Project Design By: 3.uplift Check

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 71

Sewerage Facilities to 110 Villages: Design, Engineering,

Construction and Commissioning of Sewage Treatment Plants


and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

3.UPLIFT CHECK
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

3.1) UPLIFT CHECK

Total dead Load including superimposed dead load = 12420.00 KN


(Refer static check - Staad File)
Total superimposed dead load-neglected = KN
Total dead Load without superimposed dead load = 12420.00 KN
Unit weight of soil = 0 KN/m3
FGL to BL of Chambers = 0.00 m
Area of offset of Chamber raft = 0.00 m2
FGL to BL of Wetwell = 0 m
Area of offset of WetWell raft = 0.00 m2
Total weight of soil on raft projection = 0.00 KN
Total Load = 9876.00 KN

Total uplift load = 5026.00 KN

Uplift FOS =( 0.9*(Dead load)) / Uplift > 1.25 = 1.77

FOS More than 1.25. OK


Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

Design of Wall W5
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

4.5) Design of W5
The Geometry properties of W5 Wall
The Thickness of Wall W5 is 700mm .
Crack width check is performed for water face i.e. Moment at inward, outward of tank wall.
Wall elements W5 are highlighted as given below
Orientation of STAAD model
Y axis is upward side

STAAD MODEL ----W5 - 400mm Thk.

DESIGN OF WALL- 400mm Thk.

SERVICE CONDITION
Summary of Bending moments (Group No. shaft)
Shear Membrane Bending Moment
SQX SQY SX SY SXY Mx My Mxy
Plate L/C
(local) (local) (local) (local) (local) kNm/m kNm/m kNm/m
Max Qx 11094 104 DL+WET SOIL
414.60 32.00 -283.90 -210.20 -111.30 -130.85 -7.78 11.06
Min Qx 11122 104 DL+WET -423.40
SOIL 34.10 -253.20 -182.90 127.20 -139.88 -11.06 -11.43
Max Qy 11920 162 DL+HL(1-CHANNEL,
66.30 204.70
WW EMPTY))-MWL+WET
-67.80 -82.90 -51.00
SOIL -23.78 7.06 -25.09
Min Qy 10592 155 DL+LL+HL(20.00
CHANNELS,WW
-568.30 -98.10
EMPTY-571.70
& ALL OTHERS
-10.70 FULL)-MWL+WET
-17.17 -156.82
SOIL -0.87
Max Sx 11922 193 DL + LL + -14.30
HL(1 CHANNEL
-8.60 EMPTY
139.50& ALL
1.40
OTHERS
15.70
FULL)-MWL
7.80 -1.32 -2.60
Min Sx 11008 162 DL+HL(1-CHANNEL,
406.40 51.60
WW EMPTY))-MWL+WET
-287.60 -210.40 -127.80
SOIL -120.70 -5.48 22.67
Max Sy 11914 181 1.0*(DL + HL(1
-5.60CHANNEL
0.00 EMPTY
98.50& ALL
10.30
OTHERS
-2.50
FULL)-MWL
3.32+ WL (+Z))
-0.03 0.23
Min Sy 10593 151 DL+LL+HL(FULL)-MWL+WET
10.90 -562.90 -98.10
SOIL -583.5 14.90 -17.30 -156.96 -7.66
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
Max Sxy 10605 151 DL+LL+HL(FULL)-MWL+WET
35.50 -87.90 -78.10
SOIL -276.20 238.10 -14.65 -33.64 -51.29
Min Sxy 10579 151 DL+LL+HL(FULL)-MWL+WET
-41.30 -104.40 -96.40
SOIL -279.80 -271.00 -13.74 -35.96 51.83
Max Mx 11237 104 DL+WET SOIL
-1.00 38.40 -160.00 -211.80 -2.10 125.29 125.67 0.66
Min Mx 11251 153 DL+LL+HL(1
-403.90
CHANNEL
4.00
EMPTY
-246.50
& ALL
-186.00
OTHERS
125.80
FULL)-MWL+WET
-146.02 SOIL
-14.10 3.92
Max My 11108 165 DL+HL(2 CHANNELS,
-1.20 -19.70
WW -152.10
EMPTY &-264.70
ALL OTHERS
-4.40
FULL)-MWL+WET
119.87 135.96
SOIL 0.03
Min My 10592 153 DL+LL+HL(10.30
CHANNEL
-565.20
EMPTY
-98.60
& ALL
-582.50
OTHERS-11.00
FULL)-MWL+WET
-17.45 SOIL
-158.13 -1.08
Max Mxy 10710 104 DL+WET SOIL
70.20 -117.50 -159.30 -290.80 -231.50 2.62 6.06 70.85
Min Mxy 10732 104 DL+WET SOIL
-74.60 -109.20 -131.50 -291.60 202.50 0.84 5.85 -71.17

STRENGTH CONDITION - Bending Moment Criteria


Summary of Bending moments (Group : ShaftBM)
Shear Membrane Bending Moment
SQX SQY SX SY SXY
Mx My Mxy
Plate L/C (local) (local) (local) (local) (local)
kNm/m kNm/m kNm/m
kPa kPa kPa kPa kPa
Max Qx 11094 104 DL+WET SOIL
414.6 32.0 -283.9 -210.2 -111.3 -130.9 -7.8 11.1
Min Qx 11122 104 DL+WET SOIL
-423.4 34.1 -253.2 -182.9 127.2 -139.9 -11.1 -11.4
Max Qy 11920 104 DL+WET SOIL
66.5 204.1 -61.2 -82.9 -51.2 -23.5 7.0 -25.1
Min Qy 10592 106 DL+LL+WET SOIL
0.0 -568.2 -98.0 -570.0 -10.9 -17.2 -156.7 -0.9
Max Sx 11922 111 DL+LL+HL(FULL)-MWL+EL(+X)
-13.7 -8.3 137.1 1.0 14.9 7.5 -1.3 -2.5
Min Sx 11008 104 DL+WET SOIL
406.7 51.6 -287.3 -213.5 -133.6 -120.8 -5.5 22.6
Max Sy 11922 111 DL+LL+HL(FULL)-MWL+EL(+X)
-13.7 -8.3 137.1 1.0 14.9 7.5 -1.3 -2.5
Min Sy 10593 106 DL+LL+WET10.7
SOIL -566.1 -97.3 -570.2 15.4 -17.0 -155.8 -7.5
Max Sxy 10605 106 DL+LL+WET34.5
SOIL -87.6 -83.1 -261.8 235.0 -14.3 -32.5 -51.9
Min Sxy 10579 106 DL+LL+WET
-39.7
SOIL -103.1 -97.0 -266.0 -268.4 -13.6 -34.7 52.4
Max Mx 11237 104 DL+WET SOIL
-1.0 38.4 -160.0 -211.8 -2.1 125.3 125.7 0.7
Min Mx 11251 106 DL+LL+WET
-403.9
SOIL 3.4 -256.4 -188.1 113.6 -145.4 -14.0 3.9
Max My 11108 104 DL+WET SOIL
-1.2 -19.6 -152.6 -263.7 -4.3 119.9 136.0 0.0
Min My 10592 106 DL+LL+WET SOIL
0.0 -568.2 -98.0 -570.0 -10.9 -17.2 -156.7 -0.9
Max Mxy 10710 104 DL+WET SOIL
70.2 -117.5 -159.3 -290.8 -231.5 2.6 6.1 70.9
Min Mxy 10732 104 DL+WET SOIL
-74.6 -109.2 -131.5 -291.6 202.5 0.8 5.8 -71.2
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

STRENGTH CONDITION - Shear Criteria


(Group No. ShaftBM)
Shear Membrane Bending Moment
SQX SQY SX SY SXY
Mx My Mxy
Plate L/C (local) (local) (local) (local) (local)
kNm/m kNm/m kNm/m
kPa kPa kPa kPa kPa
Max Qx 11095 104 DL+WET SOIL
360.4 31.7 -271.3 -205.3 -115.1 -80.3 9.6 14.4
Min Qx 11121 104 DL+WET SOIL
-368.6 33.8 -241.9 -184.5 126.9 -87.8 6.3 -14.9
Max Qy 11877 104 DL+WET SOIL
68.3 149.2 -60.7 -79.6 -35.7 -3.6 12.0 -24.1
Min Qy 10678 106 DL+LL+WET SOIL
0.0 -432.9 -98.9 -514.6 -9.1 16.8 -44.7 -0.9
Max Sx 11880 111 DL+LL+HL(FULL)-MWL+EL(+X)
-7.2 -4.4 116.1 -9.3 9.9 4.9 -0.7 -2.3
Min Sx 11052 104 DL+WET SOIL
356.9 36.5 -272.9 -209.0 -126.4 -76.6 10.8 21.3
Max Sy 11879 111 DL+LL+HL(FULL)-MWL+EL(+X)
-6.7 -7.6 112.2 -6.8 9.6 6.8 -1.5 -1.5
Min Sy 10678 106 DL+LL+WET SOIL
0.0 -432.9 -98.9 -514.6 -9.1 16.8 -44.7 -0.9
Max Sxy 10690 106 DL+LL+WET
-53.9
SOIL -86.7 -122.3 -289.4 225.1 -11.0 -8.9 -67.5
Min Sxy 10665 106 DL+LL+WET80.5
SOIL -30.9 -160.5 -253.3 -250.7 -21.4 -8.1 62.7
Max Mx 11237 104 DL+WET SOIL
-1.0 38.4 -160.0 -211.8 -2.1 125.3 125.7 0.7
Min Mx 11293 106 DL+LL+WET
-346.7
SOIL 9.0 -243.7 -176.4 104.4 -95.1 0.7 9.3
Max My 11108 104 DL+WET SOIL
-1.2 -19.6 -152.6 -263.7 -4.3 119.9 136.0 0.0
Min My 10678 106 DL+LL+WET SOIL
0.0 -432.9 -98.9 -514.6 -9.1 16.8 -44.7 -0.9
Max Mxy 10710 104 DL+WET SOIL
70.2 -117.5 -159.3 -290.8 -231.5 2.6 6.1 70.9
Min Mxy 10732 104 DL+WET SOIL
-74.6 -109.2 -131.5 -291.6 202.5 0.8 5.8 -71.2
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

Summary of forces from Staad


Bending Moments, kNm/m
Wall Type
Service Condition +veMx -veMx +veMy -veMy
W5 125.94 149.94 135.99 159.21

Factored moment is considered by the maximum of Strength and Serviced moments


Strength Condition
Shear Stress,
Bending Moments, kNm/m
Type N/mm2
SQX SQY +veMx -veMx +veMy -veMy
Wall 368.60 432.90 125.94 149.30 135.98 157.63

Maximum Moments of W5
X-DIRECTION (Horz.) Y-DIRECTION (Vert.)

Design for Bending moment Out side Inside Out side Inside

MX MX MY MY

Factored Moment(kN-m) 125.94 149.94 135.99 159.21


2
Grade of concrete,fck (N/mm ) 30 30 30 30

Grade of steel,fy (N/mm2) 400 400 400 400


Width of section,b (mm) 1000 1000 1000 1000
Thickness of section,h(mm) 600 600 600 600
Cover to reinforcement(mm) 60 60 60 60
2
Mu/bd 0.485 0.577 0.485 0.567

Area of Design steel required(mm2) 725 866 754 884


2
Area of Minimum steel required(mm ) 900 900 900 900

Area of steel provided(mm2) 2094 2094 3435 3435


Area of Steel provided OK OK OK OK
Dia of Main rebar(mm) 20 20 20 20
Spacing of main bars 150 150 150 150
Extra Bars dia 16 16

Extra Bars spacing 150 150 150 150

Extra Bars location 1.8m @bottom 1.8m @bottom 1.8m @bottom 1.8m @bottom
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
Effective depth,d(mm) 510 510 530 530
%pt provided 0.411 0.411 0.648 0.648
2
Es(N/mm ) 200000 200000 200000 200000
2
Ece(N/mm ) 27386 27386 27386 27386
m= Es/Ece 7.303 7.303 7.303 7.303
Depth of
Neutral axis 110.54 110.54 139.90 139.90

x=(sqrt((m.Ast)2 + 2xmAst)-mxAst)xd

Lever arm (mm) =d-x/3 473.15 473.15 483.37 483.37

fs (N/mm2) =M/AstxZ 127.09 151.30 81.91 95.89


h (mm) 600 600 600 600

ε1=(fs/Es)*((a'-x)/(d-x)) 0.0008 0.0009 0.0005 0.0006


ε2== 1.5 .b . (h-X)2/(3.Es.As.(d-X)) 0.0007 0.0007 0.0004 0.0004
ε1-ε2 0.0001 0.0002 0.0001 0.0002
acr 92.59 92.59 92.59 92.59

Wcr(mm) 0.015 0.052 0.021 0.041


SAFE SAFE SAFE SAFE

Check for Shear Stress

Maximum
% of steel Ʈc from Table 19
Shear Check shear Check
provided of IS 456-2000
stress, Ʈv

X direction 0.369 0.821 0.607 Ʈc * > Ʈv OK


Y direction 0.433 0.648 0.553 Ʈc * > Ʈv OK

Design Table Explanation for Bending moment


density, W= 10.050 Kn/Cum
B.M for Water,M1 159.205 KN-m
Mu= (M) x 1.5 159.205 KN-m
D= 600.00 mm
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
Cover to steel 60.00 mm
Bar Diameter adopted 20.00 mm
d= 530.00 mm
b= 1000.00 mm
Mu/b/d/d 0.567 Mpa
Steel Grade 500.00 Mpa
Concrete Grade 30.00 Mpa
Refer Mu formula SP16 page 10 Pt= 0.133

Ast= 707 Sqmm/M


Min. steel 0.36% required 900 Sqmm
Required Reinforcement 900 Sqmm
Provided Reinforcement 3141.6 Sqmm

Required Spacing 349.066 mm


Provided Net Spacing 150.00 mm

Provided Rebar T20+T20


Provided Spacing for T20+T20 300.000 mm
OK

Design for shear at Base:-


Pt provided 0.593 %
0.433 Mpa
0.61 Mpa
OK

Design Explanation for Crack Width Cal Table

Applied Service Moment " Ms " = 159.21 KNm


Bar Dia = 20 mm
Maximum Bar Spacing " S " = 150 mm
Area of Reinforcement " As " = 3142 mm2
Grade of Concrete Used (fcu) = 30 N/mm2
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
2
Grade of Steel Used (fy) = 500 N/mm
Width of Section b = 1000 mm
Thickness of Section h = 600.000 mm
Minimum Cover to Tension Reinforcement " CO " = 60 mm
Effective Depth of Section " d " = 530 mm
" acr " = (((S/2)^2 + (CO + DIA/2 )^2)^(1/2)-DIA/2) = 92.59 mm

Distance From the Point Considered to the Surface of Nearest Longitudinal bar
Applied Service Axial Force, T 0.00 KN
Moduli of Elasticity of Concrete " Ec " = 5000x ( sqrt(fcu) ) = 27.39 KN/mm2
Moduli of Elasticity of Steel " Es " = 200.00 KN/mm2
Modular Ratio " a " = (Es/Ec) = 7.30
r = As/bd = 0.00593
a.r = 0.04
Depth of Neutral Axis, " X " = d.a.r(((1+(2/a.r))^0.5)-1) = 134.68 mm
Lever arm " Z " = ( d - X/3) = 485.11 mm
Reinforcement Stress " fs " = Ms/(As*Z)+((Tx0.5)/As) = 104.46 N/mm2
Concrete Stress " fc " = (fs*As)/(0.5*b*X) = 4.87 N/mm2
"e1 " Strain at Soffit of Concrete Slab = (fs/Es)*(h-X)/(d-X) = 0.00061
"e1 " = (fs/Es)*(h-X)/(d-X)

e2= Strain due to stiffening effect of Concrete = 0.00044 mm


e2 = 1.5 .b . (h-X)2/(3.Es.As.(d-X))

em = e1 - e2 = 0.00018 mm

Calculated Crack Width " W " = 0.04360 mm


W = 3.acr. em/(1+2.(acr-CO)/(h-X)) = <<0.1 OK
Crack Width check for Axial Tension
Effective Cover,dc = 90 mm
acr = 117.3 mm
Strain in tensile steel, ϵ1 = fs/Es = 0.0003 mm
Strain due to siffenening effect, ϵ2 = 0.0014 mm
Average strain at the level considered,εm = ε1-ε2 = -0.0011 mm
Surface crack width,Wcr(mm), 3.acr.ϵm = 0.00 mm
= <0.1 mm, Hence Ok
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

Check for Combined Bending & Axial tension

Factored Axial Tensile stress = 137.10 N/mm2


Factored Axial Tensile stress = 137100.00 kN/sqm
Factored Moment Mu = 7.47 kNm
Ast = 33 Sqmm/M
Tu = T x D = 82260.00 kN
Ast, req on both faces = 236379.31 mm2
Ast, req on one side for Axial Tension = 118189.66 mm2
Ast, req on one side for Flexure = 33.00 mm2
=(236379.31/2+33) = 118222.66 mm2
Minimum Steel 0.24 %age = 720 mm2
Maximum of above = 118223 mm2
Dia Rebar = 20 mm
Spacing of rebar, S = 150 mm
Provided T20-150 B.Faces = 2094.40 mm2
2094.4>118222.655

Steel Provided is = Not Ok


Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment
Plants and Intermediate Sewage Pumping Stations with
Design
Project Operation & Maintenance thereof for Seven Years [Works VM
by
- A] and Procurement and Construction of Main Sewers
including Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Checked
Doc. Title VM
Screen, Wet Well, Pumping Station & Flowmeter chamber by
Apprd.
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 AMG
by
JV

Design of Wall
W2
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment
Plants and Intermediate Sewage Pumping Stations with
Design
Project Operation & Maintenance thereof for Seven Years [Works VM
by
- A] and Procurement and Construction of Main Sewers
including Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Checked
Doc. Title VM
Screen, Wet Well, Pumping Station & Flowmeter chamber by
Apprd.
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 AMG
by
JV

4.2) Design of W2
The Geometry properties of W2 Wall
The Thickness of Wall W2 is 400mm .
Crack width check is performed for water face i.e. Moment at inward, outward of tank wall.
Wall elements W2 are highlighted as given below
Orientation of STAAD model
Y axis is upward side

STAAD MODEL ----W2 - 500mm Thk.

