Following items are to be executed for external HT Line erected along the road from the point of tapping as agreed by MPSEB up to the
premises of project for bringing two sets of feeders from different locations ; The scope of work under this item may increase or decrease
as per MPEB's approval for point of supply. The contractor has to arrange all necessary approvals from various departments related to this
A.1 work and no separate charges shall be payable.
Supply, installation, testing and commissioning of `H`-BEAM (37.1KG/MTR)-13 MTR.LONG single pole including 'v' cross arm, channel for Nos. 8 44,750 358,000
i) Guarding .
Supply, installation, testing and commissioning of `H`-BEAM (37.1KG/MTR)-11 MTR.LONG single pole including 'v' cross arm, channel for Nos. 1 41,600 41,600
ii) Guarding .
Mtr. 670 15 10,050
iii) Supply installation ,testing & commissioning of Guarding wire for HT Line using 8 gauge wire complete with all hardware & accessories.
iv) Supply, Installation, Testing, Commissioning of 11 KV approved make pin insulators with hardware. Nos. 32 245 7,840
v) Supply, Installation, Testing, Commissioning of 11 KV approved make disk insulator with hardware Nos. 11 325 3,575
Supply, Installation, Testing, Commissioning ACSR DOG conductor with 30/3.0 aluminium and 7/3.0 steel conductor , overall diameter shall Mtr. 2,000 120 240,000
be minimum 21mm of approved make & providing PIN type/ EYE type heavy duty aluminum lugs at all termination ends as per
vi) requirements. All material and labour for termination and binding also to be considered in scope of work.
vii) Supply, Installation, Testing, Commissioning of 20mm Stay set with wire & all hardware Set. 5 3,800 19,000
Supply, installation, testing and commissioning of Two pole structure fabricated (approved make) from using `H`-BEAM(37.1 KG/MTR)-13
MTR.LONG to accommodate the sub station equipment with one coat of red oxide primer and two coats of aluminum paint complete in all Set. 1 118,000 118,000
respect. The work has to be executed as per dwg. & specifications and directions of consultant. The work also includes providing help in
installation of Sub Station equipment's. 1. `H`-BEAM (37.1 KG/MTR)-11 MTR.LONG-2NO. 2. ISMC 100 2.8 MTR. LONG – 4 NOS. 3. MS EQUAL
viii) ANGLE 35*35*5 mm.– 8M 4.MS FLAT 50 * 5 mm – 8 MTR.
Supply, installation, testing and commissioning of single piece non-linear resistor type lightning arrestor suitable for 3 wire, 11 KV O/H line, Set. 1 7,500 7,500
rated. Voltage of 10 KV (rms) with a nominal discharge current rating of 9 KA (station class) and complete with galvanized clamping
ix) arrangement G.I. bolts, nuts, washers etc. as required (to be provided on all phases). (1 set contains 3 pieces)
Supply, Installation, Testing, Commissioning of 200A,11KV, 3 Phase approve make AB switch (earth switch) with GI 40 mm dia B class Set. 1 14,500 14,500
x) operating rod & handle with pad locking arrangements complete in all respect.
Supply, Installation, Testing, Commissioning of 11KV, 200A approved make dropout fuse mounts complete with 5A DO fuses, fuse holders Set. 1 8,500 8,500
xi) & Operating rod complete in all aspect etc.
Providing interlocking between 11KV GOD & transformer MCCB complete using 4C*2.5 sq. mm. copper armoured cable approved make Set. 1 6,500 6,500
xii) maximum length 20 mtr. With limit switches approved make as MPEB .
1
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
Receiving, unloading, Installation, Testing & commissioning of Compact sub-station 500KVA, 11KV/433V, DYn11, Dry type, Copper Wound
transformer for HT & LT with Off load Tap Links , rating +5 to -5% @2.5% with complete HT RMU, LT Pannel Outdoor type enclosure
internal interconnections & earthing. The electrical contractor shall execute all work of interconnection of RMU, Transformer & LT Outgoings.
The Color of CSS shall be PU painted as per approved color and Finish. Work Includes Complete liasioning work with State Electricity board Nos. 3 25,000 75,000
including preparation , submission and approval of drawings/Papers as per rules of Electricity board follow up and getting the approval for
installation and connection and charging .Complete work to be arranged in a manner so as to get the power before final commissioning of
project for connection Demand . Complete liasioning work with Electrical Inspector including preparation , submission and approval of
drawings/Papers as per rules of electrical inspector follow up and getting the approval for installation ,connection and charging .Complete
xiii) work to be arranged in a manner so as to get the power before final commissioning of project.
Receiving, unloading, Installation, Testing & commissioning of Compact sub-station 630KVA, 11KV/433V, DYn11, Dry type, Copper Wound
transformer for HT & LT with Off load Tap Links , rating +5 to -5% @2.5% with complete HT RMU, LT Pannel Outdoor type enclosure
internal interconnections & earthing. The electrical contractor shall execute all work of interconnection of RMU, Transformer & LT Nos. 2 25,000 50,000
Outgoings. The Color of CSS shall be PU painted as per approved color and Finish. Work Includes Complete liasioning work with State
Electricity board including preparation , submission and approval of drawings/Papers as per rules of Electricity board follow up and getting
the approval for installation and connection and charging .Complete work to be arranged in a manner so as to get the power before final
commissioning of project for connection Demand . Complete liasioning work with Electrical Inspector including preparation , submission
and approval of drawings/Papers as per rules of electrical inspector follow up and getting the approval for installation ,connection and
xiv) charging .Complete work to be arranged in a manner so as to get the power before final commissioning of project.
Receiving, unloading, Installation, Testing & commissioning of Compact sub-station 200KVA, 11KV/433V, DYn11, Dry type, Copper Wound
transformer for HT & LT with Off load Tap Links , rating +5 to -5% @2.5% with complete HT RMU, LT Pannel Outdoor type enclosure
internal interconnections & earthing. The electrical contractor shall execute all work of interconnection of RMU, Transformer & LT Nos. 1 20,000 20,000
Outgoings. The Color of CSS shall be PU painted as per approved color and Finish. Work Includes Complete liasioning work with State
Electricity board including preparation , submission and approval of drawings/Papers as per rules of Electricity board follow up and getting
the approval for installation and connection and charging .Complete work to be arranged in a manner so as to get the power before final
commissioning of project for connection Demand . Complete liasioning work with Electrical Inspector including preparation , submission
and approval of drawings/Papers as per rules of electrical inspector follow up and getting the approval for installation ,connection and
xv) charging .Complete work to be arranged in a manner so as to get the power before final commissioning of project.
