PART 1 - GENERAL
1.2 Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this section and all other
sections of Division 26.
1.3 SUMMARY
A. Section Includes:
1.4 DEFINITIONS
1.5 SUBMITTALS
A. Product Data: For each type of lighting fixture, arranged in order of fixture designation.
Include data on features, accessories, finishes, and the following: <Engineer to Edit for
Project Requirements>
B. Shop Drawings: For nonstandard or custom lighting fixtures. Include plans, elevations,
sections, details, and attachments to other work.
C. Shop Drawings: All lighting fixtures shall include the following, in addition to the
requirements of the Submittal section:
D. Samples: For each custom lighting fixture indicated in the Interior Lighting Fixture
Schedule. Each Sample shall include the following:
1. Lamps/Modules, installed.
2. Cords and plugs.
3. Pendant support system.
4. Drivers
E. Installation instructions.
F. Coordination Drawings: Reflected ceiling plan(s) and other details, drawn to scale, on
which the following items are shown and coordinated with each other, using input from
installers of the items involved:
1. Lighting fixtures.
2. Suspended ceiling components.
3. Partitions and millwork that penetrate the ceiling or extends to within twelve (12)
inches of the plane of the luminaires.
4. Ceiling-mounted projectors.
5. Structural members to which suspension systems for lighting fixtures will be
attached.
6. Other items in finished ceiling including the following:
7. Perimeter moldings.
G. Qualification Data: For qualified agencies providing photometric data for lighting
fixtures.
H. Product Certificates: For each type of driver and dimmer-controlled fixtures, from
manufacturer.
J. Operation and Maintenance Data: For lighting equipment and fixtures to include in
emergency, operation, and maintenance manuals.
1. Provide a list of all lamp/module types used on Project; use ANSI and
manufacturers' codes.
4. IES Standard TM-21 “Projecting Long term Lumen Maintenance of LED Light
Sources”.
E. Mockups: Provide interior lighting fixtures for room or module mockups, complete with
power and control connections.
1.7 COORDINATION
A. Coordinate layout and installation of lighting fixtures and suspension system with other
construction that penetrates ceilings or is supported by them, including HVAC
equipment, fire-suppression system, and partition assemblies.
A. Furnish extra materials that match products installed and that are packaged with
protective covering for storage and identified with labels describing contents.
1. Plastic Diffusers and Lenses: [One (1) for every one hundred (100)] <Insert
quantity> of each type and rating installed. Furnish at least one (1) of each type.
2. LED-fixture-mounted, emergency battery pack: One (1) for every [twenty (20)]
[fifty (50)] <Insert number> emergency lighting unit.
3. LED Lamps/Modules: [One (1) for every one hundred (100)] <Insert quantity> of each
type and rating installed. Furnish at least one (1) of each type.
4. LED Drivers: [One (1) for every one hundred (100)] <Insert quantity> of each type and
rating installed. Furnish at least one (1) of each type.
5. Globes and Guards: [One (1) for every twenty (20)] <Insert quantity> of each
type and rating installed. Furnish at least one (1) of each type.
1.9 WARRANTY/GUARANTEE
A. See Division 26 Specification Section “Basic Electrical Requirements’ for warranty and
guarantee requirements.
C. Warranty Period: Modules (lamps), drivers and all components, provide a complete
warranty for parts and labor for a minimum of five (5) years from the date of Substantial
Completion.
1. Warranty Period for Emergency Lighting Unit Batteries: [Ten (10)] <Insert
number> years from date of Substantial Completion. Full warranty shall apply for
two (2) years, and prorated warranty for the remaining eight (8) years.
2. Warranty Period for [Emergency Fluorescent Ballast] [and] [Self-Powered Exit
Sign] Batteries: [Seven (7)] <Insert number> years from date of Substantial
Completion. Full warranty shall apply for two (2) years, and prorated warranty for
the remaining five (5) years. <Engineer to Edit for Project Requirements>
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Products: Subject to compliance with requirements, provide one of the products indicated
on Drawings.
A. Recessed Fixtures: Comply with NEMA LE 4 for ceiling compatibility for recessed
fixtures.
C. Sheet Metal Components: Steel unless otherwise indicated. Form and support to prevent
warping and sagging.
D. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage under
operating conditions, and designed to permit relamping without use of tools. Designed to
prevent doors, frames, lenses, diffusers, and other components from falling accidentally
during relamping and when secured in operating position.
H. Air-Handling LED Fixtures: For use with plenum ceiling for air return and heat
extraction and for attaching an air-diffuser-boot assembly specified in the mechanical
specifications.
1. Air-Supply Units: Slots in one or both side trims join with air-diffuser-boot
assemblies.
