORGANIZATIONS BASED ON CERTIFICATION & NOT TESTED REPORTS.
D

4.5 Kg
CO2
140 3.ALL FIRE EQUIPMENTS TO BE PAINTED RED, AND CLEARLY INDICATEDBY AN APPROVED SIGN SYSTEM.

ENLARGED VIEW

FFL FFL

ELEVATION CONSULTANT
FIRE BLANKET ELEVATION

architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

1.6MM THICK 75
M.S.BLACK SCREW HOLE HOOK
ENAMEL 4.5KG
COATED
70

70

CO2

C
60
C

FRONT VIEW SIDE VIEW PLAN VIEW

WALL BRACKET

CO2 EXTINGUISHERS MOUNTING DETAIL RESIDENTIAL VILLA FOR


SCALE : NTS MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE

''ISSUE FOR'' ''DESCRIPTION''


RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
R FOR RECORD DOCUMENTS
P PRELIMINARY TD TENDER DOCUMENTS
M MUNICIPALITY REVIEW
REFERE
500

4.5KG ENLARGED VIEW


DP
4.5KG
DP

B
B

1200

170
1050

4.5KG
DP
B 27/12/20 100 % CD FA NAGA
16 SUBMISSION
CLAMP A 12/05/20 100 % DD FA NAGA
SCREW 16 SUBMISSION
REV. DATE DESCRIPTION FOR BY
BRACKET
FFL ISSUED

ENLARGED VIEW ISSUE

PROJECT NO. PROJECT NUMBER

ELEVATION PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE 1:2

59 DRAWN BY Author

SCREW HOLE CHECKED BY Checker


1.6MM THICK MANAGEMENT M.SHAFY
CLAMP
PRINTING DATE/TIME 12/25/2016 11:58:09 AM

A
190

190

4.5KG
A

DP

M0-GE-113
FRONT VIEW SIDE VIEW PLAN VIEW

SHEET TITLE
WALL BRACKET

1 FIRE PROTECTION GENERAL DETAILS FIREFIGHTING DETAILS


1:2

1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

D
D

1 2 3 4 5 6 7 8
150x150 EAD
TO GOOZENECK

EF-03

ER 300X100
80.0 L/s
SR 300X100
80.0 L/s
POOL PUMP ROOM CONSULTANT
FAF-01

150x150 SAD
TO GOOZENECK architects engineers designers planners
TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

C
C

VD@40 L/S

IU-06
400x300 E
STAIRS
B-16
LOBBY SFBD-1SLOT-38 MM

350x300
200x100 5NOS. 485.0 L/s
B-14
RFBD-1SLOT, 38 MM
4M RESIDENTIAL VILLA FOR
MR. GIRISH HIRANANDANI

200x300
MECH. RM VD DM PLOT 6316407, EMAAR PLOT PA-02
B-13 R.074, DUBAI HILLS ESTATE

150x250
EFBD - 1SLOT-0.6 M ɸ250
25.0 L/s TYP.
DRIVER'S WC
B-07 ''ISSUE FOR'' ''DESCRIPTION''
STAIRS VD@50 L/S
B-15 D RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
200x250 ɸ250 FA FOR APPROVAL DD DESIGN DEVELOPMENT
IU-02

VD TYP.
VD 350x300 PS PROGRESS SET CD CONSTRUCTION
400x300
VD@30 L/S 200x300 R FOR RECORD DOCUMENTS
UC
SFBD-1SLOT-38 MM
SFBD - 1SLOT-25 MM DRIVER'S ROOM 250x200 5NOS. 485.0 L/s
P PRELIMINARY TD TENDER DOCUMENTS
B-08 150x100 M MUNICIPALITY REVIEW

400x300
2NOS 145.0 L/s T RFBD-1SLOT, 38 MM
150x100

ɸ200 VD@15 L/S


RFBD-1SLOT-25 MM BMO 350X200 4M
100x200

2M TYP.
C/W.M.S. 200x100
GYM
200x250

STORAGE ɸ200 B-06


EF-02
IU-01

B-10 TYP.
UC 150x250 200x250 VD
EF-02 LAUNDRY IU-06 T VD@15 L/S
300x200 FAD

B
UC B-09 T
100x200
150x100 STAIRS C
B

UC T
EFBD - 1SLOT-25 MM B-17
ɸ200 SFBD - 1SLOT-25 MM ɸ200
WATER TANK 25.0 L/s TYP. VD VD
B-11 IU-01 3NOS. 225.0 L/s TYP.
IU-03

PUMP ROOM RFBD-1SLOT-25 MM 250x250


B-12 250x250 3M 150x250
CORRIDOR B
T B-04
150x300

SCD 300X300 UC UC SFBD - 1SLOT-25 MM OFFICE


145.0 L/s STORAGE ɸ150 POWDER 3NOS. 225.0 L/s B-05
RCD 300X300 B-01 TYP. B-03 IU-03 RFBD-1SLOT-25 MM
ɸ250 PANTRY 3M
B-02 BD 250x250
200x250 EAD T B 27/12/2016 100 % CD FA NAGA
T/A EFBD - 1SLOT-25 MM BMO 450X250
25.0 L/s SUBMISSION
C/W.M.S.
EFBD - 1SLOT-0.6 M A 12/05/2016 100 % DD FA NAGA
25.0 L/s SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED

ISSUE

PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE 1 : 100
DRAWN BY MF

CHECKED BY EM
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:58:13 AM

A
A

TRUE
PRO 35°
N N JEC
T

QIBLA
258°
M1-AC-101
SCALE 1:100

1 AC-BASEMENT FLOOR PLAN 0 1 3 5m

1 : 100 SHEET TITLE

AC LAYOUT - BASEMENT
FLOOR PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

D
D

1 2 3 4 5 6 7 8

GOOSENECK
WITH MESH

CONSULTANT
GOOSENECK
WITH MESH

architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

F F
EFBD - 1SLOT-25 MM ɸ200

C
50.0 L/s VD TYP.
300x250 300x250
C

ɸ150 150x250 VD 150x250


TYP. FAMILY DINING\
RECIRCULATING SFBD - 1SLOT-25 MM FAMILY LIVING
HOOD BD 6NOS. 485.0 L/s SHOW KITCHEN G-18

400x300
RFBD-1SLOT-25 MM G-19

100x200
BMO 700X300
6M C/W.M.S.
300x100
VD@80 L/S T
T

500x250
EFBD - 1SLOT-0.6 M E E
25.0 L/s STAIRCASE
IU-06 UC G-17
DRY STORAGE
150x200 FAMILY POWDER R.
G-15
250x100 G-16 RESIDENTIAL VILLA FOR
BD
RECIRCULATING
HOOD
MR. GIRISH HIRANANDANI
200x100
DM PLOT 6316407, EMAAR PLOT PA-02
IU-02

CORRIDOR R.074, DUBAI HILLS ESTATE


LPG CABINET VD@40 L/S 200x300 ɸ250 G-10
G-20 FRY KITCHEN
300x200

SCD 300X300 G-14


EFBD - 1SLOT-0.6 M 170.0 L/s
25.0 L/s 200x200
RCD 300X300 ''ISSUE FOR'' ''DESCRIPTION''
ECD 300X300 UC
50.0 L/s BMO 350X200
T RFBD-1SLOT-25 MM RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
STAIRS
B-15 C/W.M.S. 4M D D FA FOR APPROVAL DD DESIGN DEVELOPMENT
200x100 PS PROGRESS SET CD CONSTRUCTION
MAID'S BATH R. R FOR RECORD DOCUMENTS
250x200 CORRIDOR 250x450 FAD ɸ200
P PRELIMINARY
G-13 IU-02
150x100 G-11 TYP. TD TENDER DOCUMENTS
UC MAID'S ROOM F/A M MUNICIPALITY REVIEW
100x200 G-12 200x250
VD@30 L/S
SFBD - 1SLOT-25 MM T VD@15 L/S
2NOS. 235.0 L/s SFBD - 1SLOT-25 MM
150x100 10NOS. 835.0 L/s
200x250