Supply & installation of GI chain linked fencing made from 8 gauge GI wire with each chain block are of approx. 100mm * 100 mm. (Width Mtr. 100 2,800 280,000
xvi) of fencing is 1800 mm)
Supply , Installation, Testing & commissioning of outdoor type LT meter for DTR Metering LT 3 Phase 4 wire 3x240 volts lb=5 amps Imax x Nos. 6 17,500 105,000
10 amp, trivector meter class of accuracy 0.5s, DLMS Compliant category A Meters along with GSM (GPRS compatible ) modems,
xvii) accessories,all hardwares , with Outdoor lockable Polycarbonate Meter Box ,TTB as per MPEB guidelines
A.2 11 KV HT VCB BREAKER (Out door Type)
2
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
Supplying & laying of following 11 kV grade XLPE insulated Aluminium conductor armoured cables as per IS 7098 / specification laid in
existing hume pipe/trench, with suitable clamps including, saddles fixing bolts, connecting testing and commissioning complete in all
B.1 respect as required as per site conditions.
i) 11KV 3Cx300 sqmm HT XLPE Cable Mtr. 2,000 75 150,000
ii) Same as above but inclusive of Excavation and filling with sand & Brick Protection Mtr. 600 380 228,000
B.2 Cable Termination of armoured cables 11KV grade as per following
Supplying and making Cable end termination outdoor type of the following XLPE insulated Aluminium conductor armoured cables of 11 kV
grade including termination kits, heat shrinkable sleeves including supplying and fixing of Copper crimping lugs, double compression glands
i) etc with earthing testing and commissioning complete in all respect as required as per site conditions.
EI.01.01.0 Set. 4 7,000 28,000
1.02.01 11KV 3Cx300 sqmm HT XLPE Cable
Supplying and making Cable end termination indoor type of the following XLPE insulated Aluminium conductor armoured cables of 11 kV
grade including termination kits, heat shrinkable sleeves including supplying and fixing of Copper crimping lugs, double compression glands
ii) etc with earthing testing and commissioning complete in all respect as required as per site conditions.
EI.01.01.0 Set. 18 6,500 117,000
1.02.01 11KV 3Cx300 sqmm HT XLPE Cable
Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules
B.3 suitable for following size of 3 core x 300 sqmm XLPE, XLPE aluminium conductor cable of 11 KV grade as required :
i) 11KV 3Cx300 sqmm HT XLPE Cable Set. 2 8,500 17,000
C LT CABLING WORK
Supplying & laying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured cables as per IS
7098/ specification in existing trenches, pipes, cable trays, ducts, over bed of sand, clamped to wall with suitable clamps including, saddles
C.1 fixing bolts, connecting testing and commissioning complete in all respect as required as per site conditions.
i) 3.5C x 300 Sq mm AL.AR XLPE CABLE Mtr. 2,100 60 126,000
ii) 3.5C x 150 Sq mm AL.AR XLPE CABLE Mtr. 3,450 50 172,500
3
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables
of 1100 volt grade including supplying and fixing of bimetallic crimping lugs, double compression glands with earthing testing and
C.2 commissioning complete in all respect as required as per site conditions. (3.5 core X 50 sqmm and below sizes shall be single compression)
i) 3.5C x 300 Sq mm AL.AR XLPE CABLE Set. 30 2,750 82,500
ii) 3.5C x 185 Sq mm AL.AR XLPE CABLE Set. 2 1,260 2,520
iii) 3.5C x 150 Sq mm AL.AR XLPE CABLE Set. 116 1,125 130,500
iv) 3.5C x 70 Sq mm AL.AR XLPE CABLE Set. 2 949 1,898
v) 3.5C x 35 Sq mm AL.AR XLPE CABLE Set. 8 475 3,800
vi) 4C x 25 Sq mm AL.AR XLPE CABLE Set. 10 375 3,750
vii) 4C x 16 Sq mm AL.AR XLPE CABLE Set. 400 325 130,000
viii) 4C x 10 Sq mm AL.AR XLPE CABLE Set. 28 215 6,020
ix) 3C x 10 Sq mm AL.AR XLPE CABLE Set. 38 195 7,410
x) 12CX2.5 SQMM CU.AR XLPE CABLE Set. 4 245 980
D LT EARTHING
Providing, laying, testing and commissioning of 600 x 600 x 3.15 mm thick Cu. electrode, with 2 nos. 38 X 6 mm CU strips from earth
electrode to inspection chamber, 50 mm dia medium class GI pipe, CI funnel with 20 gauge GI wire mesh, masonry chamber 400 x 500 mm Nos. 14 19,500 273,000
with concrete base heavy duty CI manhole cover with frame painted with packing with mixtures of charcoal and common salt around plate
EI.01.01.0 electrode including excavation and backfilling of all kinds of earth , masonry work , connecting the earth pit with earthing grid with
1.02.01 bitumen covering of joints , all work as per IS:3043 complete as required (Transformer Netrual Earthing)
Providing, laying, testing and commissioning of 600 x 600 x 6 mm thick GI. electrode, with 2 nos. 50 X 6 mm GI strips from earth electrode
to inspection chamber, 50 mm dia medium class GI pipe, CI funnel with 20 gauge GI wire mesh, masonry chamber 400 x 500 mm with Nos. 92 6,750 621,000
concrete base heavy duty CI manhole cover with frame painted with packing with mixtures of charcoal and common salt around plate
EI.01.01.0 electrode including excavation and backfilling of all kinds of earth , masonry work , connecting the earth pit with earthing grid with
1.02.01 bitumen covering of joints , all work as per IS:3043 complete as required (Transformer Netrual Earthing)
Supplying and installing earthing stations at locations as called for with 40 mm dia GI medium class 4.5 m long pipe with 40 x 20 mm
reducer and CI funnel with 20 gauge GI wire mesh, masonry chamber with concrete base, CI manhole cover with frame (300 mm x 300 Nos. 14 4,500 63,000
mm) and bitumen paint and packing the mixture of Charcoal and salt around plate electrode complete as per IS:3043-1987.along with GI
EI.01.01.0 test link enclosure.(For Body Earthing of Feeder Pillars External Lighting Feeder Pillars, Plumbing Panel, STP Panel ) (Including marking
1.02.01 earthing Name with paint.)
Supply, Laying of hot dipped GI/pure copper earthing strip to connect to the DBS,Poles and equipment's in outdoor yard and also in indoor
D.1 portion of substation complete in all aspects.
