Mechanical Drawings
Mechanical Drawings
100% DD LOD
REVISION
SHEET NUMBER SHEET NAME NO. DATE
M0-GE-000 COVER SHEET B 27/12/2016
M0-GE-001 MECHANICAL LIST OF DRAWINGS B 27/12/2016
M0-GE-002 MECHANICAL ABBREVIATIONS B 27/12/2016
M0-GE-003 MECHANICAL LEGENDS B 27/12/2016
D
M0-GE-004 HVAC NOTES B 27/12/2016
D
C
C
B
B
ISSUE
REVIT FILE
SCALE
DRAWN BY M.K.
CHECKED BY I.S.
MANAGEMENT M.SHAFY
A
A
M0-GE-001
SHEET TITLE
MECHANICAL LIST OF
DRAWINGS
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
SYMBOLS ABBREVIATIONS SYMBOLS ABBREVIATIONS PLUMBING SYMBOLS FIREFIGHTING SYMBOLS PIPING FITTINGS & VALVES SYMBOLS
SYMBOLS ABBREVIATIONS SYMBOLS ABBREVIATIONS SYMBOLS ABBREVIATIONS
EXHAUST CEILING DIFFUSER
BACK DRAFT DAMPER
EXPANSION TANK -VERTICAL DRY CHEMICAL FIRE EXTINGUISHER BALANCE VALVE
SUPPLY SQUARE DIFFUSER VOLUME DAMPER EXPANSION TANK -INLINE CO2 FIRE EXTINGUISHER BALL VALVE
D
D
GLOBE VALVE
SOLAR PANEL
SUPPLY REGISTER T
THERMOSTAT MULTI PURPOSE VALVE
C
C
B
B
ISSUE
REVIT FILE
SCALE N.T.S.
DRAWN BY MF
CHECKED BY EM
MANAGEMENT M.SHAFY
A
A
M0-GE-002
SHEET TITLE
MECHANICAL
ABBREVIATIONS
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
LEGENDS DESCRIPTIONS LEGENDS DESCRIPTIONS (CONT.) FIRE & PLUMBING LEGENDS FIRE & PLUMBING LEGENDS (CONT.)
D
lb POUND DR DRAIN
D
FAD FRESH AIR DUCT HVAC HEATING, VENTILATING, AND gm/hr GRAMS/HOUR BD BIDET
AIR
CONDITIONING
PRS PRESSURE REGULATING STATION BP BOOSTER PUMP
EAD EXHAUST AIR DUCT RCD RETURN CEILING DIFFUSER
C
LR LOW RISE WC WATER CLOSET
C
ECD EXHAUST CEILING DIFFUSER HR HIGH RISE CWP COLD WATER PIPE
IU INDOOR UNIT
B
B
T/B TO BELOW
W/O WALL OPENING BD BALCONY DRAIN
REVIT FILE
SCALE N.T.S.
DRAWN BY MF
CHECKED BY EM
MANAGEMENT M.SHAFY
A
A
M0-GE-003
SHEET TITLE
MECHANICAL LEGENDS
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
GENERAL HVAC NOTES:
3. ALL WORKMANSHIP AND MATERIAL SHALL COMPLY TO THE RELEVANT B.S STANDARDS, ASHRAE, NFPA AND THE SPECIFICATION.
4. ALL DUCT AND PIPE SUPPORTS TO BE DESIGNED TO WITHSTAND LATERAL MOVEMENTS AND LONGITUDINAL MOVEMENTS.
5. ALL EQUIPMENT, DUCT WORK, DAMPERS, SWITCHES, WIRES ETC. SHALL BE IDENTIFIED BY MARKERS/TAGS AS REQUIRED BY ENGINEER AND SPECIFICATION.
6. ALL THERMOSTAT IN PUBLIC AND COMMON AREA SHALL BE HOUSED IN LOCKABLE TRANSPARENT ENCLOSURE.
7. ANY DISCREPANCY ARE TO BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND RESOLVED PRIOR TO FINALIZATION OF CONTRACT. ANY VARIATION DUE TO NOT DOING SO WILL NOT BE ENTERTAINED.
D
D
8. SHOWN LOCATION OF THERMOSTATS ARE TENTATIVE, FINAL LOCATION SHALL BE COORDINATED WITH ARCHITECT DURING CONSTRUCTION STAGE.
9. WHERE MORE THAN ONE SERVICE (ELECTRICAL CABLES, DUCTS, PIPES) IS ROUTED THROUGH THE SAME AREA, THEY SHALL BE SUPPORTED BY STRUCTURAL FRAME SUPPORT WITH SERVICES STACKED ONE ABOVE THE OTHER.
10. CONTRACTOR TO COORDINATE WITH STRUCTURAL DRAWINGS FOR OPENINGS AND PENETRATORS. SUBMIT BUILDING WORK SHOP DRAWING FOR STRUCTURAL ENGINEER APPROVAL. ANY OPENING REQUIRED OTHER THAN THAT SHOWN ON STRUCTURAL DRAWING SHALL BE APPROVED BY STRUCTURAL ENGINEER.
11. ALL ELECTRICAL LOADS SHOWN ON ELECTRICAL TENDER DRAWINGS/SPECIFICATION TO BE CHECKED AND CONFIRMED AND ADJUSTED AS DEEMED NECESSARY.
12. SUITABLE APPROVED SLEEVES SHALL BE PROVIDED WHERE BOTH INSULATED AND NON INSULATED SERVICES PASS THROUGH WALLS AND FLOORS ETC.
13. PROVIDE STEEL PLATFORMS AND RAISED WALKWAYS TO CROSSOVER SERVICES ON ROOF/MECHANICAL FLOORS AND TO ACHIEVE ADEQUATE MAINTENANCE ACCESS TO THE APPROVAL OF ENGINEER.
14. ALL EXPOSED ANGLE SUPPORTS FOR DUCTS SHALL BE PAINTED AS SPECIFIED.
15. ALL EXPOSED DUCTS ON ROOF SHALL BE ALUMINUM CLADDED ON TOP OF THE INSULATION.
16. HEATING, VENTILATION AND AIR CONDITIONING (HVAC) SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS MANUAL AND OTHER APPROVED SUBMITTAL DATA.
17. VENTILATION AND AIR CONDITIONING DRAWINGS SHALL BE READ IN CONJUNCTION WITH GENERAL NOTES, SPECIFICATIONS, MISCELLANEOUS DETAILS, ARCHITECTURAL, ELECTRICAL, MECHANICAL AND STRUCTURAL DRAWINGS.
CONSULTANT
18. ANY MISSING DAMPERS (V.D,F.D.,...........ETC) TO BE PROVIDED BY CONTRACTOR.
HVAC EQUIPMENT NOTES
1. ALL CONDENSATE DRAINS FROM AHU/FCU/DX WHETHER SHOWN ON THE DRAWINGS OR NOT SHALL RUN WITH A FALL TO THE NEAREST WASTE STACK OR FLOOR DRAIN.
architects engineers designers planners
2. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING THE NOISE LEVELS IN VARIOUS AREAS WITHIN SPECIFIED LIMITS. CONTRACTOR SHALL INCLUDE IN HIS TENDER FOR ALL ATTENUATION MEANS WHETHER SPECIFIED OR NOT. TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae
3. ALL THE FAN COIL UNIT SHALL HAVE 25MM THICK WASHABLE FILTER AT 75 % EFFICIENCY.
4. CONTRACTOR SHALL SUBMIT PERFORMANCE TEST CERTIFICATE FOR EACH EQUIPMENT TO CONFIRM THAT IT CAN PRODUCE THE SCHEDULE DUTY AT THE SPECIFIED CONDITIONS.
6. CONTRACTOR SHALL FORWARD ACTUAL PHYSICAL DIMENSIONS, WEIGHTS OF EQUIPMENT FOR APPROVAL FROM STRUCTURAL ENGINEER.
C
7. EVERY HVAC EQUIPMENT SHALL BE PROVIDED WITH DISCONNECT SWITCH NEAR TO IT FOR EMERGENCY SHUT DOWN OF EQUIPMENT.
C
8. EXTERNAL STATIC PRESSURE FOR AHUs, FAHUs, FCUs, DX, FANs AND PUMP HEAD GIVEN IN SCHEDULE OF EQUIPMENT ARE ESTIMATED VALUES. THE CONTRACTOR SHALL BE RESPONSIBLE TO CALCULATE THE SAME AS PER ACTUAL CONDITIONS AND SUBMIT FOR ENGINEER'S APPROVAL.
9. COOLING LOAD CALCULATION SHALL BE DONE TO VERIFY THE SCHEDULE OF EQUIPMENT DATA AND SUBMIT FOR ENGINEERS APPROVAL.
DUCTWORK NOTES:
5. WHERE DUCT SIZES ARE NOT INDICATED, THE FOLLOWING CRITERIA SHALL BE FOLLOWED:
- MAIN AHU DUCTS ------------6.5M/S
-BRANCHES-----------------------3 M/S ''ISSUE FOR'' ''DESCRIPTION''
RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
6. PROVIDE PARTITION WITHIN CEILING VOIDS AS REQUIRED TO PREVENT MIXING OF RETURN AIR - WHEN TWO OR MORE UNITS ARE CONNECTED TO A COMMON CEILING VOID FOR RETURN AIR. SUCH PARTITIONS SHALL BE OF DRY WALL CONSTRUCTION. FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
7. UNLESS OTHERWISE INDICATED ALL OPEN END OF RETURN & EXTRACT AIR DUCT SHALL BE PROVIDED WITH STAINLESS STEEL WIRE MESH AS PER THE INSTRUCTIONS OF THE ENGINEER IN CHARGE. R FOR RECORD DOCUMENTS
P PRELIMINARY TD TENDER DOCUMENTS
8. FINAL DISTRIBUTION OF SUPPLY AIR, RETURN AIR, FRESH AIR & EXTRACT AIR DUCTWORK SHALL BE AS PER INTERIOR DESIGN LAYOUT, CONTRACTOR SHALL BE FULLY RESPONSIBLE TO COORDINATE ALL SERVICES, AS PER ENGINEER IN CHARGE.
M MUNICIPALITY REVIEW
9. FLEXIBLE DUCT TO ANY AIR OUTLET SHALL NOT EXCEED A LENGTH OF 1.5 METER AND SHOULD BE INSTALLED AS PER SMACNA STANDARDS.
10. RETURN AIR OPENING/DUCT OR PROPER SIZE WITH FRAME AND WIRE MESH SHALL BE PROVIDED ABOVE FALSE CEILING WHERE NECESSARY.
11. ALL FRESH AND EXTRACT AIR DUCT BRANCH OUTLET SHALL BE TERMINATED ADJACENT TO EACH FCU (UNLESS SHOWN ON DRAWINGS OTHERWISE) WITH VCD AND STAINLESS STEEL WIRE MESH.
B
B
12. ALL SUPPLY/RETURN AIR PLENUM SHALL BE INTERNALLY LINED AND PAINTED BLACK INTERNALLY.
13. PROVIDE SUFFICIENT TEST HOLES ON THE DUCT WORK AND PROTECT WITH PLUGS TO CHECK AIR FLOW AND PRESSURE.
14. ALL DUCT BENDS, BRANCHES AND TEES SHALL BE PROVIDED WITH TURNING VANES.
15. THE DUCT MAINS AND RISERS SHALL BE REINFORCED TO PREVENT DRUMMING.
16. CONTRACTOR IS RESPONSIBLE FOR ACHIEVING THE SYSTEM AIR BALANCE AND TO MAINTAIN THE PRESSURE RELATIONSHIP BETWEEN DIFFERENT AREAS. CONTRACTOR TO INCLUDE IN HIS TENDER FOR REGULATING DAMPERS AND OTHER ACCESSORIES AS REQUIRED, WHETHER INDICATED ON DRAWINGS OR NOT.