RFBD-1SLOT-25 MM VD
2M RFBD-1SLOT-25 MM
SFBD - 2 SLOT- 38 MM BAR 10M
300x250

400x250
200x250 305.0 L/s G-05 FORMAL LIVING & DINING
300x150

250x300 EAD VD

B
ɸ200 VD@80 L/S G-04
T/A
B

TYP. VD@40 L/S VD ɸ250 300x100 STAIRS C C


ɸ200 200x100 VD B-17
SFBD - 1SLOT-25 MM TYP.
TYP.
IU-05

IU-09
150x250

3NOS. 235.0 L/s 350x300 600x300


RFBD-1SLOT-25 MM T
3M
W/O T ɸ200 B B
CLOSET

400x250
T
250X200 ENTRANCE TYP.
VD GUEST BEDROOM G-07
G-01 SFBD - 1SLOT-25 MM
G-06 150x250 2NOS. 100.0 L/s
100x200

300x250 VD B 27/12/2016 100 % CD FA NAGA


SUBMISSION

200x250
BMO 500X250 SFBD - 1SLOT-25 MM
UC 250x300 50.0 L/s A 12/05/2016 100 % DD FA NAGA
300x250

UC
C/W.M.S. SUBMISSION
ROOF ACCESS GUEST BATHROOM RFBD-1SLOT-25 MM FORMAL POWDER R.1
G-09 IU-04 UC
G-08 G-03 REV. DATE DESCRIPTION FOR BY
ISSUED
ɸ150
ɸ150
100x200 ISSUE
TYP. EFBD - 1SLOT-0.6 M
25.0 L/s A A
EFBD - 1SLOT-0.6 M EFBD - 1SLOT-0.6 M PROJECT NO. PROJECT NUMBER
10.0 L/s 25.0 L/s
PROJECT ARCHITECT H.S.
C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE 1 : 100
DRAWN BY MF

CHECKED BY EM

? MANAGEMENT M.SHAFY
?
PRINTING DATE/TIME 12/25/2016 11:58:18 AM

A
PEDESTRIAN ENTRANCE
A

TRUE
PRO 35°
G-23
N N JEC
T

QIBLA
258°
M1-AC-102
SCALE 1:100

0 1 3 5m

A1 AC-GROUND
1 : 100
FLOOR PLAN SHEET TITLE

AC LAYOUT - GROUND
FLOOR PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

D
D

1 2 3 4 5 6 7 8
CONSULTANT

architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

VD
ɸ250 F
300x300 300x300 TYP. ɸ200 ɸ200
VD

C
150x300 150x300 TYP.

150x250
VD TYP.
400x250
C

SFBD-1SLOT-38 MM
FAMILY LIVING 250x250
6NOS. 635.0 L/s F-01
RFBD-1SLOT-25 MM SFBD - 1SLOT-25 MM
3NOS. 225.0 L/s SFBD - 1SLOT-25 MM
6M MASTER BEDROOM 5NOS. 485.0 L/s

500x300

500x250
RFBD-1SLOT-25 MM

250x250
F-02 RFBD-1SLOT-25 MM
6M
5M
BMO 900X400
150x100
C/W.M.S. T
VD@25 L/S
E
IU-03
SFBD - 1SLOT-25 MM IU-06
50.0 L/s VD 250x150
RFBD-1SLOT-25 MM T
ɸ200
ɸ250
RESIDENTIAL VILLA FOR
150x250 VD
SFBD - 1SLOT-25 MM
50.0 L/s
150x250
VD SR 350X150
MR. GIRISH HIRANANDANI
RFBD-1SLOT-25 MM 100.0 L/s DM PLOT 6316407, EMAAR PLOT PA-02
RR 350X150 R.074, DUBAI HILLS ESTATE
HIS CLOSET ɸ150 SFBD - 1SLOT-25 MM
ɸ150 F-04 50.0 L/s
TYP. STAIRCASE

300x300
W/O HER CLOSET RFBD-1SLOT-25 MM
600x300

250X150 TYP. F-03 SFBD - 1SLOT-25 MM F-18


300x100 2NOS 140.0 L/s
SFBD - 1SLOT-25 MM VD@70 L/S RFBD-1SLOT-25 MM EFBD - 1SLOT-0.6 M ''ISSUE FOR'' ''DESCRIPTION''
50.0 L/s EFBD - 1SLOT-0.6 M 6M 10.0 L/s
2NOS EACH 25.0 L/s CONCEALED ELEC. DB RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
RFBD-1SLOT-25 MM
CABINET D FA FOR APPROVAL DD DESIGN DEVELOPMENT
EFBD - 1SLOT-0.6 M PS PROGRESS SET CD CONSTRUCTION
10.0 L/s VD F-19 BATHROOM 1
100x200 F-13 ɸ200 R FOR RECORD DOCUMENTS
ɸ150 250x650 FAD VD
ɸ150 TYP. P PRELIMINARY
150x250

SFBD - 1SLOT-25 MM UC TD TENDER DOCUMENTS


600x300

TYP. F/A UC 350x250


50.0 L/s ɸ200 TYP. 200x250 M MUNICIPALITY REVIEW
BEDROOM 1
CLOSET 1UC

IU-05
IU-08 F-14

100x200
VD SFBD - 2 SLOT- 38 MM 350x300
POCKET GARDEN F-12
350x300

UC
F-06 ɸ150 2NOS 300.0 L/s SFBD - 1SLOT-25 MM
150x200

W/O TYP. VD UC VD 4NOS. 325.0 L/s


MASTER BATHROOM

400x250
250X150 RFBD-1SLOT-25 MM
F-05 150x250 ɸ150 4M
150x200 UC VD 200x200 VD@40 L/S EFBD - 1SLOT-0.6 M

B
W/O 25.0 L/s
B

SFBD - 1SLOT-25 MM 100x200 150x250 VD


40.0 L/s 250X150 T BMO 600X300 C
450x300

CLOSET 3 250x450 250ø ɸ250 C/W.M.S.


RFBD-1SLOT-25 MM 100x200
F-09 ɸ150
ɸ150 VD ɸ200 CORRIDOR 200x100
F-11 200x100
150x200 VD 350x250 200x150 ɸ150
200x250 IU-07 B
150x200 T 100x200
350x300

BEDROOM 3 T
BEDROOM 2 SFBD - 1SLOT-25 MM
150x200

SFBD- 1SLOT-0.6 M F-07 VD@40 L/S VD@40 L/S


400x250

150x200 F-15 30.0 L/s


30.0 L/s 200x100 SFBD - 1SLOT-25 MM SFBD - 1SLOT-25 MM RFBD-1SLOT-25 MM
IU-05

SFBD - 1SLOT-25 MM 30.0 L/s 4NOS. 325.0 L/s


4NOS. 335.0 L/s RFBD-1SLOT-25 MM B 27/12/2016 100 % CD FA NAGA
UC UC
ɸ150 100x200 W/O RFBD-1SLOT-25 MM SUBMISSION
RFBD-1SLOT-25 MM 250X150 ɸ150CLOSET 2 4M A 12/05/2016 100 % DD FA NAGA
IU-05
100x200

T 4M BMO 600X300 350x300


EFBD - 1SLOT-0.6 M F-16 UC SUBMISSION
100x200

BATHROOM 3 25.0 L/s C/W.M.S.


F-10 UC
200x250 REV. DATE DESCRIPTION FOR BY
BMO 600X300 350x250
UC
SFBD - 1SLOT-25 MM ɸ200 ISSUED
C/W.M.S. BATHROOM 2 VD
400x250 50.0 L/s EFBD - 1SLOT-0.6 M ɸ150 TYP.
F-17
RFBD-1SLOT-25 MM 25.0 L/s TYP. ISSUE
ɸ150
A
EFBD - 1SLOT-0.6 M PROJECT NO. PROJECT NUMBER
BALCONY 10.0 L/s
EFBD - 1SLOT-0.6 M F-08
PROJECT ARCHITECT H.S.
10.0 L/s
C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE 1 : 100
DRAWN BY MF

CHECKED BY EM
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:58:23 AM

A
A

TRUE
PRO 35°
N N JEC
T

QIBLA
258°
M1-AC-103
SCALE 1:100

0 1 3 5m

A1 AC-FIRST FLOOR PLAN SHEET TITLE


1 : 100
AC LAYOUT - FIRST FLOOR
PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

D
D

1 2 3 4 5 6 7 8

CONSULTANT

architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

C
F F
C

E E

RESIDENTIAL VILLA FOR


MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE

''ISSUE FOR'' ''DESCRIPTION''


RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
D D R FOR RECORD DOCUMENTS
P PRELIMINARY TD TENDER DOCUMENTS
OU-01 M MUNICIPALITY REVIEW
OU-02
EF-01 650x250 FAD
T/B
OU-02 SA-01 250x450 EAD