4
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
Receiving, unloading, storing, Installation, testing & commissioning of following panels including installation of all switchgears (ACB, SFU,
HRCFUSES, CONTACTOR, OVERLOAD RELAY, MCCB, CHNGEOVER SWITCH, MCB, CAPACITOR) and all metering (Ammeter, Voltmeter,
Frequency meter, PF meter, KW, KWH meter, KVA meter, Time Totaliser, multifunction meter, datalogger,) indication lamps (LED type),
selector switches, push buttons (Luminous/Non Luminous type), connectors, aux contact blocks, control fuses, instrument CTs, protection
CTs, APFCR relay, all protection relays, annunciation window etc entire fabrication of panels, complete bus bar system, wiring, installation
of all hardware, Powder Coating etc. as per technical specification & Approved Make given in tender. The Exterior Paint should be PU paint
and of Siemens Grey Color for all types Out door Panels, Outdoor Feeder panels etc. The Prior approval of Color should be required for
E.1 Architect .
i) Meter Feeder Panel Nos. 25 4,500 112,500
ii) Outdoor Lighting/Garden Panel Nos. 6 4,500 27,000
Plot Meter Box- Out door Type with MS sheet PU painted having Letter Box with Front and Back door , Name plate with Opaque Acrylic
Sheet and 600x300mm LED Panel fixture 10watt 3000K , connector box 3phase 32A Rating 2A SP MCB , Space to Install 3 phase 4 wire Nos. 222 7,250 1,609,500
E.2 energy meter 450x450mm size as per MPPKVVCL norms , cable Gland plates, stand for panel etc.
Making of brick foundation for feeder pillar 230mm thick Wall of different sizes with upto 350 mm depth (including ground PCC of 1:3:6 of
150mm, Plaster , supply and installation of RCC cover of 150 mm thick X 300mm width complete in all respect including all labour and
material . The work also includes excavation in hard soil making of all structure including plaster of above size and refilling around with soil
E.3 and disposing of balance soil outside for electrical cable.(for feeder piller)
i) 1200x700 mm Nos. 5 6,000 30,000
ii) 900x700 mm Nos. 5 4,000 20,000
iii) 1400 x700 mm Nos. 15 7,500 112,500
F RCC PIPE SLEEVE & CHAMBERS
EI.01.01.0
1.02.01 GI & HDPE PIPE
Supply and installation of following GI B class ( Medium duty ) for underground laying of cables under paved/soil/rock areas including
including excavation, back filling with excavated material, ramming and making the surface good with all necessary material in all respect
F.1 as required.
i) 100 mm Dia Mtr. 50 1,250 62,500
ii) 150 mm Dia Mtr. 50 1,500 75,000
Supplying and installing of PE 80, PN 10 HDPE pipe ( IS 14930 Part II -marked ) for cable laid under ground with necessary material and at
required depth upto 90cm. below road/ground surface, including excavation, back filling with excavated material, ramming and making the
F.2 surface good.
i) 63 mm outside dia. Mtr. 2,600 145 377,000
ii) 50 mm outside dia. Mtr. 500 115 57,500
iii) 32 outside dia. ( IS 4985-2000) 10 Kg/sq.cm Mtr. 4,434 82 363,588
5
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
Providing And Laying Non- Pressure Np-2 Class (Light Duty) R.C.C Pipe With Collars Joined With Stiff Mixture Of Cement Morter In The
F.3 Proportion Of 1:2 (1 Cement : 2 Sand ) Including excavation , back filling, laying, jointing ,Testing Of Joint Etc. Complete:
i) 150 MM Dia R.C.C Pipe Mtr. 5,530 450 2,488,500
ii) 250 MM Dia R.C.C Pipe Mtr. 1,790 600 1,074,000
iii) 300 MM Dia R.C.C Pipe Mtr. 3,200 775 2,480,000
Making of RCC Concrete chamber 100mm thick Concrete Wall of size 900mmx600mm ( internal) with 750 mm depth (including ground PCC Nos. 225 9,900 2,227,500
of 1:3:6 of 150mm , supply and installation of SFRC (Steel Fiber Reinforced Concrete cover with frame suitable for 20Ton Load for above
sizes complete in all respect including all labour and material . The work also includes excavation in hard soil making of chambers of above
F.4 size and refilling around with soil and disposing of balance soil outside for electrical cable.
Making of RCC Concrete chamber 100mm thick Concrete Wall of size 600mmx600mm ( internal) with 750 mm depth (including ground PCC Nos. 18 6,500 117,000
of 1:3:6 of 150mm, supply and installation of SFRC (Steel Fiber Reinforced Concrete cover with frame suitable for 20Ton Load for above
sizes complete in all respect including all labour and material . The work also includes excavation in hard soil making of chambers of above
F.5 size and refilling around with soil and disposing of balance soil outside for electrical cable.
Making of RCC Concrete chamber 100mm thick Concrete Wall of size 1200mmx900mm (internal) with 1000 mm depth (including ground Nos. 17 21,250 361,250
PCC of 1:3:6 of 150mm , supply and installation of SFRC (Steel Fiber Reinforced Concrete cover with frame suitable for 20Ton Load for
above sizes complete in all respect including all labour and material . The work also includes excavation in hard soil making of chambers of
F.6 above size and refilling around with soil and disposing of balance soil outside for electrical cable.
Making of RCC Concrete chamber 100mm thick Concrete Wall of size 450mmx450mm (internal) with 600 mm depth (including ground PCC Nos. 25 4,250 106,250
of 1:3:6 of 150mm , supply and installation of SFRC (Steel Fiber Reinforced Concrete cover with frame suitable for 20Ton Load for above
sizes complete in all respect including all labour and material . The work also includes excavation in hard soil making of chambers of above
F.7 size and refilling around with soil and disposing of balance soil outside for electrical cable.
Making of RCC Concrete chamber 100mm thick Concrete Wall of size 300mmx300mm (internal) with 450 mm depth (including ground PCC Nos. 160 3,250 520,000
of 1:3:6 of 150mm , supply and installation of SFRC (Steel Fiber Reinforced Concrete cover with frame suitable for 20Ton Load for above
sizes complete in all respect including all labour and material . The work also includes excavation in hard soil making of chambers of above
F.8 size and refilling around with soil and disposing of balance soil outside for electrical cable.
Making of RCC Concrete chamber 100mm thick Concrete Wall of size 1200mmx900mm (internal) with 1500 mm depth (including ground Nos. 11 21,250 233,750
PCC of 1:3:6 of 150mm , supply and installation of SFRC (Steel Fiber Reinforced Concrete cover with frame suitable for 20Ton Load for
above sizes complete in all respect including all labour and material . The work also includes excavation in hard soil making of chambers of
F.9 above size and refilling around with soil and disposing of balance soil outside for electrical cable.
6
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
Making of RCC Concrete chamber 100mm thick Concrete Wall of size 1200mmx900mm (internal) with 1200 mm depth (including ground Nos. 9 21,250 191,250
PCC of 1:3:6 of 150mm , supply and installation of SFRC (Steel Fiber Reinforced Concrete cover with frame suitable for 20Ton Load for
above sizes complete in all respect including all labour and material . The work also includes excavation in hard soil making of chambers of
F.10 above size and refilling around with soil and disposing of balance soil outside for electrical cable.
