PVsyst - Simulation report


Stand alone system

Project: simulacion con 4 extractores_VF


Variant: Nueva variante de simulación
Stand alone system with batteries
System power: 1640 Wp
LALAQUIZ - Peru

Author
Project: simulacion con 4 extractores_VF
Variant: Nueva variante de simulación

PVsyst V7.2.0
VC0, Simulation date:
12/09/23 23:47
with v7.2.0

Project summary
Geographical Site Situation Project settings
LALAQUIZ Latitude -5.19 °S Albedo 0.20
Peru Longitude -79.68 °W
Altitude 10 m
Time zone UTC-5

Meteo data
LALAQUIZ
Meteonorm 8.0 (2010-2014), Sat=100% - Sintético

System summary
Stand alone system Stand alone system with batteries

PV Field Orientation User's needs


Fixed plane Daily household consumers
Tilt/Azimuth 20 / 0 ° Constant over the year
Average 6.7 kWh/Day

System information
PV Array Battery pack
Nb. of modules 4 units Technology Lead-acid, sealed, Gel
Pnom total 1640 Wp Nb. of units 14 units
Voltage 24 V
Capacity 1330 Ah

Results summary
Available Energy 2845 kWh/year Specific production 1735 kWh/kWp/year Perf. Ratio PR 71.25 %
Used Energy 2445 kWh/year Solar Fraction SF 99.67 %

Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Detailed User's needs 5
Main results 6
Loss diagram 7
Special graphs 8

12/09/23 PVsyst Licensed to Page 2/8


Project: simulacion con 4 extractores_VF
Variant: Nueva variante de simulación

PVsyst V7.2.0
VC0, Simulation date:
12/09/23 23:47
with v7.2.0

General parameters
Stand alone system Stand alone system with batteries

PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 20 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate

User's needs
Daily household consumers
Constant over the year
Average 6.7 kWh/Day

PV Array Characteristics
PV module Battery
Manufacturer Jinkosolar Manufacturer Sonnenschein
Model JKM410M-72H Model Solar S12/230 A
(Original PVsyst database) Technology Lead-acid, sealed, Gel
Unit Nom. Power 410 Wp Nb. of units 7 in parallel x 2 in series
Number of PV modules 4 units Discharging min. SOC 20.0 %
Nominal (STC) 1640 Wp Stored energy 25.5 kWh
Modules 2 Strings x 2 In series Battery Pack Characteristics
At operating cond. (50°C) Voltage 24 V
Pmpp 1500 Wp Nominal Capacity 1330 Ah (C10)
U mpp 75 V Temperature Fixed 20 °C
I mpp 20 A

Controller Battery Management control


Manufacturer Victron Threshold commands as Battery voltage
Model SmartSolar MPPT 150/45 24V Charging 28.3 / 25.1 V
Technology MPPT converter Corresp. SOC 0.95 / 0.75
Temp coeff. -2.7 mV/°C/Elem. Discharging 23.5 / 24.4 V
Converter Corresp. SOC 0.18 / 0.45
Maxi and EURO efficiencies 98.0 / 96.0 %

Total PV power
Nominal (STC) 2 kWp
Total 4 modules
Module area 8.0 m²
Cell area 7.1 m²

Array losses
Thermal Loss factor DC wiring losses Serie Diode Loss
Module temperature according to irradiance Global array res. 62 mΩ Voltage drop 0.7 V
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC Loss Fraction 0.8 % at STC
Uv (wind) 0.0 W/m²K/m/s

Module Quality Loss Module mismatch losses Strings Mismatch loss


Loss Fraction -0.8 % Loss Fraction 2.0 % at MPP Loss Fraction 0.1 %

12/09/23 PVsyst Licensed to Page 3/8


Project: simulacion con 4 extractores_VF
Variant: Nueva variante de simulación

PVsyst V7.2.0
VC0, Simulation date:
12/09/23 23:47
with v7.2.0

Array losses
IAM loss factor
Incidence effect (IAM): Fresnel AR coating, n(glass)=1.526, n(AR)=1.290

0° 30° 50° 60° 70° 75° 80° 85° 90°


1.000 0.999 0.987 0.962 0.892 0.816 0.681 0.440 0.000

12/09/23 PVsyst Licensed to Page 4/8


Project: simulacion con 4 extractores_VF
Variant: Nueva variante de simulación

PVsyst V7.2.0
VC0, Simulation date:
12/09/23 23:47
with v7.2.0

Detailed User's needs


Daily household consumers, Constant over the year, average = 6.7 kWh/day
Annual values Hourly distribution