DESIGN OF WALL- 400mm Thk.

SERVICE CONDITION
Summary of Bending moments (Group No.801)
Shear Membrane Bending Moment
SQX SQY SX SY SXY
Mx My Mxy
Plate L/C (local) (local) (local) (local) (local)
kNm/m kNm/m kNm/m
N/mm2 N/mm2 N/mm2 N/mm2 N/mm2
Max Qx 14450 180 1.0*(DL +0.200
HL(1 CHANNEL
0.000 0.100
EMPTY0.000
& ALL OTHERS
0.000 FULL)-MWL
7.269 0.301
+ WL (-X))
7.044
Min Qx 14447 180 1.0*(DL +
-0.100
HL(1 CHANNEL
0.100 0.100
EMPTY0.000
& ALL OTHERS
0.000 -6.532
FULL)-MWL2.874
+ WL (-X))
-3.024
Max Qy 14448 180 1.0*(DL +0.100
HL(1 CHANNEL
0.100 0.100
EMPTY0.000
& ALL OTHERS
0.000 -11.918
FULL)-MWL1.940
+ WL (-X))
4.183
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment
Plants and Intermediate Sewage Pumping Stations with
Design
Project Operation & Maintenance thereof for Seven Years [Works VM
by
- A] and Procurement and Construction of Main Sewers
including Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Checked
Doc. Title VM
Screen, Wet Well, Pumping Station & Flowmeter chamber by
Apprd.
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 AMG
by
JV
Min Qy 14451 153 DL+LL+HL(1
0.100
CHANNEL
-0.100 EMPTY
0.300 &0.100
ALL OTHERS
0.200 FULL)-MWL+WET
26.159 -1.491SOIL5.641
Max Sx 14452 153 DL+LL+HL(1
-0.100
CHANNEL
-0.100 EMPTY
0.400 &0.100
ALL OTHERS
0.100 FULL)-MWL+WET
23.334 -2.873SOIL
-2.290
Min Sx 14447 162 DL+HL(1-CHANNEL,
0.100 0.000
WW-0.300
EMPTY))-MWL+WET
-0.100 0.100SOIL6.156 -0.985 3.690
Max Sy 13494 162 DL+HL(1-CHANNEL,
0.000 0.000
WW0.000
EMPTY))-MWL+WET
0.300 0.100SOIL
-0.709 -3.285 -0.732
Min Sy 13501 193 DL + LL +0.000
HL(1 CHANNEL
0.000 0.000
EMPTY
-0.400
& ALL OTHERS
0.100 -0.578
FULL)-MWL
-1.763 -0.829
Max Sxy 13485 154 DL+LL+HL(INLET,OUTLET
0.000 0.000 0.100
EMPTY
-0.100
& ALL OTHERS
0.300 -0.774
FULL)-MWL+WET
-5.797 SOIL
-1.132
Min Sxy 13505 162 DL+HL(1-CHANNEL,
0.000 0.000
WW0.100
EMPTY))-MWL+WET
0.000 -0.200SOIL
-0.408 -0.849 0.137
Max Mx 14451 153 DL+LL+HL(1
0.100
CHANNEL
-0.100 EMPTY
0.300 &0.100
ALL OTHERS
0.200 FULL)-MWL+WET
26.159 -1.491SOIL5.641
Min Mx 14466 153 DL+LL+HL(1
0.100
CHANNEL
0.100 EMPTY
0.200 &0.000
ALL OTHERS
-0.100 FULL)-MWL+WET
-20.537 0.267SOIL3.760
Max My 14132 193 DL + LL +0.000
HL(1 CHANNEL
0.000 0.200
EMPTY
-0.100
& ALL OTHERS
0.000 20.464
FULL)-MWL
7.744 0.681
Min My 13488 153 DL+LL+HL(1
0.000
CHANNEL
0.000 EMPTY
0.100 &0.100
ALL OTHERS
0.300 FULL)-MWL+WET
-1.111 -6.378SOIL
-1.457
Max Mxy 14419 180 1.0*(DL +0.000
HL(1 CHANNEL
0.000 0.200
EMPTY0.000
& ALL OTHERS
0.000 FULL)-MWL
7.738 -0.577
+ WL (-X))
10.357
Min Mxy 14398 153 DL+LL+HL(1
0.000
CHANNEL
0.000 EMPTY
0.200 &0.000
ALL OTHERS
0.000 FULL)-MWL+WET
-2.219 0.194SOIL
-4.683

STRENGTH CONDITION - Bending Moment Criteria


Summary of Bending moments (Group No. 801)
Shear Membrane Bending Moment
SQX SQY SX SY SXY
Mx My Mxy
Plate L/C (local) (local) (local) (local) (local)
kNm/m kNm/m kNm/m
N/mm2 N/mm2 N/mm2 N/mm2 N/mm2
Max Qx 14467 623 DL + LL +0.800
HL(1 CHANNEL
0.200 0.100
EMPTY
-0.200
& ALL OTHERS
0.000 -62.802
FULL)-TOW
-28.754 55.499
Min Qx 14450 632 DL + HL(1-CHANNEL,
-1.000 0.400WW
-0.100
EMPTY)-TOW
-0.100 -0.100 -57.109 -52.838 -53.900
Max Qy 14451 632 DL + HL(1-CHANNEL,
-0.600 0.900WW
-0.100
EMPTY)-TOW
-0.100 -0.100 -111.836 -26.016 -41.483
Min Qy 13495 623 DL + LL +0.000
HL(1 CHANNEL
-0.700 -0.100
EMPTY
-0.600
& ALL OTHERS
0.200 -13.853
FULL)-TOW
-179.088 0.612
Max Sx 14447 621 DL + LL -0.700
+ HL(FULL)-TOW
0.300 0.700 0.100 -0.100 -46.907 15.431 -24.173
Min Sx 13912 621 DL + LL +0.000
HL(FULL)-TOW
0.000 -0.500 -0.600 0.600 -10.640 -6.600 0.497
Max Sy 13494 562 1.5*(DL +0.000
HL(1-CHANNEL,
0.000 0.100
WW EMPTY))-MWL
0.500 0.100+ WET
-1.064
SOIL) -4.928 -1.098
Min Sy 13496 621 DL + LL +0.000
HL(FULL)-TOW
0.000 -0.200 -1.400 0.200 0.962 2.370 -5.519
Max Sxy 13538 621 DL + LL +0.000
HL(FULL)-TOW
0.000 -0.200 -0.700 0.800 1.498 5.039 -7.014
Min Sxy 13513 621 DL + LL +0.000
HL(FULL)-TOW
0.000 -0.200 -0.600 -0.600 4.284 -2.568 4.300
Max Mx 13960 623 DL + LL +0.000
HL(1 CHANNEL
0.000 -0.100
EMPTY
-0.200
& ALL OTHERS
0.100 159.093
FULL)-TOW
160.861 3.408
Min Mx 13974 623 DL + LL -0.500
+ HL(1 CHANNEL
0.000 -0.300
EMPTY
-0.400
& ALL OTHERS
0.300 -169.654
FULL)-TOW
-14.794 8.000
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment
Plants and Intermediate Sewage Pumping Stations with
Design
Project Operation & Maintenance thereof for Seven Years [Works VM
by
- A] and Procurement and Construction of Main Sewers
including Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Checked
Doc. Title VM
Screen, Wet Well, Pumping Station & Flowmeter chamber by
Apprd.
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 AMG
by
JV
Max My 13867 623 DL + LL +0.000
HL(1 CHANNEL
0.000 -0.100
EMPTY
-0.300
& ALL OTHERS
0.100 153.029
FULL)-TOW
172.594 2.168
Min My 13495 623 DL + LL +0.000
HL(1 CHANNEL
-0.700 -0.100
EMPTY
-0.600
& ALL OTHERS
0.200 -13.853
FULL)-TOW
-179.088 0.612
Max Mxy 13577 623 DL + LL +0.100
HL(1 CHANNEL
-0.100 -0.200
EMPTY
-0.400
& ALL -0.100
OTHERS FULL)-TOW
8.012 11.437 90.419
Min Mxy 13599 623 DL + LL -0.100
+ HL(1 CHANNEL
-0.100 -0.300
EMPTY
-0.400
& ALL OTHERS
0.500 FULL)-TOW
5.370 10.113 -87.704

STRENGTH CONDITION - Shear Criteria


Summary of Bending moments (Group No. 1003)
Shear Membrane Bending Moment
SQX SQY SX SY SXY
Mx My Mxy
Plate L/C (local) (local) (local) (local) (local)
kNm/m kNm/m kNm/m
N/mm2 N/mm2 N/mm2 N/mm2 N/mm2
Max Qx 13854 632 DL + HL(1-CHANNEL,
0.400 0.000WW
-0.200
EMPTY)-TOW
-0.200 -0.100 -98.875 12.576 16.338
Min Qx 13880 623 DL + LL -0.500
+ HL(1 CHANNEL
0.000 -0.400
EMPTY
-0.400
& ALL OTHERS
0.300 -100.076
FULL)-TOW
10.089 -16.111
Max Qy 14389 632 DL + HL(1-CHANNEL,
0.100 0.300WW
0.000
EMPTY)-TOW
-0.100 -0.100 -30.773 20.854 -42.009
Min Qy 13557 623 DL + LL +0.000
HL(1 CHANNEL
-0.500 -0.100
EMPTY
-0.600
& ALL OTHERS
0.200 27.614
FULL)-TOW
-44.603 0.524
Max Sx 13916 553 1.5*(DL +0.000
LL + HL(1
0.000
CHANNEL
0.500 EMPTY
0.000 & ALL
0.300
OTHERS
14.514
FULL)-MWL
6.386 + W.S.)
3.629
Min Sx 13880 621 DL + LL +0.000
HL(FULL)-TOW
0.000 -0.500 -0.600 0.600 -8.804 -5.857 -0.321
Max Sy 13556 562 1.5*(DL +0.000
HL(1-CHANNEL,
0.000 0.100
WW EMPTY))-MWL
0.400 0.100+ WET
-0.949
SOIL) -3.602 -1.432
Min Sy 13557 621 DL + LL +0.000
HL(FULL)-TOW
0.000 -0.200 -1.300 0.100 1.345 1.599 -6.344
Max Sxy 13569 621 DL + LL +0.000
HL(FULL)-TOW
0.000 -0.200 -0.700 0.800 0.493 2.098 -6.286
Min Sxy 13544 621 DL + LL +0.000
HL(FULL)-TOW
0.000 -0.200 -0.600 -0.600 5.696 -2.490 4.418
Max Mx 13960 623 DL + LL +0.000
HL(1 CHANNEL
0.000 -0.100
EMPTY
-0.200
& ALL OTHERS
0.100 159.093
FULL)-TOW
160.861 3.408
Min Mx 14004 623 DL + LL -0.400
+ HL(1 CHANNEL
0.000 -0.300
EMPTY
-0.300
& ALL OTHERS
0.200 -108.13
FULL)-TOW
3.767 15.228
Max My 13867 623 DL + LL +0.000
HL(1 CHANNEL
0.000 -0.100
EMPTY
-0.300
& ALL OTHERS
0.100 153.029
FULL)-TOW
172.594 2.168
Min My 13557 623 DL + LL +0.000
HL(1 CHANNEL
-0.500 -0.100
EMPTY
-0.600
& ALL OTHERS
0.200 27.614
FULL)-TOW
-44.603 0.524
Max Mxy 13577 623 DL + LL +0.100
HL(1 CHANNEL
-0.100 -0.200
EMPTY
-0.400
& ALL -0.100
OTHERS FULL)-TOW
8.012 11.437 90.419
Min Mxy 13599 623 DL + LL -0.100
+ HL(1 CHANNEL
-0.100 -0.300
EMPTY
-0.400
& ALL OTHERS
0.500 FULL)-TOW
5.370 10.113 -87.704
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment
Plants and Intermediate Sewage Pumping Stations with
Design
Project Operation & Maintenance thereof for Seven Years [Works VM
by
- A] and Procurement and Construction of Main Sewers
including Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Checked
Doc. Title VM
Screen, Wet Well, Pumping Station & Flowmeter chamber by
Apprd.
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 AMG
by
JV

Summary of forces from Staad


Bending Moments, kNm/m
Wall Type
Service Condition +veMx -veMx +veMy -veMy
W2 31.80 24.30 8.43 7.84

Strength Condition
Shear Stress,
2 Bending Moments, kNm/m
Type N/mm
SQX SQY +veMx -veMx +veMy -veMy
Wall 0.50 0.50 162.50 177.65 174.76 179.70

Maximum Moments of W2
X-DIRECTION (Horz.) Y-DIRECTION (Vert.)