I. LED lighting fixtures scheduled on the drawings are found to offer products similar to the
basis of design product, including performance, appearance, and quality. Listed equals
must comply with minimum performance criteria. Additional documentation and
calculations for LED lighting fixtures compliance should be made available upon request.
A. General Requirements for Exit Signs: Comply with UL 924; for, visibility, luminance,
and lettering size, comply with authorities having jurisdiction. Provide RED color sign.
1. Lamps for AC Operation: LEDs, 50,000 hours minimum rated lamp life.
2. Self-Powered Exit Signs (Battery Type): Integral automatic charger in a self-
contained power pack.
A. Acceptable Manufacturers:
1. Luminaires:
a. Refer to the Luminaires Schedule on the drawings.
2. Drivers:
a. Cree.
b. EldoLED.
c. Philips/Advance.
d. Thomas Research Products.
e. Or as supplied by the luminaire manufacturer, in compliance with these
Specifications.
3. Dimmable Drivers:
a. Cree.
b. EldoLED.
c. Philips/Advance.
d. Thomas Research Products.
e. Or as supplied by the luminaire manufacturer, in compliance with these
Specifications.
B. Luminaires:
<Engineer to coordinate exterior lighting fixture requirements with UMB Design
Standards>.
C. Drivers: Listed and so labeled per UL 8750 and UL 1310, and shall meet or exceed the
following general specification criteria:
1. Designed and tested to be compatible with the luminaire light source operating
current, voltage, and output power requirements.
1. Have an operating power factor of ≥ 0.9 at full load, and not less than 0.8 at
dimmed level.
2. Provide smooth, flicker-free, dimmable light output from 100% to less than 1%.
3. 0-10VDC "sinking" type dimming control protocol per enforced version of IEC
Standard 60929, unless otherwise noted or required.
A. Comply with Division 26 Section "Hangers and Supports for Electrical Systems" for
channel- and angle-iron supports and nonmetallic channel and angle supports.
B. Single-Stem Hangers: One half (1/2) inch steel tubing with swivel ball fittings and ceiling
canopy. Finish same as fixture.
C. Twin-Stem Hangers: Two (2), one half (1/2) inch steel tubes with single canopy designed
to mount a single fixture. Finish same as fixture.
D. Wires: ASTM A 641/A 641M, Class 3, soft temper, zinc-coated steel, [12 gage] <Insert
size>.
E. Wires for Humid Spaces: ASTM A 580/A 580M, Composition 302 or 304, annealed
stainless steel, [12 gauge] <Insert size>.
F. Rod Hangers: Three sixteenth (3/16) inch minimum diameter, cadmium-plated, threaded
steel rod.
G. Hook Hangers: Integrated assembly matched to fixture and line voltage and equipped
with threaded attachment, cord, and locking-type plug.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Lighting fixtures:
1. Set level, plumb, and square with ceilings and walls unless otherwise indicated.
2. Install lamps in each luminaire.
B. Remote Mounting of Drivers: Distance between the driver and fixture shall not exceed
that recommended by driver manufacturer. Verify, with driver manufacturers, maximum
distance between driver and luminaire. Mount in nearby accessible ceiling space and
provide label on ceiling.
1. Install ceiling support system rods or wires, independent of the ceiling suspension
devices, for each fixture. Locate not more than six (6) inches from lighting fixture
corners.
2. Fixtures of Sizes Less Than Ceiling Grid: Install as indicated on reflected ceiling
plans or center in acoustical panel, and support fixtures independently with at
least two (2) three quarter (3/4) inch metal channels spanning and secured to
ceiling tees.
1. Pendants and Rods: Where longer than forty eight (48) inches, brace to limit
swinging.
2. Stem-Mounted, Single-Unit Fixtures: Suspend with twin-stem hangers.
3. Continuous Rows: Use tubing or stem for wiring at one point and tubing or rod
for suspension for each unit length of fixture chassis, including one at each end.
4. Do not use grid as support for pendant luminaires. Connect support wires or rods
to building structure.
E. Air-Handling Lighting Fixtures: Install with dampers closed and ready for adjustment.
3.2 IDENTIFICATION
A. Install labels with panel and circuit numbers on concealed junction and outlet boxes.
Comply with requirements for identification specified in Division 26 Section
"Identification for Electrical Systems.
A. Test for Emergency Lighting: Interrupt power supply to demonstrate proper operation.
Verify transfer from normal power to battery and retransfer to normal.
A. Burn-in all lamps that require specific aging period to operate properly, prior to
occupancy by Owner. Burn-in fluorescent and compact fluorescent lamps intended to be
dimmed, for at least one hundred (100) hours at full voltage.