兰柯四通阀 eng
兰柯四通阀 eng
1、 Nomenclature
1)
C 10 C 0 0 S
N 10 C 0 0 S
N 20 C 1 0 G
“S“-main slide is nylon; ”G”- main slide is PPS; “A”-specified by customer
Number means size difference of connection tube
“0”- no installation bracket;”1” means installation bracket attached
“C” means manufacturing site, say China.
Capacity of 4-way reversing valve(USRT) with Arabic numbers, e.g. 10 ton,
20ton
Product type number, say “C”, “N” series.
2)
VH1 3 2 0 A
VH15 1 2 0
VH20 3 2 1
“A” –no installation bracket
Size difference of connection tube
Type of pilot valve”NO1CMA”
Number means difference of inner chamber of main slide:”1”-smaller
capacity,”3”-bigger capacity
Product type number and capacity, say “VH15”=30tons, “VH1”
=20tons;VH20=40tons,VH9=50tons,VH91=60tons.
3)
VH3 2 08 5
VH3 2 16 3
Use Arabic numbers to show if customer has request to attach installation bracket, ball
valve reposition, flange connection and swage of connection tubes.
Capacity of 4-way reversing valve which is shown by Arabic numbers:
08=80tons,12=120tons,16=160tons
Type of Pilot valve, say”N02CMA”
Product type of 4-way reversing valve:VH3 Combined valves
4)
V 10–4 XX XX 0 –1 AV
Customer code
Arabic numbers show the type of 4way-reversing valve
Coil information: 0=no coils, 1=24v, 2=120v, 4=208/240v, 5=277v
Size information of connection tube”HP” (inches): XX/16,”XX” of numbers means
ID of connection tube; XX/16,”XX” of letters means OD of connection tube (“I,O,Z”
cannot be used)
Size information of connection tube “E,S,C”(Inches): XX/16,”XX” of numbers
means ID of connection tube; “XX” of letters means OD of connection
tubes,”A”=1/16,”B”=2/16”,etc. (“I,O,Z” cannot be used)
Sequential number of design
Use Arabic numbers to show the capacity of 4-wat reversing valve(USRT).6=6tons,
Page 1 of 4
10=10tons, 12=12tons
Product type number ,say”V”
2、 Specifications
D
Ranco Cooling Cooling TUBE E, S, C System ΔP ΔP Suitable Product
TYPE
Page 2 of 4
V0-406050-1 0.9 / 3.1 1.1 / 3.6 5/16 3/8
V1-408060-1 1.4 / 4.9 1.6 / 5.7 3/8 1/2
V1-406060-2 1.4 / 4.9 1.6 / 5.7 3/8 3/8
V2-408050-1 2/7 2.3 / 8.2 5/16 1/2
V2-408060-2 2/7 2.3 / 8.2 3/8 1/2
V - SERIES
LDK-11 24 VAC
LDK-31 120 VAC
LDK series 1/4" Spade Terminals
LDK-41 208 / 240 VAC
LDK-51 277 VAC
50 / 60 5/4
LDL-11 24 VAC
LDL-31 120 VAC
LDL series Lead Wires on Coil
LDL-41 208 / 240 VAC
LDL-51 277 VAC
Note:
Nominal capacities are given at 130°F Condensing, 45°F Evaporator, 10°F S.H.,10°F Sub-Cool, 64
btu/lbm Δh Evap., 2 PSI.
For Nominal Capacitiy using other Refrigerants Multiply R22 Capacity By: (0.73 for R134A), (0.93 for
R407C).
For Recommended Minimum Capacacities, Multiply Nominal Capacity by 0.5
Page 3 of 4
3. Notes for application
1.The temperature of main body shall be lower than 120℃ when the connection tube is brazed;
2. The axis shall be horizontal after installation.
3. Avoid moisture or impurities entering the valve body;
4. Avoid any impact like dropping onto the floor in order to protect the tube and inside structure. A proper
check is requested prior to application for any valve impacted by outside force.
5. The solenoid coil shall be fixed with bolt and the coil shall stay away from the capillary tubes and valve
body.
6. Only enough flow and pressure difference can switch the valve.
Page 4 of 4