Design for Bending moment Inside Out side Inside Out side

MX MX MY MY
Factored Moment(kN-m) 162.50 177.65 174.76 179.70
2
Grade of concrete,fck (N/mm ) 30 30 30 30
2
Grade of steel,fy (N/mm ) 500 500 500 500
Width of section,b (mm) 1000 1000 1000 1000
Thickness of section,h(mm) 450 450 450 450
Cover to reinforcement(mm) 60 60 60 60
2
Mu/bd 1.126 1.231 1.349 1.387
Area of Design steel required(mm2) 1031 1133 1182 1218
Area of Minimum steel required(mm 540 540 540 540
Area of steel provided(mm2) 2094 2094 2094 2094
Area of Steel provided OK OK OK OK
Dia of Main rebar(mm) 20 20 20 20
Spacing of main bars 150 150 150 150
Effective depth,d(mm) 380 380 360 360
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment
Plants and Intermediate Sewage Pumping Stations with
Design
Project Operation & Maintenance thereof for Seven Years [Works VM
by
- A] and Procurement and Construction of Main Sewers
including Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Checked
Doc. Title VM
Screen, Wet Well, Pumping Station & Flowmeter chamber by
Apprd.
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 AMG
by
JV
%pt provided 0.551 0.551 0.582 0.582
Es(N/mm2) 200000 200000 200000 200000
2
Ece(N/mm ) 27386 27386 27386 27386
m= Es/Ece 7.303 7.303 7.303 7.303
Depth of
93.60 93.60 90.75 90.75
Neutral axis
x=(sqrt((m.Ast)2 + 2xmAst)-mxAst)xd
Lever arm (mm) =d-x/3 348.80 348.80 329.75 329.75
2
fs (N/mm ) =M/AstxZ 43.53 33.26 12.20 11.34
h (mm) 450 450 450 450

ε1=(fs/Es)*((a'-x)/(d-x)) 0.0003 0.0002 0.0001 0.0001


ε2= 1.5 .b . (h-X)2/(3.Es.As.(d-X)) 0.0005 0.0005 0.0006 0.0006
ε1-ε2 -0.0003 -0.0003 -0.0005 -0.0005
acr 92.59 92.59 92.59 92.59

Wcr(mm) 0.001 0.001 0.001 0.001


SAFE SAFE SAFE SAFE
Provide T20-150 mmc/c up to 2.0 m height. Then proovide T16-150 mm/c for thr rest of height.
Check for Shear Stress

Maximum Ʈc from Table


% of steel
Shear Check shear 19 of IS 456- Check
provided
stress, Ʈv 2000

X direction 0.500 0.551 0.52 Ʈc * > Ʈv OK


Y direction 0.500 0.582 0.529 Ʈc * > Ʈv OK

Design Table Explanation for Bending moment


density, W= 10.050 Kn/Cum
B.M for Water,M1 31.800 KN-m
Mu= (M) x 1.5 179.700 KN-m
D= 450.00 mm
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment
Plants and Intermediate Sewage Pumping Stations with
Design
Project Operation & Maintenance thereof for Seven Years [Works VM
by
- A] and Procurement and Construction of Main Sewers
including Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Checked
Doc. Title VM
Screen, Wet Well, Pumping Station & Flowmeter chamber by
Apprd.
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 AMG
by
JV
Cover to steel 60.00 mm
Bar Diameter 20.00 mm
d= 380.00 mm
b= 1000.00 mm
Mu/b/d/d 1.244 Mpa
Steel Grade 500.00 Mpa
Concrete Grade 30.00 Mpa
Refer Mu formula SP16 page 10 Pt= 0.301

Ast= 1144 Sqmm/M


Min. steel 0.24% required 540 Sqmm
Required Reinforcement 1144 Sqmm
Provided Reinforcement 2094.4 Sqmm
Required Spacing 274.615 mm
Provided Net Spacing 150.00 mm

Provided Rebar T20+T20


Provided Spacing for T20+T20 300.000 mm
OK

Design for shear at Base:-


Pt provided 0.551 %
0.50 Mpa
0.53 Mpa
OK

Design Explanation for Crack Width Cal Table

Applied Service Moment " Ms " = 31.80 KNm


Bar Dia = 20 mm
Maximum Bar Spacing " S " = 150 mm
2
Area of Reinforcement " As " = 2094 mm
Grade of Concrete Used (fcu) = 30 N/mm2
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment
Plants and Intermediate Sewage Pumping Stations with
Design
Project Operation & Maintenance thereof for Seven Years [Works VM
by
- A] and Procurement and Construction of Main Sewers
including Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Checked
Doc. Title VM
Screen, Wet Well, Pumping Station & Flowmeter chamber by
Apprd.
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 AMG
by
JV
Grade of Steel Used (fy) = 500 N/mm2
Width of Section b = 1000 mm
Thickness of Section h = 450.000 mm
Minimum Cover to Tension Reinforcement " CO " = 60 mm
Effective Depth of Section " d " = 380 mm
" acr " = (((S/2)^2 + (CO + DIA/2 )^2)^(1/2)-DIA/2) = 92.59 mm
Distance From the Point Considered to the Surface of Nearest Longitudinal bar
Applied Service Axial Force, T 0.00 KN
Moduli of Elasticity of Concrete " Ec " = 5000x ( sqrt(fcu) ) = 27.39 KN/mm2
Moduli of Elasticity of Steel " Es " = 200.00 KN/mm2
Modular Ratio " a " = (Es/Ec) = 7.30
r = As/bd = 0.00551
a.r = 0.04
Depth of Neutral Axis, " X " = d.a.r(((1+(2/a.r))^0.5)-1) = 93.60 mm
Lever arm " Z " = ( d - X/3) = 348.80 mm
Reinforcement Stress " fs " = Ms/(As*Z)+((Tx0.5)/As) = 43.53 N/mm2
Concrete Stress " fc " = (fs*As)/(0.5*b*X) = 1.95 N/mm2
"e1 " Strain at Soffit of Concrete Slab = (fs/Es)*(h-X)/(d-X) = 0.00027
"e1 " = (fs/Es)*(h-X)/(d-X)
e2= Strain due to stiffening effect of Concrete = 0.00053 mm
e2 = 1.5 .b . (h-X)2/(3.Es.As.(d-X))
em = e1 - e2 = -0.00026 mm
Calculated Crack Width " W " = -0.06071 mm
W = 3.acr.em/(1+2.(acr-CO)/(h-X)) = <<<<0.1 OK

Crack Width check for Axial Tension


Effective Cover,dc = 90 mm
acr = 117.3 mm
Strain in tensile steel, ϵ1 = fs/Es = 0.0000 mm
Strain due to siffenening effect, ϵ2 = 0.0011 mm
Average strain at the level considered,εm = ε1-ε2 = -0.0011 mm
Surface crack width,Wcr(mm), 3.acr.ϵm = 0.00 mm
= <0.1 mm, Hence Ok
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment
Plants and Intermediate Sewage Pumping Stations with
Design
Project Operation & Maintenance thereof for Seven Years [Works VM
by
- A] and Procurement and Construction of Main Sewers
including Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Checked
Doc. Title VM
Screen, Wet Well, Pumping Station & Flowmeter chamber by
Apprd.
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 AMG
by
JV

Check for Combined Bending & Axial tension

Factored Axial Tensile stress = 0.70 N/mm2


Factored Axial Tensile stress = 700.00 kN/sqm
Factored Moment Mu = 15.43 kNm
Ast = 94 Sqmm/M
Tu = T x D = 315.00 kN
Ast, req on both faces = 724.14 mm2
2
Ast, req on one side for Axial Tension = 362.07 mm
Ast, req on one side for Flexure = 94.00 mm2
=(724.14/2+94) = 456.07 mm2
2
Minimum Steel 0.24 %age = 540 mm
2
Maximum of above = 540 mm
Dia Rebar = 20 mm
Spacing of rebar, S = 150 mm
Provided T20-150 B.Faces = 2094.40 mm2
2094.4>540
Steel Provided is = OK
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

Design of Wall W3
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

4.3) Design of W3
The Geometry properties of W3 Wall
The Thickness of Wall W3 is 400mm .
Crack width check is performed for water face i.e. Moment at inward, outward of tank wall.
Wall elements W3 are highlighted as given below
Orientation of STAAD model
Y axis is upward side

STAAD MODEL ----W3 - 400mm Thk.

DESIGN OF WALL- 400mm Thk.

SERVICE CONDITION
Summary of Bending moments (Group No. 701)
Shear Membrane Bending Moment
SQX SQY SX SY SXY Mx kN- My kN- Mxy kN-
Plate L/C
(local) (local) (local) (local) (local) m/m m/m m/m
Max Qx 6059 128 DL+LL+WET
0.292
SOIL+EL(-Z)
-0.025 -0.913 -0.424 0.857 -22.962 -1.911 -1.684
Min Qx 6052 104 DL+WET SOIL
-0.276 -0.007 -0.484 0.012 0.283 -15.578 -0.388 0.071
Max Qy 6015 154 DL+LL+HL(INLET,OUTLET
0.004 0.346 EMPTY
-0.101 & -0.538
ALL OTHERS
0.655
FULL)-MWL+WET
0.162 -26.244
SOIL -0.056
Min Qy 6049 154 DL+LL+HL(INLET,OUTLET
0.281 -0.044 EMPTY
-0.534 & -0.361
ALL OTHERS
0.784
FULL)-MWL+WET
-19.486 0.582
SOIL -4.573
Max Sx 6159 125 DL+LL+WET
0.201
SOIL+EL(+X)
-0.03 0.881 -0.171 -0.085 -6.701 -12.002 -5.869
Min Sx 6079 154 DL+LL+HL(INLET,OUTLET
0.28 0.011 EMPTY
-2.184 & ALL
0.051
OTHERS
0.004
FULL)-MWL+WET
-21.955 -7.032
SOIL 1.897
Max Sy 6079 114 DL+LL+HL(FULL)-MWL+EL(-Z)
0.038 0.005 -0.992 0.335 0.139 -6.66 -6.398 -0.187
Min Sy 6015 154 DL+LL+HL(INLET,OUTLET
0.004 0.346 EMPTY
-0.101 & -0.538
ALL OTHERS
0.655
FULL)-MWL+WET
0.162 -26.244
SOIL -0.056
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
Max Sxy 6059 154 DL+LL+HL(INLET,OUTLET
0.291 -0.027 EMPTY
-0.924 & -0.409
ALL OTHERS
0.927
FULL)-MWL+WET
-23.484 -2.05
SOIL -1.855
Min Sxy 6099 125 DL+LL+WET
0.271
SOIL+EL(+X)
0.035 -1.443 -0.268 -0.397 -18.501 -3.451 4.886
Max Mx 6055 128 DL+LL+WET
-0.008
SOIL+EL(-Z)
-0.023 -0.731 -0.013 0.512 34.515 14.37 -1.452
Min Mx 6069 154 DL+LL+HL(INLET,OUTLET
0.279 -0.007 EMPTY
-1.906 & -0.073
ALL OTHERS
0.785
FULL)-MWL+WET
-23.756 -6.249
SOIL -0.251
Max My 6045 104 DL+WET SOIL
-0.011 0.006 -0.52 -0.15 0.482 31.959 18.035 -0.563
Min My 6015 154 DL+LL+HL(INLET,OUTLET
0.004 0.346 EMPTY
-0.101 & -0.538
ALL OTHERS
0.655
FULL)-MWL+WET
0.162 -26.244
SOIL -0.056
Max Mxy 6023 104 DL+WET SOIL
-0.043 0.126 -0.19 -0.236 0.365 5.274 0.362 10.195
Min Mxy 6028 154 DL+LL+HL(INLET,OUTLET
0.043 0.113 EMPTY
-0.172 & -0.354
ALL OTHERS
0.787
FULL)-MWL+WET
4.725 1.002
SOIL -12.245

STRENGTH CONDITION - Bending Moment Criteria


Summary of Bending moments (Group No. 701)
Shear Membrane Bending Moment
SQX SQY SX SY SXY
Mx My Mxy
Plate L/C (local) (local) (local) (local) (local)
kNm/m kNm/m kNm/m
kN/m2 kN/m2 kN/m2 kN/m2 kN/m2
Max Qx 8746 553 1.5*(DL + LL
179.7
+ HL(1 -42.8
CHANNEL479.5
EMPTY349.4
& ALL OTHERS
-8.1 FULL)-MWL
4.86 23.174
+ W.S.) -4.422
Min Qx 8921 504 1.5*(DL + WET
-168.7
SOIL) -4.4 -119.7 -294.7 38.7 -29.795 -14.402 -0.616
Max Qy 9017 554 1.5*(DL+LL+HL(INLET,OUTLET
5.2 321 -74.8
EMPTY
-422.7
& ALL OTHERS
14.3 FULL)-MWL
3.336 +40.11
W.S.) -5.851
Min Qy 9020 631 DL + HL(FULL)-TOW
-4.1 -201.4 26.9 -181.2 -93.6 3.257 -4.422 -9.435
Max Sx 8746 621 DL + LL + HL(FULL)-TOW
-54.3 28 697.3 396.8 -183.9 8.576 7.192 2.925
Min Sx 8626 621 DL + LL + HL(FULL)-TOW
-50 1.6 -584.9 0.1 17.7 -2.703 -0.139 -1.584
Max Sy 8770 621 DL + LL + HL(FULL)-TOW
-57.1 27.9 351.8 563.7 -408.7 16.627 7.656 6.189
Min Sy 9017 554 1.5*(DL+LL+HL(INLET,OUTLET
5.2 321 -74.8
EMPTY
-422.7
& ALL OTHERS
14.3 FULL)-MWL
3.336 +40.11
W.S.) -5.851
Max Sxy 8682 621 DL + LL + HL(FULL)-TOW
14.9 9.9 -45 -18.4 228.1 7.987 0.71 -5.86
Min Sxy 8770 621 DL + LL + HL(FULL)-TOW
-57.1 27.9 351.8 563.7 -408.7 16.627 7.656 6.189
Max Mx 8901 621 DL + LL + HL(FULL)-TOW
-51.8 5.6 17.3 140.1 -195.2 46.269 14.811 0.795
Min Mx 8898 553 1.5*(DL + LL
-91.8
+ HL(1 -10.7
CHANNEL
-83.5
EMPTY
-253.3
& ALL OTHERS
32.5 FULL)-MWL
-46.124 +
-16.22
W.S.) 3.714
Max My 9017 554 1.5*(DL+LL+HL(INLET,OUTLET
5.2 321 -74.8
EMPTY
-422.7
& ALL OTHERS
14.3 FULL)-MWL
3.336 +40.11
W.S.) -5.851
Min My 8961 504 1.5*(DL + WET
87.8
SOIL) 29.4 -164.6 -242 31.3 -38.369 -22.117 7.588
Max Mxy 8998 554 1.5*(DL+LL+HL(INLET,OUTLET
69.4 107.9 -129.5
EMPTY-309
& ALL OTHERS
114.1 -12.218
FULL)-MWL -5.717
+ W.S.) 16.908
Min Mxy 9021 631 DL + HL(FULL)-TOW
-11.2 -165.4 32.9 -148.1 -82.5 2.334 -3.152 -15.035
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

STRENGTH CONDITION - Shear Criteria


Summary of Bending moments (Group No. 701)
Shear Membrane Bending Moment
SQX SQY SX SY SXY
Mx kN- My kN- Mxy kN-
Plate L/C (local) (local) (local) (local) (local)
m/m m/m m/m
N/mm2 N/mm2 N/mm2 N/mm2 N/mm2
Max Qx 6059 554 1.5*(DL+LL+HL(INLET,OUTLET
0.436 -0.041 -1.385EMPTY
-0.613
& ALL OTHERS
1.39 -35.227
FULL)-MWL -3.074
+ W.S.) -2.782
Min Qx 6052 504 1.5*(DL + WET
-0.414
SOIL)
-0.011 -0.726 0.018 0.424 -23.368 -0.582 0.106
Max Qy 6025 554 1.5*(DL+LL+HL(INLET,OUTLET
-0.005 0.322 -0.264
EMPTY
-0.648
& ALL OTHERS
0.991 FULL)-MWL
17.918 +1.481
W.S.) -0.148
Min Qy 6026 635 DL + HL(2-0.003
CHANNELS,
-0.127
WW EMPTY
0.117 &-0.235
ALL OTHERS
0.269FULL)-TOW
-10.758 -4.597 0.633
Max Sx 6159 554 1.5*(DL+LL+HL(INLET,OUTLET
0.32 -0.044 1.253
EMPTY
-0.257
& ALL OTHERS
-0.122 -14.364
FULL)-MWL -18.01
+ W.S.) -8.974
Min Sx 6079 554 1.5*(DL+LL+HL(INLET,OUTLET
0.42 0.017 -3.276
EMPTY
0.076
& ALL OTHERS
0.006 -32.932
FULL)-MWL-10.548
+ W.S.) 2.845
Max Sy 6079 624 DL + LL + HL(INLET,OUTLET
0.047 0.007 -1.125
EMPTY &0.452
ALL OTHERS
0.204 FULL)-TOW
-8.15 -8.225 0.002
Min Sy 6059 562 1.5*(DL + HL(1-CHANNEL,
0.428 -0.027 WW
-1.248
EMPTY))-MWL
-0.763 +0.947
WET SOIL)
-30.814 -1.798 -1.924
Max Sxy 6059 554 1.5*(DL+LL+HL(INLET,OUTLET
0.436 -0.041 -1.385
EMPTY
-0.613
& ALL OTHERS
1.39 -35.227
FULL)-MWL -3.074
+ W.S.) -2.782
Min Sxy 6099 553 1.5*(DL + LL
0.418
+ HL(1 0.056
CHANNEL
-2.227
EMPTY
-0.282
& ALL OTHERS
-0.571 FULL)-MWL
-30.815 +
-6.371
W.S.) 7.375
Max Mx 6055 504 1.5*(DL + WET
-0.018
SOIL)
-0.034 -1.042 -0.064 0.605 51.618 21.9 -1.441
Min Mx 6069 554 1.5*(DL+LL+HL(INLET,OUTLET
0.418 -0.011 -2.858
EMPTY-0.11
& ALL OTHERS
1.178 -35.634
FULL)-MWL -9.373
+ W.S.) -0.377
Max My 6045 504 1.5*(DL + WET
-0.017
SOIL)
0.009 -0.78 -0.225 0.723 47.938 27.053 -0.845
Min My 6158 594 1.5*(DL + LL
-0.132
+ HL(INLET,OUTLET
-0.047 0.312EMPTY
0.112
& ALL
-0.052
OTHERS-4.027
FULL)-MWL)
-19.192 8.361
Max Mxy 6023 504 1.5*(DL + WET
-0.065
SOIL)
0.189 -0.285 -0.354 0.547 7.912 0.543 15.292
Min Mxy 6028 554 1.5*(DL+LL+HL(INLET,OUTLET
0.065 0.169 -0.258
EMPTY-0.53
& ALL OTHERS
1.181 FULL)-MWL
7.088 +1.503
W.S.) -18.368
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

Summary of forces from Staad


Bending Moments, kNm/m
Wall Type
Service Condition +veMx -veMx +veMy -veMy
W3 35.97 24.01 18.60 26.30

Factored moment is considered by the maximum of Strength and Serviced moments


Strength Condition
Shear Stress,
Bending Moments, kNm/m
Type N/mm2
SQX SQY +veMx -veMx +veMy -veMy
Wall 0.44 0.32 47.06 49.84 45.96 29.71

Maximum Moments of W3
X-DIRECTION (Horz.) Y-DIRECTION (Vert.)

Design for Bending moment Inside Out side Inside Out side

MX MX MY MY

Factored Moment(kN-m) 47.06 49.84 45.96 29.71


2
Grade of concrete,fck (N/mm ) 30 30 30 30

Grade of steel,fy (N/mm2) 500 500 500 500


Width of section,b (mm) 1000 1000 1000 1000
Thickness of section,h(mm) 400 400 400 400
Cover to reinforcement(mm) 60 60 60 60

Mu/bd2 0.472 0.500 0.417 0.270

Area of Design steel required(mm2) 350 371 324 209

Area of Minimum steel required(mm2) 480 480 480 480

Area of steel provided(mm2) 1340 1340 1340 1340


Area of Steel provided OK OK OK OK
Dia of Main rebar(mm) 16 16 16 16
Spacing of main bars 150 150 150 150
Effective depth,d(mm) 316 316 332 332
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
%pt provided 0.424 0.424 0.404 0.404
2
Es(N/mm ) 200000 200000 200000 200000
2
Ece(N/mm ) 27386 27386 27386 27386
m= Es/Ece 7.303 7.303 7.303 7.303
Depth of
Neutral axis 69.47 69.47 71.43 71.43

x=(sqrt((m.Ast)2 + 2xmAst)-mxAst)xd

Lever arm (mm) =d-x/3 292.84 292.84 308.19 308.19


2
fs (N/mm ) =M/AstxZ 91.63 61.16 45.02 63.66
h (mm) 400 400 400 400

ε1=(fs/Es)*((a'-x)/(d-x)) 0.0006 0.0004 0.0003 0.0004


ε2== 1.5 .b . (h-X)2/(3.Es.As.(d-X)) 0.0008 0.0008 0.0008 0.0008
ε1-ε2 -0.0002 -0.0004 -0.0005 -0.0004
acr 93.24 93.24 93.24 93.24

Wcr(mm) 0.001 0.001 0.001 0.001


SAFE SAFE SAFE SAFE

Check for Shear Stress

Maximum
% of steel Ʈc from Table 19
Shear Check shear Check
provided of IS 456-2000
stress, Ʈv

X direction 0.436 0.424 0.470 Ʈc * > Ʈv OK


Y direction 0.322 0.404 0.454 Ʈc * > Ʈv OK

Design Table Explanation for Bending moment


density, W= 10.050 Kn/Cum
B.M for Water,M1 35.967 KN-m
Mu= (M) x 1.5 49.838 KN-m
D= 400.00 mm
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
Cover to steel 60.00 mm
Bar Diameter adopted 16.00 mm
d= 332.00 mm
b= 1000.00 mm
Mu/b/d/d 0.452 Mpa
Steel Grade 500.00 Mpa
Concrete Grade 30.00 Mpa
Refer Mu formula SP16 page 10 Pt= 0.106

Ast= 351 Sqmm/M


Min. steel 0.24% required 480 Sqmm
Required Reinforcement 480 Sqmm
Provided Reinforcement 1340.4 Sqmm

Required Spacing 418.879 mm


Provided Net Spacing 150.00 mm
Provided Rebar T16+T16
Provided Spacing for T16+T16 300.000 mm
OK
Design for shear at Base:-
Pt provided 0.404 %
0.436 Mpa
0.47 Mpa
OK

Design Explanation for Crack Width Cal Table

Applied Service Moment " Ms " = 35.97 KNm


Bar Dia = 16 mm
Maximum Bar Spacing " S " = 150 mm
Area of Reinforcement " As " = 1340 mm2
Grade of Concrete Used (fcu) = 30 N/mm2
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
Grade of Steel Used (fy) = 500 N/mm2
Width of Section b = 1000 mm
Thickness of Section h = 400.000 mm
Minimum Cover to Tension Reinforcement " CO " = 60 mm
Effective Depth of Section " d " = 332 mm
" acr " = (((S/2)^2 + (CO + DIA/2 )^2)^(1/2)-DIA/2) = 93.24 mm

Distance From the Point Considered to the Surface of Nearest Longitudinal bar
Applied Service Axial Force, T 0.00 KN
Moduli of Elasticity of Concrete " Ec " = 5000x ( sqrt(fcu) ) = 27.39 KN/mm2
Moduli of Elasticity of Steel " Es " = 200.00 KN/mm2
Modular Ratio " a " = (Es/Ec) = 7.30
r = As/bd = 0.00404
a.r = 0.03
Depth of Neutral Axis, " X " = d.a.r(((1+(2/a.r))^0.5)-1) = 71.43 mm
Lever arm " Z " = ( d - X/3) = 308.19 mm
2
Reinforcement Stress " fs " = Ms/(As*Z)+((Tx0.5)/As) = 87.07 N/mm
Concrete Stress " fc " = (fs*As)/(0.5*b*X) = 3.27 N/mm2
"e1 " Strain at Soffit of Concrete Slab = (fs/Es)*(h-X)/(d-X) = 0.00055
"e1 " = (fs/Es)*(h-X)/(d-X)

e2= Strain due to stiffening effect of Concrete = 0.00077 mm


e2 = 1.5 .b . (h-X)2/(3.Es.As.(d-X))

em = e1 - e2 = -0.00022 mm

Calculated Crack Width " W " = -0.05207 mm


e
W = 3.acr. m/(1+2.(acr-CO)/(h-X)) = <<<<0.1 OK

Crack Width check for Axial Tension


Effective Cover,dc = 84 mm
acr = 110.8 mm
Strain in tensile steel, ϵ1 = fs/Es = 0.0000 mm
Strain due to siffenening effect, ϵ2 = 0.0015 mm
Average strain at the level considered,εm = ε1-ε2 = -0.0015 mm
Surface crack width,Wcr(mm), 3.acr.ϵm = 0.00 mm
= <0.1 mm, Hence Ok
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

Check for Combined Bending & Axial tension

Factored Axial Tensile stress = 0.697 N/mm2


Factored Axial Tensile stress = 697.30 kN/sqm
Factored Moment Mu = 8.58 kNm
Ast = 60 Sqmm/M
Tu = T x D = 278.92 kN
Ast, req on both faces = 641.20 mm2
Ast, req on one side for Axial Tension = 320.60 mm2
Ast, req on one side for Flexure = 60.00 mm2
=(641.2/2+60) = 380.60 mm2
Minimum Steel 0.24 %age = 480 mm2
Maximum of above = 480 mm2
Dia Rebar = 16 mm
Spacing of rebar, S = 150 mm
Provided T16-150 B.Faces = 1340.41 mm2
1340.41>480

Steel Provided is = OK
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

Design of Wall W4
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

4.4) Design of W4
The Geometry properties of W4 Wall
The Thickness of Wall W4 is 400mm .
Crack width check is performed for water face i.e. Moment at inward, outward of tank wall.
Wall elements W4 are highlighted as given below
Orientation of STAAD model
Y axis is upward side

STAAD MODEL ----W4 - 400mm Thk.

DESIGN OF WALL- 400mm Thk.

SERVICE CONDITION
Summary of Bending moments (Group No.601)
Shear Membrane Bending Moment
SQX SQY SX SY SXY Mx My Mxy
Plate L/C
(local) (local) (local) (local) (local) kNm/m kNm/m kNm/m
Max Qx 12187 153 DL+LL+HL(1
190.7
CHANNEL
8.9
EMPTY
-721.7
& ALL -47.5
OTHERS FULL)-MWL+WET
-229 43.501 SOIL
9.075 3.407
Min Qx 12172 104 DL+WET SOIL
-194.6 1.1 -738.4 -163.6 27.7 53.775 10.823 0.183
Max Qy 9017 154 DL+LL+HL(INLET,OUTLET
3.4 214 EMPTY
-49.8 & -281.8
ALL OTHERS9.6
FULL)-MWL+WET
2.224 26.74
SOIL -3.901
Min Qy 12323 154 DL+LL+HL(INLET,OUTLET
-13.7 -95.4 EMPTY
-93.7 & -337.4
ALL OTHERS
-24.1
FULL)-MWL+WET
-2.072 -17.636
SOIL 1.449
Max Sx 8746 193 DL + LL + HL(1
48.8CHANNEL
-6 EMPTY
334.3& ALL
260.8
OTHERS
-31.9
FULL)-MWL
5.831 11.664 -0.093
Min Sx 12546 106 DL+LL+WET-152
SOIL 9.6 -849.2 -172.8 -93.8 -27.981 -6.65 1.521
Max Sy 8770 193 DL + LL + HL(1
21.9CHANNEL
-23.4 EMPTY
172.1& ALL
330.4
OTHERS
-111.5
FULL)-MWL
5.85 6.003 2.835
Min Sy 12323 194 DL + LL + HL(INLET,OUTLET
-1.2 -27.2 -29.8
EMPTY -407.4
& ALL OTHERS
-103.4 FULL)-MWL
-1.057 -5.152 0.596
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
Max Sxy 12637 193 DL + LL + HL(1
15.2CHANNEL
-8.1 EMPTY
66.1& ALL
-272.6
OTHERS
123.3
FULL)-MWL
-0.005 -0.951 1.294
Min Sxy 12216 153 DL+LL+HL(1
178.2
CHANNEL-3
EMPTY
-764.3
& ALL -82.9
OTHERS-238.9
FULL)-MWL+WET
20.593 SOIL
5.694 1.874
Max Mx 12172 162 DL+HL(1-CHANNEL,
-194.2 WW
0.9 EMPTY))-MWL+WET
-737.8 -161 SOIL
23.2 53.911 10.847 0.13
Min Mx 12502 154 DL+LL+HL(INLET,OUTLET
174.1 -2.5 EMPTY
-791.4 & -183.9
ALL OTHERS
16.3
FULL)-MWL+WET
-54.28 -10.804
SOIL -0.489
Max My 9017 154 DL+LL+HL(INLET,OUTLET
3.4 214 EMPTY
-49.8 & -281.8
ALL OTHERS9.6
FULL)-MWL+WET
2.224 26.74
SOIL -3.901
Min My 12326 154 DL+LL+HL(INLET,OUTLET
13.1 -93 EMPTY
-89.2 & -337.5
ALL OTHERS
-162.7
FULL)-MWL+WET
-2.674 -18.754
SOIL 1.098
Max Mxy 8998 154 DL+LL+HL(INLET,OUTLET
46.3 72 EMPTY
-86.3 & ALL
-206
OTHERS
76.1
FULL)-MWL+WET
-8.146 -3.812
SOIL 11.272
Min Mxy 8993 162 DL+HL(1-CHANNEL,
-48.5 72.9
WW EMPTY))-MWL+WET
-85.4 -192.8 SOIL
-5.9 -7.985 -3.671 -8.696

STRENGTH CONDITION - Bending Moment Criteria


Summary of Bending moments (Group No. 601)
Shear Membrane Bending Moment
SQX SQY SX SY SXY
Mx My Mxy
Plate L/C (local) (local) (local) (local) (local)
kNm/m kNm/m kNm/m
kN/m2 kN/m2 kN/m2 kN/m2 kN/m2
Max Qx 12172 621 DL + LL + HL(FULL)-TOW
428 5.6 1399.2 -13.6 -480 -123.4 -23.655 0.271
Min Qx 12502 621 DL + LL + -450.9
HL(FULL)-TOW
1.4 1385.3 -58 -241.1 120.405 23.716 0.019
Max Qy 9017 554 1.5*(DL+LL+HL(INLET,OUTLET
5.2 321 -74.8
EMPTY
-422.7
& ALL OTHERS
14.3 FULL)-MWL
3.336 +40.11
W.S.) -5.851
Min Qy 12662 623 DL + LL + HL(1
-0.8CHANNEL
-349.2 EMPTY
27.8& ALL
-383.8
OTHERS
-305.5
FULL)-TOW
-0.185 -36.596 3.587
Max Sx 12097 621 DL + LL + HL(FULL)-TOW
145 -42.9 2233.5 -148.7 -190.5 -1.324 9.795 -5.369
Min Sx 12546 506 1.5*(DL + LL
-227.9
+ WET SOIL)
14.4 -1273.8 -259.1 -140.7 -41.971 -9.975 2.282
Max Sy 8770 621 DL + LL + HL(FULL)-TOW
-57.1 27.9 351.8 563.7 -408.7 16.627 7.656 6.189
Min Sy 12323 594 1.5*(DL + LL-1.8
+ HL(INLET,OUTLET
-40.7 -44.6EMPTY
-611.1
& ALL
-155.1
OTHERS-1.585
FULL)-MWL)
-7.728 0.894
Max Sxy 12626 621 DL + LL + HL(FULL)-TOW
118.3 -33.4 877.7 -330 746 4.804 -0.546 -2.539
Min Sxy 12143 621 DL + LL + HL(FULL)-TOW
408 -9.6 1333.4 -45.2 -548.9 -69.277 -14.433 1.061
Max Mx 12513 632 DL + HL(1-CHANNEL,
125.3 3.3
WW EMPTY)-TOW
658.1 -157.3 -117.8 133.752 25.594 -1.2
Min Mx 12173 623 DL + LL + -131.5
HL(1 CHANNEL
1.7 EMPTY
610.5& ALL
-119.3
OTHERS
-40.9
FULL)-TOW
-131.021 -24.393 1.142
Max My 9017 554 1.5*(DL+LL+HL(INLET,OUTLET
5.2 321 -74.8
EMPTY
-422.7
& ALL OTHERS
14.3 FULL)-MWL
3.336 +40.11
W.S.) -5.851
Min My 12662 623 DL + LL + HL(1
-0.8CHANNEL
-349.2 EMPTY
27.8& ALL
-383.8
OTHERS
-305.5
FULL)-TOW
-0.185 -36.596 3.587
Max Mxy 8998 554 1.5*(DL+LL+HL(INLET,OUTLET
69.4 107.9 -129.5
EMPTY-309
& ALL OTHERS
114.1 -12.218
FULL)-MWL -5.717
+ W.S.) 16.908
Min Mxy 9021 631 DL + HL(FULL)-TOW
-11.2 -165.4 32.9 -148.1 -82.5 2.334 -3.152 -15.035
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

Summary of forces from Staad


Bending Moments, kNm/m
Wall Type
Service Condition +veMx -veMx +veMy -veMy
W4 54.04 54.77 30.64 19.85

Factored moment is considered by the maximum of Strength and Serviced moments


Strength Condition
Shear Stress,
Bending Moments, kNm/m
Type N/mm2
SQX SQY +veMx -veMx +veMy -veMy
Wall 450.90 349.20 134.95 132.16 45.96 40.18

Maximum Moments of W4
X-DIRECTION (Horz.) Y-DIRECTION (Vert.)

