3G3MV-P10CDT@-E

V7 inverter PLC
The OMRON PLC technology embedded in
the most popular inverter: the V7
• OMRON PLC programmability for the 3G3MV
inverter
• Stand-alone applications.
• Flexibility and intelligence into the 3G3MV.
• Wireless installation and seamless access to the
inverter parameters and analogue/digital inputs and
outputs.
• Standard OMRON tools can be used for program-
ming and commissioning.
• Ideal for applications like: door control, pump
sequencing, Intelligent conveyor, Vertical axis
control, Industrial washing machines and general
positioning.

System configuration

CX-One (CX-Drive)
(CX-Programmer)
Varispeed V7 + PLC
HMI Interface

RS-232C and
Peripheral

RS-422

V7 inverter PLC 377


Y203-EN2-02-Katalog.book Seite 378 Mittwoch, 24. Mai 2006 2:22 14

Type designation

3G3MV-P10CDT3-E
Inverter series Options
Number of I/O's Output RTC RS422 Remarks
- NPN NO NO Standard
1 NPN NO YES
2 NPN YES NO
3 NPN YES YES Standard
5 PNP NO NO Standard
6 PNP NO YES
7 PNP YES NO
8 PNP YES YES

Specifications
Specifications by product
Item 3G3MV-P10CDT-E 3G3MV-P10CDT5-E 3G3MV-P10CDT3-E
PLC core CPM2C-S CPM2C-S CPM2C-S
Inputs 6 24 VDC inputs 6 24 VDC inputs 6 24 VDC inputs
Outputs 3 sinking/NPN transistor outputs 3 sinking/PNP transistor outputs 3 sinking/NPN transistor outputs
1 relay output 1 relay output 1 relay output
Peripheral port Yes Yes Yes
RS-232C port Yes Yes Yes
RS-422/485 port No No Yes
Calendar/clock No No Yes
Memory backup Flash memory and capacitor Flash memory and capacitor Flash memory and battery

General specifications
Item Specifications
Rated power supply voltage 24 VDC +10%/-15% (external power supply for I/O)
Vibration resistance 0.15 mm (10-57 Hz)
9.8 m/s2 (57-150 Hz)
9.8 m/s2 (57-150 Hz)
In all directions (X, Y, Z)
Ambient operating temperature -10 to 45 °C
Ambient operating relative humidity 10% to 90% (no condensation)
Ambient storage temperature -20 to 70 °C
Atmosphere Must be free from corrosive gas
Power consumption 2 W (supplied internally)
Control method Store program method
I/O control method Cyclic scan method
Programming language Ladder chart method
Instruction length 1 step/1 instruction; 1 to 5 words/1 instruction
Instruction types Basic 14 types (same as for programmable slaves.)
Special 105 types, 185 instructions (same as for programmable slaves.)
Processing speed Basic instructions 0.64 µs (LD)
Special instructions 7.8 µs (MOV)
Program capacity 4,096 words
Maximum number of I/O points 10
Input bits 00000 to 00015 (6 physical inputs)
Output bits 01000 to 01003 (4 physical outputs)
Area allocated to inverter 320 bits: 20000 to 21915
Inverter interface Direct interface with V7 inverter through
• IR-memory
• DM-memory
• Transfer command
IR area 880 bits: IR 00100 to IR 00915 (words IR 001 to IR 009),
IR 01100 to IR 02815 (words IR 011 to IR 028),
IR 03000 to IR 04915 (words IR 030 to IR 049),
IR 22000 to IR 22715 (words IR 220 to IR 227)
SR area 448 bits: SR 22800 to SR 25507 (words SR 228 to SR 255)
TR area 8 bits (TR 0 to TR 7)
HR area 320 bits: HR 0000 to HR 1915 (words HR 00 to 19)
AR area 384 bits: AR 0000 AR 2315 (words AR 00 to AR 23)
LR area 256 bits: LR 0000 to LR 1515 (words LR 00 to LR 15)
Timer/counter area 256 bits: TC 000 to TC 255
DM area Read/write 2029 words (DM 0000 to DM 0999, DM 1019 to DM 2047) DM 2000 to DM 2021: error log storage area
Read only 456 words (DM6144 to 6599)
Allocated to inverter 19 words (DM 2022 to DM 2040)
PLC setup 56 words (DM 6599 to DM 6655)
Quick-response input 2 inputs (minimum input signal width: 50 µs)

