1 Introduction
This TIB covers MXDesigner™ version 8.0. This version includes CPU801 support, VAD (Visual Alarm Devices),
FV400 devices and bug fixes reported in MXDesigner™ version 7.2.
2 Installation
If MXDesigner™ 5.0/6.0/6.1/7.0/7.1/7.2 has already been installed, it is recommended that these earlier versions are
removed using Add/Remove program features from the Control Panel in Microsoft® Windows operating System.
MXDesigner™ 8.0 requires Microsoft® .NET Framework 2.0 or later to be installed.
The MXDesigner™.msi/ZXDesignerInstaller.msi installer for Version 8.0 will guide the user through the new
installation except ADT installer MXDesigner™ADT.msi, because it runs silently in the background without showing
any installation wizard.
3 Compatibility
MXDesigner™ 8.0 is designed to run on Microsoft® Windows XP, Windows Vista, Windows 7 & Windows 8
operating system and requires at least Microsoft® .NET Framework Version 2.0 to have been installed.
MXDesigner™ 8.0 has been tested on Microsoft® Windows 7 Enterprise Edition (32/64 bit).
MXDesigner™ 8.0 is able to open projects which are saved from previous versions: 3.2.3 and later.
MXDesigner™ 8.0 is able to import files exported from MZXConsys 14.0 and above.
The MZX Panels and DDM800 introduced in version 6.0 of MXDesigner™ can only be exported to MZXConsys
Version 16 and above. For future versions of MZXConsys please check the relevant TIBs.
4 NEW FEATURES
Page 1 of 3
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
TIB 933
6 Known Issues
When importing and exporting configurations between MXDesigner™ and MZXConsys, the association between
an LPSB3000 or LPAV3000 and the device attached to it is lost.
For 6 and 8 loop configurations and for some of the different panel types where the loop can only have 125
addresses instead of the usual 250 addresses, MXDesigner™ does not check correctly if the next address is
available when adding an Intrinsically Safe loop device.
Loop IS spurs should not be copied to make a duplicate spur. This could result in an unsafe IS design.
Page 2 of 3
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
TIB 933
7 Feedback
Any feedback on this product should be sent to the local Business Development Manager. In the UK this would be
Stephen Bennett 07703 338602 sbennett@tycoint.com
Outside the UK, please contact your local BDM.
Page 3 of 3
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE