August 10, 2022 - Service Report - Lassonde Western Canada Inc.
August 10, 2022 - Service Report - Lassonde Western Canada Inc.
August 10, 2022 - Service Report - Lassonde Western Canada Inc.
Executive Summary
Minor adjustments made to cooling tower treatment. No concerns with boiler or supporting systems at this time. Please see
notes below.
Boiler
General Comment: Treatment levels are acceptable. No hardness detected. No concerns at this time. Controller
conductivity calibrated to actual. Dealkalizer cycle was almost complete 1000 g remaining, unit manually placed into
regeneration. Maintain a daily bottom boiler blowdown.
Evaporative condenser
Evaporative condenser : Low inhibitor level. Low inhibitor levels will result in scale formation and accelerated corrosion.
Evaporative condenser : Low inhibitor level. Low inhibitor levels will result in scale formation and accelerated corrosion.
General Comment: Controller conductivity required calibration, is has now been calibrated to actual. Scaling treatment just
below what is recommended, Lokor2500SF feed pump has been increased. Water clarity good.
Analysis
Boiler
Softener Left Softener Right Polisher Feedwater Boiler Condensate
Hardness 0 0 0 0 0 0
(ppm as CaCO3) 0-3 0-3 0-3 0-2 0-6 0-4
Chloride 20 20 20
(ppm as Cl)
P Alkalinity 240
(ppm as CaCO3) 150 - 700
Boiler
De-Alkalizer
Hardness 0
(ppm as CaCO3) 0-6
Sodium Sulphite
(ppm as Na2SO3)
pH
Conductivity
(µmhos)
Chloride 80
(ppm as Cl)
Total Alkalinity 20
0 - 10
P Alkalinity
(ppm as CaCO3)
Iron
(ppm as Fe)
Appearance Clear
Status Online
Conductivity Controller
(µmhos)
Boiler
De-Alkalizer
Conductivity Controller Setpoint
(µmhos)
Evaporative condenser
Evaporative condenser
Hardness 70
(ppm as CaCO3) 50 - 100
pH 9.1
7.5 - 9
Conductivity 1755
(µmhos) 1800 - 1900
Chloride 50
(ppm as Cl)
PTSA Tracer 52
(ppb) 75 - 125
Tracer
(ppm Mo6) .3 - .5
Cycles 4.5
Appearance Clear
Status Online
Reading
Boiler
System Units Current Reading Previous Reading Difference Previous Date Daily Average
Meter US Gal 459100 447600 11500 7/12/2022 396.55
Make Up Totalizer US Gal 11235290 11058000 177290 7/12/2022 6113.45
Feedwater Temperature °F 185 190 -5 7/12/2022
Stack Temperature °F 260 255 5 7/12/2022
Softener 1 Totalizer US Gal 18706213 18426271 279942 7/12/2022 9653.17
Softener 2 Totalizer US Gal 43354265 43080110 274155 7/12/2022 9453.62
Softener 1 Peak flow gpm 66 63 3 7/12/2022
Softener 2 Peak flow gpm 36 45 -9 7/12/2022
Dealkalizer Totalizer US Gal 630723 618066 12657 7/12/2022 436.45
Dealkalizer Peak Flow gpm 11 11 0 7/12/2022
Dealakalizer Last Regen Hours 100 103 -3 7/12/2022
Evaporative condenser
System Units Current Reading Previous Reading Difference Previous Date Daily Average
Meter US Gal 1668800 1537300 131500 7/12/2022 4534.48
Evaporative condenser
Products
Boiler
Kelox 1040i 19" 40 / 100 Freqency 10s/40gal 126 L Remaining
Evaporative condenser
Lokor 2500SF 9" 85 / 360 Stroke 60min/3% 60 L Remaining
95 / 360 Adj. Stroke / 360 Adj. Stroke 0 Days to Reorder