378 3G3MV-P10CDT@-E
Y203-EN2-02-Katalog.book Seite 379 Mittwoch, 24. Mai 2006 2:22 14

Item Specifications
Interrupt processing External interrupts 2 bits (used in common for input interrupt counter mode and high-speed inputs.)
Scheduled interrupts 1 bit (scheduled interrupts or one-shot interrupts)
Interrupts Interrupt inputs
2 inputs
Response time: 50 µs
Interval timer interrupts Scheduled interrupts
1 input
Set value: 0.5 to 319,968 ms One-shot interrupt
Precision: 0.1 ms
High-speed counters High-speed counter No interrupt
1 input, see note 5
• Differential phase mode (5 kHz) Count-check interrupt
• Pulse plus direction input mode (20 kHz) (an interrupt can be generated when the count equals
• Up/down input mode (20 kHz) the set value or the count lies within a preset range.)
• Increment mode (20 kHz)
Interrupt inputs (counter mode) No interrupt
2 inputs
• Incrementing counter (2 kHz) Count-up interrupt
• Decrementing counter (2 kHz)
Pulse outputs • 2 outputs:
Single-phase pulse output without acceleration/deceleration (see note 6.)
10 Hz to 10 kHz
• 2 outputs:
Variable duty ratio pulse output (see note 6.)
0.1 to 999.9 Hz, duty ratio 0 to 100%
• 1 output:
Pulse output with trapezoidal acceleration/deceleration (see note 6.)
Pulse plus direction output, up/down pulse output, 10 Hz to 10 kHz
Synchronized pulse control 1 point, see notes 5 and 6
Input frequency range: 10 to 500 Hz, 20 Hz to 1 kHz, or 300 Hz to 20 kHz
Output frequency range: 10 Hz to 10 kHz
Analog volume None
Input time constant Determines the input time constant for all inputs. (Settings: 1, 2, 3, 5, 10, 20, 40, or 80 ms)
(ON response time = OFF response time)
Clock/calendar function Yes. Shows the current year, month, day of the week, day of the month, hour, minute, and second.
Communication function Port 1 = Peripheral and RS-422
host link, peripheral bus, no-protocol, programming console
Port 2 = RS-232C port:
host link, no-protocol, 1:1 PLC link, 1:1 NT link
Power-interruption hold function Holds the contents of HR, AR, CNT, and DM areas.
Memory backup Non-volatile memory, user program, DM (read only), PLC setup
Fixed internal lithium battery (5 years, not replaceable by the user) or capacitor
DM (read/write), HR, SR and CNT areas
Self-diagnostic function CPU errors, memory errors, communications errors, setting errors, battery errors
Program check No END instruction, program errors (regularly checked during operation)
Connected tools CX-programmer After version 2.1
Programming console C200H-PRO27, CQM1-PRO01
SSS PC98 & PC/AT (SYSMAC support software, all version)
CX-drive -
Note: 1. The DM area, HR area, AR area, and counter values are 3. Changes made while in MONITOR mode using, for example,
backed up. If the backup battery or capacitor is discharged, online editing, are written to flash memory in real-time.
the contents of these areas will be lost and the data values will 4. The above figure for power consumption includes the power
revert to the defaults. consumption of the programming console.
2. The contents of the program area, read-only DM area 5. This input is shared by the high-speed counter and synchro-
(DM6144 to DM6599), and PLC setup (DM 6600 to DM 6655) nized pulse control functions.
are stored in flash memory. The contents of these areas will
6. This output is shared by the pulse output and synchronized
be read from flash memory the next time the power is turned
pulse control functions
ON, even if the backup battery or capacitor is discharged.
When data has been changed in any of these areas, write the
new values to flash memory by switching the 3G3MV-
P10CDT to MONITOR or RUN mode, or by turning the power
OFF and then ON again.

