PD For Power Transformer Using Acoutic Sensor Method Statement
PD For Power Transformer Using Acoutic Sensor Method Statement
Technical Procedures
Revision: 00
This document is issued by the Company under its General Conditions of Service accessible at http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of
liability, indemnification and jurisdiction issues defined therein. Any other holder of this document is advised that information contained hereon reflects the Company’s findings at the time of its
intervention only and within the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising
all their rights and obligations under the transaction documents. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be
prosecuted to the fullest extent of the law.
SGS Pakistan (Pvt) Ltd H-3/3, Sector 5, Korangi Industrial Area, Karachi Pakistan T 111-222-SGS (747) F +92 21 35121325 www.sgs.com
Quality Assurance Manual
Technical Procedures
Revision: 00
Table of Contents
1. PURPOSE .............................................................................................................................................. 3
2. SCOPE ................................................................................................................................................... 3
3. REFERENCE AND/OR RELEVANT DOCUMENTS ...................................................................................... 3
4. GENERAL............................................................................................................................................... 3
5. RESPONSIBILITIES ................................................................................................................................. 4
6. ACTIVITIES ............................................................................................................................................ 4
Important Safety Information .............................................................................................................. 4
7.UHF PD Measurement ........................................................................................................................... 4
PD Measurement through UVS 610 ...................................................................................................... 5
8. High-frequency current transformer HFCT
This document is issued by the Company under its General Conditions of Service accessible at http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of
liability, indemnification and jurisdiction issues defined therein. Any other holder of this document is advised that information contained hereon reflects the Company’s findings at the time of its
intervention only and within the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising
all their rights and obligations under the transaction documents. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be
prosecuted to the fullest extent of the law.
SGS Pakistan (Pvt) Ltd H-3/3, Sector 5, Korangi Industrial Area, Karachi Pakistan T 111-222-SGS (747) F +92 21 35121325 www.sgs.com
Quality Assurance Manual
Technical Procedures
Revision: 00
1. PURPOSE
This procedure describes minimum guidelines for measurement of PD using drain valve sensor
2. SCOPE
4. GENERAL
Definitions
• DM - Divisional Manager
• HO - Head of Operations
• BE - Business Executive
• CO - Co-ordinator
• IA - Internal Auditor
• IE - Inspection Engineer / Inspector
• TAS - Trade Assurance Services
• INDIV - Industrial Services
• IEC - International Electro technical commissions.
This document is issued by the Company under its General Conditions of Service accessible at http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of
liability, indemnification and jurisdiction issues defined therein. Any other holder of this document is advised that information contained hereon reflects the Company’s findings at the time of its
intervention only and within the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising
all their rights and obligations under the transaction documents. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be
prosecuted to the fullest extent of the law.
SGS Pakistan (Pvt) Ltd H-3/3, Sector 5, Korangi Industrial Area, Karachi Pakistan T 111-222-SGS (747) F +92 21 35121325 www.sgs.com
Quality Assurance Manual
Technical Procedures
Revision: 00
5. RESPONSIBILITIES
PERSONNEL RESPONSIBILITY
Director Operation Approves the Quality Manual
Operation Manager/Quality Manager Issues and review the QMS and General
procedures
Operation Manager/Technical Manager Issues and review specific procedures and
Reporting template working instructions
Designated people Draft and/or review general procedures,
specific procedures and working
instructions
6. ACTIVITIES
Always follow the Medium / High Voltage MV/HV network owner’s specific site safety rules.
Before enter a substation or switchyard, and during time inside, should always obey thus additional
safety advice.
7.UHF PD Measurement
Partial discharge (PD) measurements on HV asset are a well-established tool of quality control and
integral part of the factory acceptance tests. In the field, PD measurements on HV asset have been
considered as not applicable for decades due to a lack of strategies to overcome the tremendous
influence of external noise sources.
As the conventional PD measurement method according to IEC 60270 is known to be sensitive to
unwanted external interferences, UHF detection on or inside e.g. a transformers tank becomes more
and more popular because of its high level of noise immunity.
This document is issued by the Company under its General Conditions of Service accessible at http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of
liability, indemnification and jurisdiction issues defined therein. Any other holder of this document is advised that information contained hereon reflects the Company’s findings at the time of its
intervention only and within the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising
all their rights and obligations under the transaction documents. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be
prosecuted to the fullest extent of the law.