Design for Bending moment Inside Out side Inside Out side

MX MX MY MY

Factored Moment(kN-m) 134.95 132.16 45.96 40.18


2
Grade of concrete,fck (N/mm ) 30 30 30 30

Grade of steel,fy (N/mm2) 500 500 500 500


Width of section,b (mm) 1000 1000 1000 1000
Thickness of section,h(mm) 400 400 400 400
Cover to reinforcement(mm) 60 60 60 60

Mu/bd2 1.352 1.324 0.417 0.365


2
Area of Design steel required(mm ) 1040 1017 324 283

Area of Minimum steel required(mm2) 480 480 480 480

Area of steel provided(mm2) 1340 1340 1340 1340


Area of Steel provided OK OK OK OK
Dia of Main rebar(mm) 16 16 16 16
Spacing of main bars 150 150 150 150
Effective depth,d(mm) 316 316 332 332
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
%pt provided 0.424 0.424 0.404 0.404
2
Es(N/mm ) 200000 200000 200000 200000
2
Ece(N/mm ) 27386 27386 27386 27386
m= Es/Ece 7.303 7.303 7.303 7.303
Depth of
Neutral axis 69.47 69.47 71.43 71.43

x=(sqrt((m.Ast)2 + 2xmAst)-mxAst)xd

Lever arm (mm) =d-x/3 292.84 292.84 308.19 308.19


2
fs (N/mm ) =M/AstxZ 137.67 139.53 74.17 48.06
h (mm) 400 400 400 400

ε1=(fs/Es)*((a'-x)/(d-x)) 0.0009 0.0009 0.0005 0.0003


ε2== 1.5 .b . (h-X)2/(3.Es.As.(d-X)) 0.0008 0.0008 0.0008 0.0008
ε1-ε2 0.0001 0.0001 -0.0003 -0.0005
acr 93.24 93.24 93.24 93.24

Wcr(mm) 0.022 0.025 0.001 0.001


SAFE SAFE SAFE SAFE

Check for Shear Stress

Maximum
% of steel Ʈc from Table 19
Shear Check shear Check
provided of IS 456-2000
stress, Ʈv

X direction 450.90 0.424 0.464 Ʈc * < Ʈv CHK


Y direction 349.200 0.404 0.454 Ʈc * < Ʈv CHK

Design Table Explanation for Bending moment


density, W= 10.050 Kn/Cum
B.M for Water,M1 54.769 KN-m
Mu= (M) x 1.5 134.952 KN-m
D= 400.00 mm
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
Cover to steel 60.00 mm
Bar Diameter adopted 16.00 mm
d= 332.00 mm
b= 1000.00 mm
Mu/b/d/d 1.224 Mpa
Steel Grade 500.00 Mpa
Concrete Grade 30.00 Mpa
Refer Mu formula SP16 page 10 Pt= 0.296

Ast= 983 Sqmm/M


Min. steel 0.24% required 480 Sqmm
Required Reinforcement 983 Sqmm
Provided Reinforcement 1340.4 Sqmm

Required Spacing 204.539 mm


Provided Net Spacing 150.00 mm

Provided Rebar T16+T16


Provided Spacing for T16+T16 300.000 mm
OK
Design for shear at Base:-
Pt provided 0.404 %
0.45 Mpa
0.46 Mpa
OK

Design Explanation for Crack Width Cal Table

Applied Service Moment " Ms " = 54.77 KNm


Bar Dia = 16 mm
Maximum Bar Spacing " S " = 150 mm
Area of Reinforcement " As " = 1340 mm2
Grade of Concrete Used (fcu) = 30 N/mm2
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
Grade of Steel Used (fy) = 500 N/mm2
Width of Section b = 1000 mm
Thickness of Section h = 400.000 mm
Minimum Cover to Tension Reinforcement " CO " = 60 mm
Effective Depth of Section " d " = 332 mm
" acr " = (((S/2)^2 + (CO + DIA/2 )^2)^(1/2)-DIA/2) = 93.24 mm

Distance From the Point Considered to the Surface of Nearest Longitudinal bar
Applied Service Axial Force, T 0.00 KN
Moduli of Elasticity of Concrete " Ec " = 5000x ( sqrt(fcu) ) = 27.39 KN/mm2
Moduli of Elasticity of Steel " Es " = 200.00 KN/mm2
Modular Ratio " a " = (Es/Ec) = 7.30
r = As/bd = 0.00404
a.r = 0.03
Depth of Neutral Axis, " X " = d.a.r(((1+(2/a.r))^0.5)-1) = 71.43 mm
Lever arm " Z " = ( d - X/3) = 308.19 mm
2
Reinforcement Stress " fs " = Ms/(As*Z)+((Tx0.5)/As) = 132.58 N/mm
Concrete Stress " fc " = (fs*As)/(0.5*b*X) = 4.98 N/mm2
"e1 " Strain at Soffit of Concrete Slab = (fs/Es)*(h-X)/(d-X) = 0.00084
"e1 " = (fs/Es)*(h-X)/(d-X)

e2= Strain due to stiffening effect of Concrete = 0.00077 mm


e2 = 1.5 .b . (h-X)2/(3.Es.As.(d-X))

em = e1 - e2 = 0.00006 mm

Calculated Crack Width " W " = 0.01469 mm


e
W = 3.acr. m/(1+2.(acr-CO)/(h-X)) = <<0.1 OK

Crack Width check for Axial Tension


Effective Cover,dc = 84 mm
acr = 110.8 mm
Strain in tensile steel, ϵ1 = fs/Es = 0.0000 mm
Strain due to siffenening effect, ϵ2 = 0.0015 mm
Average strain at the level considered,εm = ε1-ε2 = -0.0015 mm
Surface crack width,Wcr(mm), 3.acr.ϵm = 0.00 mm
= <0.1 mm, Hence Ok
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

Check for Combined Bending & Axial tension

Factored Axial Tensile stress = 2.234 N/mm2


Factored Axial Tensile stress = 2233.50 kN/sqm
Factored Moment Mu = 1.32 kNm
Ast = 9 Sqmm/M
Tu = T x D = 893.40 kN
Ast, req on both faces = 2053.79 mm2
Ast, req on one side for Axial Tension = 1026.90 mm2
Ast, req on one side for Flexure = 9.00 mm2
=(2053.79/2+9) = 1035.90 mm2
Minimum Steel 0.24 %age = 480 mm2
Maximum of above = 1036 mm2
Dia Rebar = 16 mm
Spacing of rebar, S = 150 mm
Provided T16-150 B.Faces = 1340.41 mm2
1340.41>1035.895

Steel Provided is = OK
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

Design of Wall W5
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

4.5) Design of W5
The Geometry properties of W5 Wall
The Thickness of Wall W5 is 700mm .
Crack width check is performed for water face i.e. Moment at inward, outward of tank wall.
Wall elements W5 are highlighted as given below
Orientation of STAAD model
Y axis is upward side

STAAD MODEL ----W5 - 400mm Thk.

DESIGN OF WALL- 400mm Thk.

SERVICE CONDITION
Summary of Bending moments (Group No. shaft)
Shear Membrane Bending Moment
SQX SQY SX SY SXY Mx My Mxy
Plate L/C
(local) (local) (local) (local) (local) kNm/m kNm/m kNm/m
Max Qx 5923 153 DL+LL+HL(10.20
CHANNEL
0.00
EMPTY
-0.80
& ALL -0.10
OTHERS -0.30
FULL)-MWL+WET
15.63 SOIL
17.88 -0.63
Min Qx 5910 153 DL+LL+HL(1
-0.10
CHANNEL
0.00
EMPTY
-1.00
& ALL OTHERS
0.00 FULL)-MWL+WET
0.10 14.86 SOIL
15.71 -2.24
Max Qy 5037 152 DL+LL+HL(1-CHANNEL,
0.00 0.20WW -0.10
EMPTY))-MWL+WET
-0.60 -0.10
SOIL 2.88 21.81 -0.20
Min Qy 5794 153 DL+LL+HL(10.00
CHANNEL
-0.20
EMPTY
-0.70
& ALL -0.20
OTHERS -0.10
FULL)-MWL+WET
18.14 SOIL
11.51 2.79
Max Sx 5035 111 DL+LL+HL(FULL)-MWL+EL(+X)
0.00 0.20 0.60 -0.50 -0.20 4.76 31.89 -0.25
Min Sx 5500 104 DL+WET SOIL
0.00 0.00 -1.10 -0.50 0.00 2.21 -4.23 -0.05
Max Sy 5785 153 DL+LL+HL(10.00
CHANNEL
-0.10
EMPTY
-0.40
& ALL OTHERS
0.10 -0.20
FULL)-MWL+WET
8.59 SOIL
12.03 2.82
Min Sy 7860 152 DL+LL+HL(1-CHANNEL,
0.00 0.00WW EMPTY))-MWL+WET
0.10 -0.8 -0.10
SOIL -3.15 -2.21 1.02
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
Max Sxy 6038 153 DL+LL+HL(1
-0.10
CHANNEL
0.10
EMPTY
-0.80
& ALL -0.10
OTHERS FULL)-MWL+WET
0.40 13.81 SOIL
7.66 1.54
Min Sxy 5984 104 DL+WET SOIL
0.00 0.00 -0.40 -0.30 -0.40 4.41 0.50 9.07
Max Mx 6556 153 DL+LL+HL(10.00
CHANNEL
0.00
EMPTY
-0.40
& ALL -0.10
OTHERS -0.10
FULL)-MWL+WET
27.66 SOIL
8.64 0.69
Min Mx 5993 153 DL+LL+HL(10.00
CHANNEL
0.00
EMPTY
-0.70
& ALL -0.50
OTHERS -0.10
FULL)-MWL+WET
-12.21 SOIL
-2.85 -0.65
Max My 5035 192 DL + LL + HL(1-CHANNEL,
0.00 0.20 WW
0.60
EMPTY)-MWL
-0.60 -0.10 5.16 32.92 -0.26
Min My 5283 152 DL+LL+HL(1-CHANNEL,
0.00 0.00WW -0.90
EMPTY))-MWL+WET
-0.50 -0.10
SOIL -0.95 -12.09 1.33
Max Mxy 6048 154 DL+LL+HL(INLET,OUTLET
0.00 0.00 EMPTY
-0.50 & ALL
-0.20
OTHERS
-0.30
FULL)-MWL+WET
5.92 SOIL
0.80 9.62
Min Mxy 6041 154 DL+LL+HL(INLET,OUTLET
0.00 0.00 EMPTY
-0.50 & ALL
-0.20
OTHERS
0.20
FULL)-MWL+WET
5.55 -0.13
SOIL -8.49

STRENGTH CONDITION - Bending Moment Criteria


Summary of Bending moments (Group : ShaftBM)
Shear Membrane Bending Moment
SQX SQY SX SY SXY
Mx My Mxy
Plate L/C (local) (local) (local) (local) (local)
kNm/m kNm/m kNm/m
N/mm2 N/mm2 N/mm2 N/mm2 N/mm2
Max Qx 5923 553 1.5*(DL + LL +0.3
HL(1 CHANNEL
0.1 -1.2
EMPTY &-0.2
ALL OTHERS
-0.4 FULL)-MWL
23.4 + W.S.)
26.8 -0.9
Min Qx 6368 635 DL + HL(2 CHANNELS,
-0.3 0.0
WW EMPTY
0.0 & ALL
-0.3OTHERS
0.1FULL)-TOW
9.8 -0.6 -2.4
Max Qy 5037 552 1.5*(DL + LL +0.0
HL(1-CHANNEL,
0.3 -0.1
WW EMPTY))-MWL
-0.9 -0.2+ WET SOIL)
4.3 32.7 -0.3
Min Qy 5794 553 1.5*(DL + LL +0.0
HL(1 CHANNEL
-0.2 -1.0
EMPTY &-0.3
ALL OTHERS
-0.1 FULL)-MWL
27.2 + W.S.)
17.3 4.2
Max Sx 5923 621 DL + LL + HL(FULL)-TOW
0.2 -0.1 2.1 -1.2 0.3 1.2 -1.2 0.4
Min Sx 5500 504 1.5*(DL + WET
0.0
SOIL) 0.0 -1.6 -0.7 0.0 3.3 -6.3 -0.1
Max Sy 5848 621 DL + LL + HL(FULL)-TOW
0.0 0.0 0.3 0.6 -0.5 3.7 16.0 4.5
Min Sy 5859 621 DL + LL + HL(FULL)-TOW
0.2 -0.1 2.0 -1.3 -0.4 -3.4 -6.1 2.4
Max Sxy 5987 631 DL + HL(FULL)-TOW
0.2 0.0 1.5 -0.7 0.8 3.1 0.7 -1.7
Min Sxy 5792 621 DL + LL + HL(FULL)-TOW
0.1 -0.1 0.7 -0.6 -1.3 6.2 3.3 -8.6
Max Mx 6556 553 1.5*(DL + LL +0.0
HL(1 CHANNEL
0.0 -0.6
EMPTY &-0.2
ALL OTHERS
-0.1 FULL)-MWL
41.5 + W.S.)
13.0 1.0
Min Mx 6492 635 DL + HL(2 CHANNELS,
0.0 0.0
WW EMPTY
0.0 & ALL
-0.4OTHERS
0.1FULL)-TOW
-37.1 -10.7 0.3
Max My 5027 502 1.5*(DL + UPLIFT)
0.0 0.3 0.9 -0.9 0.0 8.8 52.7 0.1
Min My 5283 552 1.5*(DL + LL +0.0
HL(1-CHANNEL,
0.0 -1.4
WW EMPTY))-MWL
-0.7 -0.2+ WET SOIL)
-1.4 -18.1 2.0
Max Mxy 6048 554 1.5*(DL+LL+HL(INLET,OUTLET
0.0 0.0 -0.7
EMPTY -0.3
& ALL OTHERS
-0.4 FULL)-MWL
8.9 + W.S.)
1.2 14.4
Min Mxy 6041 554 1.5*(DL+LL+HL(INLET,OUTLET
0.0 0.0 -0.8
EMPTY -0.3
& ALL OTHERS
0.2 FULL)-MWL
8.3 + W.S.)
-0.2 -12.7
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

STRENGTH CONDITION - Shear Criteria


(Group No. ShaftBM)
Shear Membrane Bending Moment
SQX SQY SX SY SXY
Mx My Mxy
Plate L/C (local) (local) (local) (local) (local)
kNm/m kNm/m kNm/m
N/mm2 N/mm2 N/mm2 N/mm2 N/mm2
Max Qx 5923 553 1.5*(DL + LL +0.3
HL(1 CHANNEL
0.1 -1.2
EMPTY &-0.2
ALL OTHERS
-0.4 FULL)-MWL
23.4 + W.S.)
26.8 -0.9
Min Qx 6368 635 DL + HL(2 CHANNELS,
-0.3 0.0
WW EMPTY
0.0 & ALL
-0.3OTHERS
0.1FULL)-TOW
9.8 -0.6 -2.4
Max Qy 5037 552 1.5*(DL + LL +0.0
HL(1-CHANNEL,
0.3 -0.1
WW EMPTY))-MWL
-0.9 -0.2+ WET SOIL)
4.3 32.7 -0.3
Min Qy 5794 553 1.5*(DL + LL +0.0
HL(1 CHANNEL
-0.2 -1.0
EMPTY &-0.3
ALL OTHERS
-0.1 FULL)-MWL
27.2 + W.S.)
17.3 4.2
Max Sx 5923 621 DL + LL + HL(FULL)-TOW
0.2 -0.1 2.1 -1.2 0.3 1.2 -1.2 0.4
Min Sx 5500 504 1.5*(DL + WET
0.0
SOIL) 0.0 -1.6 -0.7 0.0 3.3 -6.3 -0.1
Max Sy 5848 621 DL + LL + HL(FULL)-TOW
0.0 0.0 0.3 0.6 -0.5 3.7 16.0 4.5
Min Sy 5859 621 DL + LL + HL(FULL)-TOW
0.2 -0.1 2.0 -1.3 -0.4 -3.4 -6.1 2.4
Max Sxy 5987 631 DL + HL(FULL)-TOW
0.2 0.0 1.5 -0.7 0.8 3.1 0.7 -1.7
Min Sxy 5792 621 DL + LL + HL(FULL)-TOW
0.1 -0.1 0.7 -0.6 -1.3 6.2 3.3 -8.6
Max Mx 6556 553 1.5*(DL + LL +0.0
HL(1 CHANNEL
0.0 -0.6
EMPTY &-0.2
ALL OTHERS
-0.1 FULL)-MWL
41.5 + W.S.)
13.0 1.0
Min Mx 6492 635 DL + HL(2 CHANNELS,
0.0 0.0
WW EMPTY
0.0 & ALL
-0.4OTHERS
0.1FULL)-TOW
-37.1 -10.7 0.3
Max My 5027 502 1.5*(DL + UPLIFT)
0.0 0.3 0.9 -0.9 0.0 8.8 52.7 0.1
Min My 5283 552 1.5*(DL + LL +0.0
HL(1-CHANNEL,
0.0 -1.4
WW EMPTY))-MWL
-0.7 -0.2+ WET SOIL)
-1.4 -18.1 2.0
Max Mxy 6048 554 1.5*(DL+LL+HL(INLET,OUTLET
0.0 0.0 -0.7
EMPTY -0.3
& ALL OTHERS
-0.4 FULL)-MWL
8.9 + W.S.)
1.2 14.4
Min Mxy 6041 554 1.5*(DL+LL+HL(INLET,OUTLET
0.0 0.0 -0.8
EMPTY -0.3
& ALL OTHERS
0.2 FULL)-MWL
8.3 + W.S.)
-0.2 -12.7
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

Summary of forces from Staad


Bending Moments, kNm/m
Wall Type
Service Condition +veMx -veMx +veMy -veMy
W5 28.35 12.86 33.18 13.42

Factored moment is considered by the maximum of Strength and Serviced moments


Strength Condition
Shear Stress,
Bending Moments, kNm/m
Type N/mm2
SQX SQY +veMx -veMx +veMy -veMy
Wall 0.30 0.30 42.53 37.44 52.81 20.12

Maximum Moments of W5
X-DIRECTION (Horz.) Y-DIRECTION (Vert.)

