Diameter Max Depth Class of

(inch) (ft) RCC Pipe


24 14.6 IV
27 11.8 IV
30 12.4 IV
36 16.6 IV
42 17.8 IV
48 16.0 IV
54 13.9 IV
66 16.4 IV
72 17.7 IV
Vertical Load on Sewer Pipe
Kh Cd
Wd = CdwB d
2 0.8 0.73
1 1 3.0 4.0
Where 1.5 1.25 2.1 2.5
2 1.57
dist diff 1
Wd : Total vertical load on pipe in pounds per linear foot 2.5 1.85 level diff 0.4 5834
Cd : Load coefficient for trench installation 3 2.1 0.4 3
w : Weight per cubic foot of fill, pounds 4 2.5 0.01355 4
Bd : Trench width at top of pipe, feet 5 2.8 2.114 5
H : Heigth of fill over top of sewer, feet 6 3.03 6
7 3.23 7
w : 120 lb/ft3 For Lahore Only 8 3.4 8
Sewer Size : 24 inch 9 3.5 9
H : 14.6 ft 10 3.6 10
Bd : 4.8 ft 15 3.8 11
kh : 3.0 16 3.8 12
Cd : 2.110 17 3.8 13

Depth of Sewer Pipe


Wd : 5834 lb/lin-ft 18 3.8 14
19 3.8 15
Allowance Load 20 3.8 16
17
Wc : (Lf x B x D-load)/Safety Factor 18
19
Where 20
21
Wc : Max Allowable load on pipe in pounds per linear foot 22
B : Internal pipe diameter, feet 23
D-load : Three - edge load for ultimate failure 24
Safety factor : 1.5 for concrete pipe 25
Lf : 1.9 Load factor for crushed stone bedding 26
27
D-load for Class I Sewer : 1200 lb/lin ft. ft diam 28
D-load for Class II Sewer : 1500 lb/lin ft. ft diam 29
D-load for Class III Sewer : 2000 lb/lin ft. ft diam 30
D-load for Class IV Sewer : 3000 lb/lin ft. ft diam 4.54 0.160651 31
D-load for Class V Sewer : 3750 lb/lin ft. ft diam 28.26 32
33
34
Wc for Class I Sewer : 3040 FAIL 35
Wc for Class II Sewer : 3800 FAIL 36
Wc for Class III Sewer : 5067 FAIL Max 14.6 IV
Wc for Class IV Sewer : 7600 OK

24 9.9
24 13.4
24 14.6
24 8.4
24 14.2
24 8.3
24 10.2
Diameter of RCC Pipe
9.0 12.0 15.0 18.0 21.0 24.0 27.0 30.0 33.0 36.0 42.0 48.0 54.0 60.0 66.0 72.0
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A
#N/A #N/A
#N/A
Vertical Load on Sewer Pipe
Kh Cd
Wd = CdwB d
2 0.8 0.73
1 1 2.0 3.0
Where 1.5 1.25 1.57 2.1
2 1.57
dist diff 1
Wd : Total vertical load on pipe in pounds per linear foot 2.5 1.85 level diff 0.53 5549
Cd : Load coefficient for trench installation 3 2.1 0.53 3
w : Weight per cubic foot of fill, pounds 4 2.5 0.143243 4
Bd : Trench width at top of pipe, feet 5 2.8 1.713 5
H : Heigth of fill over top of sewer, feet 6 3.03 6
7 3.23 7
w : 120 lb/ft3 For Lahore Only 8 3.4 8
Sewer Size : 27 inch 9 3.5 9
H : 11.8 ft 10 3.6 10
Bd : 5.2 ft 15 3.8 11
kh : 2.3 16 3.8 12
Cd : 1.710 17 3.8 13