B
F/B
B

C C
ACCU-01
FAHU-01

B B

B 27/12/2016 100 % CD FA NAGA


SUBMISSION
A 12/05/2016 100 % DD FA NAGA
SUBMISSION
STL 1200X350 REV. DATE DESCRIPTION FOR BY
650.0 L/s ISSUED

ISSUE

PROJECT NO. PROJECT NUMBER


A A
PROJECT ARCHITECT H.S.
C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE 1 : 100
DRAWN BY MF

CHECKED BY EM
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:58:26 AM

A
A

TRUE
PRO 35°
N N JEC
T

QIBLA
258°
M1-AC-104
SCALE 1:100

0 1 3 5m

SHEET TITLE

A1 AC-ROOF
1 : 100
PLAN AC LAYOUT - ROOF PLAN

1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

M-DX TYPE TOTAL FRESH AIR HANDLING UNIT WITH WRAP AROUND HEAT PIPE
FRESH AIR HORSE SHOE-HEAT PIPE COOLING COIL HORSE SHOE-HEAT PIPE ELECTRICAL DATA
AIR INLET TEMP. AIR OUTLET TEMP.
EQUIPMENT SUMMER PRE COOLING COIL REHEAT COIL
UNIT NO. QTY. (°C) (°C) REMARKS
LOCATION AIR FLOW E.S.P. FAN TOTAL CAP. SENS. CAP.
V PH HZ
RATE(L/S) INLET TEMP. (°C) (PA) (KW) EAT (°C) LAT (°C) (KW) (KW) EAT (°C) LAT (°C)
DB WB DB WB
DB WB DB WB DB WB DB WB DB WB

D
FAHU-01 1 ROOF 650 46.1 29.4 400 1.1 46.1 29.4 38.7 27.8 40.5 17.9 38.7 27.8 13.7 13.2 13.7 13.2 21.0 16.0 400 3 50
D

NOTES:

1. ALL EQUIPMENTS SHALL BE SELECTED FOR AN ALTITUDE OF 15.2 METERS.


2. FAHU'S FILTERS SHALL BE AS IN THE TECHNICAL SPECIFICATIONS.
3. SELECTION OF COOLING COIL SHALL BE SIZED BASED ON SENSIBLE AND TOTAL COOLING LOAD.
4. HORSE SHOE (WRAP AROUND) HEAT PIPE SHALL BE USED IN ORDER TO SATISFY THE SUPPLY FRESH AIR CONDITIONS ALL AROUND THE YEAR.
5. CONTRACTOR SHALL SELECT ALL A/C UNITS BASED ON REFRIGERANT R410A AND MINIMUM EER OF 9.5 @ AHRI CONDITIONS.
6. ALL UNITS SHALL BE SELECTED TO WORK AT HIGH AMBIENT CONDITIONS.

B.O.Q. SOUND ATTENUATORS


AIR FLOW MAX. STATIC PRESSURE DROP
UNIT NO. REMARKS
DUCT WIDTH DUCT HEIGHT (L/S) (Pa)
SA-01 650 250 650 50 SUPPLY
CONSULTANT
M-DX SPLIT AHU CONDENSING UNIT NOTE:

ACTUAL COMPRESSOR DATA CONDENSER DATA ELECTRICAL POWER CALCULATION FOR THE INSERTION LOSS OF THE SOUND ATTENUATORS SHALL BE PROVIDED BY THE CONTRACTOR
UNIT NO. COOLING LOCATION AMBIENT (COMP. & COND. FAN) REMARKS AND SUBMITTED FOR APPROVAL BASED ON THE SOUND POWER LEVEL OF THE APPROVED EQUIPMENT AND SPACE
TYPE TYPE OF FAN V PH HZ
QTY. LOAD (KW) D.B. °C W.B. °C (KW) SOUND PRESSURE LEVEL NOT EXCEEDING NC 30.
architects engineers designers planners
ACCU-01 1 40.50 ROOF SCROLL 46.1 29.4 AXIAL TOP DISCHARGE 400 3 50 17.2 TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

M-VARIABLE REFRIGERANT FLOW (VRF) INDOOR UNITS SCHEDULE


CALCULATED COOLING LOAD EAT LAT SELECTION ELECTRICAL DATA
UNIT NO. QTY. AREA SERVED SENSIBLE LOAD SENSIBLE CAP. E.S.P. (Pa) FAN (KW) REMARKS
TOTAL LOAD (KW) SUPPLY AIR FLOW (L/S) D.B. °C W.B. °C D.B. °C W.B. °C TOTAL CAP. (KW) SUPPLY AIR (L/S) V PH HZ
(KW) (KW)
IU-01 2 AS SHOWN ON PLANS 2.10 2.00 145 24.0 17.9 13.7 12.8 2.3 2.0 145 50 230 1 50 150 -

C
IU-02 3 AS SHOWN ON PLANS 2.60 2.40 170 24.0 17.9 13.7 12.8 2.9 2.5 170 50 230 1 50 150 -
C

IU-03 3 AS SHOWN ON PLANS 4.50 3.60 225 24.0 17.9 13.7 12.8 4.5 3.7 225 50 230 1 50 150
IU-04 1 AS SHOWN ON PLANS 5.10 4.60 285 24.0 17.9 13.7 12.8 5.7 4.7 285 50 230 1 50 150 -
IU-05 4 AS SHOWN ON PLANS 6.50 5.40 405 24.0 17.9 13.7 12.8 6.6 5.5 405 75 230 1 50 450 -
IU-06 4 AS SHOWN ON PLANS 8.30 6.90 485 24.0 17.9 13.7 12.8 8.5 7.0 485 75 230 1 50 450
IU-07 1 AS SHOWN ON PLANS 8.90 8.00 540 24.0 17.9 13.7 12.8 9.9 8.2 540 75 230 1 50 450
IU-08 1 AS SHOWN ON PLANS 12.00 11.00 750 24.0 17.9 13.7 12.8 12.7 11.1 750 75 230 1 50 450 -
IU-09 1 AS SHOWN ON PLANS 16.00 14.00 835 24.0 17.9 13.7 12.8 18.0 14.1 835 75 230 1 50 800

NOTES:

1. THE CONTRACTOR IS RESPONSIBLE TO SUPPLY AND INSTALL VRF A/C SYSTEM.


RESIDENTIAL VILLA FOR
VARIABLE REFERIGANT FLOW (VRF) SHALL STRICTLY COMPLY WITH ANSI/AHRI STANDARD 1230.
MR. GIRISH HIRANANDANI
2. INDOOR UNIT AND AIR OUTLETS SHALL BE SELECTED FOR PROPER AIR DISTRIBUTION AND NOISE LEVELS SHALL NOT EXCEED MORE THAN 35 NC OF HIGH SPEED & DM PLOT 6316407, EMAAR PLOT PA-02
CONTRACTOR SHALL PROVIDE DETAILED SHOP DRAWINGS FULLY COORDINATED WITH ID DESIGN. R.074, DUBAI HILLS ESTATE
3. CONTRACTOR IS RESPONSIBLE TO ARRANGE FULL TECHNICAL SUPPORT FROM THE AUTHORIZED LOCAL DISTRIBUTOR TO CHECK AND VERIFY THE LOCATION AND
INSTALLATION DETAILS OF INDOOR & OUTDOOR UNITS AND TO PROVIDE THE FOLLOWING:

A. PROVIDE FINAL EQUIPMENTS AND ACCESSORIES SELECTIONS, PIPE SIZE CALCULATIONS, INSTALLATION DETAIL AND DRAWINGS FOR COMPLETE SYSTEM, CONTROL AND BILLING SYSTEM SELECTION. ''ISSUE FOR'' ''DESCRIPTION''
B. THE INSTALLATION SHALL BE CARRIED OUT BY QUALIFIED AND CERTIFIED INSTALLATION TECHNICIANS STRICTLY AS PER WRITTEN INSTRUCTIONS AND INSTALLATION MANUAL OF THE MANUFACTURE. RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
C. TESTING AND COMMISSIONING OF THE VRF A/C SYSTEM, CONTROLS AND BILLING SYSTEM SHALL BE CARRIED OUT BY THE MANUFACTURES CERTIFIED ENGINEERS STRICTLY AS PER MANUFACTURE FA FOR APPROVAL DD DESIGN DEVELOPMENT
RECOMMENDATION AND SHALL BE WITNESSED AND APPROVD BY THE ENGINEER / CLIENT REPRESENTATIVE. PS PROGRESS SET CD CONSTRUCTION
D. AUTHORIZED LOCAL DISTRIBUTOR SHALL BE RESPONSIBLE TO INSPECT THE FINAL INSTALLATION OF VRF SYSTEM, CONTROLS AND BILLINGS SYSTEM AND ISSUE CERTIFICATE TO THE OWNER R FOR RECORD DOCUMENTS
FOR COMPLETE INSTALLATION. P PRELIMINARY TD TENDER DOCUMENTS
M MUNICIPALITY REVIEW
4. CONTRACTOR SHALL PROVIDE 1 YEAR O&M AND SPARE PARTS FOR THE COMPLETE VRF SYSTEM AND CONTROL SYSTEM TO THE OWNER.

