1600 - RKM Annexufhhfdhjf

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

RKM Annexure 3

Sl NO DESCRIPTION Unit Details AMES


≤ 2% of
41 HV no load current at rated voltage Amps
Full Load Current
42 Short-circuit withstand capacity 3s(KA) KA 26.67
43 Transformer short Voltage KV 0.92(impedance voltage)
44 No load charging KVA & PF KVA 32 & 0.078
Maximum guaranteed Temperature rise
45
above 50°C ambient
45.1 Windings fully insulated/graded insulation Full Load Current
Hot spot temperature in winding limited to
45.2 (over yearly weighted ambient temperature of °C 155
32°C)
46 Guaranteed losses
46.1 Load loss at rated current at 125 ° C (Max.) KW 14
Total Loss at Rated Voltage at Principal
46.2 Tapping, Rated Frequency, at 75Deg. C & at 14,5
100% load (Max)
47 Impedance
80 to 110% of positive sequence
47.1 Positive / zero sequence impedance
% impedence
HV-0.996
47.2 Resistance at 75 deg C Ohms
LV-0.000291
47.3 1 min Power frequency With stand Voltage HV side (KV) 35

LV side (KV) 3
Guaranteed Efficiency at 75 °C winding
48
temperature and at 0.8 p.f. lag
48.1 At 100% of full Load % 98.88
48.2 At 75% of full Load % 99.05
48.3 At 50% of full Load % 99.15
48.4 At 25% of full Load % 98.99
Maximum current density for HV & LV
49 Amp /mm2 2.5
winding
50 Transport dimensions L x W x H mmxmmxmm To be mentioned
51 Transport weight of largest item Kg To be mentioned
52 Termination arrangement
53 Reference standard for bushing IS 2099
54 HV Cable box
54.1 Degree of protection IP 52
54.2 Phase to Phase Clearances mm 130
54.3 Phase to earth Clearances mm 80
55 LV Busduct Adapter box
55.1 Degree of protection IP52
55.2 Phase to Phase Clearances mm 25
55.3 Phase to earth Clearances mm 20
56 LV Neutral Bushing Current transformers
56.1 Make Pragathi / Kappa
56.2 Type Resin cast type
56.3 Voltage class kV 0.415
56.4 Current ratio 1250/5A
56.5 Burden and accuracy class 50 VA &5P20
56.6 Short time withstand current and duration kA & sec 50 KA& 1sec
57 Marshalling box
57.1 Degree of protection IP54
57.2 Terminal Blocks —make & type Elemax & Stud type
57.3 Material of gasket Neoprene
58 Wheels
58.1 Plain / flanged Plain
58.2 Unidirection / Bidirectional Bidirectional
58.3 Quantity 4
58.4 Gauges 1070
58.5 Longitudinal mm 1070
58.6 Transverse mm 820
57 Winding Temperature indicator( Local)
57.1 Make Precimeasure / PECON
57.2 Type Digital
57.3 Number of contacts 2 NO+2 NC
57.4 Contacts voltage and rating 220V & 5A
57.5 Creepage distance casing mm 150 from HV coil to enclosure
58 Transformer Weight Kg To be mentioned
REACTANCE AT RATED CURRENT &
59 7.96
FREQUENCY
RESISTANCE AT RATED CURRENT &
60 0.75
FREQUENCY
61 Transformer dimension To be mentioned
62 Load at which max. efficiency occurs kVA To be mentioned
63 Orientation between HV & LV To be mentioned
64 Tolerance +/-10 %
65 Over Load capacity As per IS 6600

You might also like