G LIGHTING FIXTURES (External Lighting)
Supply, Unloading, Receiving, Storing, Installation , Testing & Commissioning of following lighting fixture . All fixtures should be complete
with all accessories such as lamps, starters , low loss copper chokes, PF improvement capacitors etc. As per following details the model no.
given in BOQ is for one particular make . The fixture shall be supplied and installed of given make or equivalent type from list of approved
G.1 make as per instructions of Architects / EIC . The above specification governs all work specified in item G.1 to G.14
EI.01.01.0
1.02.01 6m ht pole light and 3m high post top
Integral 50Watt LED post top lantern fitting comprises of copper dust finish cast aluminium spigot and spun aluminium canopy fixed with opal
polycarbonate, pipe arrangement for vertical mounting, open construction driver and accessories are wired up to terminal block. LED of 1 to
3 W each assembled on single MCPCB, having color temp 4000K to 6500K & having 25000 to 50000 burning hrs life with minimum @ L80,
Nos. 49 3,000 147,000
system lumen output should be minimum with efficacy>80lm/W. LED driver PF 0.90 The colour rendering index of LED light should be more
than 70. Submission LM 80-08 Form LED Source Manufacturer & LM79-08 / IS16106 from NABL approved lab. Manufacturer mandatory. i/c
connection wire, testing etc. to complete the job. 2 Yrs Guarantee certificate from manufacturer. ( Light shall be base rate rest all the
i) accessories shall be in contractor scope )
Integral 70Watt LED post top lantern fitting comprises of copper dust finish cast aluminium spigot and spun aluminium canopy fixed with
opal polycarbonate, pipe arrangement for vertical mounting, open construction driver and accessories are wired up to terminal block. LED Nos. 121 4,000 484,000
of 1 to 3 W each assembled on single MCPCB, having color temp 4000K to 6500K & having 25000 to 50000 burning hrs life with minimum
@ L80, system lumen output should be minimum with efficacy>80lm/W. LED driver PF 0.90 The colour rendering index of LED light should
be more than 70. Submission LM 80-08 Form LED Source Manufacturer & LM79-08 / IS16106 from NABL approved lab. Manufacturer
mandatory. i/c connection wire, testing etc. to complete the job. 2 Yrs Guarantee certificate from manufacturer. ( Light shall be base rate
ii) rest all the accessories shall be in contractor scope )
3.0-Meter Long Decorative Pole with arm in Parks,without foundation.( Pole connector box with connector & MCB , 3*1.5 sqmm copper
flexible wire from connector to fixture & foundation bolt and other accessories shall be in contractor scope . only pole and arm along with Each. 49 8,250 404,250
iii) channel for MCB shall be base rate item.Civil foundation shall be paid in separate item )
6.0-Meter Long Decorative Poles with arm in Parks,without foundation.( Pole connector box with connector & MCB , 3*1.5 sqmm copper
flexible wire from connector to fixture & foundation bolt and other accessories shall be in contractor scope . only pole and arm along with Each. 121 14,500 1,754,500
iv) channel for MCB shall be base rate item.Civil foundation shall be paid in separate item )
Tree uplighters - Bush Lights 1x12W LED light in complete with all accessories and lamp. 3000K IP 65. ( Light shall be base rate rest all the Nos. 84 1,750 147,000
v) accessories shall be in contractor scope )
Shrub lights - Bush Lights 1x3W LED light in complete with all accessories and lamp. 3000K IP 65 . ( Light shall be base rate rest all the Nos. 95 800 76,000
vi) accessories shall be in contractor scope )
Seats cove - LED Strip light suitable for 14watt / meter IP65 complete with all accessories and driver. ( Light shall be base rate rest all the Mtr. 111 600 66,600
vii) accessories shall be in contractor scope )
viii) LED Neon Flex Strip IP 67 RGB color changing . ( Light shall be base rate rest all the accessories shall be in contractor scope ) Mtr. 17 650 11,050
7
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
Parks - 300 mm high Bollards Lights 1x13W LED light in complete with all accessories and lamp. 3000K . ( Light shall be base rate rest all the Nos. 46 5,000 230,000
ix) accessories shall be in contractor scope )
Supply, Installation, Testing and commissioning Outdoor Type Junction boxes IP 65 Poly carbonate material complete with 32A Connectors Each. 134 900 120,600
x) suitable for terminating upto 4Cx10 sqmm A2XFY cable X2 nos complete in all aspects.
Supplying & laying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured cables as per IS
7098/ specification in existing trenches, pipes, cable trays, ducts, over bed of sand, clamped to wall with suitable clamps including, saddles
G.2 fixing bolts, connecting testing and commissioning complete in all respect as required as per site conditions.
i) 4C x 10 Sq mm AL.AR XLPE CABLE Mtr. 4,000 20 80,000
ii) 4C x 2.5 sqmm CU. ARMOURED CABLE Mtr. 1,950 20 39,000
iii) 3C x 2.5 Sq mm CU.unarmored CABLE Mtr. 1,500 20 30,000
iv) 3C x 1.5 Sq mm CU.unarmored XLPE CABLE Mtr. 2,250 20 45,000
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables
of 1100 volt grade including supplying and fixing of bimetallic crimping lugs, single compression glands with earthing testing and
G.3 commissioning complete in all respect as required as per site conditions.
i) 4C x 25 Sq mm AL.AR XLPE CABLE Set. 2 215 430
ii) 4C x 2.5 sqmm CU. ARMOURED CABLE Set. 10 165 1,650
iii) 3C x 2.5 Sq mm CU.unarmored CABLE Set. 124 165 20,460
iv) 3C x 1.5 Sq mm CU.unarmored XLPE CABLE Set. 90 155 13,950
H SAFETY EQUIPMENTS
i) Supplying & fixing of Fire Extinguisher/Refills as per IS specification ABC type duly refilled 6 Kg & ready to use Each. 1 4,200 4,200
ii) 4 buckets set with sand, self supported M.S.stand i/c shed duly painted with red colour as per IS. Each. 1 2,800 2,800
iii) Supply of Rubber mat 2 x 1.0Mtr, 1100V Tested Each. 7 2,500 17,500
iv) Supply of Hand Gloves 33KV Tested Pair. 1 1,800 1,800
v) Supply of Fiber Discharge Rod I/C Connection copper Lead Tested Each. 1 1,800 1,800
vi) Supply of Fiber D.O Operating Rod for 11 / 33KV Tested Each. 1 1,800 1,800
vii) Supply of First Aid Box complete with medicine & bandage as per specification. Set. 1 1,000 1,000
viii) Supply of shock instruction chart duly framed with glass, as reqd. Each. 1 1,500 1,500
Designing and construction of Pedestal (Plinth) for transformer/CSS/Pole/Bollard of desired size including excavation in hard rock/soft rock,
base concrete 1:4:8, 20mm thick and pedestal of RCC 1:2:4 including required tar steel reinforcement for required height as per IE Rules Cum. 75 4,500 337,500
from base concrete including shuttering and finishing with 10mm thick plaster in cement mortor 1:3 curing & white washing etc. complete
ix) as per specifications.
