500 - RKM Annexg HDGHD DGHH D

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

RKM Annexure 1

Sl
DESCRIPTION Unit Details AMES
NO
41 Short-circuit withstand capacity 3s(KA) KA 16.67

42 Transformer short Voltage KV 0.46(impedance voltage)


43 No load charging KVA & PF KVA 9.99 & 0.098
45 Winding material HV -Copper / LV-Copper
45.1 Windings fully insulated/graded insulation Full
45.2 Type of winding Spiral /cross over
Hot spot temperature in winding limited to
46 (over yearly weighted ambient °C 155
temperature of 32°C)
47 Guaranteed losses
Load loss at rated current at 125 ° C
47.3 KW 4.96 (Max)
(Max.)
Total Loss at Rated Voltage at Principal
Tapping, Rated
47.4 5.26 kW
Frequency, at 75Deg. C & at 100% load
(Max)
48 Impedance

80 to 110 % of positive
48.2 Positive / zero sequence impedance
% zero sequence impedance

HV - 3.78
48.3 Resistance at 75 deg C Ohms
LV - 0.001143
Guaranteed Efficiency at 75 °C winding
49
temperature and at 0.8 p.f. lag
49.1 At 100% of full Load % 98.7
49.2 At 75% of full Load % 98.88
49.3 At 50% of full Load % 98.98
49.4 At 25% of full Load % 98.76
Maximum current density for HV & LV
50 Amp /mm2 2.5
winding
Magnetizing current at rated voltage and
51 <1.5% of FL Current
frequency ( % of full load current )
mmxmmxm
52 Transport dimensions L x W x H To be mentioned
m
53 Transport weight of largest item Kg To be mentioned
54 Termination arrangement To be mentioned
55 Reference standard for Bushing IS 2099
56 HV Cable box
56.1 Degree of protection IP 52
56.2 Phase to Phase Clearances mm 130
56.3 Phase to earth Clearances mm 80
Cable Box- for both top and
57 LV Cable Adapter box
bottom cable entry
57.1 Degree of protection IP52
57.2 Phase to Phase Clearances mm 25
57.3 Phase to earth Clearances mm 20
LV Neutral Bushing Current
58
transformers
58.1 Make kappa/ pragathi
58.2 Type Resin casted
58.3 Voltage class kV 0.415
58.4 Current ratio 400 / 5 A
58.5 Burden and accuracy class 50VA & 5p20
60 Cover details
60.1 Thickness of side/top/bottom plate mm 2 / 3.15 / 2
60.2 Pressure withstand capacity Kg /m2 NA
60.3 Vacuum withstand capacity mm of Hg NA
61 Marshalling box
61.1 Degree of protection IP54
61.2 Terminal Blocks —make & type Elemax & Stud type
61.3 Material of gasket Neoprene
62 Wheels
62.1 Plain / flanged Plain
62.2 Unidirection / Bidirectional Bidirectional
62.3 Quantity 4
62.4 Gauges 820
62.5 Longitudinal mm 820
62.6 Transverse mm 670
63 Winding Temperature indicator( Local)

63.1 Make Precimeasure / PECON


63.2 Type Digital
63.3 Number of contacts 2 NO+2 NC
63.4 Contacts voltage and rating 220V, 5A
64 Creepage distance casing mm 150mm from HV coil to Enclosure
REACTANCE AT RATED CURRENT &
65 3.90%
FREQUENCY
RESISTANCE AT RATED CURRENT &
66 0.85%
FREQUENCY
67 Load at which max. efficiency occurs kVA DDE
68 Altitude 1000 ABOVE MSL
71 Orientation between HV & LV As per GA drawing
72 Tolerance +/-10 %
73 Over Load capacity AS PER IS 6600
3Rx3.5Cx300 sq,mm cable overall
74 LV Cable size
dia approx. 57 mm

You might also like