B 27/12/2016 100 % CD FA NAGA
SUBMISSION
DUCTWORK ACCESSORIES NOTES: A 12/05/2016 100 % DD FA NAGA
SUBMISSION
1. ACCESS PANELS TO BE PROVIDED WITHIN FALSE CEILING AT ALL LOCATIONS OF FCUs, VALVES, VCD, NRD & SPD. CONTRACTOR SHALL COORDINATE WITH ALL MEP SERVICES AND FALSE CEILING LAYOUT TO ENSURE THAT COMMON ACCESS PANELS ARE PROVIDED FOR MAINTENANCE. REV. DATE DESCRIPTION FOR BY
ISSUED
2. NON RETURN DAMPERS SHALL BE PROVIDED AFTER EACH DUCTED EXTRACT FAN.
ISSUE
3. VOLUME CONTROL DAMPER SHALL BE PROVIDED AT ALL A/C DUCT BRANCHES, WHETHER SHOWN ON DRAWINGS OR NOT FOR PROPER AIR BALANCING.
PROJECT NO. PROJECT NUMBER
REVIT FILE
AIR TERMINALS NOTES:
SCALE
1. AIR OUTLET SHALL BE ALUMINUM ANODIZED EXTRUDED CONSTRUCTION WITH POWDER COATED OVEN BAKED ENAMEL FINISH. THE COLOR SHALL BE AS PER APPROVED MATERIAL SUBMITTAL. DRAWN BY MF
2. FINAL LOCATION AND TYPE OF AIR DEVICES SHALL BE COORDINATED WITH INTERIOR DESIGN LAYOUT AND THE CONTRACTOR SHALL REVISE IF REQUIRED WITHOUT ANY EXTRA COST. CHECKED BY EM
3. ALL SUPPLY AND EXTRACT DIFFUSERS/GRILLS SHALL HAVE BUILT IN VCD FOR FINAL FINE TUNING. MANAGEMENT M.SHAFY
4. FINAL LOCATION OF FRESH AIR LOVER AND EXTRACT AIR LOUVER TO BE CO-ORDINATE WITH ARCHITECT AT SITE AND COLOR IS SUBJECT TO ARCHITECTS APPROVAL. PRINTING DATE/TIME 12/25/2016 11:57:24 AM
A
A
M0-GE-004
SHEET TITLE
HVAC NOTES
1 2 3 4 5 6 7
1 2 3 4 5 6 7
STAMPS
D
D
5. UNLESS OTHERWISE INDICATED ALL PIPE WORK IN TOILETS/BATH ROOMS ETC SHALL BE 20MM DIA DN WITH REDUCTIONS TO 15MM DIA DN ONLY AT FINAL OUTLETS AS APPROPRIATE.
6. BRANCH SUPPLY PIPES TO ALL AREAS WILL HAVE ISOLATING VALVES MOUNTED AT ACCESSIBLE HEIGHTS ABOVE FALSE CEILING.
7. FINAL LOCATION OF SOLAR WATER HEATER SHALL BE COORDINATED WITH OTHER SERVICE AND FALSE CEILING HEIGHTS AT SHOP DRAWINGS STAGE.
8. CONTRACTOR TO INCLUDE FOR PRESSURE REDUCING VALVES, ISOLATING VALVES AND NON RETURN VALVES AS REQUIRED BY THE SYSTEM.
10. ALL HIGH POINTS OF THE WATER SYSTEM SHALL BE PROVIDED WITH AUTOMATIC AIR VENT AND THE LOW POINT SHALL BE PROVIDED WITH DRAIN POINT WHETHER SHOWN ON LAYOUT OR NOT.
11. CONTRACTOR TO ENSURE ALL PUMPS ARE INSTALLED ON MINIMUM 150MM CONCRETE BASE.
12. ALL BURIED PIPES SHALL BE LAID ON COMPACT AND LEVEL SURFACE.
14. FOR ALL THE PUMPS THE ACTUAL HEAD/FLOW TO BE ESTABLISHED BY CONTRACTOR AND CALCULATIONS TO BE FORWARDED TO CONSULTANT FOR APPROVAL. CONSULTANT
C
C
B
B
ISSUE
REVIT FILE
SCALE
DRAWN BY Author
CHECKED BY Checker
MANAGEMENT M.SHAFY
A
A
M0-GE-005
SHEET TITLE
1 2 3 4 5 6 7
1 2 3 4 5 6 7
STAMPS
D
A-7 TOTAL NO OF DM STORM WATER . CONNECTION - NIL
D
C
6- TYPICAL OUTLET SIZE (MM) 7- STACK SIZES SHALL BE AS FOLLOWS: - 8- STACK SIZES SHALL BE AS FOLLOWS: - SUBMITED TO DM ENGINEERS.
C
WC 100 UP TO GROUND PLUS SEVEN STORY ABOVE SEVEN STORY E) SEPTIC TANKS, SOAKAWAY AND HOLDING TANKS
W . BASIN 32 SOIL PIPE 100 SOIL PIPE 150 D-1 SEPTIC TANK AND SOAKAWAY SHALL BE CONSTRUCTED AND SELECTED TO DM DETAILS AND SHALL BE ACCORDING TO BS 6297
KITCHEN SINK 40 WASTE PIPE 100 WASTE PIPE 150 D-2 THE FOUNDATION LEVEL OF THE BASE OF THE SOAKAWAY SHALL BE KEPT AT LEAST 1 M ABOVE THE WINTER WATER TABLE.
FLOOR DRAIN 75 VENT PIPE 75 VENT PIPE 100 D-3 THE FLOOR AREA OF THE SOAKAWAY SHALL BE DETERMINED ACCORDING TO THE 'PERCOLATION RATE IN ACCORDANCE WITH
BATH TUB/SHOWER 40 RAIN WATER PIPE 100 RAIN WATER PIPE 100 APPROPRIATE TEST IN THE BS 6297
WASHING M/C 40 BALCONY DRAIN PIPE 50 BALCONY DRAIN PIPE 50 D-4 LOCATIONS OF SEPTIC TANK AND SOAKAWAY SHOULD SHOWN ON SETTING OUT PLANS AND ON A GENERAL FOUNDATION LAYOUT PLANS.
BALCONY DRAIN 50 A/C DRAIN PIPE 32 A/C DRAIN PIPE 32 D-5 SOAKAWAY SHALL BE 1000 MM AWAY FROM THE SEPTIC TANK PLACED AT LEAST.
C)MANHOLES D-6 SEPTIC TANK & SOAK AWAY SHOULD BE CONSTRUCTED AT LEAST 3 MS AWAY FROM ANY FOOTING FOR A BUILDING OR A BOUNDARY WALL
1- THE MANHOLE SCHEDULE SHALL BE ARRANGED IN THE MANNER SHOWN BELOW ,THE MANHOLE INVERT LEVEL (I L) , COVER LEVEL (C L) AND SHOULD BE CONSTRUCTED FROM SOLID BLOCK WITH A PROVISION OF PROPER INSULATION FOR THE SEPTIC TANK.
DEPTH AND DISTANCE BETWEEN MANHOLES SHALL BE REFERENCED FROM D.M C , F.I.C USING DM'S DATUM D-7 IN CASE THERE IS A NEED TO CONSTRUCT THESE TANKS AT A DISTANCE LESS THAN 3. MS AND MORE THAN 1 MS FROM ADJACENT
AND ALL UNITS SHALL BE IN SYSTEM IS FOOTINGS. THE SEPTIC TANK SHOULD BE STRUCTURES FROM REINFORCED CONCRETE WITH A PROVISION OF PROPER INSULATION TO
MH NO
DMC
CL IL DISTANCE TO NEXT MH DEPTH COVER TYPE REMARK PREVENT ANY LEAKAGE FROM THE TANK
D-8 IF THE SEPTIC TANK & SOAK AWAY ARE TO BE FOUNDED AT A LOWER LEVEL THAN THAT OF ADJACENT FOOTING THEY SHOULD
RESIDENTIAL VILLA FOR
FIC
MH NO
BE CONSTRUCTED FIRST.
D-9 IF SEPTIC TANK CONSTRUCTED FROM FIBERGLASS MATERIAL THE DIMENSION SHALL BE THE SAME ,THE THICKNESS SHALL NOT LESS
MR. GIRISH HIRANANDANI
2- A SKETCH SHOWING THE RELATIVE LEVEL BETWEEN F.I.C AND BUILDING MANHOLES SHALL BE PROVIDED THAN 6 MM AND IT SHOULD BE INCASED WITH PROPER PROTECTION SOLID BLOCKS . DM PLOT 6316407, EMAAR PLOT PA-02
3- THE INVERT LEVEL OF THE EXTERNAL DRAINAGE SYSTEM SHALL BE DETERMINED BY THE CONSULTANT TAKING INTO CONSIDERATION D-10 PROPER INSULATION SHOULD BE PROVIDED FOR FOUNDATIONS OF BUILDINGS IN SUCH CIRCUMSTANCES FOR PROTECTION R.074, DUBAI HILLS ESTATE
THE DRAINAGE CONNECTION LEVEL TO MATCH THAT OF F.I.C, IN CASE OF N.O.C THE DEEP OF LAST MANHOLE SHALL BE LESS THAN 1200 MM. AGAINST SULFATES .
4- THE DEPTH OF FIRST MANHOLE SHALL BE AT LEAST 450 MM D-11 SOAKAWAY SHOULD BE FILLED WITH BOULDERS OF SIZE 75 MM TO 100 MM
5- SLOPES FOR HORIZONTAL RUNS SHALL BE AS FOLLOWS: FOR 100 MM - 1:60 FOR 150 MM - 1:90 FOR 200 MM - 1:120 D-12 GRP SEALING PLATE SHALL BE PROVIDED FOR THE LAST MANHOLE BEFORE THE SEPTIC TANK AND THE MANHOLE FOR
6- MANHOLES AND ACCESS CHAMBERS SHALL BE LAY OUT ACCORDING TO CONSULTANT'S SCHEME., COVERS PROVIDED SHALL BE ''ISSUE FOR'' ''DESCRIPTION''
THE FUTURE CONNECTION BEFORE THE DM SEWER LINE
SUITABLE FOR THE LOADS THEY ARE SUBJECTED TO, AND IN ACCORDANCE WITH BS 497 RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
7- ACUTE ANGLE CONNECTIONS SHALL NOT BE ALLOWED WITHIN JUNCTION MANHOLES. D-13 SIDE LEAKAGE FROM SOAK AWAY SHOULD BE PREVENTED OF CONSTRUCTED AT THE SAME LEVEL OF ADJACENT FOOTING OF
A BUILDING OR A BOUNDARY WALL FA FOR APPROVAL DD DESIGN DEVELOPMENT
8- AT A MH THE TOPS OF ALL SEWERS SHOULD BE AT THE SAME LEVEL SO THAT THE PIPES OF SMALLER DIAMETER ARE NOT PS PROGRESS SET CD CONSTRUCTION
FLOODED WHEN THE BIGGER PIPES ARE RUNNING FULL R FOR RECORD DOCUMENTS
9- BACKDROP SHALL BE PROVIDED WHEN THE LEVEL DIFFERENCE BETWEEN INCOMING AND MAIN SEWER IS CONSIDERABLE P PRELIMINARY TD TENDER DOCUMENTS
10- AN INSPECTION CHAMBER / MANHOLE / GULLY TRAP CONSTRUCTED IN COVERED AREA SHALL BE DRY TYPE AND PROVIDED WITH RECESSED M MUNICIPALITY REVIEW
DOUBLE SEAL TYPE COVER.