Collection and spreading of metal dust, Murom and 40mm graded hard metal in sub-station yard or as required as mentioned below - Cum. 15 6,000 90,000
x) Metal 40 mm
I EXISTING OVER HEAD HT LINE SHIFTING WORK ( CABELINGH )
Following items are to be executed for external HT Line removing and erected along the road from the point of tapping as agreed by
MPSEB up to the premises of project for bringing two sets of feeders from different locations ; The scope of work under this item may
increase or decrease as per MPEB's approval for point of supply. The contractor has to arrange all necessary approvals from various
I.1 departments related to this work and no separate charges shall be payable.
EI.01.01.0
1.02.01 Removal of 33 kV overhead conductor from sub station to point of tapping as agreed by MPSEB
8
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
i Coordination and consultation charges are in contractor's scope for shutdown, energization and inspection of material etc. Mtr. 1,700 60 102,000
I.2 HT Cabling
Supply & Laying of cables in Existing RCC Hume pipe , testing & commissioning. The cable shall be 33KV grade, aluminium armoured of
approved make as per following sizes. The scope includes supply & fixing of aluminium cable tags (at every 6 Mts distance), clamps/
EI.01.01.0 saddles for dressing of cable/cable route markers at every 40 Mtr. distance as per drawings, specifications & instructions of client. (Cable
1.02.01 schedule release to contractor as per drawing actual length of cable shell be measured by contractor at site before execution).
i) 33KV 3Cx300 sqmm HT XLPE Cable Mtr. 3,000 100 300,000
ii) Same as above but inclusive of Excavation and filling with sand & Brick Protection Mtr. 400 400 160,000
Supply, Installation, Testing & commissioning of Cable jointing of outdoor cable end termination with heat shrinkable jointing kit complete
with all accessories including lugs suitable for following size of 3 core Cx300 sqmm HT XLPE aluminium conductor cable of 33 KV grade Set. 4 9,500 38,000
I.3 suitable for outdoor installation with water proof trifurcating box.
Supply, Installation, Testing & commissioning of Cable jointing of indoor cable end termination with heat shrinkable jointing kit complete
with all accessories including lugs suitable for following size of 3 core Cx300 sqmm HT XLPE aluminium conductor cable of 33 KV grade as Set. 4 8,500 34,000
I.4 required : for indoor installation.
Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules
I.5 suitable for following size of 3 core 300 sqmm, XLPE aluminium conductor cable of 33 KV grade as required :
i) 3C X 300 sq. mm Set. 9 12,500 112,500
Making of RCC Concrete chamber 100mm thick Concrete Wall of size 1200mmx900mm (internal) with 1200 mm depth (including ground Nos. 120 21,250 2,550,000
PCC of 1:3:6 of 150mm , supply and installation of SFRC (Steel Fiber Reinforced Concrete cover with frame suitable for 20Ton Load for
above sizes complete in all respect including all labour and material . The work also includes excavation in hard soil making of chambers of
I.6 above size and refilling around with soil and disposing of balance soil outside for electrical cable.
Providing And Laying Non- Pressure Np-2 Class (Light Duty) R.C.C Pipe With Collars Joined With Stiff Mixture Of Cement Morter In The
I.7 Proportion Of 1:2 (1 Cement : 2 Sand ) Including excavation , back filling, laying, jointing ,Testing Of Joint Etc. Complete:
i) 300 MM Dia R.C.C Pipe (B) Mtr. 3,400 775 2,635,000
Provisional Sum
A Provisional Sum
A1 CSS , distribution panels & HT Panel Works (Co ordination Charges @)
Other
A General Notes
Coordination and consultation charges with MPEB are in contractor's scope for work installation NOC, shutdown, energization and LS 1 250,000 250,000
A1 inspection of material etc.Govt. Fee shall be borne by client only.
A 11 KV HT SUB STATION WORK
Following items are to be executed for external HT Line erected along the road from the point of tapping as agreed by MPSEB up to the
premises of project for bringing two sets of feeders from different locations ; The scope of work under this item may increase or decrease as
per MPEB's approval for point of supply. The contractor has to arrange all necessary approvals from various departments related to this
A.1 work and no separate charges shall be payable.
Supply, installation, testing and commissioning of `H`-BEAM (37.1KG/MTR)-13 MTR.LONG single pole including 'v' cross arm, channel for Nos. 3 44,750 134,250
i) Guarding .
9
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
Supply, installation, testing and commissioning of `H`-BEAM (37.1KG/MTR)-11 MTR.LONG single pole including 'v' cross arm, channel for Nos. 1 41,600 41,600
ii) Guarding .
Mtr. 200 15 3,000
iii) Supply installation ,testing & commissioning of Guarding wire for HT Line using 8 gauge wire complete with all hardware & accessories.
iv) Supply, Installation, Testing, Commissioning of 11 KV approved make pin insulators with hardware. Nos. 12 245 2,940
v) Supply, Installation, Testing, Commissioning of 11 KV approved make disk insulator with hardware Nos. 6 325 1,950
Supply, Installation, Testing, Commissioning ACSR DOG conductor with 30/3.0 aluminium and 7/3.0 steel conductor , overall diameter shall
be minimum 21mm of approved make & providing PIN type/ EYE type heavy duty aluminum lugs at all termination ends as per Mtr. 200 120 24,000
vi) requirements. All material and labour for termination and binding also to be considered in scope of work.
vii) Supply, Installation, Testing, Commissioning of 20mm Stay set with wire & all hardware Set. 2 3,800 7,600
Supply, installation, testing and commissioning of Two pole structure fabricated (approved make) from using `H`-BEAM(37.1 KG/MTR)-13
MTR.LONG to accommodate the sub station equipment with one coat of red oxide primer and two coats of aluminum paint complete in all
respect. The work has to be executed as per dwg. & specifications and directions of consultant. The work also includes providing help in Set. 1 118,000 118,000
installation of Sub Station equipment's. 1. `H`-BEAM (37.1 KG/MTR)-11 MTR.LONG-2NO. 2. ISMC 100 2.8 MTR. LONG – 4 NOS. 3. MS
viii) EQUAL ANGLE 35*35*5 mm.– 8M 4.MS FLAT 50 * 5 mm – 8 MTR.
Supply, installation, testing and commissioning of single piece non-linear resistor type lightning arrestor suitable for 3 wire, 11 KV O/H line,
rated. Voltage of 10 KV (rms) with a nominal discharge current rating of 9 KA (station class) and complete with galvanized clamping Set. 1 7,500 7,500
ix) arrangement G.I. bolts, nuts, washers etc. as required (to be provided on all phases). (1 set contains 3 pieces)
Supply, Installation, Testing, Commissioning of 200A,11KV, 3 Phase approve make AB switch (earth switch) with GI 40 mm dia B class Set. 1 14,500 14,500
x) operating rod & handle with pad locking arrangements complete in all respect.
Supply, Installation, Testing, Commissioning of 11KV, 200A approved make dropout fuse mounts complete with 5A DO fuses, fuse holders Set. 1 8,500 8,500
xi) & Operating rod complete in all aspect etc.
