04 - Report Appendix M - 2017 Subtransmission System - Load Flow Results
04 - Report Appendix M - 2017 Subtransmission System - Load Flow Results
Appendix
ALUMINM-1
ALUMINM-1
NAG-HAMD-1
NAG-HAMD-2
ALUMINM-2
ALUMINM-3
ASWAN
KEMA
Buses
QUENA
QUENA
KOMOMBO
SOHAG
ISNA-GEN
IDFO
FEROSLKN
ISNA
LXRSHRK
0.85 0.9 0.95 1 1.05 1.1
Voltage [pu]
EETC2017 - Peak - Nominal Tap Position EETC2017 - Peak - Actual Tap Position
EETC2017 - Peak - Auto-Tapping Vmin (0.95 pu)
Vmax (1.05 pu)
Figure M 1 EETC2017 Peak Model – Voltage Profile at 132 kV Level – Zone 1 – Nominal Tap Position vs.
Actual Tap Position vs. Auto-Tapping
SAMALUT
C-MINA
N-ASSYUT
ASMNT-1
ASMNT-2
WAHAT
Buses
DEMO
MAGAGA
MENIA
ASSYUT-STEAM
BNISWIF
MALAWI
0.9 0.95 1 1.05 1.1
Voltage [pu]
EETC2017 - Peak - Nominal Tap Position EETC2017 - Peak - Actual Tap Position
EETC2017 - Peak - Auto-Tapping Vmin (0.95 pu)
Vmax (1.05 pu)
Figure M 2 EETC2017 Peak Model – Voltage Profile at 132 kV Level – Zone 2 – Nominal Tap Position vs.
Actual Tap Position vs. Auto-Tapping
BALAT
A.TARTOR 2
TOSHK 2
ESLAH 2
ESLAH 1
ESLAH 3
ESLAH 4
TOSHK 1
A.SEMBEL
A. DAM
N.HAMADY 1
W.NOKRA 66
H.D WEST
W.NAKRA 2
W.NAKRA 3
ASWAN.E
H.D EAST
W.NAKRA 1
OYNAT66
ASWAN W
N.HAM EAST
SIEL
SELWA
DISHNA
EDFO_E
ASWAN.N
N.HAMADY 2
BAHGORA
TLMBAT DARB
KALABSHA
OYNAT 1
ELSAIDA
KOM OMBO
AL AAKAB
ELSEBAIA NEW
N.H DAM
OYNAT 2
Buses
ABUTESHT
QENA-S
MARASHDA
ESNA
D1B.HMIL
D2B.HMIL
BANIHMIL
TEMA 1
TEMA 2
LUXOR_E
LUXOR_W
TEBA
NEW ESNA66
ARMANT
HUMIDAT
TAHTA
AUDISAT
RADWANIA
SALHYA
HEGAZA
C.ELNAHD
GERGA 2
GERGA
C.QENA
MESHTA
NAKADA
QOUS PAPER 2
QEFT
TEMA 33
EL MRAGHA 1
SHAND. MOBIL
SOHAG N
SAQLTA
DARSLAM
EL MRAGHA 2
ELBLIANA
ELMONSHA
ELKOAMEL
AKHMEM
0.55 0.65 0.75 0.85 0.95 1.05 1.15 1.25
Voltage [pu]
EETC2017 - Peak - Nominal Tap Position EETC2017 - Peak - Actual Tap Position
EETC2017 - Peak - Auto-Tapping Vmin (0.95 pu)
Vmax (1.05 pu)
Figure M 3 EETC2017 Peak Model – Voltage Profile at 66 kV Level – Zone 1 – Nominal Tap Position vs.
Actual Tap Position vs. Auto-Tapping
MGAGA-W1
E.MGHAGH
AL MANGAM
A.TARTOR 1
MOUT
MGAGA-W2
ELFASHN
SAMALUT 1
SAMALUT 2
AL KHARGA
SAMOSTA 2
DER SAMALOT
MATAY
MALAWI
BANIMZAR 1
BANIMZAR 2
WESTFAUM
ASSUIT.INT
MAASARA
DER MOAS
ABUGNDER
BANI GHALEB
EL SHOSHNA
MINIA W.