5. EACH INDOOR FCU SHALL BE CONNECTED TO ITS RESPECTIVE VRF OUTDOOR UNIT.

B
B

M-VARIABLE REFRIGERANT FLOW (VRF) OUTDOOR UNITS SCHEDULE


CALCULATED SELECTION ELECT'L DATA
AMBIENT ELECT'L
UNIT NO. QTY. LOCATION TOTAL COOLING TOTAL COOLING REFRIGERANT REMARKS
TEMP. (C) POWER (KW) V PH HZ
CAP. (KW) CAP. (KW)
OU-01 1 ROOF 29.8 32.3 46.1 10.3 R410A 400 3 50 COOLING ONLY-SERVING BASEMENT
FLOOR- SERVING GROUND & FIRST
OU-02 2 ROOF 44.8 48.4 46.1 13.8 R410A 400 3 50 COOLING ONLY-SERVING BASEMENT
FLOOR- SERVING GROUND & FIRST B 27/12/2016 100 % CD FA NAGA
SUBMISSION
A 12/05/2016 100 % DD FA NAGA
NOTES: SUBMISSION
REV. DATE DESCRIPTION FOR BY
1. UNITS SHALL BE SELECTED FOR 46.1 °C AMBIENT TEMPERATURE. ISSUED
2. UNITS SHALL BE INSTALLED ON ANTI VIBRATION MOUNTS.
3. UNITS SHALL HAVE HEAVY DUTY CORROSION PROTECTION FINISH AND COIL TREATED WITH ANTI CORROSION COATING WITH 5 YEARS GUARANTEE.
4. UNITS SHALL BE INSTALLED STRICTLY IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS. ISSUE
5. REFRIGERANT PIPE SIZE SHALL BE RESIZED IF NECESSARY AND ALL ACCESSORIES SHALL BE PROVIDED FOR PROPER FUNCTIONING OF THE UNITS.
6. UNIT SHALL BE SUPPLIED WITH CORROSION PROTECTION FINISH. PROJECT NO. PROJECT NUMBER
7. OUTDOOR UNITS FOR COASTAL AREAS SHALL BE PROVIDED WITH SPECIAL CORROSION PROTECTION COATING AND SHALL BE INSTALLED AS PER
SATISFACTION AND APPROVAL OF THE ENGINEER. PROJECT ARCHITECT H.S.
8. CONTRACTOR SHALL SELECT ALL A/C UNITS BASED ON REFRIGERANT R410A AND ESTIDAMA REQUIREMENTS. C:\Users\mhegazy\Documents\15-030
9. ALL VRF OUTDOOR UNITS SHALL BE SELECTED TO WORK AT HIGH AMBIENT CONDITIONS. M-VILLA_mhegazy.rvt

REVIT FILE

M-VENTILATING FANS SCALE


DRAWN BY MF
ELECTRICAL DATA
UNIT NO. FAN TYPE AREA SERVED LOCATION QTY CAPACITY (L/S) DRIVE E.S.P. (Pa) RPM REMARKS
KW V PH HZ CHECKED BY EM
EF-01 ROOFTOP DOWN BLAST EXHAUST FAN TOILETS ROOF 1 470 DIRECT 250 1450 0.37 230 1 50 -
MANAGEMENT M.SHAFY
EF-02 AXIAL-WALL MOUNTED PUMP ROOM - STORAGE BASEMENT 2 35 DIRECT 0 1450 0.09 230 1 50 -
EF-03 INLINE EXHAUST FAN POOL PUMP ROOM BASEMENT 1 80 DIRECT 50 1450 0.09 230 1 50 - PRINTING DATE/TIME 12/25/2016 11:58:46 AM

A
FAF-01 INLINE SUPPLY FAN POOL PUMP ROOM BASEMENT 1 80 DIRECT 50 1450 0.09 230 1 50 -
A

NOTES:

1. ALL EF'S SHALL BE PROVIDED WITH BACKDRAFT DAMPER AND SPEED CONTROLLER.
2. EXTERNAL STATIC PRESSURE IS APPROXIMATE, CONTRACTOR TO VERIFY AS PER ACTUAL CONDITION ON SITE. M1-AC-105
3. FAN SELECTION SHALL BE BASED ON NOISE PRESSURE LEVEL NOT TO EXCEED NC 35 IN THE SUPPLIED SPACE OR NOISE LEVEL REFLECTED TO OTHER SPACES.

SHEET TITLE

HVAC EQUIPMENT
SCHEDULE
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

1 2 3 4 5 6 7 8

D
D

SWIMMING POOL DRAIN


CONSULTANT

F F
architects engineers designers planners

SHOWER DRAIN TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

E E

C
C

F F DW RESIDENTIAL VILLA FOR


D D
MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE

''ISSUE FOR'' ''DESCRIPTION''


RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
C C R FOR RECORD DOCUMENTS
P PRELIMINARY TD TENDER DOCUMENTS
M MUNICIPALITY REVIEW

B B
ELV

B
B

ø80 mm RW T/B
ø50 mm FM BFS
ø80 mm VENT T/A
ø80 mm VENT T/A
ø80 mm VENT U/G
ø80 mm VENT U/G
A A
GT GT GT GT
PBM MH-01 B 27/12/2016 100 % CD FA NAGA
ø80 mm VENT U/G SUBMISSION
MH-03
MH-04 MH-02 ø150 mm SAN SLOPE 1:100 A 12/05/2016 100 % DD FA NAGA
ø150 mm SAN ø150 mm SAN
ø80 mm VENT U/G SUBMISSION
ø150 mm SAN SLOPE 1:100

2085 1690 5577.15 REV. DATE DESCRIPTION FOR BY


ISSUED
4957.477

ISSUE

PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


FIC C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE 1 : 100
DRAWN BY INITIALS

CHECKED BY INITIALS
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:58:52 AM

A
A

TRUE
PRO 35°
N N
C1 DR-SETTING OUT PLAN
JEC
T

1 : 100

QIBLA
258°
M3-DR-100
SCALE 1:100

0 1 3 5m

SHEET TITLE

DRAINAGE LAYOUT -
SETTING OUT PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

D
D

1 2 3 4 5 6 7 8

POOL PUMP ROOM


B-19

CONSULTANT

architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

F F

C
C

E E
STAIRS
B-16

MECH. RM
B-13
RESIDENTIAL VILLA FOR
LOBBY
B-14
MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE
ø1
10
m

STAIRS
m

D D ''ISSUE FOR'' ''DESCRIPTION''


SP

B-15 DRIVER'S WC
ø80 mm WS B-07 RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
ø110 mm SP U/G FA FOR APPROVAL DD DESIGN DEVELOPMENT
ø80 mm WS U/G PS PROGRESS SET CD CONSTRUCTION
R FOR RECORD DOCUMENTS
ø80 mm WS
P PRELIMINARY TD TENDER DOCUMENTS
ø110 mm SP U/G
ø80 mm WS U/G DRIVER'S ROOM GYM M MUNICIPALITY REVIEW
B-08 ELECTRICAL CABINET B-06
B-18
AD ø80 mm WS LAUNDRY ø80 mm WS AD
STORAGE B-09
B-10
ø80 mm WS D W W STAIRS C C

B
ø110 mm SP U/G ø80 mm WS U/G B-17
B

WATER TANK ø80 mm WS U/G CORRIDOR ø110 mm SP U/G


B-11 PUMP ROOM B-04
ø110 mm SP U/G
B-12
B B
STORAGE ø80 mm WS U/G OFFICE
ø80 mm WS