Providing interlocking between 11KV GOD & transformer MCCB complete using 4C*2.5 sq. mm. copper armoured cable approved make Set. 1 6,500 6,500
xii) maximum length 20 mtr. With limit switches approved make as MPEB .
Receiving, unloading, Installation, Testing & commissioning of Compact sub-station 630KVA, 11KV/433V, DYn11, Dry type, Copper Wound
transformer for HT & LT with Off load Tap Links , rating +5 to -5% @2.5% with complete HT RMU, LT Pannel Outdoor type enclosure
internal interconnections & earthing. The electrical contractor shall execute all work of interconnection of RMU, Transformer & LT Outgoings.
The Color of CSS shall be PU painted as per approved color and Finish. Work Includes Complete liasioning work with State Electricity board Nos. 1 25,000 25,000
including preparation , submission and approval of drawings/Papers as per rules of Electricity board follow up and getting the approval for
installation and connection and charging .Complete work to be arranged in a manner so as to get the power before final commissioning of
project for connection Demand . Complete liasioning work with Electrical Inspector including preparation , submission and approval of
drawings/Papers as per rules of electrical inspector follow up and getting the approval for installation ,connection and charging .Complete
xiv) work to be arranged in a manner so as to get the power before final commissioning of project.
Supply & installation of GI chain linked fencing made from 8 gauge GI wire with each chain block are of approx. 100mm * 100 mm. (Width of Mtr. 100 2,800 280,000
xvi) fencing is 1800 mm)
Supply , Installation, Testing & commissioning of outdoor type LT meter for DTR Metering LT 3 Phase 4 wire 3x240 volts lb=5 amps Imax x
10 amp, trivector meter class of accuracy 0.5s, DLMS Compliant category A Meters along with GSM (GPRS compatible ) modems, Nos. 1 17,500 17,500
xvii) accessories,all hardwares , with Outdoor lockable Polycarbonate Meter Box ,TTB as per MPEB guidelines
A.2 11 KV HT VCB BREAKER (Out door Type)
10
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
11
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables
of 1100 volt grade including supplying and fixing of bimetallic crimping lugs, double compression glands with earthing testing and
C.2 commissioning complete in all respect as required as per site conditions. (3.5 core X 50 sqmm and below sizes shall be single compression)
i) 3.5C x 300 Sq mm AL.AR XLPE CABLE Set. 10 2,750 27,500
ii) 3.5C x 185 Sq mm AL.AR XLPE CABLE Set. 2 1,260 2,520
iii) 3.5C x 150 Sq mm AL.AR XLPE CABLE Set. 40 1,125 45,000
iv) 3.5C x 70 Sq mm AL.AR XLPE CABLE Set. 4 949 3,796
v) 3.5C x 35 Sq mm AL.AR XLPE CABLE Set. 4 475 1,900
vi) 4C x 25 Sq mm AL.AR XLPE CABLE Set. 4 375 1,500
vii) 4C x 16 Sq mm AL.AR XLPE CABLE Set. 136 325 44,200
viii) 4C x 10 Sq mm AL.AR XLPE CABLE Set. 10 215 2,150
ix) 3C x 10 Sq mm AL.AR XLPE CABLE Set. 14 195 2,730
x) 12CX2.5 SQMM CU.AR XLPE CABLE Set. 2 245 490
D LT EARTHING
Providing, laying, testing and commissioning of 600 x 600 x 3.15 mm thick Cu. electrode, with 2 nos. 38 X 6 mm CU strips from earth
electrode to inspection chamber, 50 mm dia medium class GI pipe, CI funnel with 20 gauge GI wire mesh, masonry chamber 400 x 500 mm
with concrete base heavy duty CI manhole cover with frame painted with packing with mixtures of charcoal and common salt around plate Nos. 6 19,500 117,000
electrode including excavation and backfilling of all kinds of earth , masonry work , connecting the earth pit with earthing grid with bitumen
D1 covering of joints , all work as per IS:3043 complete as required (Transformer Netrual Earthing)
Providing, laying, testing and commissioning of 600 x 600 x 6 mm thick GI. electrode, with 2 nos. 50 X 6 mm GI strips from earth electrode to
inspection chamber, 50 mm dia medium class GI pipe, CI funnel with 20 gauge GI wire mesh, masonry chamber 400 x 500 mm with
concrete base heavy duty CI manhole cover with frame painted with packing with mixtures of charcoal and common salt around plate Nos. 32 6,750 216,000
electrode including excavation and backfilling of all kinds of earth , masonry work , connecting the earth pit with earthing grid with bitumen
D2 covering of joints , all work as per IS:3043 complete as required (Transformer Netrual Earthing)
Supplying and installing earthing stations at locations as called for with 40 mm dia GI medium class 4.5 m long pipe with 40 x 20 mm reducer
and CI funnel with 20 gauge GI wire mesh, masonry chamber with concrete base, CI manhole cover with frame (300 mm x 300 mm) and
bitumen paint and packing the mixture of Charcoal and salt around plate electrode complete as per IS:3043-1987.along with GI test link Nos. 5 4,500 22,500
enclosure.(For Body Earthing of Feeder Pillars External Lighting Feeder Pillars, Plumbing Panel, STP Panel ) (Including marking earthing
D3 Name with paint.)
Supply, Laying of hot dipped GI/pure copper earthing strip to connect to the DBS,Poles and equipment's in outdoor yard and also in indoor
D4 portion of substation complete in all aspects.
i) 25*6 mm GI strip Mtr. 260 122 31,720
ii) 50*6 mm GI strip Mtr. 120 265 31,800
iii) 50*10 mm GI strip Mtr. 10 410 4,100
iv) 38*6 mm CU strip Mtr. 60 1,580 94,800
v) 8 G GI wire Mtr. 1,700 15 25,500
E LT PANELS AND DB
12
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
Receiving, unloading, storing, Installation, testing & commissioning of following panels including installation of all switchgears (ACB, SFU,
HRCFUSES, CONTACTOR, OVERLOAD RELAY, MCCB, CHNGEOVER SWITCH, MCB, CAPACITOR) and all metering (Ammeter,
Voltmeter, Frequency meter, PF meter, KW, KWH meter, KVA meter, Time Totaliser, multifunction meter, datalogger,) indication lamps (LED
type), selector switches, push buttons (Luminous/Non Luminous type), connectors, aux contact blocks, control fuses, instrument CTs,
protection CTs, APFCR relay, all protection relays, annunciation window etc entire fabrication of panels, complete bus bar system, wiring,
installation of all hardware, Powder Coating etc. as per technical specification & Approved Make given in tender. The Exterior Paint should
be PU paint and of Siemens Grey Color for all types Out door Panels, Outdoor Feeder panels etc. The Prior approval of Color should be
E.1 required for Architect .
i) Meter Feeder Panel Nos. 6 4,500 27,000
ii) Outdoor Lighting/Garden Panel Nos. 2 4,500 9,000
Plot Meter Box- Out door Type with MS sheet PU painted having Letter Box with Front and Back door , Name plate with Opaque Acrylic
Sheet and 600x300mm LED Panel fixture 10watt 3000K , connector box 3phase 32A Rating 2A SP MCB , Space to Install 3 phase 4 wire Nos. 50 7,250 362,500
E.2 energy meter 450x450mm size as per MPPKVVCL norms , cable Gland plates, stand for panel etc.
