CONDENSER FAN SPEED CONTROLLERS

Type RGE

GENERAL DESCRIPTION
• T he most suitable for controlling the speed of a
condenser fan of freezing and refrigeration condensing
unit, package air conditioner and other units which are
operated throughout a year.
• K eep condensing pressure constant in winter and
intermediate seasons for stable operation.
• One of the following operation models is selectable
when low speed.
Minimum Speed Operation
Cut off Operation
• Excellent noise-resisting design.
• Applicable to the external forced operation switch.

mark applicable
Single-phase type
listed (available upon request)

SPECIFICATIONS
Three-phase type
• Max.working pressure: 4.7MPa
• Control method: Phase control
• Enclosure: IP54

TYPE NUMBER SELECTION


*1 F.V.S. Setting (MPa) *2
Ambient
E.P.B. Electrical Wt.
Catalog No. Factory Adjusting Range (MPa) Refrigerants Function Temp. Operation
Ratings (kg)
Set (°C)
Min. Max. Ampere
RGE–Z1L4–7 1.9 0.8 2.8 Fixed 0.6 R22, R404A, R407C
0.2 to 3A At approx. 45% (50Hz) 0.36
RGE–Z1L6–7 3.2 1.6 3.9 Fixed 0.9 R410A
at approx. 35% (60Hz)
RGE–Z1N4–7 1.9 0.8 2.8 Fixed 0.4 R22, R404A, R407C Cut Off or Minimum
Single phase 0.2 to 4A Speed function is 0.5
RGE–Z1N6–7 3.2 1.6 3.9 Fixed 0.8 R410A
200 to 240V. AC selectable with −20 to 55 ①
RGE–Z1P4–7 1.9 0.8 2.8 Fixed 0.4 R22, R404A, R407C 50/60Hz 0.2 to 6A changeover switch. 0.54
RGE–Z1P6–7 3.2 1.6 3.9 Fixed 0.8 R410A
Default setting:
RGE–Z1Q4–7 1.9 0.8 2.8 Fixed 0.4 R22, R404A, R407C
0.2 to 8A Cut Off 0.58
RGE–Z1Q6–7 3.2 1.6 3.9 Fixed 0.8 R410A
RGE–Z3R4–7 1.6 0.8 2.8 Fixed 0.4 R22, R404A, R407C
Three phase 0.2 to 5A At approximately 35%, 1.4
RGE–Z3R6–7 3.2 1.6 3.9 Fixed 0.8 R410A Cut Off or Minimum
200 to 240V. AC Speed function is −20 to 50
RGE–Z3T4–7 1.6 0.8 2.8 Fixed 0.6 R22, R404A, R407C 50/60Hz 0.2 to 7A selectable with ② 1.53
RGE–Z3T6–7 3.2 1.6 3.9 Fixed 0.8 R410A changeover switch.
RGE–X3R4–7 1.6 0.8 2.8 Fixed 0.4 R22, R404A, R407C Three phase Default setting:
380 to 415V. AC 0.2 to 5A Min. Speed −15 to 50 1.4
RGE–X3R6–7 3.2 1.6 3.9 Fixed 0.8 R410A 50/60Hz
* 1: The pressure at which the control delivers 95% output effective voltage (VRMS).
* 2: Pressure width where effective voltage corresponds to the minimum speed or causes cut off operation
・ Min. speed: Fan motor will be kept running at the specific value (V%) when pressure band increase more than E.P.B.
・ Cut off: Fan motor will be stopped when pressure decrease to the specific value (V%) for R.M.S.
・ For other pressure set values or min. speed/cut off set values, please contact us.

OPERATION
① Single-phase type ② Three-phase type
F.V.S.(Adjustable) F.V.S.(Adjustable)
100 Max. Speed 100 Max. Speed
. V%)

. V%)

95 95
23 0V

Effective Voltage R .M.S(


Effective Voltage R .M.S(

0V
3
Hz at 2
Hz

at
50
60

Min. Speed
45
Min. Speed
35 35
Cut Off

Cut Off

E.P.B.(Fixed) E.P.B.(Fixed)

Pressure Pressure
The operating characteristic may vary according to the voltage, frequency, and fan motor characteristics.

110
WIRING
Single-phase type Three-phase type
for 2A (RGE−Z1) for 4A, 6A, 8A (RGE−Z1)

External
Forced Operation Switch
On: Full speed
Ground Off: Auto speed Ground External Forced
Circuit Breaker or Fuse
Operation Ground
Circuit Breaker or Fuse Switch
Circuit Breaker or Fuse Fan Motor On: Max. speed Switch
Off: Auto speed
Switch
Power Supply
Switch Fan Motor
Fan Motor
External
Forced Operation Switch

Apply external forced operation switches that afford to cut consumption curret of fan motors. Use a forced operation switch with non-voltage contact signal.

DIMENSIONS
Single-phase type Three-phase type
105 185
104
95 175
95
4−φ5.4 160
4−φ4.4
4−φ5.4
(125)
75

150
100

200

130
12

900±100

900±100

1/4" Female Flare with Schrader Copper Packing

1/4" Female Flare with Schrader Copper Packing


φ22.5 Conduit Gland
(102) 900±100
(36) φ22.5 Conduit Gland

1/4" Female Flare with Schrader Copper Packing


(55)

(67)
58

for 3A
7

for 4A

φ22.5 Conduit Gland


98

(36)
58
16

φ22.5 Conduit Gland


for 5A(REG−Z3,X3)
76

(67)
25

for 6A

φ22.5 Conduit Gland


(36)
98

58
16
76

φ22.5 Conduit Gland


for 7A(REG−Z3)
25

for 8A
Unit: mm