11- ANY MANHOLE LOCATED IN GARAGE, DRIVEWAY OR OTHER TRAFFIC AREAS SHALL BE PROVIDED WITH HEAVY DUTY COVERS.
12- IF INSPECTION CHAMBERS / MANHOLES ARE IN AGRICULTURAL LAND, MANHOLE COVERS SHOULD BE RAISED 75 MM ABOVE THE
THE NATURAL GROUND LEVEL.
13- DISTANCE BETWEEN MH TO MH SHALL NOT EXCEED 15 METERS IN VILLAS AND BUILDINGS
14- MINIMUM REQUIREMENT FOR MANHOLE VENTING SHALL BE THE PROVISION OF VENT PIPE TO FIRST AND LAST MANHOLES OF DRAINAGE LINE.
B
B
CHECKED BY Checker
MANAGEMENT M.SHAFY
A
A
SHEET TITLE
DRAINAGE NOTES
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
LIQUID LINE
D
OU - VRF SIGHT GLASS
D
RAWL PLUG
IU - VRF
4700 architects engineers designers planners
VIBRATION KIT TEL +971 4 332 4455 FAX +971 4 332 2113
4380 TRAP FOR LOWER UNITS
TWO ELBOWS OIL TRAP 3000 po box 73033 dubai web site www.naga.ae
(CAN BE DELETED IF
SUCTION LIFT IS < 2.4 m)
FAN COIL UNIT
4300
4140
C
C
IU - VRF
B
MOUNTING PLATE UNDER MOTOR DOME. PIPE
B
TYPE "L"
5. FOR KITCHEN EXHAUST FAN, THE BACKDRAFT DAMPER AND
FLEXIBLE DUCT CONNECTOR SHALL BE DISREGARDED.
BRASS SECTION-A
SCREWED PLAN REVIT FILE
F/A IN @ 6 F/A OUT TO CABLE
1 2 3 4 5 SCALE As indicated
VARIES
A
A
A4 REFRIGERANT
N.T.S.
PIPE IN GALVANIZED TRUNK ON ROOF SHEET TITLE
3 TOTAL FRESH AIR HANDLING UNIT WITH WRAP AROUND HEAT PIPE 4 EXHAUST FAN INSTALLATION DETAIL
N.T.S. N.T.S.
HVAC DETAILS 1
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
To CDU-1
FR CDU-1
U-1 REFRIGERANT LINES TO BE INSULATED WITH 20mm
CD ARMAFLEX AND PROTECTIVE ALUMINUM JACKETING
TYP. MIN 6"x6" PRESSURE TREATED SLEEPERS; FASTEN TO REFRIGERANT LINES TO BE INSULATED WITH 20mm
CONDENSER BASE. COORDINATE INSTALLATION WITH ROOFING SEAL WATERTIGHT AT PENETRATIONS THRU ROOF - ARMAFLEX
CONTRACTOR AND w ARCH. DIV. TYPICAL
TYP. WALL MTD. EVAP./FAN COIL (FC-1 & 2); INSTALLATION HGT. TO
CD
MANUFACT. GUIDELINES. COORD. ON-SITE. UNIT MAY NOT BE
D
EXACTLY AS ILLUSTRATED; REFER TO MANUFACTURER'S LITERATURE. NES
D
C
C
5 10
B
INSULATION AND LAGGING DETAIL
B
22 mm Ø HOLE
ITEM DESCRIPTION
1 G.S.S. DUCTING
2 INSULATION / LINER ADHESIVE
2a SELF ADHESIVE PIN / HANGER
3 ACCOUSTIC LINER
1 4 F.G. FLEX. BLANKET
TYPICAL INSTRUMENT TEST PORT DETAIL 2 4a F.G. FLEX. BLANKET B 27/12/2016 100 % CD FA NAGA
4b F.G. RIGID BOARD SUBMISSION
2a
5 ALUMINIUM FOIL SELF ADHESIVE TAPE A 12/05/2016 100 % DD FA NAGA
6 VAPOUR BARRIER FIRST COAT SUBMISSION
7 CANVAS CLOTH REV. DATE DESCRIPTION FOR BY
3
9 ISSUED
8 6 SECOND COAT
SAME AS ITEM BUT
ALUMINUM CLADDING 8 9 ALUMINIUM CLADDING ISSUE
OVER INSULATION FOR 7 10 50X50X0.6 mm G.I. ANGLE
EXPOSED DUCTS 1 PROJECT NO. PROJECT NUMBER
2a 4 6
2 4a
FLASHING 4b PROJECT ARCHITECT H.S.
DUCT ATTENUATOR
INSULATED C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt
ACCESS DOOR
SLOPE
REVIT FILE
AT GRILLE'S
ACOUSTIC APPLICATION SCALE As indicated
PLENUM BOX
LINING 3
DRAWN BY MF
FA FAHU A. INDOOR A/C S & R DUCT
1 2 2a 4 5 6 7 8 10
IN COND SPACES CHECKED BY EM
B. A/C DUCT S & R DUCTS IN
SHAFTS & NON COND. SPACES
1 2 2a 4b 5 6 7 8 10
10 MANAGEMENT M.SHAFY
INSTRUMENT TEST PORTS
C. ROOF EXPOSED S & R DUCTS 1 2 2a 3 4b 5 6 7 8 9
ROOF SLAB FIRE DAMPER PRINTING DATE/TIME 12/25/2016 11:57:36 AM
A
A
CONC. SLAB
HVAC DETAILS 2
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
REINFORCEMENT SUPPORT
4 Nos, 15Ø HOLES LONGEST SIZE OF DUCT ROD SIZE GAL. SPACING
25
LONGITUDINAL CLASS TYPE
FOR M-12 (mm) ANGLE (m)
ANCHOR BOLTS DUCT (mm) GAUGE CONNECTIONS
50
150
LAPPED AND BUTTED CORNER 0-300 G 26 PITTSBURGH - 6 25x25 2.4
-
50
M.S PLATE 325 - 450 G 24 PITTSBURGH * T1 8 25x25 2.4
4mm THICK A 24 *T12 - 1"X26ga
25
LINER INTERIOR THE VELOCITY RATED
No. * T1
D
SIDE OF LINER MUST 475 - 750 G 24 PITTSBURGH C 24 8 25x25 2
*T12 - 1"x26ga
D
C
800 - 900 G 22 PITTSBURGH * T1 10 25x25 2
MS ANGLE 3 0 8" dn D 22 *T12 - 1"x24ga
(FOR SIZE SEE TABLE-2) SECTION A-A 2 9"-16" * T1
950 - 1050 G 22 PITTSBURGH 10 40x40 2
B
3 17"-28" E 22 *T12 - 1 1/8"x18ga
M-10 NUT AND BOLT ALTERNATE FOLDED
4 29"-40" CORNER * T1
C
DUCT INSULATION 5 41"-52" A 1100 - 1350 G 20 PITTSBURGH F 20 10 40x40 1.8
*T12 - 1½"x24ga
(AS PER DETAIL) 6 53"-64" E
C
100
300x300x100 HIGH po box 73033 dubai web site www.naga.ae
ROOF INSULATION T-1
T-12 T-14
STANDING ANGLE REIFORCED DRIVE SLIP
C
C
B
B
FIG. B
N.T.S.
A
RETURN/EXHAUST
A
AIR FLOW
A1 FLEXIBLE
N.T.S.
CONNECTION DETAIL RECT DUCT ANGULAR TAP WITH VOLUME DAMPER
M0-GE-103
RECT DUCT ANGULAR TAP WITH VOLUME DAMPER
A4 AND
N.T.S.
SPLIT UNIT HANGING DETAIL SHEET TITLE
HVAC DETAILS 3
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
DUCT JOINT
BW2
R=1-1/2BW
T
2"
T
T=1/4W
D
W
T
D
W
3" MAX DISTANCE
ANGLE TO SUPPORT
W
SUGGESTED SIZING FOR
SUPPORT OF 12 FT. OF DUCT
R=1-1/2W
DUCT SIZE ANGLE
R=1-1/2BW
T
36" x 18" 1 1/2" x 1 1/2" x 1/8"
T
W
T
48" x 24" 1 1/2" x 1 1/2" x 1/8" R=1-1/2W
W BW
60" x 30" 1 1/2" x 1 1/2" x 3/16"
C1 RISER
N.T.S.
SUPPORTS-FROM FLOOR
TURN VANES
TURN VANES CONSULTANT
W
BW+2
W
architects engineers designers planners
TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae
W
BW
BW
BRANCH TAKE-OFF TEE SQUARE TURN TEE SQUARE TURN 90° ELBOW
C
C
DUCT INSULATION
DUCT SECTION
87mm (TYP)
22 GAGE
TURN VANE
R2
DUCT INSULATION DETAIL (INSIDE THE BUILDING)
N.T.S.
B
B
DENSE FIBERGLASS
50
A
MASTIC FILLER ALL AROUND
A
A1 DUCT
N.T.S.
PASSING THRU WALL A3 TYPI.
N.T.S.
DUCT THRU SLAB DETAIL M0-GE-104
SHEET TITLE
HVAC DETAILS 4
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
D
D
a: TABLE BASED ON SQUARE DUCTS, 1.46 mm.THICK, AND ALLOWS FOR DUCT WT. NORMAL
REINFORCEMENTS AND TRAPEZE WEIGHTS, AND FOR INSULATION WT. NO. EXTERNAL LOADS.
b: SEE AISC MANUAL FOR HANGER DESIGN CRITERIA.
25X25X1.46
40X40X1.46
(mm)
25X25X3
40X40X4
40X40X5
40X40X6
50X50X5
50X50X6
70X70X6
WIDTH
OF HANGER 50
(d)IN mm
UP THROUGH 750 30 70 80 160 230 295 425 560 890
1050 15 50 65 145 220 275 410 540 875
1200 - 35 50 130 205 260 395 525 860 ANGLE
1500 - - - 85 160 220 355 480 815
50
1650 - - - 45 120 180 320 445 780
FASTENERS
1800 - - - - 85 145 280 410 745 CONSULTANT
2000 - - - - 35 95 230 360 695
2100 - - - - - 35 170 300 635
3 NOS SANDWICH RUBBER PADS
2400 - - - - - - - 145 480 OF SIZE 100x100x32mm THICK
2750 - - - - - - - - 275
architects engineers designers planners
TEL +971 4 332 4455 FAX +971 4 332 2113
STRAP (WXT(min)mm LOAD, kg po box 73033 dubai web site www.naga.ae
ALTERNATE STRAP 25X0.75 120
OR ANGLE ROD 25X0.91 145 RISER SUPPORT FROM FLOOR
STRAP (TYP.) UPPER 25X1.18 190
ATTACHMENTS 25X1.46 320
40X1.46 500
C
76 mm 10 310
C
13 570
(150 mm) 25mm MIN. 16 910
SCREWS
BOLT d MAX (TYP)
MAXIMUM ALLOWABLE
TRAPEZE HANGER STRAP HANGER STRAP AND ROD LOADS
ALTERNATE
GALVANIZED SUPPORTS (TYP)
HANGER HANGER
STRAP COUPLING STRAP
WASHER
HANGER ROD SUGGESTED SIZING RESIDENTIAL VILLA FOR
NUT X
DUCT SIZE BAND
MR. GIRISH HIRANANDANI
Y
EXPANSION SHIELDS EXPANSION NAIL POWER ACTUATED
DM PLOT 6316407, EMAAR PLOT PA-02
450 x 300 40 x 16 Ga. R.074, DUBAI HILLS ESTATE
STUDS INTO STEEL WELDED STUDS
CONCRETE ANCHORS 600 x 500 25 x 3.2
R ALLOWABLE
HO ''ISSUE FOR'' ''DESCRIPTION''
ANC LOAD PER
UPPER ATTACHMENTS RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
DUCT GAGE FASTENER* FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
B
WIDTH AND UP. ADD ALONG SIDES NEAREST ANCHORS.