Number Power Use Energy


W Hour/day Wh/day
Lámparas (LED o fluo) 3 10W/lamp 12.0 360
Extractores 4 66W/app 24.0 6336
Consumidores en espera 24.0 24
Total daily energy 6720Wh/day

12/09/23 PVsyst Licensed to Page 5/8


Project: simulacion con 4 extractores_VF
Variant: Nueva variante de simulación

PVsyst V7.2.0
VC0, Simulation date:
12/09/23 23:47
with v7.2.0

Main results
System Production
Available Energy 2845 kWh/year Specific production 1735 kWh/kWp/year
Used Energy 2445 kWh/year Performance Ratio PR 71.25 %
Excess (unused) 234 kWh/year Solar Fraction SF 99.67 %
Loss of Load Battery aging (State of Wear)
Time Fraction 0.3 % Cycles SOW 86.9 %
Missing Energy 8 kWh/year Static SOW 90.0 %

Normalized productions (per installed kWp) Performance Ratio PR

Balances and main results

GlobHor GlobEff E_Avail EUnused E_Miss E_User E_Load SolFrac


kWh/m² kWh/m² kWh kWh kWh kWh kWh ratio
January 185.1 152.8 211.2 0.01 0.000 208.3 208.3 1.000
February 155.8 137.8 190.9 0.01 0.000 188.2 188.2 1.000
March 190.3 181.0 246.4 6.10 0.000 208.3 208.3 1.000
April 180.7 185.9 254.4 37.62 0.000 201.6 201.6 1.000
May 180.7 200.6 276.5 42.78 0.000 208.3 208.3 1.000
June 169.1 193.6 270.9 45.09 0.000 201.6 201.6 1.000
July 174.1 196.1 276.3 45.84 0.000 208.3 208.3 1.000
August 176.2 187.2 264.2 33.24 0.000 208.3 208.3 1.000
September 173.4 169.6 238.0 18.55 0.000 201.6 201.6 1.000
October 168.0 153.2 215.7 4.45 0.000 208.3 208.3 1.000
November 166.2 139.9 197.9 0.00 0.000 201.6 201.6 1.000
December 177.7 144.5 202.6 0.01 8.089 200.2 208.3 0.961
Year 2097.5 2042.0 2845.0 233.67 8.089 2444.7 2452.8 0.997

Legends
GlobHor Global horizontal irradiation E_User Energy supplied to the user
GlobEff Effective Global, corr. for IAM and shadings E_Load Energy need of the user (Load)
E_Avail Available Solar Energy SolFrac Solar fraction (EUsed / ELoad)
EUnused Unused energy (battery full)
E_Miss Missing energy

12/09/23 PVsyst Licensed to Page 6/8


Project: simulacion con 4 extractores_VF
Variant: Nueva variante de simulación

PVsyst V7.2.0
VC0, Simulation date:
12/09/23 23:47
with v7.2.0

Loss diagram
2097 kWh/m² Global horizontal irradiation

-0.25% Global incident in coll. plane


-2.40% IAM factor on global

2042 kWh/m² * 8 m² coll. Effective irradiation on collectors

efficiency at STC = 20.50% PV conversion

3368 kWh Array nominal energy (at STC effic.)


-0.37% PV loss due to irradiance level

-9.56% PV loss due to temperature

+0.75% Module quality loss

-2.10% Mismatch loss, modules and strings

-2.06% Ohmic wiring loss

-7.97% Unused energy (battery full)

2696 kWh Effective energy at the output of the array

-3.01% Converter Loss during operation (efficiency)

-0.20% Converter Loss over nominal conv. power


-0.03% Converter Loss due to power threshold
0.00% Converter Loss over nominal conv. voltage
0.00% Converter Loss due to voltage threshold
2611 kWh Converter losses (effic, overload)
Missing Direct use Stored Battery Storage
34.6% 65.4%
energy -0.40% Battery Stored Energy balance
0.33% -3.77% Battery efficiency loss
8.1 kWh
-1.93% Charge/Disch. Current Efficiency Loss

-2.05% Gassing Current (electrolyte dissociation)


-0.82% Battery Self-discharge Current
2445 kWh Energy supplied to the user

2453 kWh Energy need of the user (Load)

12/09/23 PVsyst Licensed to Page 7/8


Project: simulacion con 4 extractores_VF
Variant: Nueva variante de simulación

PVsyst V7.2.0
VC0, Simulation date:
12/09/23 23:47
with v7.2.0

Special graphs
Diagrama entrada/salida diaria

12/09/23 PVsyst Licensed to Page 8/8