Design for Bending moment Out side Inside Out side Inside

MX MX MY MY

Factored Moment(kN-m) 42.53 37.44 52.81 20.12


2
Grade of concrete,fck (N/mm ) 30 30 30 30

Grade of steel,fy (N/mm2) 400 400 400 400


Width of section,b (mm) 1000 1000 1000 1000
Thickness of section,h(mm) 400 400 400 400
Cover to reinforcement(mm) 60 60 60 60
2
Mu/bd 0.426 0.375 0.480 0.183

Area of Design steel required(mm2) 394 346 467 176


2
Area of Minimum steel required(mm ) 720 720 720 720

Area of steel provided(mm2) 1340 1340 1340 1340


Area of Steel provided OK OK OK OK
Dia of Main rebar(mm) 16 16 16 16
Spacing of main bars 150 150 150 150
Extra Bars dia
Extra Bars spacing 150 150 150 150

Extra Bars location 1.8m @bottom 1.8m @bottom 1.8m @bottom 1.8m @bottom
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
Effective depth,d(mm) 316 316 332 332
%pt provided 0.424 0.424 0.404 0.404
2
Es(N/mm ) 200000 200000 200000 200000
2
Ece(N/mm ) 27386 27386 27386 27386
m= Es/Ece 7.303 7.303 7.303 7.303
Depth of
Neutral axis 69.47 69.47 71.43 71.43

x=(sqrt((m.Ast)2 + 2xmAst)-mxAst)xd

Lever arm (mm) =d-x/3 292.84 292.84 308.19 308.19

fs (N/mm2) =M/AstxZ 72.23 32.75 80.31 32.47


h (mm) 400 400 400 400

ε1=(fs/Es)*((a'-x)/(d-x)) 0.0005 0.0002 0.0005 0.0002


ε2== 1.5 .b . (h-X)2/(3.Es.As.(d-X)) 0.0008 0.0008 0.0008 0.0008
ε1-ε2 -0.0003 -0.0006 -0.0003 -0.0006
acr 93.24 93.24 93.24 93.24

Wcr(mm) 0.001 0.001 0.001 0.001


SAFE SAFE SAFE SAFE

Check for Shear Stress

Maximum
% of steel Ʈc from Table 19
Shear Check shear Check
provided of IS 456-2000
stress, Ʈv

X direction 0.300 0.424 0.464 Ʈc * > Ʈv OK


Y direction 0.300 0.404 0.454 Ʈc * > Ʈv OK

Design Table Explanation for Bending moment


density, W= 10.050 Kn/Cum
B.M for Water,M1 33.177 KN-m
Mu= (M) x 1.5 52.810 KN-m
D= 400.00 mm
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
Cover to steel 60.00 mm
Bar Diameter adopted 16.00 mm
d= 332.00 mm
b= 1000.00 mm
Mu/b/d/d 0.479 Mpa
Steel Grade 500.00 Mpa
Concrete Grade 30.00 Mpa
Refer Mu formula SP16 page 10 Pt= 0.112

Ast= 373 Sqmm/M


Min. steel 0.36% required 720 Sqmm
Required Reinforcement 720 Sqmm
Provided Reinforcement 1340.4 Sqmm

Required Spacing 279.253 mm


Provided Net Spacing 150.00 mm

Provided Rebar T16+T16


Provided Spacing for T16+T16 300.000 mm
OK

Design for shear at Base:-


Pt provided 0.404 %
0.000 Mpa
0.45 Mpa
OK

Design Explanation for Crack Width Cal Table

Applied Service Moment " Ms " = 33.18 KNm


Bar Dia = 16 mm
Maximum Bar Spacing " S " = 150 mm
Area of Reinforcement " As " = 1340 mm2
Grade of Concrete Used (fcu) = 30 N/mm2
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
2
Grade of Steel Used (fy) = 500 N/mm
Width of Section b = 1000 mm
Thickness of Section h = 400.000 mm
Minimum Cover to Tension Reinforcement " CO " = 60 mm
Effective Depth of Section " d " = 332 mm
" acr " = (((S/2)^2 + (CO + DIA/2 )^2)^(1/2)-DIA/2) = 93.24 mm

Distance From the Point Considered to the Surface of Nearest Longitudinal bar
Applied Service Axial Force, T 0.00 KN
Moduli of Elasticity of Concrete " Ec " = 5000x ( sqrt(fcu) ) = 27.39 KN/mm2
Moduli of Elasticity of Steel " Es " = 200.00 KN/mm2
Modular Ratio " a " = (Es/Ec) = 7.30
r = As/bd = 0.00404
a.r = 0.03
Depth of Neutral Axis, " X " = d.a.r(((1+(2/a.r))^0.5)-1) = 71.43 mm
Lever arm " Z " = ( d - X/3) = 308.19 mm
Reinforcement Stress " fs " = Ms/(As*Z)+((Tx0.5)/As) = 80.31 N/mm2
Concrete Stress " fc " = (fs*As)/(0.5*b*X) = 3.01 N/mm2
"e1 " Strain at Soffit of Concrete Slab = (fs/Es)*(h-X)/(d-X) = 0.00051
"e1 " = (fs/Es)*(h-X)/(d-X)

e2= Strain due to stiffening effect of Concrete = 0.00077 mm


e2 = 1.5 .b . (h-X)2/(3.Es.As.(d-X))

em = e1 - e2 = -0.00027 mm

Calculated Crack Width " W " = -0.06198 mm


W = 3.acr. em/(1+2.(acr-CO)/(h-X)) = <<<<0.1 OK
Crack Width check for Axial Tension
Effective Cover,dc = 84 mm
acr = 110.8 mm
Strain in tensile steel, ϵ1 = fs/Es = 0.0000 mm
Strain due to siffenening effect, ϵ2 = 0.0015 mm
Average strain at the level considered,εm = ε1-ε2 = -0.0015 mm
Surface crack width,Wcr(mm), 3.acr.ϵm = 0.00 mm
= <0.1 mm, Hence Ok
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

Check for Combined Bending & Axial tension

Factored Axial Tensile stress = 2.10 N/mm2


Factored Axial Tensile stress = 2100.00 kN/sqm
Factored Moment Mu = 1.18 kNm
Ast = 8 Sqmm/M
Tu = T x D = 840.00 kN
Ast, req on both faces = 2413.79 mm2
Ast, req on one side for Axial Tension = 1206.90 mm2
Ast, req on one side for Flexure = 8.00 mm2
=(2413.79/2+8) = 1214.90 mm2
Minimum Steel 0.24 %age = 480 mm2
Maximum of above = 1215 mm2
Dia Rebar = 16 mm
Spacing of rebar, S = 150 mm
Provided T16-150 B.Faces = 1340.41 mm2
1340.41>1214.895

Steel Provided is = OK
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

Design of Wall W6

Page 95 of 195
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG
JV

4.6) Design of W6
The Geometry properties of W6 Wall
The Thickness of Wall W6 is 300mm .
Wall elements W6 are highlighted as given below
Orientation of STAAD model
Y axis is upward side

STAAD MODEL ----W6 - 300mm Thk.

DESIGN OF WALL- 300mm Thk.

SERVICE CONDITION
Summary of Bending moments (Group No. VLAVECHAMWALL)
Shear Membrane Bending Moment
SQX SQY SX SY SXY
Mx My Mxy
Plate L/C (local) (local) (local) (local) (local)
kNm/m kNm/m kNm/m
N/mm2 N/mm2 N/mm2 N/mm2 N/mm2
Max Qx 16147 101 DL+LL 0.1 0 0.1 0 0 -8.403 -0.162 2.66
Min Qx 16120 101 DL+LL 0 0 0.1 0 0 -9.567 -0.213 -1.681
Max Qy 15445 106 DL+LL+WET SOIL
0 0.1 0 -0.1 0 4.697 25.235 1.288
Min Qy 15876 101 DL+LL 0 0 0 0 0 0.045 0.079 3.378
Max Sx 16140 101 DL+LL 0 0 0.2 0 0 9.001 0.332 0.906
Min Sx 15456 101 DL+LL 0 0 -0.2 0 0.1 -2.425 -0.336 0.591
Max Sy 15432 101 DL+LL 0 0 0 0 0 -1.993 1.698 2.648
Min Sy 15424 101 DL+LL 0 0 0 -0.1 0 4.35 21.757 6.407

Page 96 of 195
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG
JV
Max Sxy 15456 171 1.0*(DL+HL(FULL)-MWL+WL(+X))
0 0 -0.2 0 0.1 -3.155 -0.417 0.813
Min Sxy 15674 101 DL+LL 0 0 0 -0.1 -0.1 -1.782 4.185 7.138
Max Mx 16140 101 DL+LL 0 0 0.2 0 0 9.001 0.332 0.906
Min Mx 16165 101 DL+LL 0 0 0.1 0 0 -20.712 -0.651 0.422
Max My 15446 106 DL+LL+WET SOIL
0 0.1 0 -0.1 0 4.91 25.622 0.178
Min My 15869 171 1.0*(DL+HL(FULL)-MWL+WL(+X))
0 0 0 0 0 -14.219 -2.922 0.556
Max Mxy 15438 101 DL+LL 0 0 0 -0.1 0 2.293 14.071 11.216
Min Mxy 15407 101 DL+LL 0 0 0 -0.1 0 1.56 10.167 -7.845

STRENGTH CONDITION - Bending Moment Criteria


Summary of Bending moments (Group No. VLAVECHAMWALL)
Shear Membrane Bending Moment
SQX SQY SX SY SXY
Mx My Mxy
Plate L/C (local) (local) (local) (local) (local)
kNm/m kNm/m kNm/m
N/mm2 N/mm2 N/mm2 N/mm2 N/mm2
Max Qx 16147 501 1.5*(DL + LL)0.1 0 0.1 0 0 -12.604 -0.242 3.99
Min Qx 16120 501 1.5*(DL + LL)-0.1 0 0.1 0 0 -14.35 -0.319 -2.521
Max Qy 15445 506 1.5*(DL + LL + WET
0 SOIL)
0.1 0 -0.1 0 7.045 37.852 1.932
Min Qy 15876 501 1.5*(DL + LL) 0 0 0 0 0 0.067 0.119 5.068
Max Sx 16140 501 1.5*(DL + LL) 0 0 0.3 0 0 13.502 0.498 1.359
Min Sx 15456 501 1.5*(DL + LL) 0 0 -0.3 -0.1 0.1 -3.637 -0.505 0.886
Max Sy 15432 501 1.5*(DL + LL) 0 0.1 0 0.1 0 -2.99 2.546 3.972
Min Sy 15424 501 1.5*(DL + LL) 0 0 0 -0.2 0 6.525 32.635 9.611
Max Sxy 15456 502 1.5*(DL + UPLIFT)
0 0 -0.3 -0.1 0.1 -4.728 -0.624 1.218
Min Sxy 15674 501 1.5*(DL + LL) 0 0 0.1 -0.1 -0.1 -2.673 6.278 10.707
Max Mx 16140 501 1.5*(DL + LL) 0 0 0.3 0 0 13.502 0.498 1.359
Min Mx 16165 501 1.5*(DL + LL) 0 0 0.1 0 0 -31.068 -0.977 0.633
Max My 15446 506 1.5*(DL + LL + WET
0 SOIL)
0.1 0 -0.1 0 7.365 38.432 0.267
Min My 15869 502 1.5*(DL + UPLIFT)
0 0 0 0 0 -21.329 -4.383 0.834
Max Mxy 15438 501 1.5*(DL + LL) 0 0 0 -0.1 -0.1 3.44 21.107 16.824
Min Mxy 15407 501 1.5*(DL + LL) 0 0 0 -0.1 0.1 2.34 15.251 -11.767

Page 97 of 195
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG
JV

Summary of forces from Staad


Bending Moments, kNm/m
Wall Type
Service Condition +veMx -veMx +veMy -veMy

W6 9.91 21.13 25.80 3.48

Strength Condition
Shear Stress,
Bending Moments, kNm/m
Type N/mm2
SQX SQY +veMx -veMx +veMy -veMy

Wall 0.10 0.10 14.86 31.70 38.70 5.22

Maximum Moments of W6
X-DIRECTION (Horz.) Y-DIRECTION (Vert.)
Design for Bending moment Inside Out side Inside Out side
MX MX MY MY

Un-Factored Moment(kN-m) 9.91 21.13 25.80 3.48

Factored Moment(kN-m) 14.86 31.70 38.70 5.22

Grade of concrete,fck (N/mm2) 30 30 30 30

Grade of steel,fy (N/mm2) 500 500 500 500

Width of section,b (mm) 1000 1000 1000 1000

Thickness of section,h(mm) 300 300 300 300

Cover to reinforcement(mm) 60 60 60 60

Mu/bd2 0.302 0.644 0.707 0.096

Area of Design steel required(mm2) 157 338 392 52

Area of Minimum steel required(mm2) 360 360 360 360

Area of steel provided(mm2) 754 754 754 754

Area of Steel provided OK OK OK OK

Dia of Main rebar(mm) 12 12 12 12

Spacing of main bars 150 150 150 150

Effective depth,d(mm) 222 222 234 234

Page 98 of 195
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG
JV
%pt provided 0.340 0.340 0.322 0.322

Es(N/mm2) 200000 200000 200000 200000


2
Ece(N/mm ) 27386 27386 27386 27386

m= Es/Ece 7.303 7.303 7.303 7.303


Depth of
Neutral axis 44.24 44.24 45.56 45.56

x=(sqrt((m.Ast)2 + 2xmAst)-mxAst)xd

Lever arm (mm) =d-x/3 207.25 207.25 218.81 218.81


2
fs (N/mm ) =M/AstxZ 63.40 135.25 156.38 21.08

h (mm) 300 300 300 300

ε1=(fs/Es)*((a'-x)/(d-x)) 0.0005 0.0010 0.0011 0.0001

ε2== 1.5 .b . (h-X)2/(3.Es.As.(d-X)) 0.0012 0.0012 0.0011 0.0011

ε1-ε2 -0.0008 -0.0002 -0.0001 -0.0010

acr 93.90 93.90 93.90 93.90

Wcr(mm) 0.001 0.001 0.001 0.001


SAFE SAFE SAFE SAFE

Check for Shear Stress

Maximum
% of steel Ʈc from Table 19
Shear Check shear Check
provided of IS 456-2000
stress, Ʈv

X direction 0.10 0.340 0.422 Ʈc * > Ʈv OK

Y direction 0.10 0.322 0.412 Ʈc * > Ʈv OK

Design Table Explanation for Bending moment


density, W= 10.050 Kn/Cum
B.M for Water,M1 25.800 KN-m
Mu= (M) x 1.5 38.699 KN-m
D= 300.00 mm

Page 99 of 195
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG
JV
Cover to steel 60.00 mm
Bar Diameter adopted 12.00 mm
d= 234.00 mm
b= 1000.00 mm
Mu/b/d/d 0.707 Mpa
Steel Grade 500.00 Mpa
Concrete Grade 30.00 Mpa
Refer Mu formula SP16 page 10 Pt= 0.167

Ast= 391 Sqmm/M


Min. steel 0.24% required 360 Sqmm
Required Reinforcement 391 Sqmm
Provided Reinforcement 754.0 Sqmm

Required Spacing 289.251 mm


Provided Net Spacing 150.00 mm

Provided Rebar T12+T12

Provided Spacing for T12+T12 300.000 mm


OK

Design for shear at Base:-


Pt provided 0.322 %
0.000 Mpa
0.41 Mpa
OK

Page 100 of 195


Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG
JV
Design Explanation for Crack Width Cal Table

Applied Service Moment " Ms " = 25.80 KNm


Bar Dia = 12 mm
Maximum Bar Spacing " S " = 150 mm
Area of Reinforcement " As " = 754 mm2
2
Grade of Concrete Used (fcu) = 30 N/mm
Grade of Steel Used (fy) = 500 N/mm2

Width of Section b = 1000 mm


Thickness of Section h = 300.000 mm
Minimum Cover to Tension Reinforcement " CO " = 60 mm
Effective Depth of Section " d " = 234 mm
" acr " = (((S/2)^2 + (CO + DIA/2 )^2)^(1/2)-DIA/2) = 93.90 mm