B
NO REDUCTION IN
FULL RADIUS ELBOW TAKE-OFF WITH MAIN DUCT SIZE
REDUCTION IN MAIN DUCT SIZE.
CURVED FOR 45 33/64
SPLITTER B 27/12/2016 100 % CD FA NAGA
SPLITTER AIR FLOW STRAIGHT
DAMPER SUBMISSION
DAMPER SLOPE 1"IN 7"
A 12/05/2016 100 % DD FA NAGA
AIR FLOW SUBMISSION
AIR FLOW D1
REV. DATE DESCRIPTION FOR BY
D1 D ISSUED
SPLITTER 3/4
4D
3/4D D+ HEEL RADIUS
ROD
D +3/ STRAIGHT ISSUE
HEEL RADIUS D SUGGESTED SIZING
SPLITTER THROAT RADIUS
ROD D 3/4 D DUCT SIZE BAND PROJECT NO. PROJECT NUMBER
THROAT RADIUS 750 x 300 25 x 25 x 3.2 PROJECT ARCHITECT H.S.
3/4 D DOUBLE THICKNESS VANES 900 x 450 25 x 25 x 3.2 C:\Users\mhegazy\Documents\15-030
1050 x 600 32 x 32 x 3.2 M-VILLA_mhegazy.rvt
A
CURVED FOR DAMPER
A
A1 DUCT
N.T.S.
TAKE OFFS SHEET TITLE
HVAC DETAILS 5
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
AIR AIR
FLOW FLOW
D
FRAME WITH CLINCH LOCK
D
C
2
C
N.T.S.
SPONGE RUBBER GASKET ALL AROUND
A3 AIR
N.T.S.
REGISTERS
RESIDENTIAL VILLA FOR
MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE
B
(TYP.)
B
B1 TYPICAL
N.T.S.
DETAIL OF FACE GRILLE N.T.S.
A6 SQUARE
N.T.S.
SUPPLY CEILING DIFFUSER PROJECT ARCHITECT H.S.
C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt
REVIT FILE
SCALE N.T.S.
DRAWN BY MF
CHECKED BY EM
MANAGEMENT M.SHAFY
A
A
M0-GE-106
SHEET TITLE
HVAC DETAILS 6
1 2 3 4 5 6 7
1 2 3 4 5 6 7
STAMPS
1000
1150
100 100 300 300 100 100
100mm CONCRETE 350 350
MAKEUP COVER GRADE 2 200mm PLASTER
200mm SOLID CONCRETE BLOCK
BENCHING RENDERED AND
PLASTIC OR STEEL RENTENTION STRAPS 100 TROWLLED TO 1:6 SIDE SLOPE
TO BE USED AT 300mm MIN CENTERS 150mm CONCRETE BASE
CLASS- C
BARRIER MATERIAL
(2mm THICK) BUTT JOINTS ARE ALWAYS TO BE 75mm CONCRETE BLINDING 70 350 350 70
200 300 300 200
COVERED WITH RETENTION STRAPS CLASS- D 1290
1140
VENT COWL NOTE: SHOWN DETAILS ARE FOR MANHOLES LOCATED IN FINISHED/PAVED AREA. FOR MANHOLES LOCATED IN
FIBER GLASS BATTING (25mm THICK) NON FINISHED AREA SHALL BE PROVIDED WITH CORBELLING FOR FUTURE ADJUSTMENT AT OF MANHOLE TOP.
WASTE PIPE SOIL PIPE
D
600x600 / 750x750 I.C DETAILS (FOR DEPTHS UP TO 1200 DEPTH)
D
A
ACOUSTIC LAGGING OF DRAINAGE PIPING BENCHING
750
ALL HORIZONTAL uPVC SOIL AND WASTE PIPES EXCEPT THOSE AT H/L OF CAR PARKING AREAS SHALL BE PROVIDED
WITH ACOUSTIC LAGGING AS DETAILED BELOW. FLEX. COUPLINGS
60
THE BARRIER SHALL BE CONSTRUCTED OF A 2mm THICK BARIUM SULPHATE LOADED LIMP VINYL SHEET BONDED TO A THIN LAYER OF REINFORCED ALUMINIUM FOIL ON ONE SIDE. B 0
THE BARRIER SHALL HAVE A NOMINAL DENSITY OF 4.8 kg/m3 AND SHALL HAVE MINIMUM STC RATING OF 28. BATH TUB W.C. A 750
BIDET (TO NEXT JOINT) 200 600 200
THE BARRIER SHALL BE CONSTRUCTED OF A 2mm THICK BARIUM SULPHATE LOADED LIMP VINYL SHEET BONDED TO A THIN LAYER OF REINFORCED ALUMINIUM FOIL ON ONE SIDE. Ø50 TYP
THE BARRIER SHALL HAVE A NOMINAL DENSITY OF 4.8 kg/m3 AND SHALL HAVE MINIMUM STC RATING OF 28. Ø50 Ø50
THE BARRIER SHALL EXHIBIT MINIUM FLAMMABILITY RATINGS OF 0.0 SECONDS FOR FLAME OUT AND AFTERGLOW AND 0.2 INCHES FOR CHAR LENGTH WHEN TESTED IN ACCORDANCE WITH FEDERAL TEST STD NO. 191-5903. TYPICAL CONNECTION DETAIL (FOR 600x600m MANHOLE)
THE BARRIER SHALL HAVE A MINIMUM THERMAL CONDUCTIVITY "K" VALUE OF 0.29 AND A RATED SERVICE TEMPERATURE RANGE OF 40F (-40C) TO 220F(105C). WHEN TESTED FOR SURFACE BUMING CHARACTERISTICS PER ASTM E84. NOTE : PURPOSE OF ABOVE DETAIL IS TO BE SHOW LOCATION OF FLEXIBLE COUPLINGS. SAME PRINCIPAL
THE BARRIER WILL HAVE A FLAME SPREAD INDEX OF NO MORE THAN 10 AND A SMOKE DEVELOPMENT INDEX OF NO MORE THAN 40. SHALL BE FOLLOWED FOR MUTIPLE CONNECTION MANHOLES.
SYPHON FLOOR GULLY
INSPECTION EYE INSPECTION EYE
Ø110 mm WASTE PIPE
SOUND TRANSMISSION LOSS CHARACHTERISTIES FOR BARRIER SHALL BE AS FOLLOWS : CLASS-C = GRADE M:40
WASH BASIN Ø110 mm SOIL PIPE
CLASS-D =PCC 1:3:6
TESTED AS A FREE HANGING BARRIER (ASTM E-90-90) CONSULTANT
FREQENCY, Hz
PRODUCT 125 250 500 1000 2000 4000 STC BATH TUB W.C. BIDET
KNM 100 ALQ-1 16 24 33 43 49 28 NOTES FOR MANHOLES CONSTRUCTION (RCC MANHOLE)
13
Ø50 Ø50 Ø50
BARRIER SHALL BE TYPE KNM100 ALQ-1 BY 'KINETICS NOISE CONTROL INC.' OR EQUAL APPROVED. 1. FOR CONCRETE CLASS DETAILS, REFER CIVIL WORKS SPECIFICATIONS. architects engineers designers planners
2. FOR EXTERNAL SURFACES OF MANHOLE WALLS, 3 COATS OF COLD APPLIED BITUMINIOUS POINT ARE REQUIRED.
TEL +971 4 332 4455 FAX +971 4 332 2113
THE DECOUPLING LAYER SHALL BE 25mm THICK FIBER GLASS BATTING, NON WOVEN POROUS SCRIM 3. FOR INTERNAL SURFACES AND BENCHING, PROVIDE 2 COAT OF EPOXY PAINT. po box 73033 dubai web site www.naga.ae
COATED GLASS CLOTH, QUILTED TOGETHER IN A MARTIX OF 100mm DIAMOND STITCH PATTERN WHICH SYPHON FLOOR GULLY 4. PROVIDE BLINDING ON POLYTHENE SHEET, 2000 GUAGE.
ENCAPSULATES THE GLASS FIBERS. THE COMPOSITE MATERIAL SHALL BE FABRICATED TO INCULDE A INSPECTION EYE 5. PROVIDE EPOXY COATED C. I. STEPS AT 300 MM INTERNAL, STAGGEREAD, FOR ALL MANHOLES DEEPER THAN 1200 MM.
INSPECTION EYE
NOMINAL 152mm WIDE BARRIER OVERLAP TAB EXTENDING BEYOND THE QUILTED FIBER GLASS TO
FACILITATE A LEAK-TIGHT SEAL AROUND FIELD JOINTS. TO GULLY TRAP
NOTE: SHOWN DETAILS ARE FOR MANHOLES LOCATED IN FINISHED/PAVED AREA.
THE DECOUPLING LAYER SHALL BE TYPE KFA BY 'KINETICS NOISE CONTROL INC' OR EQUAL APPROVED. FOR MANHOLES LOCATED IN NON FINISHED AREA SHALL BE PROVIDED WITH CORBELLING FOR FUTURE ADJUSTMENT AT OF MANHOLE TO
TO MANHOLE
C
C
D1 ACOUSTIC
N.T.S.
LAGGING OF DRAIN PIPES C4 TYPICAL
N.T.S.
DRAIN CONNECTION DETAIL C6 TYPICAL
N.T.S.
MANHOLE CONNECTION DETAIL
300
(REFER TO MECH. DRWGS.) F.CEILING AT EVERY FLOOR. R.074, DUBAI HILLS ESTATE
PROPRIETARY METAL ROOF OUTLET
ADJUSTABLE TO REQUIRED LEVEL
LOOSE GRAVEL AROUND DRAIN WASHING MACHINE
NO CUT SLABS HOSE ''ISSUE FOR'' ''DESCRIPTION''
2" MAIN VENT
400x400x40 LOOSELY LAID 7cm seal PIPE RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
CONCRETE TILES ON P.V.C PAD min FA FOR APPROVAL DD DESIGN DEVELOPMENT
2"
SQ. GRATING 50 EXTRUDED POLYSTYRENE F.F.L PS PROGRESS SET CD CONSTRUCTION
INSULATION DOUBLE SEALED Ø 50 mm SEALED CHROME
ACCESS PLUG F.F.L. R FOR RECORD DOCUMENTS
RECESSED COVER PLATED COVER F.F.L
WATERPROOFING MEMBRANE P PRELIMINARY TD TENDER DOCUMENTS
1000 MM
4 TORCH APPLIED
(3'-3")
B
Ø100 R.W.P.
B
ISSUE
150
200MM
(MIN)
VARIES
150
FFL Ø82 OUTLET
FFL PRINTING DATE/TIME 12/25/2016 11:57:53 AM
A
PIPE SUPPORT(TYP)
A
M0-GE-107
FCU/AHU CONDENSATE CONCRETE PROTECTION
A1 FLOOR
N.T.S.
CLEAN OUT A2 DRAIN
N.T.S.
CONNECTION A3 PIPE
N.T.S.
BEND IN STACKS A4 PIPE
N.T.S.