Depth of Sewer Pipe


Wd : 5549 lb/lin-ft 18 3.8 14
19 3.8 15
Allowance Load 20 3.8 16
17
Wc : (Lf x B x D-load)/Safety Factor 18
19
Where 20
21
Wc : Max Allowable load on pipe in pounds per linear foot 22
B : Internal pipe diameter, feet 23
D-load : Three - edge load for ultimate failure 24
Safety factor : 1.5 for concrete pipe 25
Lf : 1.9 Load factor for crushed stone bedding 26
27
D-load for Class I Sewer : 1200 lb/lin ft. ft diam 28
D-load for Class II Sewer : 1500 lb/lin ft. ft diam 29
D-load for Class III Sewer : 2000 lb/lin ft. ft diam 30
D-load for Class IV Sewer : 3000 lb/lin ft. ft diam 4.54 0.160651 31
D-load for Class V Sewer : 3750 lb/lin ft. ft diam 28.26 32
33
34
Wc for Class I Sewer : 3420 FAIL 35
Wc for Class II Sewer : 4275 FAIL 36
Wc for Class III Sewer : 5700 OK Max 11.8 IV

27 11.81
27 7.26
27 9.9
Diameter of RCC Pipe
9.0 12.0 15.0 18.0 21.0 24.0 27.0 30.0 33.0 36.0 42.0 48.0 54.0 60.0 66.0 72.0
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A
#N/A #N/A
#N/A
Vertical Load on Sewer Pipe
Kh Cd
Wd = CdwB d
2 0.8 0.73
1 1 2.0 3.0
Where 1.5 1.25 1.57 2.1
2 1.57
dist diff 1
Wd : Total vertical load on pipe in pounds per linear foot 2.5 1.85 level diff 0.53 6322
Cd : Load coefficient for trench installation 3 2.1 0.53 3
w : Weight per cubic foot of fill, pounds 4 2.5 0.114272 4
Bd : Trench width at top of pipe, feet 5 2.8 1.684 5
H : Heigth of fill over top of sewer, feet 6 3.03 6
7 3.23 7
w : 120 lb/ft3 For Lahore Only 8 3.4 8
Sewer Size : 30 inch 9 3.5 9
H : 12.4 ft 10 3.6 10
Bd : 5.6 ft 15 3.8 11
kh : 2.2 16 3.8 12
Cd : 1.680 17 3.8 13

Depth of Sewer Pipe


Wd : 6322 lb/lin-ft 18 3.8 14
19 3.8 15
Allowance Load 20 3.8 16
17
Wc : (Lf x B x D-load)/Safety Factor 18
19
Where 20
21
Wc : Max Allowable load on pipe in pounds per linear foot 22
B : Internal pipe diameter, feet 23
D-load : Three - edge load for ultimate failure 24
Safety factor : 1.5 for concrete pipe 25
Lf : 1.9 Load factor for crushed stone bedding 26
27
D-load for Class I Sewer : 1200 lb/lin ft. ft diam 28
D-load for Class II Sewer : 1500 lb/lin ft. ft diam 29
D-load for Class III Sewer : 2000 lb/lin ft. ft diam 30
D-load for Class IV Sewer : 3000 lb/lin ft. ft diam 4.54 0.160651 31
D-load for Class V Sewer : 3750 lb/lin ft. ft diam 28.26 32
33
34
Wc for Class I Sewer : 3800 FAIL 35
Wc for Class II Sewer : 4750 FAIL 36
Wc for Class III Sewer : 6333 OK Max 12.4 IV
8.0 6.0 48.00 0.000280
9.0 6.0 54.00 0.000260
9.0 6.5 58.50 0.000250
9.0 6.5 58.50 0.000250
9.0 6.5 58.50 0.000250
30 12.4 10.0 7.5 75.00 0.000210
30 7.4 10.0 7.5 75.00 0.000210
30 9.3 10.0 7.5 75.00 0.000210
10.0 8.0 80.00 0.000200
10.0 8.0 80.00 0.000200
10.0 8.0 80.00 0.000200
10.0 8.0 80.00 0.000200
10.0 8.0 80.00 0.000200
10.0 8.0 80.00 0.000200
Diameter of RCC Pipe
9.0 12.0 15.0 18.0 21.0 24.0 27.0 30.0 33.0 36.0 42.0 48.0 54.0 60.0 66.0 72.0
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A
#N/A #N/A
#N/A
Vertical Load on Sewer Pipe
Kh Cd
Wd = CdwB d
2 0.8 0.73
1 1 2.0 3.0
Where 1.5 1.25 1.57 2.1
2 1.57
dist diff 1
Wd : Total vertical load on pipe in pounds per linear foot 2.5 1.85 level diff 0.53 9097
Cd : Load coefficient for trench installation 3 2.1 0.53 3
w : Weight per cubic foot of fill, pounds 4 2.5 0.340697 4
Bd : Trench width at top of pipe, feet 5 2.8 1.911 5
H : Heigth of fill over top of sewer, feet 6 3.03 6
7 3.23 7
w : 120 lb/ft3 For Lahore Only 8 3.4 8
Sewer Size : 36 inch 9 3.5 9
H : 16.6 ft 10 3.6 10
Bd : 6.3 ft 15 3.8 11
kh : 2.6 16 3.8 12
Cd : 1.910 17 3.8 13