KIMNFARS
GAM.ASSUIT
ABUKORKS
ABUKSA
ASSIUT 2
BNISWIF-W
RIVA
KOM AHMR
MWAD BENAA
Buses
BANI RAFE
SWIF-E
MINIA IN
MINIA E.
CM.BINSWIF
DEMO MOBILE
W.ELNIL
EL GHRQ
DIROT
DEMO
DEMO-2
AHNASEA
ABO RADY
ABU TEEG
WADISH2
ASSUIT NEW
ELGHNAIM
SODFA
SAHEL SLEEM
ELBATS
QOHAFA
QOHAFA2
KOMOSHEM
ELWASTA
S.WADY CMNT
ABNOB
ELBDARI
SANORS
CM.GAYADA
NASR
KURIMAT
BEBA
D.B.2
D.B.1
QOSHESHA
SAMOSTA 1
0.6 0.7 0.8 0.9 1 1.1 1.2 1.3
Voltage [pu]
EETC2017 - Peak - Nominal Tap Position EETC2017 - Peak - Actual Tap Position
EETC2017 - Peak - Auto-Tapping Vmin (0.95 pu)
Vmax (1.05 pu)
Figure M 4 EETC2017 Peak Model – Voltage Profile at 66 kV Level – Zone 2 – Nominal Tap Position vs.
Actual Tap Position vs. Auto-Tapping
Bus No. Bus Name Voltage [kV] Bus No. Bus Name Voltage [kV] (a) (b) (c)
586 A.DAM220 2501 ASWAN 9 6 9
586 A.DAM220 220 2501 ASWAN 132 9 6 9
586 A.DAM220 2501 ASWAN 9 6 9
*) (a) - Nominal Tap Position. (b) - Actual Tap Position as Measured. (c) - Optimum Tap Position from PSS®E with Automatic Tap Adjustment
Table M 3 EETC2017 Peak Model – Voltage Violations at 132 kV Level – Zone 1 – Nominal Tap Position
vs. Actual Tap Position vs. Auto-Tapping
Table M 4 EETC2017 Peak Model – Voltage Violations at 132 kV Level – Zone 2 – Nominal Tap Position
vs. Actual Tap Position vs. Auto-Tapping
Table M 5 EETC2017 Peak Model – Voltage Violations at 66 kV Level – Zone 1 – Nominal Tap Position
vs. Actual Tap Position vs. Auto-Tapping
Table M 6 EETC2017 Peak Model – Voltage Violations at 66 kV Level – Zone 2 – Nominal Tap Position
vs. Actual Tap Position vs. Auto-Tapping
80
70
60
50
Loading [%]
40
30
20
10
0
0 200 400 600 800 1000 1200 1400
Cumulative Circuit Length [km]
EETC2017 - Peak - Auto Tapping
Figure M 5 EETC2017 Peak Model – Line Loading vs. Circuit Length – 132 kV Level – Zone 1 – Auto-
Tapping
100
90
80
70
Loading [%]
60
50
40
30
20
10
0
0 200 400 600 800 1000 1200
Cumulative Circuit Length [km]
Figure M 6 EETC2017 Peak Model – Line Loading vs. Circuit Length – 132 kV Level – Zone 2 – Auto-
Tapping
140
120
100
Loading [%]
80
60
40
20
0
0 500 1000 1500 2000 2500
Cumulative Circuit Length [km]
Figure M 7 EETC2017 Peak Model – Line Loading vs. Circuit Length – 66 kV Level – Zone 1 – Auto-
Tapping
140
120
100
Loading [%]
80
60
40
20
0
0 500 1000 1500 2000
Cumulative Circuit Length [km]
EETC2017 - Peak - Auto Tapping
Figure M 8 EETC2017 Peak Model – Line Loading vs. Circuit Length – 66 kV Level – Zone 2 – Auto-
Tapping