I/O specifications
Input specifications
Item Inputs Specification
Input voltage All 24 VDC +10%/-15%
Input impedance IN00000 to IN00001 2.7 kΩ
IN00002 to IN00004 3.9 kΩ
IN00005 4.7 kΩ
Input current IN00000 to IN00001 8 mA typical
IN00002 to IN00004 6 mA typical
IN00005 5 mA typical
ON voltage/current IN00000 to IN00001 17 VDC min., 5 mA
IN00002 to IN00005 14.4 VDC min., 3.5 mA
OFF voltage/current All 5.0 VDC max., 1.1 mA
ON delay All 1 to 80 ms max. Default: 10 ms (see note)

V7 inverter PLC 379


Y203-EN2-02-Katalog.book Seite 380 Mittwoch, 24. Mai 2006 2:22 14

Item Inputs Specification


OFF delay All 1 to 80 ms max. default: 10 ms (see note.)
Circuit configuration IN00000 to IN00001
IN
2.7 kW
0.01

Internal circuits
µF
1 kW

COM

Input LED

IN00002 to IN00004
IN
3.9 kW

Internal circuits
820 W

COM

Input LED

IN00005
IN
4.7 kW

Internal circuits
750 W

COM

Input LED

Note: The input time constant can be set to 1, 2, 3, 5, 10, 20, 40, or 80 ms in the PLC setup.

High speed counter inputs


The following unit input bits can be used as high-speed counter inputs. The maximum count frequency is 5 kHz in differential phase mode and
20 kHz in the other modes.
Input Function
Differential phase mode Pulse plus direction input mode Up/down input mode Increment mode
IN00000 A-phase pulse input Pulse input Increment pulse input Increment pulse input
IN00001 B-phase pulse input Direction input Decrement pulse input Normal input
IN00002 Z-phase pulse input or hardware reset input
(IN00002 can be used as a normal input when it is not used as a high-speed counter input.)

The minimum pulse widths for inputs IN00000 (A-phase input) and IN00001 (B-phase input) are as follows:
Pulse plus direction input mode, Differential phase mode
Up/down input mode, increment mode
100 µs min.
50 µs min.
ON 90%
Phase A 50%
ON 90% OFF 10%
50%
OFF 10% ON 90%
Phase B 50%
12.5 µs 12.5 µs OFF 10%
min. min. T1 T2 T3 T4

T1 T2 T3 T4: 12.5 µs min.

The minimum pulse width for input IN00002 (Z-phase input) is as follows:
50 µs min.

ON 90%
Phase Z 50%
OFF 10%
500 µs min.

Interrupt inputs
The 3G3MV-P10CDT is equipped with inputs that can be used as inter-
rupt inputs (interrupt input mode or counter mode) and quick-response
inputs. The minimum pulse width for these inputs is 50 µs.
Inputs IN00003 and IN00004 can be used as interrupt inputs.

380 3G3MV-P10CDT@-E
Y203-EN2-02-Katalog.book Seite 381 Mittwoch, 24. Mai 2006 2:22 14

Output Specification
Relay output
Item Specification
Maximum switching capacity 2 A, 250 VAC (cosϕ=1)
2A, 24VDC
Minimum switching load 10 mA, 5 VDC
Service life of relay Electrical: 150,000 operations (24 VDC resistive load)
100,000 operations (240 VAC inductive load cosϕ=0.4)
Mechanical: 20,000,000 operations
ON delay 15 ms max.
OFF delay 15 ms max.
Circuit configuration
Output LED OUT

Internal OUT
circuits

COM Maximum
250 VAC: 2 A
24 VDC: 2 A

Note: The service life of relay output contacts shown in the table assumes the worst conditions. The following graph shows the results of OMRON's
service life tests at a switching rate of 1,800 times/hour.
Life (x 104)
120 VAC, resistive load
300
24 VDC, τ = 7 ms
200
120 VAC, cosφ = 0.4
240 VAC, cosφ = 0.4
100
24 VDC/240 VAC, resistive load

50

30
20

10

5
Switching rate: 1,800 times/hour
3
2

0.1 0.2 0.3 0.5 0.7 1 2 3 5


Contact current (A)

Transistor outputs (sinking/NPN)


Item Specification
Maximum switching capacity 4.5 to 30 VDC, 0.2 A/ output
Minimum switching capacity 0.5 mA
Maximum inrush current 0.9 A for 10 ms
Leakage current 0.1 mA
Residual voltage 1.5 V max.
ON response time 20 µs max.
OFF response time 40 µs max. for 4.5 to 26.4 VDC, 10 to 100 mA
0.1 ms max for 4.5 to 30 VDC, 10 to 200 mA
Fuse One fuse per output (cannot be replaced by user)
Circuit configuration
Output LED OUT

Internal
circuits OUT 24 VDC

COM (-)

Note: When using OUT01000 or OUT01001 as a pulse output, connect


a dummy resistor as required to bring the load current between !Caution
0.01 and 0.1 A. If the load current is below 0.1 A, the ON-to-OFF Do not apply voltage in excess of the maximum switching capacity
response time will be longer and high-speed pulses (source-type to an output terminal. It may result in damage to the product or fire
transistor outputs) will not be output. If the load current is above
0.1 A, the transistor will generate more heat and components
may be damaged.