Depth of Sewer Pipe


Wd : 9097 lb/lin-ft 18 3.8 14
19 3.8 15
Allowance Load 20 3.8 16
17
Wc : (Lf x B x D-load)/Safety Factor 18
19
Where 20
21
Wc : Max Allowable load on pipe in pounds per linear foot 22
B : Internal pipe diameter, feet 23
D-load : Three - edge load for ultimate failure 24
Safety factor : 1.5 for concrete pipe 25
Lf : 1.9 Load factor for crushed stone bedding 26
27
D-load for Class I Sewer : 1200 lb/lin ft. ft diam 28
D-load for Class II Sewer : 1500 lb/lin ft. ft diam 29
D-load for Class III Sewer : 2000 lb/lin ft. ft diam 30
D-load for Class IV Sewer : 3000 lb/lin ft. ft diam 4.54 0.160651 31
D-load for Class V Sewer : 3750 lb/lin ft. ft diam 28.26 32
33
34
Wc for Class I Sewer : 4560 FAIL 35
Wc for Class II Sewer : 5700 FAIL 36
Wc for Class III Sewer : 7600 FAIL Max 16.6 IV
Wc for Class IV Sewer : 11400 OK 8.0 6.0 48.00 0.000280
9.0 6.0 54.00 0.000260
9.0 6.5 58.50 0.000250
9.0 6.5 58.50 0.000250
9.0 6.5 58.50 0.000250
36 16.5 10.0 7.5 75.00 0.000210
36 16.6 10.0 7.5 75.00 0.000210
36 13.5 10.0 7.5 75.00 0.000210
36 14.9 10.0 8.0 80.00 0.000200
36 15.8 10.0 8.0 80.00 0.000200
36 15.5 10.0 8.0 80.00 0.000200
36 16.6 10.0 8.0 80.00 0.000200
36 15.6 10.0 8.0 80.00 0.000200
10.0 8.0 80.00 0.000200
Diameter of RCC Pipe
9.0 12.0 15.0 18.0 21.0 24.0 27.0 30.0 33.0 36.0 42.0 48.0 54.0 60.0 66.0 72.0
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A
#N/A #N/A
#N/A
Vertical Load on Sewer Pipe
Kh Cd
Wd = CdwB d
2 0.8 0.73
1 1 2.0 3.0
Where 1.5 1.25 1.57 2.1
2 1.57
dist diff 1
Wd : Total vertical load on pipe in pounds per linear foot 2.5 1.85 level diff 0.53 11511
Cd : Load coefficient for trench installation 3 2.1 0.53 3
w : Weight per cubic foot of fill, pounds 4 2.5 0.229555 4
Bd : Trench width at top of pipe, feet 5 2.8 1.800 5
H : Heigth of fill over top of sewer, feet 6 3.03 6
7 3.23 7
w : 120 lb/ft3 For Lahore Only 8 3.4 8
Sewer Size : 42 inch 9 3.5 9
H : 17.8 ft 10 3.6 10
Bd : 7.3 ft 15 3.8 11
kh : 2.4 16 3.8 12
Cd : 1.800 17 3.8 13