Distance From the Point Considered to the Surface of Nearest Longitudinal bar
Applied Service Axial Force, T 0.00 KN
2
Moduli of Elasticity of Concrete " Ec " = 5000x ( sqrt(fcu) ) = 27.39 KN/mm
Moduli of Elasticity of Steel " Es " = 200.00 KN/mm2

Modular Ratio " a " = (Es/Ec) = 7.30


r = As/bd = 0.00322
a.r = 0.02
Depth of Neutral Axis, " X " = d.a.r(((1+(2/a.r))^0.5)-1) = 45.56 mm
Lever arm " Z " = ( d - X/3) = 218.81 mm
Reinforcement Stress " fs " = Ms/(As*Z)+((Tx0.5)/As) = 156.38 N/mm2
Concrete Stress " fc " = (fs*As)/(0.5*b*X) = 5.18 N/mm2

"e1 " Strain at Soffit of Concrete Slab = (fs/Es)*(h-X)/(d-X) = 0.00106


"e1 " = (fs/Es)*(h-X)/(d-X)

e2= Strain due to stiffening effect of Concrete = 0.00114 mm


e2 = 1.5 .b . (h-X)2/(3.Es.As.(d-X))
em = e1 - e2 = -0.00008 mm

Calculated Crack Width " W " = -0.01855 mm


W = 3.acr.em/(1+2.(acr-CO)/(h-X)) = <<<<0.1 OK

Page 101 of 195


Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG
JV
Crack Width check for Axial Tension
Effective Cover,dc = 78 mm
acr = 104.3 mm
Strain in tensile steel, ϵ1 = fs/Es = 0.0000 mm
Strain due to siffenening effect, ϵ2 = 0.0020 mm
Average strain at the level considered,εm = ε1-ε2 = -0.0020 mm
Surface crack width,Wcr(mm), 3.acr.ϵm = 0.00 mm
= <0.1 mm, Hence Ok

Check for Combined Bending & Axial tension

Factored Axial Tensile stress = 0.000 N/mm2


Factored Axial Tensile stress = 0.30 kN/sqm
Factored Moment Mu = 13.50 kNm
Ast = 134 Sqmm/M
Tu = T x D = 0.09 kN
Ast, req on both faces = 0.21 mm2
Ast, req on one side for Axial Tension = 0.11 mm2
Ast, req on one side for Flexure = 134.00 mm2
=(0.21/2+134) = 134.11 mm2
Minimum Steel 0.24 %age = 360 mm2
Maximum of above = 360 mm2
Dia Rebar = 12 mm
Spacing of rebar, S = 150 mm
Provided T12-150 B.Faces = 753.98 mm2
753.98>360

Steel Provided is = OK

Page 102 of 195


Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG
JV

Design of Wall W7
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG
JV

4.7) Design of W7
The Geometry properties of W7 Wall
The Thickness of Wall W7 is 300mm .
Wall elements W6 are highlighted as given below
Orientation of STAAD model
Y axis is upward side

STAAD MODEL ----W7 - 300mm Thk.

DESIGN OF WALL- 300mm Thk.

SERVICE CONDITION
Summary of Bending moments (Group No. 301)
Shear Membrane Bending Moment
SQX SQY SX SY SXY Mx My Mxy
Plate L/C
(local) (local) (local) (local) (local) kNm/m kNm/m kNm/m
Max Qx 13078 153 DL+LL+HL(1
386.9
CHANNEL
-50.3
EMPTY
345.7
& ALL OTHERS
28.2 FULL)-MWL+WET
11.9 -31.75 SOIL
-8.955 -1.489
Min Qx 12812 151 DL+LL+HL(FULL)-MWL+WET
-208 -109.6 -415.1
SOIL -81.7 -140.8 11.461 -1.448 -2.261
Max Qy 13084 153 DL+LL+HL(1
302.7
CHANNEL
288.9
EMPTY103
& ALL101.2
OTHERS364.5
FULL)-MWL+WET
-17.879 SOIL
-2.447 -10.828
Min Qy 12811 151 DL+LL+HL(FULL)-MWL+WET
124.1 -138.6 -279.8
SOIL -30.3 -138.8 14.339 0.02 2.908
Max Sx 13078 104 DL+WET SOIL
358.7 -64.3 352.8 55.7 34.6 -31.411 -8.391 -0.963
Min Sx 13030 151 DL+LL+HL(FULL)-MWL+WET
28.6 33.9 -511.3
SOIL -59 -102.8 9.136 0.801 1.868
Max Sy 12864 193 DL + LL + HL(1
-51.1CHANNEL
-11.6 EMPTY
51& ALL402
OTHERS
-459.1
FULL)-MWL
1.887 -1.678 -0.862
Min Sy 12867 111 DL+LL+HL(FULL)-MWL+EL(+X)
6 -15.2 14.7 -420.9 -264.5 -0.544 -2.354 -0.603
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG
JV
Max Sxy 12677 111 DL+LL+HL(FULL)-MWL+EL(+X)
8.1 45.3 -12.6 339.5 399.1 -1.115 -3.923 4.417
Min Sxy 12864 111 DL+LL+HL(FULL)-MWL+EL(+X)
-50.8 -13.3 49.5 398.8 -464.3 1.833 -1.75 -0.891
Max Mx 12811 151 DL+LL+HL(FULL)-MWL+WET
124.1 -138.6 -279.8
SOIL -30.3 -138.8 14.339 0.02 2.908
Min Mx 13078 153 DL+LL+HL(1
386.9
CHANNEL
-50.3
EMPTY
345.7
& ALL OTHERS
28.2 FULL)-MWL+WET
11.9 -31.75 SOIL
-8.955 -1.489
Max My 12953 151 DL+LL+HL(FULL)-MWL+WET
1.8 107.5 -26.4
SOIL -262.2 65.8 1.554 9.159 1.272
Min My 12674 151 DL+LL+HL(FULL)-MWL+WET
3.9 -99.5 -15.8
SOIL -258.5 158 -1.758 -10.009 1.054
Max Mxy 12677 133 DL+LL+HL(1
-22.1
CHANNEL71
EMPTY &
-4ALL361.3
OTHERS375.6
FULL)-MWL+DRY
-2.585 SOIL
-4.293 4.831
Min Mxy 13084 153 DL+LL+HL(1
302.7
CHANNEL
288.9
EMPTY103
& ALL101.2
OTHERS364.5
FULL)-MWL+WET
-17.879 SOIL
-2.447 -10.828

STRENGTH CONDITION - Bending Moment Criteria


Summary of Bending moments (Group No. 301)
Shear Membrane Bending Moment
SQX SQY SX SY SXY
Mx My Mxy
Plate L/C (local) (local) (local) (local) (local)
kNm/m kNm/m kNm/m
kN/m2 kN/m2 kN/m2 kN/m2 kN/m2
Max Qx 13079 553 1.5*(DL + LL
248.9
+ HL(1 120.8
CHANNEL235.7
EMPTY-93.7
& ALL OTHERS
34.8 FULL)-MWL
-13.3 +
-8.446
W.S.) -3.355
Min Qx 12812 551 1.5*(DL + LL
-311.9
+ HL(FULL)-MWL
-164.3 -622.6
+ WET-122.5
SOIL) -211.2 17.192 -2.172 -3.392
Max Qy 13085 553 1.5*(DL + LL96.1
+ HL(1 314.1
CHANNEL131
EMPTY 37.6
& ALL OTHERS
132.3 FULL)-MWL
-4.22 +2.337
W.S.) -3.982
Min Qy 13085 631 DL + HL(FULL)-TOW
-117.2 -286.5 -203.5 -158.4 -467.7 4.408 -4.536 2.175
Max Sx 13073 562 1.5*(DL + HL(1-CHANNEL,
201.8 -31.3 WW
258.1
EMPTY))-MWL
-41.5 +-70.9
WET SOIL)
-16.188 -7.702 -2.739
Min Sx 12812 621 DL + LL + HL(FULL)-TOW
-57.7 -51.2 -717.6 -91.6 -186.2 2.596 0.054 -0.086
Max Sy 12815 621 DL + LL + HL(FULL)-TOW
-35.1 3.8 -71.9 58.7 -131.3 -2.662 -0.159 -0.506
Min Sy 12867 591 1.5*(DL + LL + HL(FULL)-MWL)
9 -22.8 22 -631.4 -396.8 -0.816 -3.531 -0.905
Max Sxy 12684 591 1.5*(DL + LL32.7
+ HL(FULL)-MWL)
-45.1 27.2 -41.6 429.6 -1.298 -6.897 2.94
Min Sxy 12859 621 DL + LL + HL(FULL)-TOW
-11.2 -28 135.3 22.1 -684.4 -1.363 -2.157 -0.673
Max Mx 12811 551 1.5*(DL + LL
186.1
+ HL(FULL)-MWL
-207.9 -419.7
+ WET SOIL)
-45.5 -208.2 21.508 0.031 4.362
Min Mx 12815 551 1.5*(DL + LL-239
+ HL(FULL)-MWL
9.3 -9.7
+ WET SOIL)
42.9 -114.7 -21.627 -1.524 -2.168
Max My 12953 551 1.5*(DL + LL +2.7
HL(FULL)-MWL
161.3 -39.6
+ WET-393.3
SOIL) 98.7 2.331 13.739 1.908
Min My 12674 551 1.5*(DL + LL +5.8
HL(FULL)-MWL
-149.3 -23.7
+ WET-387.8
SOIL) 237 -2.637 -15.014 1.582
Max Mxy 12811 551 1.5*(DL + LL
186.1
+ HL(FULL)-MWL
-207.9 -419.7
+ WET SOIL)
-45.5 -208.2 21.508 0.031 4.362
Min Mxy 13039 553 1.5*(DL + LL
-62.9
+ HL(1 -19.5
CHANNEL
-247.5
EMPTY-41.1
& ALL OTHERS
-169.9 FULL)-MWL
-1.45 +
-1.984
W.S.) -5.85
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG
JV
Summary of forces from Staad
Bending Moments, kNm/m
Wall Type
Service Condition +veMx -veMx +veMy -veMy
W6 17.25 33.24 10.43 11.06

Strength Condition
Shear Stress,
2 Bending Moments, kNm/m
Type N/mm
SQX SQY +veMx -veMx +veMy -veMy
Wall 311.90 314.10 25.87 23.80 15.65 16.60

Maximum Moments of W7
X-DIRECTION (Horz.) Y-DIRECTION (Vert.)
Design for Bending moment Inside Out side Inside Out side
MX MX MY MY

Factored Moment(kN-m) 25.87 23.80 15.65 16.60

Grade of concrete,fck (N/mm2) 30 30 30 30


2
Grade of steel,fy (N/mm ) 500 500 500 500
Width of section,b (mm) 1000 1000 1000 1000
Thickness of section,h(mm) 300 300 300 300
Cover to reinforcement(mm) 60 60 60 60
2
Mu/bd 0.525 0.483 0.286 0.304

Area of Design steel required(mm2) 274 252 156 166


2
Area of Minimum steel required(mm ) 360 360 360 360

Area of steel provided(mm2) 754 754 754 754


Area of Steel provided OK OK OK OK
Dia of Main rebar(mm) 12 12 12 12
Spacing of main bars 150 150 150 150
Effective depth,d(mm) 222 222 234 234
%pt provided 0.340 0.340 0.322 0.322
2
Es(N/mm ) 200000 200000 200000 200000

Ece(N/mm2) 27386 27386 27386 27386


m= Es/Ece 7.303 7.303 7.303 7.303
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG
JV
Depth of
Neutral axis 44.24 44.24 45.56 45.56

x=(sqrt((m.Ast)2 + 2xmAst)-mxAst)xd

Lever arm (mm) =d-x/3 207.25 207.25 218.81 218.81


2
fs (N/mm ) =M/AstxZ 110.37 212.71 63.22 67.06
h (mm) 300 300 300 300

ε1=(fs/Es)*((a'-x)/(d-x)) 0.0008 0.0015 0.0004 0.0005


ε2== 1.5 .b . (h-X)2/(3.Es.As.(d-X)) 0.0012 0.0012 0.0011 0.0011
ε1-ε2 -0.0004 0.0003 -0.0007 -0.0007
acr 93.90 93.90 93.90 93.90

Wcr(mm) 0.001 0.069 0.001 0.001


SAFE SAFE SAFE SAFE

Check for Shear Stress

Maximum
% of steel Ʈc from Table 19
Shear Check shear Check
provided of IS 456-2000
stress, Ʈv

X direction 311.90 0.340 0.422 Ʈc * < Ʈv CHK


Y direction 314.10 0.322 0.412 Ʈc * < Ʈv CHK

Design Table Explanation for Bending moment


density, W= 10.050 Kn/Cum
B.M for Water,M1 33.239 KN-m
Mu= (M) x 1.5 25.870 KN-m
D= 300.00 mm
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG
JV
Cover to steel 60.00 mm
Bar Diameter adopted 12.00 mm
d= 234.00 mm
b= 1000.00 mm
Mu/b/d/d 0.472 Mpa
Steel Grade 500.00 Mpa
Concrete Grade 30.00 Mpa
Refer Mu formula SP16 page 10 Pt= 0.111

Ast= 259 Sqmm/M


Min. steel 0.24% required 360 Sqmm
Required Reinforcement 360 Sqmm
Provided Reinforcement 754.0 Sqmm

Required Spacing 314.159 mm


Provided Net Spacing 150.00 mm

Provided Rebar T12+T12


Provided Spacing for T12+T12 300.000 mm
OK

Design for shear at Base:-


Pt provided 0.322 %
0.314 Mpa
0.41 Mpa
OK

Design Explanation for Crack Width Cal Table

Applied Service Moment " Ms " = 33.24 KNm


Bar Dia = 12 mm
Maximum Bar Spacing " S " = 150 mm
Area of Reinforcement " As " = 754 mm2
Grade of Concrete Used (fcu) = 30 N/mm2
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG
JV
2
Grade of Steel Used (fy) = 500 N/mm
Width of Section b = 1000 mm
Thickness of Section h = 300.000 mm
Minimum Cover to Tension Reinforcement " CO " = 60 mm
Effective Depth of Section " d " = 234 mm
" acr " = (((S/2)^2 + (CO + DIA/2 )^2)^(1/2)-DIA/2) = 93.90 mm

Distance From the Point Considered to the Surface of Nearest Longitudinal bar
Applied Service Axial Force, T 0.00 KN
Moduli of Elasticity of Concrete " Ec " = 5000x ( sqrt(fcu) ) = 27.39 KN/mm2
Moduli of Elasticity of Steel " Es " = 200.00 KN/mm2
Modular Ratio " a " = (Es/Ec) = 7.30
r = As/bd = 0.00322
a.r = 0.02
Depth of Neutral Axis, " X " = d.a.r(((1+(2/a.r))^0.5)-1) = 45.56 mm
Lever arm " Z " = ( d - X/3) = 218.81 mm
Reinforcement Stress " fs " = Ms/(As*Z)+((Tx0.5)/As) = 201.47 N/mm2
Concrete Stress " fc " = (fs*As)/(0.5*b*X) = 6.67 N/mm2
"e1 " Strain at Soffit of Concrete Slab = (fs/Es)*(h-X)/(d-X) = 0.00136
"e1 " = (fs/Es)*(h-X)/(d-X)

e2= Strain due to stiffening effect of Concrete = 0.00114 mm


e2 = 1.5 .b . (h-X)2/(3.Es.As.(d-X))

em = e1 - e2 = 0.00022 mm

Calculated Crack Width " W " = 0.04916 mm


e
W = 3.acr. m/(1+2.(acr-CO)/(h-X)) = <<0.1 OK

Crack Width check for Axial Tension


Effective Cover,dc = 78 mm
acr = 104.3 mm
Strain in tensile steel, ϵ1 = fs/Es = 0.0000 mm
Strain due to siffenening effect, ϵ2 = 0.0020 mm
Average strain at the level considered,εm = ε1-ε2 = -0.0020 mm
Surface crack width,Wcr(mm), 3.acr.ϵm = 0.00 mm
= <0.1 mm, Hence Ok
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by
KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG
JV

Check for Combined Bending & Axial tension

Factored Axial Tensile stress = 0.258 N/mm2


Factored Axial Tensile stress = 258.10 kN/sqm
Factored Moment Mu = -2.74 kNm
Ast = -27 Sqmm/M
Tu = T x D = 77.43 kN
Ast, req on both faces = 178.00 mm2
Ast, req on one side for Axial Tension = 89.00 mm2
Ast, req on one side for Flexure = -27.00 mm2
=(178/2+-27) = 62.00 mm2
Minimum Steel 0.24 %age = 360 mm2
Maximum of above = 360 mm2
Dia Rebar = 12 mm
Spacing of rebar, S = 150 mm
Provided T12-150 B.Faces = 753.98 mm2
753.98>360

Steel Provided is = OK
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

Design of Base Slab for Inlet chambers


Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

5.1) Design of Base Slab


The Geometry properties of Base Slab
Base Slab section thickness is 500mm throughout.
Crack width check is performed for base slab of Inlet chambers.
Base Slab elements are highlighted as given below

STAAD MODEL ----Base Slab of Inlet chambers - 500mm Thk.

