Professional Documents
Culture Documents
PEE10L M Front Page Laboratory 5
PEE10L M Front Page Laboratory 5
LABORATORY NO.: 5
PEE10L – M
ELECTRICAL APPARATUS AND DEVICES – LABORATORY
Submitted By:
NAME SIGNATURE
Belay, Edgardo Jr R.
Caducio, Katherine G.
Casanova, Shane Alexis S.
Cleto, Kathlene Kaye S.
Conge, Arjie Rose G.
Contreras, Kristine Jewel
BSEE – 3C
GROUP NO. 2
Date Submitted:
April 8, 2024
The low voltage source is applied across the secondary winding, which is approximately 5 to 10% of
the normal rated voltage. The flux is set up in the core of the transformer. The magnitude of the flux
is small as compared to the normal flux. The iron loss of the transformer depends on the flux. It is
less occur in the short circuit test because of the low value of flux. The reading of the wattmeter only
determines the copper loss occurred, in their windings. The voltmeter measures the voltage applied
to their high voltage winding. The secondary current induces in the transformer because of the
applied voltage.
LABORATORY PROCEDURE:
1. Make the circuit o Simulink as shown in figure 1.
2. Short circuit the secondary side terminals.
3. Connect voltmeter, ammeter and wattmeter to the primary side and as well as an ammeter
in secondary side.
4. Note the values of ammeter, voltmeter and wattmeter in table.
5. Attach full screenshot including the Simulink circuit.
@ 50 Hz @ 60 Hz
V SC 120 V SC 124.9
Ze1 = = = 288.18Ω Ze1 = = = 312.09Ω
I SC 0.4164 I SC 0.4002
V SC 120 V SC 124.9
Re1 = 2 = 2 = 692.09Ω Re1 = 2 = 2 = 779.84Ω
I sc 0.4164 I sc 0.4002
Xe1 = √ Z 2e 1 − R 2e1 =
Xe1 = √ Z 2e 1 − R 2e1 = √ 312.092 − 779.842 = Ω
√ 288.182 − 692.092 = 749.69 Ω
DISCUSSION:
Short circuit is an electrical connection in which current flows along a path that has very little
resistance. This may result in high current flow, damage to the equipment, heating, etc.
The transformer's short circuit test is conducted on the low voltage side and shorted out on
the high voltage side. To pass the test, the secondary short-circuited winding's rated load
current must be gradually increased by the supplied voltage while maintaining frequency.
The rated current on the high voltage side is lower than on the low voltage side, making it
more convenient to short circuit the LV terminals. Meters are typically attached to the
primary side, making the main aspect the preferred area for conducting a short circuit test.
By measuring primary current and voltage, and connecting a wattmeter to the primary, the
following parameters can be calculated: total resistance, total reactance voltage drop of
primary and secondary, referred to primary. Total transformer winding losses, in watts, and
transformer regulation. Also the temperature rise of the windings, this is done by comparing
winding resistance measurements before and after a long term short circuit test. In addition
short circuit test usually performed in conjunction with an open circuit test, which is used to
calculate core losses, magnetizing current and to confirm correct winding ratios.
And to simulate this given circuit we are tasked to use Matlab as our simulator.
DOCUMENTATION:
@ 50 Hz