BEND AND CLEAN OUT A5 TYPICAL
N.T.S.
FLOOR TRAP DETAIL A7 OF PIPES UNDER BUILDINGS
N.T.S.
SHEET TITLE
DRAINAGE DETAILS 1
1 2 3 4 5 6 7
1 2 3 4 5 6 7
STAMPS
WASH BASIN
WB
15Ø FLEXIBLE BLOCK WALL
BOTTLE TRAP CONNECTOR
SINK COUNTER
4100
KITCHEN
40Ø TRAPPED WASTE
550
KITCHEN SINK
2250
1260
F.F.L F.F.L
32Ø WP
D
FT
D
32ØWP
140
82Ø WP 75Ø SLEEVE IN BEAM 2ND FL. FT
82Ø WP
C1 TYPICAL
N.T.S.
DETAIL FOR WASH BASIN CONNECTED TO FLOOR DRAIN architects engineers designers planners
TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae
110 VENT
160 WASTE
C
STACK
STACK
C
160 SOIL
ACCESS PANEL FOR STACK
DRAINAGE CLEANOUT
AT EVERY FLOOR (TO
ARCHITECT'S DETAIL
BY OTHERS) ACCESS PLUG
PIPE CLAMP
VENT CONNECTION
3000
@ EACH FLOOR
FLOOR OPENING
RESIDENTIAL VILLA FOR
FLOOR SLAB MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE
CONNECTION FROM CONNECTION FROM
INDIVIDUAL FLOOR INDIVIDUAL FLOOR
B
B
A
150 PIPE 150
A
8 URINAL 32
9 CLEANERS SINK 40
10 FLOOR TRAP OUTLET 80
M0-GE-108
BEDDING & BACKFILL DETAIL SHEDULE OF PIPE SIZES
1 2 3 4 5 6 7
1 2 3 4 5 6 7
STAMPS
φ75 VENT
D
D
ALUMINIUM PERFORATED
BUCKET FOR FILTRATION
R.C. SLAB
RWP
CONSULTANT
C
φ100mm
C
A A
3mm Thick G.R.P Lining
Applied in Concrete
two coats TOILET TOILET
200mm Thick solid concrete To receiving Manhole slope 1%
blocks or concrete with 'X' IS SUBJECT TO THE
normal steel IL depends upon the
WC APPROVAL OF SAN. FIXTURE.
150mm Concrete (Slag cement) base receiving manhole IL
100mm Concrete Blinding 110Ø SP @
-600 from F.G.L L/L INSIDE WC
FFL SSL F.F.L S.S.L
THE CAVITY X
X
Incoming Pipe from
Lifting Section FLOOR BEAM
PLAN SECTION A-A FLOOR BEAM 300x200 CUTOUT 110Ø SP
RESIDENTIAL VILLA FOR
600
(max)
IN BEAM
Ø110 SP FROM WC
MR. GIRISH HIRANANDANI
110 SP TO 'X' IS SUBJECT TO THE DM PLOT 6316407, EMAAR PLOT PA-02
MAIN PIPE APPROVAL OF SAN. FIXTURE. PIPE SUPPORT R.074, DUBAI HILLS ESTATE
D6 PRESSURE
N.T.S
BREAK MANHOLE RC
FA
REVIEW & COMMENTS
FOR APPROVAL
SD SCHEMATIC DESIGN
DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
R FOR RECORD DOCUMENTS
B
B
ISSUE
REVIT FILE
COLD APPLIED GALVANIZED STEEL PIPE SCALE As indicated
WATERPROOFING MEMBRANE SLEEVE WITH NON-LEAK
PUDDLE FLANGE DRAWN BY Author
LIGHT WEIGHT CONCRETE
LAID TO SLOPE (MINIMUM CHECKED BY Checker
RC SLAB (REFER TO THE
THICKNESS 50 mm)
STRUCTURAL DRAWINGS)
MANAGEMENT M.SHAFY
A
A
M0-GE-109
D7 PLANTER
N.T.S.
DRAIN DETAIL
SHEET TITLE
DRAINAGE DETAILS 3
1 2 3 4 5 6 7
1 2 3 4 5 6 7
STAMPS
15mm PIPE
1) SHOULD BE HEAVY DUTY FOR
R.C.C. BLOCK PARKING AREA AND DRIVE WAY.
2) MEDIUM DUTY FOR OTHER AREAS.
BIB TAP
RCC SLAB
RCC SLAB REDHEAD FIXING INTO CONCRETE
D
REDHEAD FIXING
D
VARIES
0'-10"
INTO CONCRETE P.P.R PIPE
VARIES
GALVANISED DROP STANDARD BINDER EYEBOLT
800mm
N.T.S.
CONSULTANT
FALSE CEILING
C
C
PIPE
M.S GALV FLAT CHROME PLATED IV IV
ANGLE VALVE
15
CLOSING VALVE
FORK SUPPORT
50 150
150
CONCRETE BLOCK WALL ''ISSUE FOR'' ''DESCRIPTION''
RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
A5 TYPICAL W.C WATER SUPPLY CONNECTION DETAILS FA FOR APPROVAL DD DESIGN DEVELOPMENT
PS PROGRESS SET CD CONSTRUCTION
N.T.S.
50 CWS PIPE FOR TANK INLET OR SUCTION PIPE R FOR RECORD DOCUMENTS
CONTINUOUS WELD
150
S.STEEL (4MM THICK)
B
B
EXPANSION
5 ANCHOR (TYP.) THREADED ROD
20 CWS 20 CWS (TYP.)
4 22 HWS
TOILET
N.T.S
PROJECT NO. PROJECT NUMBER
ABLUTION HOSE
300 FLEXIBLE CONNECTION REVIT FILE
120
(TYP.) PLATE
A
A
A1 TYPICAL
N.T.S.
ROOF WATER SUPPLY INSTALLATION M0-GE-110
SHEET TITLE
A3 TYPICAL
N.T.S.
PEX PIPE INSTALLATION
WATER SUPPLY DETAILS 1
1 2 3 4 5 6 7
1 2 3 4 5 6 7
STAMPS
C A
D
10
G
E OUTLET
9
8 7 6
B 5
4
D
3
D
2
F 1
CONSULTANT
Dimension in CM
A B C D E F G H I J
40 60 20 20 20 25 10 80 (Min:) 120 (Max:) 7.5 (dia:)
1 2 3 4 5 6 7 8 9 10
REGULATING VALVE
C
G.M.P.F G.M Inlet Nozzel Pad Locking Water Meter Viewing Protection Cover Outlet Gate Valve Union ( Threaded
NORMALLY CLOSED Adaptor Stop Meter Nozzle (Consumer side) Type )
C
C1 PRESSURE
N.T.S.
REDUCING VALVE ASSEMBLY (PRV) 1 ARRANGEMENT OF WATER METERING CABINET ON WALL
N.T.S
6 5
B
B
500
FLOOR SLAB
(INCH) SIZE (DIA mm) SIZE (DIA mm) (DIA mm) HORIZONTAL (m) FILL LINE 25mm (MIN.) 50mm
GALVANISED ANGLE 40x40mm (MIN.)
1/2" 15 15 8 1.050 FRAME ALL AROUND
3/4" 20 20 8 1.050 GAL. CHEQUERED PLATE RCC WATER TANK
HIGH LEVEL ALARM
4mm THICK HOT DIPPED 9 M3
1500
1" 25 25 8 1.050 GALVANISED.
HANGER ROD OFF FOR TRANSFER PUMP
1 1/4" 32 32 8 1.050
B 27/12/20 100 % CD FA NAGA
1 1/2" 40 40 8 1.050 GAL. ANGLE 40x40 ON FOR TRANSFER PUMP 16 SUBMISSION
2" 50 50 8 1.050 PIPES AT LOWER LEV. LOW LEVEL. A 12/05/20 100 % DD FA NAGA
DOMESTIC FOOT VALVE 16 SUBMISSION
2 1/2" 65 65 8 1.020 PIPE CLAMP
WATER REV. DATE DESCRIPTION FOR BY
3" 80 80 10 1.350 ISSUED
4" 100 100 10 1.750 40x40mm FRAME
ISSUE
1. HANGER WITHIN 600mm OF EACH SIDE OF VALVE, ELBOW & TEE TO BE PROVIDED.
PROJECT NO. PROJECT NUMBER
B1 SCHEDULE OF PIPE SIZE AND PIPE HANGER DETAIL FOR uPVC/PPR REVIT FILE
N.T.S.
CHECKED BY Checker
MANAGEMENT M.SHAFY
A
A
M0-GE-111
SHEET TITLE
1 2 3 4 5 6 7
1 2 3 4 5 6 7
STAMPS
D
D
I.V
EXPANSION VESSEL
I.V. N.R.V. I.V. AND DRAIN
P
STRAINER
HEATER
P PUMPS P.R.V
PRESSURE TEST POINTS. COIL FOR I.V
I.V. I.V. (TYPICAL) SOLAR
FORM SCW architects engineers designers planners
PRESSURE TEST POINTS. TEL +971 4 332 4455 FAX +971 4 332 2113
SUCTION PIPE (TYPICAL)
DRV po box 73033 dubai web site www.naga.ae
FROM TANK(S)
PRESSURE REGULATING
I.V I.V. VALVE (TYPICAL) SOLAR SYSTEM
SCHEMATIC DIAGRAM
A1 TYPICAL
N.T.S.
DETAIL OF DOMESTIC BOOSTER WATER PUMP SET 1 SOLAR SYSTEM
N.T.S.
C
C
CONTROL PANEL
CONTROL PANEL
B
B
MOTOR
MOTOR B 27/12/20 100 % CD FA NAGA
16 SUBMISSION
18 LIT PRESSURE VESSEL (P.V.)
A 12/05/20 100 % DD FA NAGA
FLEXIBLE PIPE 16 SUBMISSION
PRESSURE GUAGE REV. DATE DESCRIPTION FOR BY
18 LIT PRESSURE VESSEL (P.V.) ISSUED
NON-RETURN VALVE
REGULATING VALVE ISSUE
REGULATING VALVE
PROJECT NO. PROJECT NUMBER
REVIT FILE
SCALE As indicated
DRAWN BY Author
A
A
M0-GE-112
SHEET TITLE
1 2 3 4 5 6 7
1 2 3 4 5 6 7
STAMPS
HOOK
REFER BRACKET
ENLARGED
VIEW SCREW
FB
670
4.5 Kg
CO2 FIRE PROTECTION EQUIPMENTS NOTES SCREW
1. ALL FIRE SERVICES EQUIPMENT SHALL BE MANUFACTURED BY ONE OF THE CIVIL DEFENSE APPROVED MAKE. BRACKET
4.5 Kg.
CO2
1200
1200
2.ALL FIXED AND PORTABLE FIRE FIGHTING EQUIPMENTS SHALL BE TESTED BY INTERNATIONALLY RECOGNIZED FIRE
1160
1160
D
TESTING LABORATORIES & SAFETY ORGANIZATIONS BASED ON CERTIFICATION & NOT TESTED REPORTS.
D
4.5 Kg
CO2
140 3.ALL FIRE EQUIPMENTS TO BE PAINTED RED, AND CLEARLY INDICATEDBY AN APPROVED SIGN SYSTEM.
ENLARGED VIEW
FFL FFL
ELEVATION CONSULTANT
FIRE BLANKET ELEVATION
1.6MM THICK 75
M.S.BLACK SCREW HOLE HOOK
ENAMEL 4.5KG
COATED
70
70
CO2
C
60
C
WALL BRACKET
B
B
1200
170
1050
4.5KG
DP
B 27/12/20 100 % CD FA NAGA
16 SUBMISSION
CLAMP A 12/05/20 100 % DD FA NAGA
SCREW 16 SUBMISSION
REV. DATE DESCRIPTION FOR BY
BRACKET
FFL ISSUED
REVIT FILE
SCALE 1:2
59 DRAWN BY Author
A
190
190
4.5KG
A
DP
M0-GE-113
FRONT VIEW SIDE VIEW PLAN VIEW
SHEET TITLE
WALL BRACKET
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
D
D
1 2 3 4 5 6 7 8
150x150 EAD
TO GOOZENECK
EF-03
ER 300X100
80.0 L/s
SR 300X100
80.0 L/s
POOL PUMP ROOM CONSULTANT
FAF-01
150x150 SAD
TO GOOZENECK architects engineers designers planners
TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae
C
C
VD@40 L/S
IU-06
400x300 E
STAIRS
B-16
LOBBY SFBD-1SLOT-38 MM
350x300
200x100 5NOS. 485.0 L/s
B-14
RFBD-1SLOT, 38 MM
4M RESIDENTIAL VILLA FOR
MR. GIRISH HIRANANDANI
200x300
MECH. RM VD DM PLOT 6316407, EMAAR PLOT PA-02
B-13 R.074, DUBAI HILLS ESTATE
150x250
EFBD - 1SLOT-0.6 M ɸ250
25.0 L/s TYP.
DRIVER'S WC
B-07 ''ISSUE FOR'' ''DESCRIPTION''
STAIRS VD@50 L/S
B-15 D RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
200x250 ɸ250 FA FOR APPROVAL DD DESIGN DEVELOPMENT
IU-02
VD TYP.
VD 350x300 PS PROGRESS SET CD CONSTRUCTION
400x300
VD@30 L/S 200x300 R FOR RECORD DOCUMENTS
UC
SFBD-1SLOT-38 MM
SFBD - 1SLOT-25 MM DRIVER'S ROOM 250x200 5NOS. 485.0 L/s
P PRELIMINARY TD TENDER DOCUMENTS
B-08 150x100 M MUNICIPALITY REVIEW
400x300
2NOS 145.0 L/s T RFBD-1SLOT, 38 MM
150x100
2M TYP.
C/W.M.S. 200x100
GYM
200x250
B-10 TYP.
UC 150x250 200x250 VD
EF-02 LAUNDRY IU-06 T VD@15 L/S
300x200 FAD
B
UC B-09 T
100x200
150x100 STAIRS C
B
UC T
EFBD - 1SLOT-25 MM B-17
ɸ200 SFBD - 1SLOT-25 MM ɸ200
WATER TANK 25.0 L/s TYP. VD VD
B-11 IU-01 3NOS. 225.0 L/s TYP.
IU-03
ISSUE
REVIT FILE
SCALE 1 : 100
DRAWN BY MF
CHECKED BY EM
MANAGEMENT M.SHAFY
A
A
TRUE
PRO 35°
N N JEC
T
QIBLA
258°
M1-AC-101
SCALE 1:100
AC LAYOUT - BASEMENT
FLOOR PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
D
D
1 2 3 4 5 6 7 8
GOOSENECK
WITH MESH
CONSULTANT
GOOSENECK
WITH MESH
F F
EFBD - 1SLOT-25 MM ɸ200
C
50.0 L/s VD TYP.
300x250 300x250
C
400x300
RFBD-1SLOT-25 MM G-19
100x200
BMO 700X300
6M C/W.M.S.
300x100
VD@80 L/S T
T
500x250
EFBD - 1SLOT-0.6 M E E
25.0 L/s STAIRCASE
IU-06 UC G-17
DRY STORAGE
150x200 FAMILY POWDER R.
G-15
250x100 G-16 RESIDENTIAL VILLA FOR
BD
RECIRCULATING
HOOD
MR. GIRISH HIRANANDANI
200x100
DM PLOT 6316407, EMAAR PLOT PA-02
IU-02
RFBD-1SLOT-25 MM VD
2M RFBD-1SLOT-25 MM
SFBD - 2 SLOT- 38 MM BAR 10M
300x250
400x250
200x250 305.0 L/s G-05 FORMAL LIVING & DINING
300x150
250x300 EAD VD
B
ɸ200 VD@80 L/S G-04
T/A
B
IU-09
150x250
400x250
T
250X200 ENTRANCE TYP.
VD GUEST BEDROOM G-07
G-01 SFBD - 1SLOT-25 MM
G-06 150x250 2NOS. 100.0 L/s
100x200
200x250
BMO 500X250 SFBD - 1SLOT-25 MM
UC 250x300 50.0 L/s A 12/05/2016 100 % DD FA NAGA
300x250
UC
C/W.M.S. SUBMISSION
ROOF ACCESS GUEST BATHROOM RFBD-1SLOT-25 MM FORMAL POWDER R.1
G-09 IU-04 UC
G-08 G-03 REV. DATE DESCRIPTION FOR BY
ISSUED
ɸ150
ɸ150
100x200 ISSUE
TYP. EFBD - 1SLOT-0.6 M
25.0 L/s A A
EFBD - 1SLOT-0.6 M EFBD - 1SLOT-0.6 M PROJECT NO. PROJECT NUMBER
10.0 L/s 25.0 L/s
PROJECT ARCHITECT H.S.
C:\Users\mhegazy\Documents\15-030
M-VILLA_mhegazy.rvt
REVIT FILE
SCALE 1 : 100
DRAWN BY MF
CHECKED BY EM
? MANAGEMENT M.SHAFY
?
PRINTING DATE/TIME 12/25/2016 11:58:18 AM
A
PEDESTRIAN ENTRANCE
A
TRUE
PRO 35°
G-23
N N JEC
T
QIBLA
258°
M1-AC-102
SCALE 1:100
0 1 3 5m
A1 AC-GROUND
1 : 100
FLOOR PLAN SHEET TITLE
AC LAYOUT - GROUND
FLOOR PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
D
D
1 2 3 4 5 6 7 8
CONSULTANT
VD
ɸ250 F
300x300 300x300 TYP. ɸ200 ɸ200
VD
C
150x300 150x300 TYP.
150x250
VD TYP.
400x250
C
SFBD-1SLOT-38 MM
FAMILY LIVING 250x250
6NOS. 635.0 L/s F-01
RFBD-1SLOT-25 MM SFBD - 1SLOT-25 MM
3NOS. 225.0 L/s SFBD - 1SLOT-25 MM
6M MASTER BEDROOM 5NOS. 485.0 L/s
500x300
500x250
RFBD-1SLOT-25 MM
250x250
F-02 RFBD-1SLOT-25 MM
6M
5M
BMO 900X400
150x100
C/W.M.S. T
VD@25 L/S
E
IU-03
SFBD - 1SLOT-25 MM IU-06
50.0 L/s VD 250x150
RFBD-1SLOT-25 MM T
ɸ200
ɸ250
RESIDENTIAL VILLA FOR
150x250 VD
SFBD - 1SLOT-25 MM
50.0 L/s
150x250
VD SR 350X150
MR. GIRISH HIRANANDANI
RFBD-1SLOT-25 MM 100.0 L/s DM PLOT 6316407, EMAAR PLOT PA-02
RR 350X150 R.074, DUBAI HILLS ESTATE
HIS CLOSET ɸ150 SFBD - 1SLOT-25 MM
ɸ150 F-04 50.0 L/s
TYP. STAIRCASE
300x300
W/O HER CLOSET RFBD-1SLOT-25 MM
600x300
IU-05
IU-08 F-14
100x200
VD SFBD - 2 SLOT- 38 MM 350x300
POCKET GARDEN F-12
350x300
UC
F-06 ɸ150 2NOS 300.0 L/s SFBD - 1SLOT-25 MM
150x200
400x250
250X150 RFBD-1SLOT-25 MM
F-05 150x250 ɸ150 4M
150x200 UC VD 200x200 VD@40 L/S EFBD - 1SLOT-0.6 M
B
W/O 25.0 L/s
B
BEDROOM 3 T
BEDROOM 2 SFBD - 1SLOT-25 MM
150x200
REVIT FILE
SCALE 1 : 100
DRAWN BY MF
CHECKED BY EM
MANAGEMENT M.SHAFY
A
A
TRUE
PRO 35°
N N JEC
T
QIBLA
258°
M1-AC-103
SCALE 1:100
0 1 3 5m
D
D
1 2 3 4 5 6 7 8
CONSULTANT
C
F F
C
E E
B
F/B
B
C C
ACCU-01
FAHU-01
B B
ISSUE
REVIT FILE
SCALE 1 : 100
DRAWN BY MF
CHECKED BY EM
MANAGEMENT M.SHAFY
A
A
TRUE
PRO 35°
N N JEC
T
QIBLA
258°
M1-AC-104
SCALE 1:100
0 1 3 5m
SHEET TITLE
A1 AC-ROOF
1 : 100
PLAN AC LAYOUT - ROOF PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
M-DX TYPE TOTAL FRESH AIR HANDLING UNIT WITH WRAP AROUND HEAT PIPE
FRESH AIR HORSE SHOE-HEAT PIPE COOLING COIL HORSE SHOE-HEAT PIPE ELECTRICAL DATA
AIR INLET TEMP. AIR OUTLET TEMP.
EQUIPMENT SUMMER PRE COOLING COIL REHEAT COIL
UNIT NO. QTY. (°C) (°C) REMARKS
LOCATION AIR FLOW E.S.P. FAN TOTAL CAP. SENS. CAP.
V PH HZ
RATE(L/S) INLET TEMP. (°C) (PA) (KW) EAT (°C) LAT (°C) (KW) (KW) EAT (°C) LAT (°C)
DB WB DB WB
DB WB DB WB DB WB DB WB DB WB
D
FAHU-01 1 ROOF 650 46.1 29.4 400 1.1 46.1 29.4 38.7 27.8 40.5 17.9 38.7 27.8 13.7 13.2 13.7 13.2 21.0 16.0 400 3 50
D
NOTES:
ACTUAL COMPRESSOR DATA CONDENSER DATA ELECTRICAL POWER CALCULATION FOR THE INSERTION LOSS OF THE SOUND ATTENUATORS SHALL BE PROVIDED BY THE CONTRACTOR
UNIT NO. COOLING LOCATION AMBIENT (COMP. & COND. FAN) REMARKS AND SUBMITTED FOR APPROVAL BASED ON THE SOUND POWER LEVEL OF THE APPROVED EQUIPMENT AND SPACE
TYPE TYPE OF FAN V PH HZ
QTY. LOAD (KW) D.B. °C W.B. °C (KW) SOUND PRESSURE LEVEL NOT EXCEEDING NC 30.