V7 inverter PLC 381


Y203-EN2-02-Katalog.book Seite 382 Mittwoch, 24. Mai 2006 2:22 14

Operation
CPU unit component descriptions

Front view

13. Low battery


detection switch
1. DIP switch
4. PC status indicators
2. Input indicators
3. Output indicators

5. Communications port

6. Communications switch

Bottom view

8. RS-422/485 switch
9. Terminating 22/485 port
Resistance switch

11. Relay connector


10. I/O connector 12. FE-connection

1.DIP switch 4. PLC status indicators


• RS-232C and peripheral port settings The following indicators show the operating status of the PLC.
Pin 1 Effective port settings Indicator Status Meaning
OFF The ports operate according to the settings in the PWR ON Power is being supplied to the unit
(default) PLC Setup. (green)
1

OFF Power isn't being supplied to the unit


ON

RS-232C port settings: DM 6645 to DM 6649 RUN ON The PLC is operating in RUN or MONITOR mode
2

Peripheral port settings: DM 6650 to DM 6654 (green) OFF The PLC is in PROGRAM mode or a fatal error has
ON The ports operate with the standard communications occurred.
ON settings.
ERR/ALM ON A fatal error has occurred. (PLC operation stops.)
(red) Flashing A non-fatal error has occurred. (PLC operation continues.)
• Operating mode at startup OFF Indicates normal operation.
Pin 2 determines the operating mode at startup only if there isn't a COMM1 Flashing Data is being transferred via the peripheral or RS-422/485
programming Device connected to the peripheral port. (yellow) port.
OFF Data isn't being transferred via communications port.
Programming device Startup mode with Startup mode with
COMM2 Flashing Data is being transferred via the RS-232C port
connected pin 2 OFF (default) pin 2 ON
(yellow) OFF Data isn't being transferred via communications port.
None PROGRAM mode RUN mode
Programming console Operating mode set on the programming console's
mode switch 5. Communications port
Other device PROGRAM mode Connects the PLC to a programming device (including programming
consoles), host computer, or standard external device. Use a proper
2. Input indicators (yellow) connecting cable (CPM2C-CN111, CS1W-CN114, CS1W-CN118, or
CS1W-CN226).
The input indicators are lit when the corresponding input terminal is ON.
The status of an input indicator will reflect the status of the input even Note: 1. A CQM1H-PRO01-E programming console can be connect-
when that input is being used for a high-speed counter. ed directly to the PLC.
Note: 1. When interrupt inputs are used in interrupt input mode, the in- 2. A C200H-PRO27-E programming console can be connected
dicator may not light even when the interrupt condition is met directly to the PLC with a CS1W-CN224/CN624 connecting
if the input is not ON long enough. cable.
2. Input indicators will reflect the status of the corresponding in- 3. Use a CPM2C-CN111 or CS1W-CN114 connecting cable to
puts even when the PLC is stopped, but the corresponding in- connect to the communications port as a peripheral port. The
put bits will not be refreshed. communications port can be used simultaneously as both a
peripheral port and RS-232C port by using the CPM2C-
3. Output indicators (yellow) CN111 connecting cable.
The output indicators are lit when the corresponding output terminal is 4. Use a CPM2C-CN111, CS1W-CN118 or CS1W-CN226 con-
ON. The indicators are lit during I/O refreshing. The status of an output necting cable to connect to the communications port as a RS-
indicator will also reflect the status of the corresponding output when 232C port. The communications port can be used simulta-
the output is being used as a pulse output. neously as both a peripheral port and RS-232C port by using
the CPM2C-CN111 connecting cable
Note: The peripheral port and RS-422/485 port cannot be used simul-
taneously. When using the peripheral port disconnect any
devices connected to the RS-422/485 port.