SAND TRAP B-01 B-05


POWDER
PANTRY B-03
B-02
SP SP
B 27/12/2016 100 % CD FA NAGA
SUBMISSION
A 12/05/2016 100 % DD FA NAGA
SUBMERSABLE PUMP SUBMISSION
SUMP PIT 1000X1000X1000mm REV. DATE DESCRIPTION FOR BY
ISSUED
A A
ISSUE

PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE 1 : 100
DRAWN BY Author

CHECKED BY Checker
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:58:55 AM

A
A

TRUE
PRO 35°
N N JEC
T

QIBLA
258°
M3-DR-101
SCALE 1:100

0 1 3 5m

SHEET TITLE
1 DR-BASEMENT
1 : 100
DRAINAGE LAYOUT -
BASEMENT FLOOR PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

REAR ACCESS GATE


G-24

D
D

1 2 3 4 5 6 7 8

CONSULTANT

architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
F F po box 73033 dubai web site www.naga.ae

FAMILY DINING\
FAMILY LIVING
SHOW KITCHEN G-18

ø80 mm WS BFS
G-19

C
C

E E
STAIRS
B-16
DRY STORAGE STAIRCASE
G-15 FAMILY POWDER R. G-17
G-16

LPG CABINET FRY KITCHEN CORRIDOR


G-20 G-14 G-10
RESIDENTIAL VILLA FOR
MR. GIRISH HIRANANDANI
F F DW DM PLOT 6316407, EMAAR PLOT PA-02
STAIRS
B-15 D D R.074, DUBAI HILLS ESTATE

MAID'S BATH R. CORRIDOR


G-11
G-13
''ISSUE FOR'' ''DESCRIPTION''
DB + TELE. CABINET
G-25 RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
FA FOR APPROVAL DD DESIGN DEVELOPMENT
MAID'S ROOM ELECTRICAL CABINET
B-18 PS PROGRESS SET CD CONSTRUCTION
G-12 BAR R FOR RECORD DOCUMENTS
G-05 P PRELIMINARY TD TENDER DOCUMENTS
M MUNICIPALITY REVIEW
ø110 mm SP BFS

STAIRS
ø80 mm WS BFS

ø110 mm SP BFS

C C
ø80 mm WS BFS

ø110 mm SP BFS
ø110 mm SP BFS

ø80 mm WS BFS

ø80 mm WS BFS
B-17
CORRIDOR FORMAL LIVING & DINING
ENTRANCE G-02 G-04
G-01 B B

B
FORMAL POWDER R.1
B

GUEST BEDROOM G-03


G-06 CLOSET
G-07

ø50 mm FM BFS ROOF ACCESS GUEST BATHROOM


ø80 mm VENT T/A G-09 G-08
ø80 mm VENT T/A
B 27/12/2016 100 % CD FA NAGA
SUBMISSION

ø80 mm VENT U/G


A A A 12/05/2016 100 % DD FA NAGA
ø80 mm VENT U/G SUBMISSION
ø150 mm SAN ø150 mm SAN ø150 mm SAN SLOPE 1:100 REV. DATE DESCRIPTION FOR BY
ø80 mm VENT U/G
MH-04 MH-03 MH-02 MH-01 ISSUED
ø80 mm WS
ø80 mm VENT U/G ISSUE
ø110 mm SP
PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

FIC REVIT FILE


?
? SCALE 1 : 100
? PEDESTRIAN ENTRANCE DRAWN BY INITIALS
? G-23
CHECKED BY INITIALS
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:59:00 AM

A
A

TRUE
PRO 35°
N N JEC
T

QIBLA
258°
M3-DR-102
A1 DR-GROUND
1 : 100
FLOOR PLAN
SCALE 1:100

0 1 3 5m

SHEET TITLE

DRAINAGE LAYOUT -
GROUND FLOOR PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

REAR ACCESS GATE


G-24

D
1 2 3 4 5 6 7 8
D

CONSULTANT

architects engineers designers planners


F F TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

FAMILY LIVING
F-01

MASTER BEDROOM
F-02

C
C

E E
STAIRCASE
F-18

HER CLOSET HIS CLOSET


F-03
F-04 RESIDENTIAL VILLA FOR
CONCEALED ELEC. DB MR. GIRISH HIRANANDANI
CABINET
F-19 D D DM PLOT 6316407, EMAAR PLOT PA-02
MAID'S BATH R. R.074, DUBAI HILLS ESTATE
G-13 CORRIDOR
G-11 BATHROOM 1
F-13 BEDROOM 1
ø80 mm WS BFS ø110 mm SP F-14 ''ISSUE FOR'' ''DESCRIPTION''
RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
POCKET GARDEN MASTER BATHROOM FA FOR APPROVAL DD DESIGN DEVELOPMENT
F-06 F-05 CLOSET 1 PS PROGRESS SET CD CONSTRUCTION
F-12 R FOR RECORD DOCUMENTS
P PRELIMINARY TD TENDER DOCUMENTS
C C M MUNICIPALITY REVIEW

ø110 mm SP BFS

ø80 mm WS BFS
CLOSET 3
F-09

CORRIDOR B B
BEDROOM 3 F-11
F-07

B
B

BATHROOM 3 BATHROOM 2
F-17
F-10
BEDROOM 2
ø110 mm SP BFS F-15
CLOSET 2
F-16
ROOF ACCESS
G-09 GUEST BATHROOM
G-08

ø80 mm WS BFS B 27/12/2016 100 % CD FA NAGA


A A SUBMISSION
BALCONY
F-08 A 12/05/2016 100 % DD FA NAGA
SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED

ISSUE

PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE 1 : 100
DRAWN BY INITIALS

CHECKED BY INITIALS
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:59:05 AM

A
A

TRUE
PRO 35°
N N JEC
T

A1 DR-FIRST FLOOR PLAN

QIBLA
258°
1 : 100
M3-DR-103
SCALE 1:100

0 1 3 5m

SHEET TITLE

DRAINAGE LAYOUT - FIRST


FLOOR PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

1 2 3 4 5 6 7 8

D
D

CONSULTANT

F F architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

C
E E
C

RESIDENTIAL VILLA FOR


D D MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE

''ISSUE FOR'' ''DESCRIPTION''


RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
R FOR RECORD DOCUMENTS
C C P PRELIMINARY TD TENDER DOCUMENTS
M MUNICIPALITY REVIEW

B B

B
B

A A
B 27/12/2016 100 % CD FA NAGA
SUBMISSION
A 12/05/2016 100 % DD FA NAGA
SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED

ISSUE

PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE 1 : 100
DRAWN BY INITIALS

CHECKED BY INITIALS
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:59:08 AM

A
A

TRUE
PRO 35°
N N JEC
T

A1 DR-ROOF PLAN

QIBLA
258°
1 : 100 M3-DR-104
SCALE 1:100

0 1 3 5m

SHEET TITLE

DRAINAGE LAYOUT - ROOF


FLOOR PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

REAR ACCESS GATE


G-24

1 2 3 4 5 6 7 8

D
D

CONSULTANT
DN OD SIZE (PPR) PN (16)
12 20
F F
15 25 architects engineers designers planners
TEL +971 4 332 4455 FAX +971 4 332 2113
FAMILY LIVING po box 73033 dubai web site www.naga.ae
FAMILY DINING\ 20 32
G-18
SHOW KITCHEN
G-19 25 40

32 50

E E

C
STAIRCASE
FAMILY POWDER R.
C

G-17
DRY STORAGE G-16 STAIRS
G-15 B-16

FRY KITCHEN CORRIDOR


LPG CABINET G-14 G-10
G-20

STAIRS
F F DW RESIDENTIAL VILLA FOR
B-15 D D
MR. GIRISH HIRANANDANI
CORRIDOR DM PLOT 6316407, EMAAR PLOT PA-02
G-11
R.074, DUBAI HILLS ESTATE
DB + TELE. CABINET
G-25

MAID'S ROOM ELECTRICAL CABINET


G-12 B-18 ''ISSUE FOR'' ''DESCRIPTION''
BAR
G-05 RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
STAIRS C C DOCUMENTS
B-17 R FOR RECORD
FORMAL LIVING & DINING P PRELIMINARY TD TENDER DOCUMENTS
CORRIDOR M MUNICIPALITY REVIEW
G-02 G-04
ENTRANCE
G-01 B B
GUEST BEDROOM
G-06 CLOSET FORMAL POWDER R.1
G-07
G-03