architects engineers designers planners
ACCU-01 1 40.50 ROOF SCROLL 46.1 29.4 AXIAL TOP DISCHARGE 400 3 50 17.2 TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae
C
IU-02 3 AS SHOWN ON PLANS 2.60 2.40 170 24.0 17.9 13.7 12.8 2.9 2.5 170 50 230 1 50 150 -
C
IU-03 3 AS SHOWN ON PLANS 4.50 3.60 225 24.0 17.9 13.7 12.8 4.5 3.7 225 50 230 1 50 150
IU-04 1 AS SHOWN ON PLANS 5.10 4.60 285 24.0 17.9 13.7 12.8 5.7 4.7 285 50 230 1 50 150 -
IU-05 4 AS SHOWN ON PLANS 6.50 5.40 405 24.0 17.9 13.7 12.8 6.6 5.5 405 75 230 1 50 450 -
IU-06 4 AS SHOWN ON PLANS 8.30 6.90 485 24.0 17.9 13.7 12.8 8.5 7.0 485 75 230 1 50 450
IU-07 1 AS SHOWN ON PLANS 8.90 8.00 540 24.0 17.9 13.7 12.8 9.9 8.2 540 75 230 1 50 450
IU-08 1 AS SHOWN ON PLANS 12.00 11.00 750 24.0 17.9 13.7 12.8 12.7 11.1 750 75 230 1 50 450 -
IU-09 1 AS SHOWN ON PLANS 16.00 14.00 835 24.0 17.9 13.7 12.8 18.0 14.1 835 75 230 1 50 800
NOTES:
A. PROVIDE FINAL EQUIPMENTS AND ACCESSORIES SELECTIONS, PIPE SIZE CALCULATIONS, INSTALLATION DETAIL AND DRAWINGS FOR COMPLETE SYSTEM, CONTROL AND BILLING SYSTEM SELECTION. ''ISSUE FOR'' ''DESCRIPTION''
B. THE INSTALLATION SHALL BE CARRIED OUT BY QUALIFIED AND CERTIFIED INSTALLATION TECHNICIANS STRICTLY AS PER WRITTEN INSTRUCTIONS AND INSTALLATION MANUAL OF THE MANUFACTURE. RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
C. TESTING AND COMMISSIONING OF THE VRF A/C SYSTEM, CONTROLS AND BILLING SYSTEM SHALL BE CARRIED OUT BY THE MANUFACTURES CERTIFIED ENGINEERS STRICTLY AS PER MANUFACTURE FA FOR APPROVAL DD DESIGN DEVELOPMENT
RECOMMENDATION AND SHALL BE WITNESSED AND APPROVD BY THE ENGINEER / CLIENT REPRESENTATIVE. PS PROGRESS SET CD CONSTRUCTION
D. AUTHORIZED LOCAL DISTRIBUTOR SHALL BE RESPONSIBLE TO INSPECT THE FINAL INSTALLATION OF VRF SYSTEM, CONTROLS AND BILLINGS SYSTEM AND ISSUE CERTIFICATE TO THE OWNER R FOR RECORD DOCUMENTS
FOR COMPLETE INSTALLATION. P PRELIMINARY TD TENDER DOCUMENTS
M MUNICIPALITY REVIEW
4. CONTRACTOR SHALL PROVIDE 1 YEAR O&M AND SPARE PARTS FOR THE COMPLETE VRF SYSTEM AND CONTROL SYSTEM TO THE OWNER.
5. EACH INDOOR FCU SHALL BE CONNECTED TO ITS RESPECTIVE VRF OUTDOOR UNIT.
B
B
REVIT FILE
A
FAF-01 INLINE SUPPLY FAN POOL PUMP ROOM BASEMENT 1 80 DIRECT 50 1450 0.09 230 1 50 -
A
NOTES:
1. ALL EF'S SHALL BE PROVIDED WITH BACKDRAFT DAMPER AND SPEED CONTROLLER.
2. EXTERNAL STATIC PRESSURE IS APPROXIMATE, CONTRACTOR TO VERIFY AS PER ACTUAL CONDITION ON SITE. M1-AC-105
3. FAN SELECTION SHALL BE BASED ON NOISE PRESSURE LEVEL NOT TO EXCEED NC 35 IN THE SUPPLIED SPACE OR NOISE LEVEL REFLECTED TO OTHER SPACES.
SHEET TITLE
HVAC EQUIPMENT
SCHEDULE
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
1 2 3 4 5 6 7 8
D
D
F F
architects engineers designers planners
SHOWER DRAIN TEL +971 4 332 4455 FAX +971 4 332 2113
po box 73033 dubai web site www.naga.ae
E E
C
C
B B
ELV
B
B
ø80 mm RW T/B
ø50 mm FM BFS
ø80 mm VENT T/A
ø80 mm VENT T/A
ø80 mm VENT U/G
ø80 mm VENT U/G
A A
GT GT GT GT
PBM MH-01 B 27/12/2016 100 % CD FA NAGA
ø80 mm VENT U/G SUBMISSION
MH-03
MH-04 MH-02 ø150 mm SAN SLOPE 1:100 A 12/05/2016 100 % DD FA NAGA
ø150 mm SAN ø150 mm SAN
ø80 mm VENT U/G SUBMISSION
ø150 mm SAN SLOPE 1:100
ISSUE
REVIT FILE
SCALE 1 : 100
DRAWN BY INITIALS
CHECKED BY INITIALS
MANAGEMENT M.SHAFY
A
A
TRUE
PRO 35°
N N
C1 DR-SETTING OUT PLAN
JEC
T
1 : 100
QIBLA
258°
M3-DR-100
SCALE 1:100
0 1 3 5m
SHEET TITLE
DRAINAGE LAYOUT -
SETTING OUT PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
D
D
1 2 3 4 5 6 7 8
CONSULTANT
F F
C
C
E E
STAIRS
B-16
MECH. RM
B-13
RESIDENTIAL VILLA FOR
LOBBY
B-14
MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE
ø1
10
m
STAIRS
m
B-15 DRIVER'S WC
ø80 mm WS B-07 RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
ø110 mm SP U/G FA FOR APPROVAL DD DESIGN DEVELOPMENT
ø80 mm WS U/G PS PROGRESS SET CD CONSTRUCTION
R FOR RECORD DOCUMENTS
ø80 mm WS
P PRELIMINARY TD TENDER DOCUMENTS
ø110 mm SP U/G
ø80 mm WS U/G DRIVER'S ROOM GYM M MUNICIPALITY REVIEW
B-08 ELECTRICAL CABINET B-06
B-18
AD ø80 mm WS LAUNDRY ø80 mm WS AD
STORAGE B-09
B-10
ø80 mm WS D W W STAIRS C C
B
ø110 mm SP U/G ø80 mm WS U/G B-17
B
REVIT FILE
SCALE 1 : 100
DRAWN BY Author
CHECKED BY Checker
MANAGEMENT M.SHAFY
A
A
TRUE
PRO 35°
N N JEC
T
QIBLA
258°
M3-DR-101
SCALE 1:100
0 1 3 5m
SHEET TITLE
1 DR-BASEMENT
1 : 100
DRAINAGE LAYOUT -
BASEMENT FLOOR PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
D
D
1 2 3 4 5 6 7 8
CONSULTANT
FAMILY DINING\
FAMILY LIVING
SHOW KITCHEN G-18
ø80 mm WS BFS
G-19
C
C
E E
STAIRS
B-16
DRY STORAGE STAIRCASE
G-15 FAMILY POWDER R. G-17
G-16
STAIRS
ø80 mm WS BFS
ø110 mm SP BFS
C C
ø80 mm WS BFS
ø110 mm SP BFS
ø110 mm SP BFS
ø80 mm WS BFS
ø80 mm WS BFS
B-17
CORRIDOR FORMAL LIVING & DINING
ENTRANCE G-02 G-04
G-01 B B
B
FORMAL POWDER R.1
B
A
A
TRUE
PRO 35°
N N JEC
T
QIBLA
258°
M3-DR-102
A1 DR-GROUND
1 : 100
FLOOR PLAN
SCALE 1:100
0 1 3 5m
SHEET TITLE
DRAINAGE LAYOUT -
GROUND FLOOR PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
D
1 2 3 4 5 6 7 8
D
CONSULTANT
FAMILY LIVING
F-01
MASTER BEDROOM
F-02
C
C
E E
STAIRCASE
F-18
ø110 mm SP BFS
ø80 mm WS BFS
CLOSET 3
F-09
CORRIDOR B B
BEDROOM 3 F-11
F-07
B
B
BATHROOM 3 BATHROOM 2
F-17
F-10
BEDROOM 2
ø110 mm SP BFS F-15
CLOSET 2
F-16
ROOF ACCESS
G-09 GUEST BATHROOM
G-08
ISSUE
REVIT FILE
SCALE 1 : 100
DRAWN BY INITIALS
CHECKED BY INITIALS
MANAGEMENT M.SHAFY
A
A
TRUE
PRO 35°
N N JEC
T
QIBLA
258°
1 : 100
M3-DR-103
SCALE 1:100
0 1 3 5m
SHEET TITLE
1 2 3 4 5 6 7 8
D
D
CONSULTANT
C
E E
C
B B
B
B
A A
B 27/12/2016 100 % CD FA NAGA
SUBMISSION
A 12/05/2016 100 % DD FA NAGA
SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED
ISSUE
REVIT FILE
SCALE 1 : 100
DRAWN BY INITIALS
CHECKED BY INITIALS
MANAGEMENT M.SHAFY
A
A
TRUE
PRO 35°
N N JEC
T
A1 DR-ROOF PLAN
QIBLA
258°
1 : 100 M3-DR-104
SCALE 1:100
0 1 3 5m
SHEET TITLE
1 2 3 4 5 6 7 8
D
D
CONSULTANT
DN OD SIZE (PPR) PN (16)
12 20
F F
15 25 architects engineers designers planners
TEL +971 4 332 4455 FAX +971 4 332 2113
FAMILY LIVING po box 73033 dubai web site www.naga.ae
FAMILY DINING\ 20 32
G-18
SHOW KITCHEN
G-19 25 40
32 50
E E
C
STAIRCASE
FAMILY POWDER R.
C
G-17
DRY STORAGE G-16 STAIRS
G-15 B-16
STAIRS
F F DW RESIDENTIAL VILLA FOR
B-15 D D
MR. GIRISH HIRANANDANI
CORRIDOR DM PLOT 6316407, EMAAR PLOT PA-02
G-11
R.074, DUBAI HILLS ESTATE
DB + TELE. CABINET
G-25
B
B
ROOF ACCESS
G-09
GUEST BATHROOM
G-08
A A
B 27/12/2016 100 % CD FA NAGA
SUBMISSION
A 12/05/2016 100 % DD FA NAGA
SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED
ISSUE
SCALE 1 : 100
DRAWN BY INITIALS
CHECKED BY INITIALS
MANAGEMENT M.SHAFY
A
A
TRUE
PRO 35°
N N JEC
T
A1 WS-SETTING
1 : 100
OUT PLAN
QIBLA
258°
M4-WS-100
SCALE 1:100
0 1 3 5m
SHEET TITLE
D
D
1 2 3 4 5 6 7 8
CONSULTANT
C
C
E E
STAIRS
B-16
MECH. RM
B-13
LOBBY
B-14
RESIDENTIAL VILLA FOR
ø15 mm PW H/L ø15 mm HWR H/L MR. GIRISH HIRANANDANI
ø15 mm HW H/L ø15 mm HW H/L
ø15 mm PW H/L DM PLOT 6316407, EMAAR PLOT PA-02
ø15 mm HWR H/L
STAIRS R.074, DUBAI HILLS ESTATE
B-15 D D
B
STORAGE OFFICE
B
B-01 B-05
PANTRY
ø40 mm CW H/L B-02 POWDER
B-03
ø15 mm PW H/L
ø15 mm HW H/L B 27/12/2016 100 % CD FA NAGA
SUBMISSION
A A A 12/05/2016 100 % DD FA NAGA
SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED
ISSUE
REVIT FILE
SCALE 1 : 100
DRAWN BY Author
CHECKED BY Checker
MANAGEMENT M.SHAFY
A
A
TRUE
PRO 35°
N N JEC
T
QIBLA
258°
M4-WS-101
1 WS-BASEMENT SCALE 1:100
1 : 100
0 1 3 5m
SHEET TITLE
D
D
1 2 3 4 5 6 7 8
CONSULTANT
DN OD SIZE (PPR) PN (16)
12 20
25 40
FAMILY DINING\
FAMILY LIVING
ø15 mm PW U/G
ø15 mm HW U/G
SHOW KITCHEN G-18 32 50
G-19
C
ø15 mm HW H/L
C
ø15 mm PW H/L
STAIRS E E
B-16
FAMILY POWDER R.