382 3G3MV-P10CDT@-E
Y203-EN2-02-Katalog.book Seite 383 Mittwoch, 24. Mai 2006 2:22 14

6. Communications switch
Switch to select port 1 type of connected device 10. I/O connector
Position Communication Port 1 Connects the CPU unit to external input and output devices.
OFF (default) Programming console Sinking/NPN outputs
ON RS-422/485 communication

COM (-)
IN0 (A)

IN1 (B)

IN2 (Z)

OUT0

OUT1

OUT2

OUT3
COM

COM

COM
IN3

IN4

IN5
7. RS-422/485 port (3G3MV-P10CDT3-E only)
Used to connect to host computers, or standard external devices.
Terminal arrangement 1 2 3 4 5 6 7 8 9 10 11 12 1 2

Receive data Send data


(input) (output) Connector: WAGO 733-112 (wire cross section 0.08 to 0.50 mm2)

11. Relay connector


RDA- RDB+ Shield SDA- SDB+ Connects the CPU unit to an external output device.
Connector: WAGO 734-102 (wire cross section 0.08 to 1.50 mm2)
Connector: Phoenix MSTB 2.5/5-STF-5.08AU
Note: The maximum line length is 500 m. 12. FE-connection
Note: The peripheral port and RS-422/485 port cannot be used simul- AMP tab to connect functional earth. Internally connected to pin 3 of the
taneously. When using the peripheral port disconnect any RS-422/485 connector and to the shell of the peripheral connector.
devices connected to the RS-422/485 port.
13. Low battery detection switch (3G3MV-P10CDT3-E only)
8. RS-422/485 switch (3G3MV-P10CDT3-E only) This switch enables or disables the detection of a low-battery error.
Switch to select 4-wire (RS-422) or 2-wire (RS-485) communication
Position Low-battery detection
Position Status Enabled ON (up) (default) Error detection enabled
OFF (down) 4-wire communications
(default)
ON (up) 2-wire communications OFF (down) Error detection disabled
Disabled
OFF
9. Terminating resistance switch (3G3MV-P10CDT3-E only)
Position Termination
OFF (down) Disabled
(default)
ON (up) Enabled
Set this switch to ON only for double-ended connection to a host link
network.

Dimensions

128

68 55

V7 inverter PLC 383


Y203-EN2-02-Katalog.book Seite 384 Mittwoch, 24. Mai 2006 2:22 14

Applications examples
V7 + PLC in positioning application
point-to-point applications are posible adding the PLC to the V7, including the possibility to add position and speed tables or even use recipes that
could be select using a HMI

Home
Operation description

Speed

V7 + PLC

HMI interface

Position

Time
Motor
RS-232 Encoder

Note: For detailed information about the inverter, please refer to Varispeed V7 section.

V7 + PLC with pump


Using the PLC, it is possible to control a modulated plus several auxiliar pumps according your own parameters and system demand. It is also
possible to add a GSM modem to advice about any problem.

HMI interface

Water
GSM Modem

Pressure
sensor V7 + PLC

Power
supply

Main
pump

Aux.
pump 1

Aux.
Up to 6 pump 2

Aux.
pump N
Water

Note: For detailed information about the inverter, please see into the Varispeed V7 section.

384 3G3MV-P10CDT@-E
Y203-EN2-02-Katalog.book Seite 385 Mittwoch, 24. Mai 2006 2:22 14

Ordering information

3G3IV-PCN329-E CX-Drive
Inverter to PC cable

B B

Varispeed V7 Varispeed V7 + V7
Inverter PLC

V7 Inverter
PLC
A

CS1W-CN226 CX-One
PLC to PC cable

B B

V7 inverter PLC
Specifications Model
Inputs Outputs RS422 port RTC
6 4 No No 3G3MV-P10CDT-E
6 4 Yes Yes 3G3MV-P10CDT3-E

A Varispeed
Specifications Model
Sensorless vector control inverter Varispeed V7

Note: For detailed information, please refer to Varispeed V7 series section.

B Cables
Specifications Model
Computer connecting cable CS1W-CN226
Programmable console cable CS1W-CN224

B Software
Specifications Model
PLC programming software: CX-programmer CX-One
Inverter configurator software: CX-drive

V7 inverter PLC 385


Y203-EN2-02-Katalog.book Seite 386 Mittwoch, 24. Mai 2006 2:22 14

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.


To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

Cat. No. I24E-EN-02 In the interest of product improvement, specifications are subject to change without notice.

386 3G3MV-P10CDT@-E