Professional Documents
Culture Documents
DSE5220-Installation-Instructions 230908 121157
DSE5220-Installation-Instructions 230908 121157
Start delay Timer (secs) 2 Stop/Reset button and the configure/log button.
If a PIN number has been set, press + / - to set the first digit, then press 9 to adjust the next
Preheat Timer (secs) 3 digit.
Crank attempt Timer (secs) 4 Repeat this until all four digits have been entered.
The first configurable parameter is now displayed. Pressing the + or - buttons will cycle through the
Crank rest Timer (secs) 5
parameters.
Safety delay Timer (secs) 6
Overspeed overshoot Timer (secs) 7 NOTE:- To exit the front panel configuration editor at any time, press the Stop/Reset
button. Ensure you have saved any changes you have made by pressing the 9 button first.
Warming up Timer (secs) 8
Transfer delay Timer (secs) 9 Editing an analogue value
Return delay Timer (secs) 10 Access the front panel config editor as detailed above. Press the +/- buttons to view the parameter you
wish to change (see parameter table overleaf). Press the 9 button to enter adjust mode. The value to be
Cooling run Timer (secs) 11
adjusted will flash. Press the +/- buttons to adjust the parameter to the desired value. Press the 9 button
E.T.S.(Energise to stop) solenoid hold Timer (secs) 12 to ‘save’ the value. The value will stop flashing to confirm that it has been saved. To select another value to
Mains (utility) supply Mains Low Voltage Trip V edit, press the + button. Continuing to press the +/- buttons will cycle through the available parameters.
Mains High Voltage Trip V Editing the time
Mains Low Frequency Trip The date/time should initially be set using the 5200 series configuration software. However there may be
Mains High Frequency Trip certain circumstances where a minor change to the module’s time is required. One such instance is
correction for daylight saving. Access the front panel config editor as detailed above. Press the + button
Generator output Generator Under Voltage L1-N Trip V until the calendar is shown :
Generator Under Voltage L1-N Pre Alarm V To edit the time, press the 9 button. The minutes, ‘30’ in this
example, will begin flashing. Press the + or - buttons to adjust
Generator Over Voltage Pre Alarm V
the minutes. Press the button to select hours, day, month
Generator Over Voltage Trip V and year. The selected parameter will flash.
Generator Under Frequency Trip Press the 9 button to save the change. The time stops flashing
Generator Under Frequency Pre Alarm to confirm that it has been successfully stored.
st
Example : This display is showing a time of 4:30 on 21
Generator Over Frequency Pre Alarm October 2002.
Generator Over Frequency Trip
Delayed Overcurrent % Trip A
Engine speed Under Speed (RPM) Trip
NOTE:- Full configuration of the 5220 module is possible using the 5200 series configuration
Under Speed (RPM) Pre Alarm
software for PC in conjunction with the P810 interface.
Over Speed (RPM) Pre Alarm
Over Speed (RPM) Trip Deep Sea Electronics Plc.
Deep Sea Electronics Inc.
DC Voltages Low DC Voltage Warning V Highfield House, Hunmanby Industrial Estate,
3230 Williams Avenue, Rockford,
North Yorkshire. YO14 0PH. ENGLAND.
High DC Voltage Warning V IL 61101-2668, USA
Tel:+44 (0)1723 890099
Phone: +1 (815) 316-8706
Charge Alternator Failure Warning Fax: +44 (0)1723 893303.
Fax: +1 (815) 316-8708
Email: sales@deepseaplc.com
Email: dsesales@deepseausa.com
Web: www.deepseaplc.com
Web: www.deepseausa.com
LO CALL (from UK BT landlines) : Telephone
TOLL FREE (USA only) Tel: 1 866 636 9703
0845 260 8900.
configuration software
Typical Wiring Diagram
5200 series
Dimensions
Module Dimensions - 240mm x 172mm x 57mm (9.45” x 6.77” x 2¼”)
Generator
548 annunciator
157/548
810 interface
or
Alternative AC wiring
L2
L1
L3
N
2 phase, 3 wire ( 2 phase centre tap neutral)
Supply for
controller
810
1
LOAD
Starter
motor
2
F
Mechanical interlock
Generator Mains (utility)
39
3
Emergency
F L1 L1
stop
40
CT
Earth
5
L2
Battery
L2
41
+
common
Fuel
N N
F2A F2A F2A F2A
CT
4
Electrical interlock
42
G M
Charge WL
alt.
43
Not connected
CT
common
9
Earth
CT
39 40 41 42 43 35 36 37 38 29 30 27 28 31 32 33 34
Oil pressure sender
Not connected
connection to any other device.
not be used to provide a ground
The ground wire to terminal 47 must
to the sender bodies.
a sound electrical connection
on the engine block and must be
These ground connections must be
44
F2A
Generator Mains
loading loading
35
relay relay
Coolant temp. sender
F2A
5220 controller
36
45
F2A
37
38
47
29
Generator
loading
relay
3 phase, 3 wire
Mechanical interlock
30
LOAD
Configurable auxiliary input 2
Mechanical interlock
11
relay
CT
Earth
Configurable auxiliary input 4 L2 L2
28
13
F2A
31
L3 L3
To plant supply +ve
F2A
32
F2A
Electrical interlock
G M
33
common
6
39 40 41 42 43 35 36 37 29 30 38 34 27 28 31 32 33
Configurable auxiliary output 2
Not connected
Not connected
Not connected
7
Optional
RS232
9 way D
Generator Mains
Configurable auxiliary output 3 loading loading
relay
8
relay
COM
20
SCR
23
Not connected 19
Not connected 26
Optional
CanBus
L2
L1
L3
N
Optional
RS485
21
24
H
Mains (utility)
22
25
L
B
17
18
16
at one end only
Ground screen
Earth
Functional
MPU