DRY STORAGE G-16 STAIRCASE
G-15 G-17
ø40 mm PW H/L ø15 mm CW H/L
ø20 mm HW H/L ø15 mm HW H/L
ø15 mm HWR H/L ø15 mm HWR H/L
B
GUEST BEDROOM CLOSET
B
ISSUE
REVIT FILE
?
?
SCALE 1 : 100
? PEDESTRIAN ENTRANCE
? G-23 DRAWN BY INITIALS
CHECKED BY INITIALS
MANAGEMENT M.SHAFY
A
A
TRUE
PRO 35°
N N JEC
T
QIBLA
258°
M4-WS-102
0 1 3 5m
1 : 100
SHEET TITLE
D
D
1 2 3 4 5 6 7 8
CONSULTANT
DN OD SIZE (PPR) PN (16)
12 20
25 40
32 50
C
C
E E
B
ø20 mm HWR H/L
B
ø40 mm CW H/L
ø15 mm HWR H/L ø15 mm CW H/L ø20 mm HW H/L
ø15 mm HW H/L ø15 mm HW H/L
ø15 mm PW H/L ø15 mm HWR H/L ø15 mm HWR H/L
B 27/12/2016 100 % CD FA NAGA
ø15 mm HWR H/L SUBMISSION
ø15 mm HW H/L A A A 12/05/2016 100 % DD FA NAGA
ø15 mm PW H/L
SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED
ISSUE
REVIT FILE
SCALE 1 : 100
DRAWN BY INITIALS
CHECKED BY INITIALS
MANAGEMENT M.SHAFY
A
A
TRUE
PRO 35°
N N JEC
T
QIBLA
258°
M4-WS-103
A1 WS-FIRST
1 : 100
FLOOR PLAN SCALE 1:100
0 1 3 5m
SHEET TITLE
1 2 3 4 5 6 7 8
D
D
CONSULTANT
DN OD SIZE (PPR) PN (16)
SWH 300 LIT 12 20
25 40
D
32 50
WR
ø40 mm H ø50 mm CW T/B
ø40 mm HW T/B
C
HW ø25 mm HWR F/B
ø40 mm
C
B
RESIDENTIAL VILLA FOR
MR. GIRISH HIRANANDANI
ø50 mm CW FILLING LINE ø50 mm CW FILING LINE DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE
B
C1 WS-ROOF PLAN
B
1 : 100
25°
REV. DATE DESCRIPTION FOR BY
Average Daily Hot Water Consumption: ISSUED
Average Daily Hot Water Consumption per Villa= No. of Toilets / Bathrooms x 50 L= 7 350 L
SOLAR WATER HEATER SCHEDULE ISSUE
+No. of WCs x 30 L= 4 120 L
TAG EQUIPMENT DESCRIPTION SYSTEM STORAGE TANK CAPACITY PANEL TYPE NO. OF PANEL LOCATION QTY.
+No. of Kitchens x 80 L= 1 80 L PROJECT NO. PROJECT NUMBER
CHECKED BY INITIALS
Undertaking:
I/we hereby commit to full requirements of circular No. 183/2011 issued by Dubai Municipality regarding Solar Water Heaters.
This commitment without exception applies to the design, installation and commissioning of Solar Water Heaters.
MANAGEMENT M.SHAFY
The solar water heater system shall be installed, operated and maintained by registered licensed company by the Department
of Economic Development and approved by Dubai Municipality. The solar water heater system shall be approved by Dubai
Central laboratory. PRINTING DATE/TIME 12/25/2016 11:59:27 AM
A
It is understood that failure to comply with the regulations may also result in fine or other penalty.
A
TRUE
PRO 35°
Notes: N N JEC
T
1- This sheet shall be attached to the roof plan of water supply drawings, and uploaded with the sewerage drawings in the
plumbing folder.
2- No Separate electric water heater shall be used.
3- Incase more than one type of typical villas (with different Average Daily Hot Water Consumption) is available, then additional
QIBLA
sheet(s) for each type to be attached.
258°
M4-WS-104
SCALE 1:100
Applicant:.................................................................................................... 0 1 3 5m
NAGA
SHEET TITLE
D
D
1 2 3 4 5 6 7 8
CONSULTANT
FAMILY DINING\
FAMILY LIVING
SHOW KITCHEN G-18
G-19
C
C
E E
STAIRS
B-16
FAMILY POWDER R.
DRY STORAGE G-16 STAIRCASE
G-15 G-17
B
B
GUEST BEDROOM
G-06 CLOSET FORMAL POWDER R.1
G-07
G-03
ROOF ACCESS
G-09
ø15 mm NPG
GUEST BATHROOM
G-08
B 27/12/2016 100 % CD FA NAGA
SUBMISSION
A A A 12/05/2016 100 % DD FA NAGA
SUBMISSION
REV. DATE DESCRIPTION FOR BY
ø25 mm NPG U/G
ISSUED
75 MBAR/21 MBAR REGULATOR
ISSUE
A
A
M5-NG-100
1 NG-GROUND FLOOR PLAN
1 : 100
SHEET TITLE
NG LAYOUT - GROUND
FLOOR PLAN
1 2 3 4 5 6 7
1 2 3 4 5 6 7
KEYPLAN
D
D
1 2 3 4 5 6 7 8
CONSULTANT
F F
C
C
E E
STAIRS
B-16
MECH. RM
B-13
RESIDENTIAL VILLA FOR
LOBBY
B-14
MR. GIRISH HIRANANDANI
DM PLOT 6316407, EMAAR PLOT PA-02
R.074, DUBAI HILLS ESTATE
4.5 KG DRY
STAIRS CHEMICAL
B-15 POWDER
D D ''ISSUE FOR'' ''DESCRIPTION''
RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
5KG CO2
FA FOR APPROVAL DD DESIGN DEVELOPMENT
9 LIT WATER
PS PROGRESS SET CD CONSTRUCTION
EXTINGHER
DRIVER'S WC R FOR RECORD DOCUMENTS
DRIVER'S ROOM B-07 P PRELIMINARY TD TENDER DOCUMENTS
B-08 M MUNICIPALITY REVIEW
GYM
ELECTRICAL CABINET B-06
B-18
STORAGE LAUNDRY
B-10 B-09
D W W STAIRS C C
B
B-17
B
PANTRY
B-02 POWDER
B-03
B 27/12/2016 100 % CD FA NAGA
SUBMISSION
A 12/05/2016 100 % DD FA NAGA
SUBMISSION
REV. DATE DESCRIPTION FOR BY
ISSUED
A A
ISSUE
REVIT FILE
SCALE 1 : 100
DRAWN BY Author
CHECKED BY Checker
MANAGEMENT M.SHAFY
A
A
TRUE
PRO 35°
N N JEC
T
QIBLA
258°
M6-FP-101
SCALE 1:100
0 1 3 5m
SHEET TITLE
D
D
1 2 3 4 5 6 7 8
CONSULTANT
F F
C
C
FAMILY DINING\
FAMILY LIVING
SHOW KITCHEN G-18
G-19
E E
STAIRCASE
STAIRS
FAMILY POWDER R. G-17
B-16
DRY STORAGE G-16
G-15
RESIDENTIAL VILLA FOR
2KG CO2
MR. GIRISH HIRANANDANI
4.5 KG DRY FRY KITCHEN CORRIDOR DM PLOT 6316407, EMAAR PLOT PA-02
LPG CABINET CHEMICAL G-14 G-10 R.074, DUBAI HILLS ESTATE
G-20
POWDER
4.5 KG DRY
CHEMICAL
POWDER ''ISSUE FOR'' ''DESCRIPTION''
DW 5KG CO2
STAIRS RC REVIEW & COMMENTS SD SCHEMATIC DESIGN
B-15 9 LIT WATER D D
FA FOR APPROVAL DD DESIGN DEVELOPMENT
EXTINGHER
MAID'S BATH R. PS PROGRESS SET CD CONSTRUCTION
G-13 CORRIDOR R FOR RECORD DOCUMENTS
G-11 P PRELIMINARY TD TENDER DOCUMENTS
DB + TELE. CABINET M MUNICIPALITY REVIEW
G-25
B
STAIRS
B
C C
B-17
CORRIDOR FORMAL LIVING & DINING
G-02 G-04
ENTRANCE
G-01 B B
GUEST BEDROOM
G-06 CLOSET FORMAL POWDER R.1
G-07
G-03
B 27/12/2016 100 % CD FA NAGA
SUBMISSION
A 12/05/2016 100 % DD FA NAGA
ROOF ACCESS SUBMISSION
G-09 REV. DATE DESCRIPTION FOR BY
GUEST BATHROOM
G-08 ISSUED
A A ISSUE
REVIT FILE
SCALE 1 : 100
DRAWN BY Author
CHECKED BY Checker
? MANAGEMENT M.SHAFY
?
PEDESTRIAN ENTRANCE PRINTING DATE/TIME 12/25/2016 11:59:37 AM
?
A
G-23
A
TRUE
? PRO 35°
N N JEC
T
QIBLA
258°
M6-FP-102
SCALE 1:100
0 1 3 5m
SHEET TITLE
D
D
1 2 3 4 5 6 7 8
CONSULTANT
F F
C
C
E E
B
B
C C
B B
A A ISSUE
REVIT FILE
SCALE 1 : 100
DRAWN BY Author
CHECKED BY Checker
MANAGEMENT M.SHAFY
A
A
TRUE
PRO 35°
N N JEC
T
QIBLA
258°
M6-FP-103
SCALE 1:100
0 1 3 5m
SHEET TITLE
D
D
P-PUMPS SCHEDULE
ELECTRIC DATA
UNIT NO. QTY. DESCRIPTION LOCATION TDH (M) FLOW (L/S) POWER (KW) REMARKS
VOLT PHASE HERTZ
HWP 1 HOT WATER BOOSTER PUMP ROOF 20 1 1.50 220 1 50
HWP 1 HOT WATER BOOSTER PUMP ROOF 20 1 1.50 220 1 50
CP 1 CIRCULATION PUMP ROOF 10 1 0.50 220 1 50
TP 1 TRANSFER PUMP PUMP ROOM 25 1 1.50 220 1 50
TP 1 TRANSFER PUMP PUMP ROOM 25 1 1.50 220 1 50
SP 1 SUMP PUMP BASEMENT 10 2 1.00 220 1 50
SP 1 SUMP PUMP BASEMENT 10 2 1.00 220 1 50
CBP 1 COLD WATER BOOSTER PUMP ROOF 20 2 1.50 220 1 50
CBP 1 COLD WATER BOOSTER PUMP ROOF 20 2 1.50 220 1 50
CONSULTANT
P-MANHOLES SCHEDULE
MANHOLE NO. COVER LEVEL INVERT LEVEL DEPTH COVER SIZE DRAWING LOCATION REMARKS
MH-01 0.0 -0.45 0.45 600X600 SETTINGOUT PLAN
C
MH-02 0.0 -050 0.50 600X600 SETTINGOUT PLAN
C
B
B
ISSUE
REVIT FILE
SCALE
DRAWN BY Author
CHECKED BY Checker
MANAGEMENT M.SHAFY
A
A
M8-PG-100
SHEET TITLE