B
B

ROOF ACCESS
G-09
GUEST BATHROOM
G-08

A A
B 27/12/2016 100 % CD FA NAGA
SUBMISSION
A 12/05/2016 100 % DD FA NAGA
SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED

ISSUE

PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


GARBAGE ROOM MAIN WATER METER C:\Users\mhegazy\Documents\15-030
G-21 M-VILLA_mhegazy.rvt
PEDESTRIAN ENTRANCE
G-23 REVIT FILE

SCALE 1 : 100
DRAWN BY INITIALS

CHECKED BY INITIALS
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:59:14 AM

A
A

TRUE
PRO 35°
N N JEC
T

A1 WS-SETTING
1 : 100
OUT PLAN

QIBLA
258°
M4-WS-100
SCALE 1:100

0 1 3 5m

SHEET TITLE

WATER SUPPLY LAYOUT -


SETTING OUT PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

D
D

1 2 3 4 5 6 7 8

POOL PUMP ROOM


B-19

CONSULTANT

architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae
F F

C
C

E E
STAIRS
B-16

MECH. RM
B-13
LOBBY
B-14
RESIDENTIAL VILLA FOR
ø15 mm PW H/L ø15 mm HWR H/L MR. GIRISH HIRANANDANI
ø15 mm HW H/L ø15 mm HW H/L
ø15 mm PW H/L DM PLOT 6316407, EMAAR PLOT PA-02
ø15 mm HWR H/L
STAIRS R.074, DUBAI HILLS ESTATE
B-15 D D

DRIVER'S ROOM ''ISSUE FOR'' ''DESCRIPTION''


B-08 DRIVER'S WC
B-07 RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
GYM FA FOR APPROVAL DD DESIGN DEVELOPMENT
ø20 mm PW H/L ELECTRICAL CABINET B-06 PS PROGRESS SET CD CONSTRUCTION
B-18 R FOR RECORD DOCUMENTS
LAUNDRY P PRELIMINARY
STORAGE B-09 TD TENDER DOCUMENTS
B-10 ø40 mm CW ø40 mm CW H/L M MUNICIPALITY REVIEW
D W W STAIRS C C
PUMP ROOM B-17
WATER TANK B-12 ø15 mm PW H/L ø15 mm PW H/L
B-11 ø15 mm PW H/L ø40 mm PW H/L CORRIDOR ø15 mm HW H/L
ø15 mm HW H/L B-04 ø15 mm HWR H/L
ø15 mm HWR H/L B B

B
STORAGE OFFICE
B

B-01 B-05

PANTRY
ø40 mm CW H/L B-02 POWDER
B-03

ø15 mm PW H/L
ø15 mm HW H/L B 27/12/2016 100 % CD FA NAGA
SUBMISSION
A A A 12/05/2016 100 % DD FA NAGA
SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED

ISSUE

PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE 1 : 100
DRAWN BY Author

CHECKED BY Checker
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:59:17 AM

A
A

TRUE
PRO 35°
N N JEC
T

QIBLA
258°
M4-WS-101
1 WS-BASEMENT SCALE 1:100
1 : 100
0 1 3 5m

SHEET TITLE

WATER SUPPLY LAYOUT -


BASEMENT FLOOR PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

REAR ACCESS GATE


G-24

D
D

1 2 3 4 5 6 7 8

CONSULTANT
DN OD SIZE (PPR) PN (16)
12 20

15 25 architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
F F po box 73033 dubai web site www.naga.ae
20 32

25 40
FAMILY DINING\
FAMILY LIVING

ø15 mm PW U/G

ø15 mm HW U/G
SHOW KITCHEN G-18 32 50
G-19

ø15 mm HWR H/L

C
ø15 mm HW H/L
C

ø15 mm PW H/L
STAIRS E E
B-16
FAMILY POWDER R.
DRY STORAGE G-16 STAIRCASE
G-15 G-17
ø40 mm PW H/L ø15 mm CW H/L
ø20 mm HW H/L ø15 mm HW H/L
ø15 mm HWR H/L ø15 mm HWR H/L

FRY KITCHEN CORRIDOR


LPG CABINET G-14 ø15 mm HWR H/L G-10
G-20 ø20 mm HW H/L
ø40 mm PW H/L RESIDENTIAL VILLA FOR
ø15 mm HWR H/L
ø25 mm HW H/L
MR. GIRISH HIRANANDANI
F F DW DM PLOT 6316407, EMAAR PLOT PA-02
STAIRS ø40 mm PW H/L
B-15 D D R.074, DUBAI HILLS ESTATE
ø40 mm PW H/L
ø15 mm HW H/L
CORRIDOR
G-11
ø15 mm HWR H/L
ø15 mm HW H/L MAID'S BATH R. ø15 mm HWR H/L
ø15 mm PW H/L G-13 ø50 mm PW H/L DB + TELE. CABINET ''ISSUE FOR'' ''DESCRIPTION''
G-25
MAID'S ROOM ø40 mm HW H/L RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
G-12 ø25 mm HWR H/L ELECTRICAL CABINET FA FOR APPROVAL DD DESIGN DEVELOPMENT
B-18 PS PROGRESS SET CD CONSTRUCTION
ø40 mm PW H/L BAR R FOR RECORD DOCUMENTS
ø25 mm HW H/L G-05 P PRELIMINARY TD TENDER DOCUMENTS
ø20 mm HWR H/L
ø20 mm HWR H/L M MUNICIPALITY REVIEW
ø20 mm HW H/L
STAIRS C C
ø40 mm PW H/L B-17
CORRIDOR FORMAL LIVING & DINING
G-02 G-04
ENTRANCE ø15 mm HWR H/L
G-01 B B
ø15 mm HW H/L

B
GUEST BEDROOM CLOSET
B

G-06 G-07 FORMAL POWDER R.1 ø15 mm PW H/L


G-03
ø15 mm HWR H/L
ø15 mm HW H/L
ø15 mm PW H/L
ROOF ACCESS
G-09 GUEST BATHROOM
G-08 ø40 mm PW H/L
ø20 mm HW H/L B 27/12/2016 100 % CD FA NAGA
ø15 mm HWR H/L ø15 mm CW H/L SUBMISSION
A A
A 12/05/2016 100 % DD FA NAGA
ø40 mm CW H/L SUBMISSION
ø15 mm PW H/L ø15 mm PW H/L REV. DATE DESCRIPTION FOR BY
ø15 mm HW H/L ø20 mm HW H/L
ø15 mm HWR H/L ø15 mm HWR H/L ISSUED

ISSUE

PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE
?
?
SCALE 1 : 100
? PEDESTRIAN ENTRANCE
? G-23 DRAWN BY INITIALS

CHECKED BY INITIALS
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:59:23 AM

A
A

TRUE
PRO 35°
N N JEC
T

QIBLA
258°
M4-WS-102

A1 WS-GROUND FLOOR PLAN SCALE 1:100

0 1 3 5m
1 : 100
SHEET TITLE

WATER SUPPLY LAYOUT -


GROUND FLOOR PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

D
D

1 2 3 4 5 6 7 8

CONSULTANT
DN OD SIZE (PPR) PN (16)
12 20

15 25 architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
F F po box 73033 dubai web site www.naga.ae
20 32

25 40

32 50

C
C

E E

RESIDENTIAL VILLA FOR


ø15 mm CW H/L MR. GIRISH HIRANANDANI
ø40 mm CW H/L ø15 mm HW H/L DM PLOT 6316407, EMAAR PLOT PA-02
ø15 mm HWR H/L ø15 mm HWR H/L D D R.074, DUBAI HILLS ESTATE
ø15 mm HW H/L
ø15 mm PW H/L
ø40 mm CW H/L
ø20 mm HW H/L
ø15 mm HWR H/L
''ISSUE FOR'' ''DESCRIPTION''
ø40 mm CW H/L ø40 mm CW H/L
ø20 mm HW H/L RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
ø20 mm HWR H/L ø40 mm HW H/L
FA FOR APPROVAL DD DESIGN DEVELOPMENT
ø25 mm HWR H/L
PS PROGRESS SET CD CONSTRUCTION
ø15 mm PW H/L ø40 mm CW H/L R FOR RECORD DOCUMENTS
ø40 mm CW H/L P PRELIMINARY TD TENDER DOCUMENTS
M MUNICIPALITY REVIEW
C C
ø15 mm HWR H/L
ø15 mm HW H/L
ø20 mm HWR H/L ø15 mm HWR H/L
ø20 mm HW H/L
ø40 mm CW H/L B B
ø40 mm CW H/L