Making of brick foundation for feeder pillar 230mm thick Wall of different sizes with upto 350 mm depth (including ground PCC of 1:3:6 of
150mm, Plaster , supply and installation of RCC cover of 150 mm thick X 300mm width complete in all respect including all labour and
material . The work also includes excavation in hard soil making of all structure including plaster of above size and refilling around with soil
E.3 and disposing of balance soil outside for electrical cable.(for feeder piller)
i) 1200x700 mm Nos. 2 6,000 10,020
ii) 900x700 mm Nos. 1 4,000 4,000
iii) 1400 x700 mm Nos. 3 7,500 22,500
F RCC PIPE SLEEVE & CHAMBERS
EI.01.01.0
1.02.01 GI & HDPE PIPE
Supply and installation of following GI B class ( Medium duty ) for underground laying of cables under paved/soil/rock areas including
including excavation, back filling with excavated material, ramming and making the surface good with all necessary material in all respect as
F.1 required.
i) 100 mm Dia Mtr. 20 1,250 25,000
ii) 150 mm Dia Mtr. 20 1,500 30,000
Supplying and installing of PE 80, PN 10 HDPE pipe ( IS 14930 Part II -marked ) for cable laid under ground with necessary material and at
required depth upto 90cm. below road/ground surface, including excavation, back filling with excavated material, ramming and making the
F.2 surface good.
i) 63 mm outside dia. Mtr. 865 145 125,425
ii) 50 mm outside dia. Mtr. 165 115 18,975
iii) 32 outside dia. ( IS 4985-2000) 10 Kg/sq.cm Mtr. 1,478 82 121,196
iv) 25 outside dia. ( IS 4985-2000) 10 Kg/sq.cm Mtr. 170 78 13,260
EI.01.01.0
1.02.01 SLLEVE
Providing And Laying Non- Pressure Np-2 Class (Light Duty) R.C.C Pipe With Collars Joined With Stiff Mixture Of Cement Morter In The
F.3 Proportion Of 1:2 (1 Cement : 2 Sand ) Including excavation , back filling, laying, jointing ,Testing Of Joint Etc. Complete:
i) 150 MM Dia R.C.C Pipe Mtr. 1,850 450 832,500
ii) 250 MM Dia R.C.C Pipe Mtr. 600 600 360,000
iii) 300 MM Dia R.C.C Pipe Mtr. 1,065 775 825,375
13
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
Making of RCC Concrete chamber 100mm thick Concrete Wall of size 900mmx600mm ( internal) with 750 mm depth (including ground PCC
of 1:3:6 of 150mm , supply and installation of SFRC (Steel Fiber Reinforced Concrete cover with frame suitable for 20Ton Load for above Nos. 75 9,900 742,500
sizes complete in all respect including all labour and material . The work also includes excavation in hard soil making of chambers of above
F.4 size and refilling around with soil and disposing of balance soil outside for electrical cable.
Making of RCC Concrete chamber 100mm thick Concrete Wall of size 600mmx600mm ( internal) with 750 mm depth (including ground PCC
of 1:3:6 of 150mm, supply and installation of SFRC (Steel Fiber Reinforced Concrete cover with frame suitable for 20Ton Load for above Nos. 6 6,500 39,000
sizes complete in all respect including all labour and material . The work also includes excavation in hard soil making of chambers of above
F.5 size and refilling around with soil and disposing of balance soil outside for electrical cable.
Making of RCC Concrete chamber 100mm thick Concrete Wall of size 1200mmx900mm (internal) with 1000 mm depth (including ground
PCC of 1:3:6 of 150mm , supply and installation of SFRC (Steel Fiber Reinforced Concrete cover with frame suitable for 20Ton Load for Nos. 6 21,250 127,500
above sizes complete in all respect including all labour and material . The work also includes excavation in hard soil making of chambers of
F.6 above size and refilling around with soil and disposing of balance soil outside for electrical cable.
Making of RCC Concrete chamber 100mm thick Concrete Wall of size 450mmx450mm (internal) with 600 mm depth (including ground PCC
of 1:3:6 of 150mm , supply and installation of SFRC (Steel Fiber Reinforced Concrete cover with frame suitable for 20Ton Load for above Nos. 9 4,250 38,250
sizes complete in all respect including all labour and material . The work also includes excavation in hard soil making of chambers of above
F.7 size and refilling around with soil and disposing of balance soil outside for electrical cable.
Making of RCC Concrete chamber 100mm thick Concrete Wall of size 300mmx300mm (internal) with 450 mm depth (including ground PCC
of 1:3:6 of 150mm , supply and installation of SFRC (Steel Fiber Reinforced Concrete cover with frame suitable for 20Ton Load for above Nos. 54 3,250 175,500
sizes complete in all respect including all labour and material . The work also includes excavation in hard soil making of chambers of above
F.8 size and refilling around with soil and disposing of balance soil outside for electrical cable.
Making of RCC Concrete chamber 100mm thick Concrete Wall of size 1200mmx900mm (internal) with 1500 mm depth (including ground
PCC of 1:3:6 of 150mm , supply and installation of SFRC (Steel Fiber Reinforced Concrete cover with frame suitable for 20Ton Load for Nos. 4 21,250 85,000
above sizes complete in all respect including all labour and material . The work also includes excavation in hard soil making of chambers of
F.9 above size and refilling around with soil and disposing of balance soil outside for electrical cable.
Making of RCC Concrete chamber 100mm thick Concrete Wall of size 1200mmx900mm (internal) with 1200 mm depth (including ground
PCC of 1:3:6 of 150mm , supply and installation of SFRC (Steel Fiber Reinforced Concrete cover with frame suitable for 20Ton Load for Nos. 3 21,250 63,750
above sizes complete in all respect including all labour and material . The work also includes excavation in hard soil making of chambers of
F.10 above size and refilling around with soil and disposing of balance soil outside for electrical cable.
