RKM Annexure 2

Sl NO DESCRIPTION Unit Details AMES


≤ 2 % of
41 HV no load current at rated voltage Amps
Full Load Current
42 Short-circuit withstand capacity 3s(KA) KA 21
43 Transformer short Voltage KV 0.46(impedance voltage)
44 No load charging KVA & PF KVA 12.61 & 0.11
Hot spot temperature in winding limited to
45 (over yearly weighted ambient temperature of °C 155
32°C)
46 Guaranteed losses
46.1 Load loss at rated current at 125 ° C (Max.) KW 6.03
Total Loss at Rated Voltage at Principal
46.2 Tapping, Rated Frequency, at 75Deg. C & at 6.64
100% load (Max)
47 Impedance
80 to 110 % of positive
47.1 Positive / zero sequence impedance
% zero sequence impedance
HV- 2.79
47.2 Resistance at 75 deg C Ohms
LV - 0.00091
47.3 1 min Power frequency With stand Voltage HV side (KV) 35
LV side (KV) 3
Guaranteed Efficiency at 75 °C winding
48
temperature and at 0.8 p.f. lag
48.1 At 100% of full Load % 98.7
49.1 At 75% of full Load % 98.86
50.1 At 50% of full Load % 98.92
51.1 At 25% of full Load % 98.61
Guaranteed Efficiency at 75 °C winding
52
temperature and at 0.UPF lag
52.1 At 25% of full Load % 98.39
53 Regulation at full load and at 75° C
Maximum current density for HV & LV
54 Amp /mm2 2.5
winding
55 Transport dimensions L x W x H mmxmmxmm To be mentioned
56 Transport weight of largest item Kg To be mentioned
57 Termination arrangement To be mentioned
57.1 LV Neutral Epoxy Bushing
58 Reference standard for bushing IS 2099
58.1 HV Cable box
58.2 Degree of protection IP 52
58.3 Phase to Phase Clearances mm 130
58.4 Phase to earth Clearances mm 80
Cable Box- for both top and bottom
59 LV Cable Adapter box
cable entry
59.1 Degree of protection IP52
59.2 Phase to Phase Clearances mm 25
59.3 Phase to earth Clearances mm 20
60 LV Neutral Bushing Current transformers
60.1 Make Pragathi/ Kappa
60.2 Type Resin casted
60.3 Voltage class kV 0.415
60.4 Current ratio 500 / 5A
60.5 Burden and accuracy class 50VA , 5p20
60.6 Short time withstand current and duration kA & sec 50 KA for 1 sec
60.7 Thickness of side/top/bottom plate mm 2 / 3.15 / 2
61 Marshalling box
61.1 Degree of protection IP54
61.2 Terminal Blocks —make & type Elemax & Stud type
61.3 Material of gasket Neoprene
62 Wheels
62.1 Plain / flanged Plain
62.2 Unidirection / Bidirectional Bidirectional
62.3 Quantity 4
62.4 Gauges 820
62.5 Longitudinal mm 820
62.6 Transverse mm 820
63 Winding Temperature indicator( Local)
63.1 Make Precimeasure /PECON
63.2 Type Digital
63.3 Number of contacts 2 NO+2 NC
63.4 Contacts voltage and rating 220V, 5A
64 Creepage distance casing mm 150mm from HV coil to Enclosure
REACTANCE AT RATED CURRENT &
65 3.91
FREQUENCY
RESISTANCE AT RATED CURRENT &
66 0.82
FREQUENCY
67 Load at which max. efficiency occurs kVA DDE
68 Orientation between HV & LV To be mentioned
69 Tolerance +/-10 %
70 Over Load capacity As per IS 6600
4Rx3.5Cx300 sq,mm cable overall
71 LV Cable size
dia approx. 57 mm