DESIGN OF Base Slab- 500mm Thk.

SERVICE CONDITION
Summary of Bending moments
Shear Membrane Bending Moment
SQX SQY SX SY SXY
Mx My Mxy
Plate L/C (local) (local) (local) (local) (local)
kNm/m kNm/m kNm/m
N/mm2 N/mm2 N/mm2 N/mm2 N/mm2
Max Qx 8298 165 DL+HL(2 CHANNELS,
0 WW 0 EMPTY0 & ALL OTHERS
0 FULL)-MWL+WET
0 8.474 SOIL
2.542 1.154
Min Qx 8414 193 DL + LL + HL(1 0CHANNEL
0 EMPTY0& ALL OTHERS
0 FULL)-MWL
0 16.154 9.92 -0.165
Max Qy 8298 194 DL + LL + HL(INLET,OUTLET
0 0 EMPTY
0 & ALL0 OTHERS0FULL)-MWL
20.975 13.442 -0.973
Min Qy 8454 102 0.9 DL+UPLIFT 0 0 0 0 0 12.092 9.433 -0.55
Max Sx 8454 101 DL+LL 0 0 0 0 0 14.597 10.491 -1.193
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
Min Sx 8454 101 DL+LL 0 0 0 0 0 14.597 10.491 -1.193
Max Sy 8454 101 DL+LL 0 0 0 0 0 14.597 10.491 -1.193
Min Sy 8454 101 DL+LL 0 0 0 0 0 14.597 10.491 -1.193
Max Sxy 8454 101 DL+LL 0 0 0 0 0 14.597 10.491 -1.193
Min Sxy 8454 101 DL+LL 0 0 0 0 0 14.597 10.491 -1.193
Max Mx 8378 194 DL + LL + HL(INLET,OUTLET
0 0 EMPTY
0 & ALL0 OTHERS0FULL)-MWL
22.89 14.193 -0.552
Min Mx 8454 165 DL+HL(2 CHANNELS,
0 WW
0 EMPTY0 & ALL OTHERS
0 FULL)-MWL+WET
0 8.321 SOIL
2.142 1.122
Max My 8378 194 DL + LL + HL(INLET,OUTLET
0 0 EMPTY
0 & ALL0 OTHERS0FULL)-MWL
22.89 14.193 -0.552
Min My 8374 165 DL+HL(2 CHANNELS,
0 WW
0 EMPTY0 & ALL OTHERS
0 FULL)-MWL+WET
0 9.122 SOIL
1.493 -0.405
Max Mxy 8334 193 DL + LL + HL(1 0CHANNEL
0 EMPTY0& ALL OTHERS
0 FULL)-MWL
0 14.976 10.442 2.437
Min Mxy 8454 194 DL + LL + HL(INLET,OUTLET
0 0 EMPTY
0 & ALL0 OTHERS0FULL)-MWL
16.034 10.784 -1.504

STRENGTH CONDITION - Bending Moment Criteria


Summary of Bending moments (GROUP No.902)
Shear Membrane Bending Moment
SQX SQY SX SY SXY
Mx My Mxy
Plate L/C (local) (local) (local) (local) (local)
kNm/m kNm/m kNm/m
N/mm2 N/mm2 N/mm2 N/mm2 N/mm2
Max Qx 8261 621 DL + LL + HL(FULL)-TOW
0.2 0 0 0 0 -14.798 33.109 -9.158
Min Qx 8420 554 1.5*(DL+LL+HL(INLET,OUTLET
-0.3 0 EMPTY
0 & ALL
0 OTHERS
0 FULL)-MWL
-18.564 +-7.076
W.S.) -6.876
Max Qy 8276 553 1.5*(DL + LL + HL(1
0 CHANNEL
0.6 EMPTY
0 & ALL
0 OTHERS
0 FULL)-MWL
-29.987 -155.987
+ W.S.) -0.244
Min Qy 8316 621 DL + LL + HL(FULL)-TOW
0 -0.8 0 0 0 35.804 169.089 -0.737
Max Sx 8494 501 1.5*(DL + LL) 0 -0.1 0 0 0 16.22 16.87 -0.01
Min Sx 8494 501 1.5*(DL + LL) 0 -0.1 0 0 0 16.22 16.87 -0.01
Max Sy 8494 501 1.5*(DL + LL) 0 -0.1 0 0 0 16.22 16.87 -0.01
Min Sy 8494 501 1.5*(DL + LL) 0 -0.1 0 0 0 16.22 16.87 -0.01
Max Sxy 8494 501 1.5*(DL + LL) 0 -0.1 0 0 0 16.22 16.87 -0.01
Min Sxy 8494 501 1.5*(DL + LL) 0 -0.1 0 0 0 16.22 16.87 -0.01
Max Mx 8276 621 DL + LL + HL(FULL)-TOW
0 -0.8 0 0 0 51.5 268.713 -0.985
Min Mx 8274 562 1.5*(DL + HL(1-CHANNEL,
0 0.6 WW EMPTY))-MWL
0 0 + WET0 SOIL)
-33.95 -160.211 3.014
Max My 8276 621 DL + LL + HL(FULL)-TOW
0 -0.8 0 0 0 51.5 268.713 -0.985
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
Min My 8275 562 1.5*(DL + HL(1-CHANNEL,
0 0.6 WW EMPTY))-MWL
0 0 + WET0 SOIL)
-31.889 -161.821 1.35
Max Mxy 8287 621 DL + LL + HL(FULL)-TOW
-0.2 -0.3 0 0 0 21.734 123.483 14.257
Min Mxy 8265 621 DL + LL + HL(FULL)-TOW
0.1 -0.3 0 0 0 22.401 122.228 -16.102

STRENGTH CONDITION - Shear Criteria


Summary of Bending moments (Group No. 901)
Shear Membrane Bending Moment
SQX SQY SX SY SXY
Mx My Mxy
Plate L/C (local) (local) (local) (local) (local)
kNm/m kNm/m kNm/m
N/mm2 N/mm2 N/mm2 N/mm2 N/mm2
Max Qx 8298 565 1.5*(DL + 0.0000
HL(2 CHANNELS,0 WW EMPTY
0 & 0ALL OTHERS0 FULL)-MWL
12.712 +3.813
W.S.) 1.73
Min Qx 8374 623 DL + LL + HL(1
-0.1CHANNEL
0 EMPTY0& ALL OTHERS
0 FULL)-TOW
0 19.444 14.058 -0.987
Max Qy 8298 621 DL + LL + HL(FULL)-TOW
0 0 0 0 0 29.684 25.39 -5.215
Min Qy 8454 621 DL + LL + HL(FULL)-TOW
-0.1 0 0 0 0 18.174 17.132 -0.46
Max Sx 8454 501 1.5*(DL + LL) 0 0 0 0 0 21.896 15.736 -1.79
Min Sx 8454 501 1.5*(DL + LL) 0 0 0 0 0 21.896 15.736 -1.79
Max Sy 8454 501 1.5*(DL + LL) 0 0 0 0 0 21.896 15.736 -1.79
Min Sy 8454 501 1.5*(DL + LL) 0 0 0 0 0 21.896 15.736 -1.79
Max Sxy 8454 501 1.5*(DL + LL) 0 0 0 0 0 21.896 15.736 -1.79
Min Sxy 8454 501 1.5*(DL + LL) 0 0 0 0 0 21.896 15.736 -1.79
Max Mx 8378 594 1.5*(DL + LL + HL(INLET,OUTLET
0 0 0EMPTY &0 ALL OTHERS
0 34.336
FULL)-MWL)21.29 -0.827
Min Mx 8454 635 DL + HL(2 CHANNELS,
0 WW
0 EMPTY
0 & ALL 0OTHERS FULL)-TOW
0 11.201 8.557 0.024
Max My 8338 621 DL + LL + HL(FULL)-TOW
0 0 0 0 0 31.819 26.956 -3.107
Min My 8374 565 1.5*(DL + HL(2 0CHANNELS,
0 WW EMPTY
0 & 0ALL OTHERS
0 FULL)-MWL
13.683 +2.239
W.S.) -0.607
Max Mxy 8334 621 DL + LL + HL(FULL)-TOW
0 0 0 0 0 18.967 22.797 10.456
Min Mxy 8454 623 DL + LL + HL(1
-0.1CHANNEL
0 EMPTY0& ALL OTHERS
0 FULL)-TOW
0 18.388 14.204 -5.321
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

Summary of forces from Staad


Bending Moments, kNm/m
Slab Type
Service Condition +veMx -veMx +veMy -veMy

BS1 23.44 9.44 14.75 1.90

Strength Condition
Shear Stress,
Bending Moments, kNm/m
Type N/mm2
SQX SQY +veMx -veMx +veMy -veMy

Base slab 0.10 0.00 52.49 36.96 269.70 163.17

Maximum Moments of Base slab


X-DIRECTION (Horz.) Y-DIRECTION (Vert.)
Design for Bending moment Top Bottom Top Bottom
MX MX MY MY

Factored Moment(kN-m) 52.49 36.96 269.70 163.17

Grade of concrete,fck (N/mm2) 30 30 30 30

Grade of steel,fy (N/mm2) 500 500 500 500

Width of section,b (mm) 1000 1000 1000 1000

Thickness of section,h(mm) 600 600 600 600


Cover to reinforcement(mm) 60 60 60 60

Mu/bd2 0.193 0.136 0.961 0.581

Area of Design steel required(mm2) 234 165 1219 725


2
Area of Minimum steel required(mm ) 600 600 600 600

Area of steel provided(mm2) 754 754 2094 2094

Area of Steel provided OK OK OK OK

Dia of Main rebar(mm) 12 12 20 20

Spacing of main bars 150 150 150 150

Effective depth,d(mm) 522 522 530 530


Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
%pt provided 0.144 0.144 0.395 0.395
2
Es(N/mm ) 200000 200000 200000 200000

Ece(N/mm2) 27386 27386 27386 27386

m= Es/Ece 7.303 7.303 7.303 7.303


Depth of
Neutral axis 70.51 70.51 112.95 112.95

x=(sqrt((m.Ast)2 + 2xmAst)-mxAst)xd

Lever arm (mm) =d-x/3 498.50 498.50 492.35 492.35


2
fs (N/mm ) =M/AstxZ 62.37 25.12 14.30 1.84
h (mm) 600 600 600 600

ε1=(fs/Es)*((a'-x)/(d-x)) 0.0004 0.0001 0.0001 0.0000

ε2== 1.5 .b . (h-X)2/(3.Es.As.(d-X)) 0.0021 0.0021 0.0007 0.0007

ε1-ε2 -0.0017 -0.0019 -0.0006 -0.0007


acr 93.90 93.90 92.59 92.59

Wcr(mm) 0.001 0.001 0.001 0.001


SAFE SAFE SAFE SAFE

Check for Shear Stress

Maximum
% of steel Ʈc from Table 19
Shear Check shear Check
provided of IS 456-2000
stress, Ʈv

X direction 0.10 0.144 0.29 Ʈc * > Ʈv OK


Y direction 0.00 0.395 0.450 Ʈc * > Ʈv OK

Design Table Explanation for Bending moment


density, W= 10.050 Kn/Cum
Wall Height, H 7.910 m
Water height, h= 7.910 m
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
B.M for Water,M1 23.442 KN-m
Mu= (M) x 1.5 269.698 KN-m
D= 600.00 mm
Cover to steel 60.00 mm
Bar Diameter adopted 20.00 mm
d= 530.00 mm
b= 1000.00 mm
Mu/b/d/d 0.960 Mpa
Steel Grade 500.00 Mpa
Concrete Grade 30.00 Mpa
Refer Mu formula SP16 page 10 Pt= 0.230

Ast= 1216 Sqmm/M


Min. steel 0.24% required 600 Sqmm
Required Reinforcement 1216 Sqmm
Provided Reinforcement 2094.4 Sqmm

Required Spacing 258.355 mm


Provided Net Spacing 150.00 mm

Provided Rebar T20+T20

Provided Spacing for T20+T20 300.000 mm


OK

Design for shear at Base:-


Pt provided 0.395 %
0.100 Mpa
0.45 Mpa
OK
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV
Design Explanation for Crack Width Cal Table

Applied Service Moment " Ms " = 23.44 KNm


Bar Dia = 12 mm
Maximum Bar Spacing " S " = 150 mm
Area of Reinforcement " As " = 2094 mm2
Grade of Concrete Used (fcu) = 30 N/mm2

Grade of Steel Used (fy) = 500 N/mm2

Width of Section b = 1000 mm


Thickness of Section h = 600 mm
Minimum Cover to Tension Reinforcement " CO " = 60 mm
Effective Depth of Section " d " = 534 mm
" acr " = (((S/2)^2 + (CO + DIA/2 )^2)^(1/2)-DIA/2) = 93.90 mm

Distance From the Point Considered to the Surface of Nearest Longitudinal bar
Applied Service Axial Force, T 0.00 KN
Moduli of Elasticity of Concrete " Ec " = 5000x ( sqrt(fcu) ) = 27.39 KN/mm2
Moduli of Elasticity of Steel " Es " = 200.00 KN/mm2

Modular Ratio " a " = (Es/Ec) = 7.30


r = As/bd = 0.00392
a.r = 0.03
Depth of Neutral Axis, " X " = d.a.r(((1+(2/a.r))^0.5)-1) = 113.43 mm
Lever arm " Z " = ( d - X/3) = 496.19 mm
Reinforcement Stress " fs " = Ms/(As*Z)+((Tx0.5)/As) = 22.56 N/mm2
Concrete Stress " fc " = (fs*As)/(0.5*b*X) = 0.83 N/mm2

"e1 " Strain at Soffit of Concrete Slab = (fs/Es)*(h-X)/(d-X) = 0.00013


"e1 " = (fs/Es)*(h-X)/(d-X)

e2= Strain due to stiffening effect of Concrete = 0.00067 mm


e2 = 1.5 .b . (h-X)2/(3.Es.As.(d-X))
em = e1 - e2 = -0.00054 mm

Calculated Crack Width " W " = -0.13388 mm


W = 3.acr. em/(1+2.(acr-CO)/(h-X)) = <<<<0.1 OK
Sewerage Facilities to 110 Villages: Design, Engineering,
Construction and Commissioning of Sewage Treatment Plants
and Intermediate Sewage Pumping Stations with Operation &
Design
Project Maintenance thereof for Seven Years [Works - A] and VM
by
Procurement and Construction of Main Sewers including
Manholes in Dasarahalli and R R Nagar Zones
(V Valley Catchment) [Works – B]
Structural design calculation of Receiving chamber, Coarse Screen, Checked
Doc. Title VM
Wet Well, Pumping Station & Flowmeter chamber by

KBR-AIPPL- Doc. No. BWSSP III/27/DAS/ISPS/HER/CV/CL/4001 R0 Apprd. by AMG


JV

Crack Width check for Axial Tension


Effective Cover,dc = 82 mm
acr = 110.0 mm
Strain in tensile steel, ϵ1 = fs/Es = 0.0000 mm
Strain due to siffenening effect, ϵ2 = 0.0040 mm
Average strain at the level considered,εm = ε1-ε2 = -0.0040 mm
Surface crack width,Wcr(mm), 3.acr.ϵm = 0.00 mm
= <0.1 mm, Hence Ok
Check for Combined Bending & Axial tension

Factored Axial Tensile stress = 0.00 N/mm2


Factored Axial Tensile stress = 0.00 kN/sqm
Factored Moment Mu = 16.87 kNm
Ast = 73 Sqmm/M
Tu = T x D = 0.00 kN
Ast, req on both faces = 0.00 mm2
Ast, req on one side for Axial Tension = 0.00 mm2
Ast, req on one side for Flexure = 73.00 mm2
=(0/2+73) = 73.00 mm2
Minimum Steel 0.24 %age = 720 mm2
Maximum of above = 720 mm2
Dia Rebar = 12 mm
Spacing of rebar, S = 150 mm
Provided T12-150 B.Faces = 753.98 mm2
753.98>720

Steel Provided is = OK

You might also like