SGS Pakistan (Pvt) Ltd H-3/3, Sector 5, Korangi Industrial Area, Karachi Pakistan T 111-222-SGS (747) F +92 21 35121325 www.sgs.com
Quality Assurance Manual
Technical Procedures
Revision: 00
Therefore, the application of UHF PD measurement technology can help to verify internal PD and can
provide statistically relevant data to be used for PD pattern classification without overlapping
external interferences.
For the Transformer also another feature of the UHF method is its ability to provide a precise trigger
signal for acoustical PD localization.
The UVS 610, together with the MPD 600 measuring system, allows partial discharge
measurements to be taken in liquid-insulated power transformers. The UHF Sensor is inserted
into the power transformer via the vent of an oil drain valve. Partial discharge measurements in
a UHF frequency range can be made inside the tank
• The UHF valve sensor allows partial discharge measurements in high-frequency ranges (upto 1
GHz) in power transformers with liquid insulation.
• UVS 610 is inserted through the oil drain valve (DN 50 and DN 80).
• It is used with a UHF converter; the UVS 610 is connected to the MPD 600 measuring system.
• A useful scale on the slide-rod ensures that the device is correctly inserted into the oil drain valve
This document is issued by the Company under its General Conditions of Service accessible at http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of
liability, indemnification and jurisdiction issues defined therein. Any other holder of this document is advised that information contained hereon reflects the Company’s findings at the time of its
intervention only and within the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising
all their rights and obligations under the transaction documents. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be
prosecuted to the fullest extent of the law.
SGS Pakistan (Pvt) Ltd H-3/3, Sector 5, Korangi Industrial Area, Karachi Pakistan T 111-222-SGS (747) F +92 21 35121325 www.sgs.com
Quality Assurance Manual
Technical Procedures
Revision: 00
High-frequency current transformers HFCT for monitoring and diagnostics The diagnostic
HFCTs are gapped and can be installed and removed easily. They allow spacers to
compensate saturation by high AC currents. Typically used for diagnostic measurements.
The HFCTs for monitoring use, are typical single color to have a better UV resistance and
can be ungapped
This document is issued by the Company under its General Conditions of Service accessible at http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of
liability, indemnification and jurisdiction issues defined therein. Any other holder of this document is advised that information contained hereon reflects the Company’s findings at the time of its
intervention only and within the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising
all their rights and obligations under the transaction documents. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be
prosecuted to the fullest extent of the law.
SGS Pakistan (Pvt) Ltd H-3/3, Sector 5, Korangi Industrial Area, Karachi Pakistan T 111-222-SGS (747) F +92 21 35121325 www.sgs.com
Quality Assurance Manual
Technical Procedures
Revision: 00
The coupling method based on high-frequency current transformer (HFCT sensor) is used especially in
case of ground connection. In this case, a very low current is expected, so no external quadripole is
required. In the MPD software, the internal quadripole of the MPD is selected and the “V” BNC connection
is left disconnected.
This document is issued by the Company under its General Conditions of Service accessible at http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of
liability, indemnification and jurisdiction issues defined therein. Any other holder of this document is advised that information contained hereon reflects the Company’s findings at the time of its
intervention only and within the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising
all their rights and obligations under the transaction documents. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be
prosecuted to the fullest extent of the law.
SGS Pakistan (Pvt) Ltd H-3/3, Sector 5, Korangi Industrial Area, Karachi Pakistan T 111-222-SGS (747) F +92 21 35121325 www.sgs.com
Quality Assurance Manual
Technical Procedures
Revision: 00
Setup of a 1-channel-measurement:
Performing a measurement with a HFCT is not compliant to the IEC60270.
Since the IEC60270 was intended for laboratory use only. There is no connection scheme including
something like a high frequency current transformer.
This document is issued by the Company under its General Conditions of Service accessible at http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of
liability, indemnification and jurisdiction issues defined therein. Any other holder of this document is advised that information contained hereon reflects the Company’s findings at the time of its
intervention only and within the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising
all their rights and obligations under the transaction documents. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be
prosecuted to the fullest extent of the law.
SGS Pakistan (Pvt) Ltd H-3/3, Sector 5, Korangi Industrial Area, Karachi Pakistan T 111-222-SGS (747) F +92 21 35121325 www.sgs.com
Quality Assurance Manual
Technical Procedures
Revision: 00
Another use case for HFCTs is the installation at the grounding connection of a high-voltage device.
High-frequency signals can be measured. These signals could either be related to PD inside the test object
or could be considered as interferences from the grounding system.
These interferences are usually created by other electric devices connected to the same grounding
system.