G LIGHTING FIXTURES (External Lighting)
Supply, Unloading, Receiving, Storing, Installation , Testing & Commissioning of following lighting fixture . All fixtures should be complete
with all accessories such as lamps, starters , low loss copper chokes, PF improvement capacitors etc. As per following details the model no.
given in BOQ is for one particular make . The fixture shall be supplied and installed of given make or equivalent type from list of approved
G.1 make as per instructions of Architects / EIC . The above specification governs all work specified in item G.1 to G.14
EI.01.01.0
1.02.01 6m ht pole light and 3m high post top
Integral 50Watt LED post top lantern fitting comprises of copper dust finish cast aluminium spigot and spun aluminium canopy fixed with opal
polycarbonate, pipe arrangement for vertical mounting, open construction driver and accessories are wired up to terminal block. LED of 1 to
3 W each assembled on single MCPCB, having color temp 4000K to 6500K & having 25000 to 50000 burning hrs life with minimum @ L80,
Nos. 17 3,000 51,000
system lumen output should be minimum with efficacy>80lm/W. LED driver PF 0.90 The colour rendering index of LED light should be more
than 70. Submission LM 80-08 Form LED Source Manufacturer & LM79-08 / IS16106 from NABL approved lab. Manufacturer mandatory. i/c
connection wire, testing etc. to complete the job. 2 Yrs Guarantee certificate from manufacturer. ( Light shall be base rate rest all the
i) accessories shall be in contractor scope )
14
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
Integral 70Watt LED post top lantern fitting comprises of copper dust finish cast aluminium spigot and spun aluminium canopy fixed with opal
polycarbonate, pipe arrangement for vertical mounting, open construction driver and accessories are wired up to terminal block. LED of 1 to
3 W each assembled on single MCPCB, having color temp 4000K to 6500K & having 25000 to 50000 burning hrs life with minimum @ L80,
Nos. 41 4,000 164,000
system lumen output should be minimum with efficacy>80lm/W. LED driver PF 0.90 The colour rendering index of LED light should be more
than 70. Submission LM 80-08 Form LED Source Manufacturer & LM79-08 / IS16106 from NABL approved lab. Manufacturer mandatory. i/c
connection wire, testing etc. to complete the job. 2 Yrs Guarantee certificate from manufacturer. ( Light shall be base rate rest all the
ii) accessories shall be in contractor scope )
3.0-Meter Long Decorative Pole with arm in Parks,without foundation.( Pole connector box with connector & MCB , 3*1.5 sqmm copper
flexible wire from connector to fixture & foundation bolt and other accessories shall be in contractor scope . only pole and arm along with Each. 17 8,250 140,250
iii) channel for MCB shall be base rate item.Civil foundation shall be paid in separate item )
6.0-Meter Long Decorative Poles with arm in Parks,without foundation.( Pole connector box with connector & MCB , 3*1.5 sqmm copper
flexible wire from connector to fixture & foundation bolt and other accessories shall be in contractor scope . only pole and arm along with Each. 41 14,500 594,500
iv) channel for MCB shall be base rate item.Civil foundation shall be paid in separate item )
Tree uplighters - Bush Lights 1x12W LED light in complete with all accessories and lamp. 3000K IP 65. (Light shall be base rate rest all the Nos. 28 1,750 49,000
v) accessories shall be in contractor scope )
Shrub lights - Bush Lights 1x3W LED light in complete with all accessories and lamp. 3000K IP 65 . ( Light shall be base rate rest all the Nos. 32 800 25,600
vi) accessories shall be in contractor scope )
Seats cove - LED Strip light suitable for 14watt / meter IP65 complete with all accessories and driver. ( Light shall be base rate rest all the Mtr. 37 600 22,200
vii) accessories shall be in contractor scope )
viii) LED Neon Flex Strip IP 67 RGB color changing . ( Light shall be base rate rest all the accessories shall be in contractor scope ) Mtr. 6 650 3,900
Parks - 300 mm high Bollards Lights 1x13W LED light in complete with all accessories and lamp. 3000K . ( Light shall be base rate rest all Nos. 16 5,000 80,000
ix) the accessories shall be in contractor scope )
Supply, Installation, Testing and commissioning Outdoor Type Junction boxes IP 65 Poly carbonate material complete with 32A Connectors Each. 45 900 40,500
x) suitable for terminating upto 4Cx10 sqmm A2XFY cable X2 nos complete in all aspects.
Supplying & laying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured cables as per IS
7098/ specification in existing trenches, pipes, cable trays, ducts, over bed of sand, clamped to wall with suitable clamps including, saddles
G.2 fixing bolts, connecting testing and commissioning complete in all respect as required as per site conditions.
i) 4C x 10 Sq mm AL.AR XLPE CABLE Mtr. 1,350 20 27,000
ii) 4C x 2.5 sqmm CU. ARMOURED CABLE Mtr. 650 20 13,000
iii) 3C x 2.5 Sq mm CU.unarmored CABLE Mtr. 500 20 10,000
iv) 3C x 1.5 Sq mm CU.unarmored XLPE CABLE Mtr. 750 20 15,000
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables
of 1100 volt grade including supplying and fixing of bimetallic crimping lugs, single compression glands with earthing testing and
G.3 commissioning complete in all respect as required as per site conditions.
i) 4C x 25 Sq mm AL.AR XLPE CABLE Set. 6 215 1,290
ii) 4C x 2.5 sqmm CU. ARMOURED CABLE Set. 6 165 990
iii) 3C x 2.5 Sq mm CU.unarmored CABLE Set. 42 165 6,930
iv) 3C x 1.5 Sq mm CU.unarmored XLPE CABLE Set. 30 155 4,650
H SAFETY EQUIPMENTS
i) Supplying & fixing of Fire Extinguisher/Refills as per IS specification ABC type duly refilled 6 Kg & ready to use Each. 1 4,200 4,200
ii) 4 buckets set with sand, self supported M.S.stand i/c shed duly painted with red colour as per IS. Each. 1 2,800 2,800
iii) Supply of Rubber mat 2 x 1.0Mtr, 1100V Tested Each. 7 2,500 17,500
iv) Supply of Hand Gloves 33KV Tested Pair. 1 1,800 1,800
v) Supply of Fiber Discharge Rod I/C Connection copper Lead Tested Each. 1 1,800 1,800
vi) Supply of Fiber D.O Operating Rod for 11 / 33KV Tested Each. 1 1,800 1,800
15
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
vii) Supply of First Aid Box complete with medicine & bandage as per specification. Set. 1 1,000 1,000
viii) Supply of shock instruction chart duly framed with glass, as reqd. Each. 1 1,500 1,500
Designing and construction of Pedestal (Plinth) for transformer/ CSS/ Pole/ Bollard of desired size including excavation in hard rock/soft
rock, base concrete 1:4:8, 20mm thick and pedestal of RCC 1:2:4 including required tar steel reinforcement for required height as per IE Cum. 25 4,500 112,500
Rules from base concrete including shuttering and finishing with 10mm thick plaster in cement mortor 1:3 curing & white washing etc.
ix) complete as per specifications.
Collection and spreading of metal dust, Murom and 40mm graded hard metal in sub-station yard or as required as mentioned below - Metal Cum. 5 6,000 30,000
x) 40 mm
Total 35,082,648
16
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
17
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
18
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
19
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
20
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
21
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
22
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
23
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01
15500
14000
17000
24
WO No:HITECH/SAPPHIRE/INDORE GREEN/WO/001/AMEND 01