PRODUCT DEFINITION
Model GA55VSD+
Frequency 50Hz
Supply voltage 400V
Cooling Air
Options
LIMITATIONS
Minimum ambient temperature 0 °C
Minimum effective working pressure 4 bar(g)
Maximum effective working pressure
Workplace P 13 bar(g)
Workplace FF 12,75 bar(g)
Maximum altitude 1000 m
Maximum allowable inlet temperature P 46 °C
Maximum allowable inlet temperature FF 46 °C
REFERENCE CONDITIONS
Absolute inlet pressure 1 bar(a)
Relative humidity 0 %
Air inlet temperature 20 °C
Cooling medium inlet (water or air) temperature 20 °C
Setpoint thermostatic valve 60 °C
Normal effective working pressure 4 7 9,5 12,5 bar(g)
PERFORMANCE DATA
Free Air Delivery
at effective motor speeds stated
850 rpm 25,8 26,2 25,9 - l/s
1267 rpm 40,5 40,3 39,9 40,2 l/s
1500 rpm 48,9 48,5 47,9 48,0 l/s
2000 rpm 66,9 66,3 65,5 65,0 l/s
2250 rpm 75,9 75,2 74,4 73,7 l/s
2500 rpm 84,9 84,2 83,4 82,5 l/s
3000 rpm 102,9 102,3 101,4 100,2 l/s
3500 rpm 120,8 120,4 119,5 118,1 l/s
4117 rpm 142,9 142,7 141,5 140,0 l/s
4817 rpm 168,0 167,7 166,1 - l/s
5400 rpm 188,9 188,1 - - l/s
DESIGN DATA
Compression stage C106*
Blow off volume 38 l
Time to reach 80% blow-off 45 s
Oil capacity 32 l
Cooling air flow referred to air inlet grating compressor 4,00 m³/s
Drive motor efficiency at full load 96 %
Fan motor efficiency 77 %
INTEGRATED DRYER
Integrated Dryer type ID180
Pressure Dew Point Full Feature at amb = 20°C; RH = 100% 3 °C
Pressure drop over dryer 0,180 bar(g)
Total power consumption
at full load (amb = 20°C; RH = 100%; incl fan) 1,8 kW
Cooling air flow 10,6 m³/min
Heat dissipated by cooling air (ambient = 20°C, RH = 100%) 5,9 kW
Refrigerant type R410A
Total amount 1,250 kg
REMARKS
(1) Unless otherwise stated, at reference conditions.
All values given with a tolerance according to specified.
Codes are guaranteed; all other values are to be considered typical.
(2) Free Air Delivery measured according ISO 1217 ed. 4 2009, annex E
25 l/s < FAD < 250 l/s Tolerance 5%
FAD > 250 l/s Tolerance 4%
(3) Specific Energy Requirement measured according ISO 1217 ed. 4 2009, annex E
25 l/s < FAD < 250 l/s Tolerance 6%
FAD > 250 l/s Tolerance 5%
(4) Measured according to ISO 2151: 2004 using ISO 9614/2 (sound intensity method).
The International ISO 1217 ed. 4 2009 standard refers to following standards :
- ISO 5167 - British BS 1571 Part 2
- ISO 9300 - American ASME PTC9
- German DIN 1950