This document is issued by the Company under its General Conditions of Service accessible at http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of
liability, indemnification and jurisdiction issues defined therein. Any other holder of this document is advised that information contained hereon reflects the Company’s findings at the time of its
intervention only and within the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising
all their rights and obligations under the transaction documents. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be
prosecuted to the fullest extent of the law.
SGS Pakistan (Pvt) Ltd H-3/3, Sector 5, Korangi Industrial Area, Karachi Pakistan T 111-222-SGS (747) F +92 21 35121325 www.sgs.com
Quality Assurance Manual
Technical Procedures
Revision: 00
This document is issued by the Company under its General Conditions of Service accessible at http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of
liability, indemnification and jurisdiction issues defined therein. Any other holder of this document is advised that information contained hereon reflects the Company’s findings at the time of its
intervention only and within the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising
all their rights and obligations under the transaction documents. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be
prosecuted to the fullest extent of the law.
SGS Pakistan (Pvt) Ltd H-3/3, Sector 5, Korangi Industrial Area, Karachi Pakistan T 111-222-SGS (747) F +92 21 35121325 www.sgs.com
Quality Assurance Manual
Technical Procedures
Revision: 00
This document is issued by the Company under its General Conditions of Service accessible at http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of
liability, indemnification and jurisdiction issues defined therein. Any other holder of this document is advised that information contained hereon reflects the Company’s findings at the time of its
intervention only and within the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising
all their rights and obligations under the transaction documents. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be
prosecuted to the fullest extent of the law.
SGS Pakistan (Pvt) Ltd H-3/3, Sector 5, Korangi Industrial Area, Karachi Pakistan T 111-222-SGS (747) F +92 21 35121325 www.sgs.com
Quality Assurance Manual
Technical Procedures
Revision: 00
Depending on their rated voltage level and construction type, some transformers bushings are equipped
with measuring taps.The bushing tap can be used to connect the coupling device / CPL and the MPD to the
transformer.
This document is issued by the Company under its General Conditions of Service accessible at http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of
liability, indemnification and jurisdiction issues defined therein. Any other holder of this document is advised that information contained hereon reflects the Company’s findings at the time of its
intervention only and within the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising
all their rights and obligations under the transaction documents. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be
prosecuted to the fullest extent of the law.
SGS Pakistan (Pvt) Ltd H-3/3, Sector 5, Korangi Industrial Area, Karachi Pakistan T 111-222-SGS (747) F +92 21 35121325 www.sgs.com
Quality Assurance Manual
Technical Procedures
Revision: 00
This document is issued by the Company under its General Conditions of Service accessible at http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of
liability, indemnification and jurisdiction issues defined therein. Any other holder of this document is advised that information contained hereon reflects the Company’s findings at the time of its
intervention only and within the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising
all their rights and obligations under the transaction documents. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be
prosecuted to the fullest extent of the law.
SGS Pakistan (Pvt) Ltd H-3/3, Sector 5, Korangi Industrial Area, Karachi Pakistan T 111-222-SGS (747) F +92 21 35121325 www.sgs.com
Quality Assurance Manual
Technical Procedures
Revision: 00
There are several connectors available depending on the bushing tap structure.
It is strongly recommended to avoid any kind of clamps, because of the damages that can appear as a result of
accidental disconnections
This document is issued by the Company under its General Conditions of Service accessible at http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of
liability, indemnification and jurisdiction issues defined therein. Any other holder of this document is advised that information contained hereon reflects the Company’s findings at the time of its
intervention only and within the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising
all their rights and obligations under the transaction documents. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be
prosecuted to the fullest extent of the law.
SGS Pakistan (Pvt) Ltd H-3/3, Sector 5, Korangi Industrial Area, Karachi Pakistan T 111-222-SGS (747) F +92 21 35121325 www.sgs.com
Quality Assurance Manual
Technical Procedures
Revision: 00
The presence of the measuring taps makes easy the PD measurement process.
The main advantage of the tapped bushings is that no coupling capacitor is necessary.
Thus, some problems caused by the coupling capacitor which might be not PD-free, are avoided.
8.Test Values
This document is issued by the Company under its General Conditions of Service accessible at http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of
liability, indemnification and jurisdiction issues defined therein. Any other holder of this document is advised that information contained hereon reflects the Company’s findings at the time of its
intervention only and within the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising
all their rights and obligations under the transaction documents. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be
prosecuted to the fullest extent of the law.
SGS Pakistan (Pvt) Ltd H-3/3, Sector 5, Korangi Industrial Area, Karachi Pakistan T 111-222-SGS (747) F +92 21 35121325 www.sgs.com