Appendix 2
Appendix 2
Thermal resistivity of
factor(K=Kt*Kr*Kg*K
Cable Data % .Voltage Drop
depth of laying(Kd)
Approx. Cable
Group De-rating
rating factor(Kt)
Total De-rating
soil de-rating
Power Startin Cable Rated Selected
factor(Kg)
No. of
factor(Kr)
Remarks
Ambient
Load Factor g Full load Required Length Current cable current Resistance Reactance Cable
S. No
From
Cable
Rev.
Voltage No. of Cores
d)
TO Rating Efficiency at Load Power Current Cable Size Per rating after @ 90 deg. C @50HZ Selected as
(Volts) Runs in Impedance
(kW) Factor Factor (A) (Sq.mm) Run De-rating per sizing
Cable (m) (A)
cos ø Cos ø S = I*K*R (ohms/km) (ohms/km) (ohms/km) (Start) (Run)
1 MOV DB (TK-114) FWS-105 LCP 400 3 1.00 0.80 N/A 5.41 0.82 0.77 0.93 0.95 0.56 1 4 4 60 44 24.64 5.880 0.092 5.881 N/A 0.67 1R x 4C x 4 00
2 MOV DB (TK-114) FWS-106 LCP 400 3 1.00 0.80 N/A 5.41 0.82 0.77 0.93 0.95 0.56 1 4 4 60 44 24.64 5.880 0.092 5.881 N/A 0.67 1R x 4C x 4 00
3 FWS-105 LCP FCV 05-09 400 0.5 0.85 0.80 N/A 1.06 0.82 0.77 0.93 0.95 0.56 1 3 4 15 44 24.64 5.880 0.092 5.881 N/A 0.03 1R x 3C x 4 00
4 FWS-105 LCP XV 05-15 400 0.5 0.85 0.80 N/A 1.06 0.82 0.77 0.93 0.95 0.56 1 3 4 15 44 24.64 5.880 0.092 5.881 N/A 0.03 1R x 3C x 4 00
5 FWS-106 LCP FCV 06-09 400 0.5 0.85 0.80 N/A 1.06 0.82 0.77 0.93 0.95 0.56 1 3 4 15 44 24.64 5.880 0.092 5.881 N/A 0.03 1R x 3C x 4 00
6 FWS-106 LCP XV 06-15 400 0.5 0.85 0.80 N/A 1.06 0.82 0.77 0.93 0.95 0.56 1 3 4 15 44 24.64 5.880 0.092 5.881 N/A 0.03 1R x 3C x 4 00
7 Existing UPS DB New UPS DB 230 1 1.00 0.80 N/A 5.43 0.82 0.77 0.93 0.95 0.56 1 3 4 150 44 24.64 5.880 0.092 5.881 N/A 1.687 1R x 3C x 4 00
8 New UPS DB FWS-105 LCP 230 0.5 1.00 0.80 N/A 2.72 0.82 0.77 0.93 0.95 0.56 1 3 4 25 44 24.64 5.880 0.092 5.881 N/A 0.141 1R x 3C x 4 00
9 New UPS DB FWS-106 LCP 230 0.5 1.00 0.80 N/A 2.72 0.82 0.77 0.93 0.95 0.56 1 3 4 25 44 24.64 5.880 0.092 5.881 N/A 0.141 1R x 3C x 4 00
Appendix-2 Page 1 of 1