B
ø20 mm HWR H/L
B

ø25 mm HWR H/L ø40 mm CW H/L


ø40 mm CW H/L
ø32 mm HW H/L ø25 mm HW H/L
ø40 mm CW H/L

ø40 mm CW H/L
ø15 mm HWR H/L ø15 mm CW H/L ø20 mm HW H/L
ø15 mm HW H/L ø15 mm HW H/L
ø15 mm PW H/L ø15 mm HWR H/L ø15 mm HWR H/L
B 27/12/2016 100 % CD FA NAGA
ø15 mm HWR H/L SUBMISSION
ø15 mm HW H/L A A A 12/05/2016 100 % DD FA NAGA
ø15 mm PW H/L
SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED

ISSUE

PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE 1 : 100
DRAWN BY INITIALS

CHECKED BY INITIALS
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:59:27 AM

A
A

TRUE
PRO 35°
N N JEC
T

QIBLA
258°
M4-WS-103
A1 WS-FIRST
1 : 100
FLOOR PLAN SCALE 1:100

0 1 3 5m

SHEET TITLE

WATER SUPPLY LAYOUT -


FIRST FLOOR PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

1 2 3 4 5 6 7 8

D
D

CONSULTANT
DN OD SIZE (PPR) PN (16)
SWH 300 LIT 12 20

15 25 architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae
SWH 300 LIT 20 32

25 40

D
32 50
WR
ø40 mm H ø50 mm CW T/B
ø40 mm HW T/B

C
HW ø25 mm HWR F/B
ø40 mm
C

ø50 mm CW SUPPLY LINE

B
RESIDENTIAL VILLA FOR
MR. GIRISH HIRANANDANI
ø50 mm CW FILLING LINE ø50 mm CW FILING LINE DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE

''ISSUE FOR'' ''DESCRIPTION''


ø50 mm CW FILING LINE
RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
ø50 mm CW FA FOR APPROVAL DD DESIGN DEVELOPMENT
A PS PROGRESS SET CD CONSTRUCTION
R FOR RECORD DOCUMENTS
P PRELIMINARY TD TENDER DOCUMENTS
M MUNICIPALITY REVIEW

B
C1 WS-ROOF PLAN
B

1 : 100

Form No. 1 Solar Domestic Water Heater, Applied for villas.


19/2/2012 v1

Solar Water Heater Scheme:


The size and performance of solar system must be
B 27/12/2016 100 % CD FA NAGA
calculated using actual design and installation conditions SUBMISSION
South r
taking into consideration all the affecting parameters
A 12/05/2016 100 % DD FA NAGA
including the collector slope angle and direction. Any
ecto
Coll changes that are incorporated into the system during
Sola
r
construction shall be considered.
SUBMISSION

25°
REV. DATE DESCRIPTION FOR BY
Average Daily Hot Water Consumption: ISSUED

Average Daily Hot Water Consumption per Villa= No. of Toilets / Bathrooms x 50 L= 7 350 L
SOLAR WATER HEATER SCHEDULE ISSUE
+No. of WCs x 30 L= 4 120 L

TAG EQUIPMENT DESCRIPTION SYSTEM STORAGE TANK CAPACITY PANEL TYPE NO. OF PANEL LOCATION QTY.
+No. of Kitchens x 80 L= 1 80 L PROJECT NO. PROJECT NUMBER

550 L PROJECT ARCHITECT H.S.


SWH DOMESTIC SOLAR WATER HEATER THERMOSYPHON 300 LTR. FLAT PLATE 2 ROOF 1
C:\Users\mhegazy\Documents\15-030
Design Parameters and requirements: M-VILLA_mhegazy.rvt
Design parameters and requirements shall be according to circular No. 183/2011 and international Best Practices, with emphasis
on the following:
1- Hot water storage temp. =60 ºC REVIT FILE
2- Average dry ambient temp. (Summer): 42 ºC
3- Average dry ambient temp. (Winter): 14 ºC
4- The minimum hot water storage tank capacity equal to seventy five percent (75%) of the total daily consumption of hot water. SCALE 1 : 100
5- Back-up electrical immersion heater to be provided.
6- The solar water heater system shall be installed, operated and maintained by a registered and licensed company by the
Department of Economic Development and approved by Dubai Municipality. DRAWN BY INITIALS
7- The solar water heater system shall be approved by Dubai Central Laboratory.

CHECKED BY INITIALS
Undertaking:
I/we hereby commit to full requirements of circular No. 183/2011 issued by Dubai Municipality regarding Solar Water Heaters.
This commitment without exception applies to the design, installation and commissioning of Solar Water Heaters.
MANAGEMENT M.SHAFY
The solar water heater system shall be installed, operated and maintained by registered licensed company by the Department
of Economic Development and approved by Dubai Municipality. The solar water heater system shall be approved by Dubai
Central laboratory. PRINTING DATE/TIME 12/25/2016 11:59:27 AM

A
It is understood that failure to comply with the regulations may also result in fine or other penalty.
A

TRUE
PRO 35°

Notes: N N JEC
T

1- This sheet shall be attached to the roof plan of water supply drawings, and uploaded with the sewerage drawings in the
plumbing folder.
2- No Separate electric water heater shall be used.
3- Incase more than one type of typical villas (with different Average Daily Hot Water Consumption) is available, then additional

QIBLA
sheet(s) for each type to be attached.

258°
M4-WS-104
SCALE 1:100
Applicant:.................................................................................................... 0 1 3 5m

NAGA
SHEET TITLE

WATER SUPPLY LAYOUT -


ROOF FLOOR PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

REAR ACCESS GATE


G-24

D
D

1 2 3 4 5 6 7 8

CONSULTANT

architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
F F po box 73033 dubai web site www.naga.ae

FAMILY DINING\
FAMILY LIVING
SHOW KITCHEN G-18
G-19

C
C

E E
STAIRS
B-16
FAMILY POWDER R.
DRY STORAGE G-16 STAIRCASE
G-15 G-17

APPLIANEES VALVE CORRIDOR


FRY KITCHEN
LPG CABINET G-14 G-10
G-20
RESIDENTIAL VILLA FOR
MR. GIRISH HIRANANDANI
F F DW DM PLOT 6316407, EMAAR PLOT PA-02
STAIRS
B-15 D D R.074, DUBAI HILLS ESTATE
MAID'S BATH R.
G-13 CORRIDOR
G-11
''ISSUE FOR'' ''DESCRIPTION''
DB + TELE. CABINET
G-25 RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
FA FOR APPROVAL DD DESIGN DEVELOPMENT
MAID'S ROOM ELECTRICAL CABINET PS PROGRESS SET CD CONSTRUCTION
G-12 B-18 R FOR RECORD DOCUMENTS
BAR P PRELIMINARY TD TENDER DOCUMENTS
G-05 STAIRS M MUNICIPALITY REVIEW
B-17
C C

CORRIDOR FORMAL LIVING & DINING


G-02 G-04
ENTRANCE B B
G-01

B
B

GUEST BEDROOM
G-06 CLOSET FORMAL POWDER R.1
G-07
G-03

ROOF ACCESS
G-09
ø15 mm NPG

GUEST BATHROOM
G-08
B 27/12/2016 100 % CD FA NAGA
SUBMISSION
A A A 12/05/2016 100 % DD FA NAGA
SUBMISSION
REV. DATE DESCRIPTION FOR BY
ø25 mm NPG U/G
ISSUED
75 MBAR/21 MBAR REGULATOR
ISSUE

PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
ELECTRICAL DB ROOM ø25 mm NPG U/G M-VILLA_mhegazy.rvt
G-22
REVIT FILE
GARBAGE ROOM
G-21 SCALE 1 : 100
PEDESTRIAN ENTRANCE
G-23 DRAWN BY INITIALS

GAS METER CHECKED BY INITIALS

ø25 mm NPG U/G FROM NETWORK MANAGEMENT M.SHAFY


SV PRINTING DATE/TIME 12/25/2016 11:59:29 AM

A
A

M5-NG-100
1 NG-GROUND FLOOR PLAN
1 : 100
SHEET TITLE

NG LAYOUT - GROUND
FLOOR PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

D
D

1 2 3 4 5 6 7 8

POOL PUMP ROOM


B-19

CONSULTANT

architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

F F

C
C

E E
STAIRS
B-16

MECH. RM
B-13
RESIDENTIAL VILLA FOR
LOBBY
B-14
MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE

4.5 KG DRY
STAIRS CHEMICAL
B-15 POWDER
D D ''ISSUE FOR'' ''DESCRIPTION''
RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
5KG CO2
FA FOR APPROVAL DD DESIGN DEVELOPMENT
9 LIT WATER
PS PROGRESS SET CD CONSTRUCTION
EXTINGHER
DRIVER'S WC R FOR RECORD DOCUMENTS
DRIVER'S ROOM B-07 P PRELIMINARY TD TENDER DOCUMENTS
B-08 M MUNICIPALITY REVIEW
GYM
ELECTRICAL CABINET B-06
B-18
STORAGE LAUNDRY
B-10 B-09

D W W STAIRS C C

B
B-17
B

WATER TANK CORRIDOR


B-11 PUMP ROOM B-04
B-12 STORAGE
B-01 B B
OFFICE
B-05

PANTRY
B-02 POWDER
B-03
B 27/12/2016 100 % CD FA NAGA
SUBMISSION
A 12/05/2016 100 % DD FA NAGA
SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED
A A
ISSUE

PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE 1 : 100
DRAWN BY Author

CHECKED BY Checker
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:59:32 AM

A
A

TRUE
PRO 35°
N N JEC
T

QIBLA
258°
M6-FP-101
SCALE 1:100

0 1 3 5m

SHEET TITLE

1 FP-BASEMENT FIRE PROTECTION LAYOUT -


1 : 100
BASEMENT FLOOR PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

D
D

REAR ACCESS GATE


G-24

1 2 3 4 5 6 7 8

CONSULTANT

architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

F F

C
C

FAMILY DINING\
FAMILY LIVING
SHOW KITCHEN G-18
G-19

E E
STAIRCASE
STAIRS
FAMILY POWDER R. G-17
B-16
DRY STORAGE G-16
G-15
RESIDENTIAL VILLA FOR
2KG CO2
MR. GIRISH HIRANANDANI
4.5 KG DRY FRY KITCHEN CORRIDOR DM PLOT 6316407, EMAAR PLOT PA-02
LPG CABINET CHEMICAL G-14 G-10 R.074, DUBAI HILLS ESTATE
G-20
POWDER
4.5 KG DRY
CHEMICAL
POWDER ''ISSUE FOR'' ''DESCRIPTION''
DW 5KG CO2
STAIRS RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
B-15 9 LIT WATER D D
FA FOR APPROVAL DD DESIGN DEVELOPMENT
EXTINGHER
MAID'S BATH R. PS PROGRESS SET CD CONSTRUCTION
G-13 CORRIDOR R FOR RECORD DOCUMENTS
G-11 P PRELIMINARY TD TENDER DOCUMENTS
DB + TELE. CABINET M MUNICIPALITY REVIEW
G-25

MAID'S ROOM ELECTRICAL CABINET


G-12 B-18
BAR
G-05

B
STAIRS
B

C C
B-17
CORRIDOR FORMAL LIVING & DINING
G-02 G-04
ENTRANCE
G-01 B B
GUEST BEDROOM
G-06 CLOSET FORMAL POWDER R.1
G-07
G-03
B 27/12/2016 100 % CD FA NAGA
SUBMISSION
A 12/05/2016 100 % DD FA NAGA
ROOF ACCESS SUBMISSION
G-09 REV. DATE DESCRIPTION FOR BY
GUEST BATHROOM
G-08 ISSUED

A A ISSUE

PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE 1 : 100
DRAWN BY Author

CHECKED BY Checker
? MANAGEMENT M.SHAFY
?
PEDESTRIAN ENTRANCE PRINTING DATE/TIME 12/25/2016 11:59:37 AM
?

A
G-23
A

TRUE
? PRO 35°
N N JEC
T

QIBLA
258°
M6-FP-102
SCALE 1:100

0 1 3 5m

SHEET TITLE

1 FP-GROUND FLOOR PLAN FIRE PROTECTION LAYOUT -


1 : 100
GROUND FLOOR PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

D
D

1 2 3 4 5 6 7 8

CONSULTANT

architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

F F

C
C

E E

RESIDENTIAL VILLA FOR


MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE

''ISSUE FOR'' ''DESCRIPTION''


RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
D D
FA FOR APPROVAL DD DESIGN DEVELOPMENT
9 LIT WATER PS PROGRESS SET CD CONSTRUCTION
EXTINGHER R FOR RECORD DOCUMENTS
P PRELIMINARY TD TENDER DOCUMENTS
5KG CO2
M MUNICIPALITY REVIEW
4.5 KG DRY
CHEMICAL
POWDER

B
B

C C

B B

B 27/12/2016 100 % CD FA NAGA


SUBMISSION
A 12/05/2016 100 % DD FA NAGA
SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED

A A ISSUE

PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE 1 : 100
DRAWN BY Author

CHECKED BY Checker
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:59:41 AM

A
A

TRUE
PRO 35°
N N JEC
T

QIBLA
258°
M6-FP-103
SCALE 1:100

0 1 3 5m

SHEET TITLE

1 FP-FIRST FLOOR PLAN FIRE PROTECTION LAYOUT -


1 : 100
FIRST FLOOR
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN

P-SOLAR WATER HEATER SCHEDULE


UNIT NO. DESCRIPTION SYSTEM STORAGE TANK CAPACITY (LITRE) PANEL TYPE NO. OF PANEL LOCATION QTY. REMARKS
SWH 300 LIT DOMESTIC SOLAR WATER HEATER THERMOSYPHON 300 FLAT PLATE 2 ROOF 1
SWH 300 LIT DOMESTIC SOLAR WATER HEATER THERMOSYPHON 300 FLAT PLATE 2 ROOF 1

D
D

P-PUMPS SCHEDULE
ELECTRIC DATA
UNIT NO. QTY. DESCRIPTION LOCATION TDH (M) FLOW (L/S) POWER (KW) REMARKS
VOLT PHASE HERTZ
HWP 1 HOT WATER BOOSTER PUMP ROOF 20 1 1.50 220 1 50
HWP 1 HOT WATER BOOSTER PUMP ROOF 20 1 1.50 220 1 50
CP 1 CIRCULATION PUMP ROOF 10 1 0.50 220 1 50
TP 1 TRANSFER PUMP PUMP ROOM 25 1 1.50 220 1 50
TP 1 TRANSFER PUMP PUMP ROOM 25 1 1.50 220 1 50
SP 1 SUMP PUMP BASEMENT 10 2 1.00 220 1 50
SP 1 SUMP PUMP BASEMENT 10 2 1.00 220 1 50
CBP 1 COLD WATER BOOSTER PUMP ROOF 20 2 1.50 220 1 50
CBP 1 COLD WATER BOOSTER PUMP ROOF 20 2 1.50 220 1 50

CONSULTANT

architects engineers designers planners


TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae

P-MANHOLES SCHEDULE
MANHOLE NO. COVER LEVEL INVERT LEVEL DEPTH COVER SIZE DRAWING LOCATION REMARKS
MH-01 0.0 -0.45 0.45 600X600 SETTINGOUT PLAN

C
MH-02 0.0 -050 0.50 600X600 SETTINGOUT PLAN
C

MH-03 0.0 -0.52 0.50 600X600 SETTINGOUT PLAN


MH-04 0.0 -0.54 0.54 600X600 SETTINGOUT PLAN
MH-05 0.0 -0.59 0.59 600X600 SETTINGOUT PLAN

RESIDENTIAL VILLA FOR


MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE

''ISSUE FOR'' ''DESCRIPTION''


RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
R FOR RECORD DOCUMENTS
P PRELIMINARY TD TENDER DOCUMENTS
M MUNICIPALITY REVIEW

B
B

B 27/12/2016 100 % CD FA NAGA


SUBMISSION
A 12/05/2016 100 % DD FA NAGA
SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED

ISSUE

PROJECT NO. PROJECT NUMBER

PROJECT ARCHITECT H.S.


C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt

REVIT FILE

SCALE
DRAWN BY Author

CHECKED BY Checker
MANAGEMENT M.SHAFY

PRINTING DATE/TIME 12/25/2016 11:59:41 AM

A
A

M8-PG-100

SHEET TITLE

EQUIPMENT AND FIXTURES


SCHEDULES
1 2 3 4 5 6 7