Depth of Sewer Pipe


Wd : 11511 lb/lin-ft 18 3.8 14
19 3.8 15
Allowance Load 20 3.8 16
17
Wc : (Lf x B x D-load)/Safety Factor 18
19
Where 20
21
Wc : Max Allowable load on pipe in pounds per linear foot 22
B : Internal pipe diameter, feet 23
D-load : Three - edge load for ultimate failure 24
Safety factor : 1.5 for concrete pipe 25
Lf : 1.9 Load factor for crushed stone bedding 26
27
D-load for Class I Sewer : 1200 lb/lin ft. ft diam 28
D-load for Class II Sewer : 1500 lb/lin ft. ft diam 29
D-load for Class III Sewer : 2000 lb/lin ft. ft diam 30
D-load for Class IV Sewer : 3000 lb/lin ft. ft diam 4.54 0.160651 31
D-load for Class V Sewer : 3750 lb/lin ft. ft diam 28.26 32
33
34
Wc for Class I Sewer : 5320 FAIL 35
Wc for Class II Sewer : 6650 FAIL 36
Wc for Class III Sewer : 8867 FAIL Max 17.8 IV
Wc for Class IV Sewer : 13300 OK

42 12.26
42 17.8
42 14.1
Diameter of RCC Pipe
9.0 12.0 15.0 18.0 21.0 24.0 27.0 30.0 33.0 36.0 42.0 48.0 54.0 60.0 66.0 72.0
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A
#N/A #N/A
#N/A
Vertical Load on Sewer Pipe
Kh Cd
Wd = CdwB d
2 0.8 0.73
1 1 2.0 3.0
Where 1.5 1.25 1.57 2.1
2 1.57
dist diff 1
Wd : Total vertical load on pipe in pounds per linear foot 2.5 1.85 level diff 0.53 11681
Cd : Load coefficient for trench installation 3 2.1 0.53 3
w : Weight per cubic foot of fill, pounds 4 2.5 0.028702 4
Bd : Trench width at top of pipe, feet 5 2.8 1.599 5
H : Heigth of fill over top of sewer, feet 6 3.03 6
7 3.23 7
w : 120 lb/ft3 For Lahore Only 8 3.4 8
Sewer Size : 48 inch 9 3.5 9
H : 16.0 ft 10 3.6 10
Bd : 7.8 ft 15 3.8 11
kh : 2.1 16 3.8 12
Cd : 1.600 17 3.8 13

Depth of Sewer Pipe


Wd : 11681 lb/lin-ft 18 3.8 14
19 3.8 15
Allowance Load 20 3.8 16
17
Wc : (Lf x B x D-load)/Safety Factor 18
19
Where 20
21
Wc : Max Allowable load on pipe in pounds per linear foot 22
B : Internal pipe diameter, feet 23
D-load : Three - edge load for ultimate failure 24
Safety factor : 1.5 for concrete pipe 25
Lf : 1.9 Load factor for crushed stone bedding 26
27
D-load for Class I Sewer : 1200 lb/lin ft. ft diam 28
D-load for Class II Sewer : 1500 lb/lin ft. ft diam 29
D-load for Class III Sewer : 2000 lb/lin ft. ft diam 30
D-load for Class IV Sewer : 3000 lb/lin ft. ft diam 4.54 0.160651 31
D-load for Class V Sewer : 3750 lb/lin ft. ft diam 28.26 32
33
34
Wc for Class I Sewer : 6080 FAIL 35
Wc for Class II Sewer : 7600 FAIL 36
Wc for Class III Sewer : 10133 FAIL Max 16.0 IV
Wc for Class IV Sewer : 15200 OK

48 16.0
48 15.6
48 14.8
Diameter of RCC Pipe
9.0 12.0 15.0 18.0 21.0 24.0 27.0 30.0 33.0 36.0 42.0 48.0 54.0 60.0 66.0 72.0
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A
#N/A #N/A
#N/A
Vertical Load on Sewer Pipe
Kh Cd
Wd = CdwB d
2 0.8 0.73
1 1 1.0 2.0
Where 1.5 1.25 1 1.57
2 1.57
dist diff 1
Wd : Total vertical load on pipe in pounds per linear foot 2.5 1.85 level diff 0.57 11600
Cd : Load coefficient for trench installation 3 2.1 0.57 3
w : Weight per cubic foot of fill, pounds 4 2.5 0.372213 4
Bd : Trench width at top of pipe, feet 5 2.8 1.372 5
H : Heigth of fill over top of sewer, feet 6 3.03 6
7 3.23 7
w : 120 lb/ft3 For Lahore Only 8 3.4 8
Sewer Size : 54 inch 9 3.5 9
H : 13.9 ft 10 3.6 10
Bd : 8.4 ft 15 3.8 11
kh : 1.7 16 3.8 12
Cd : 1.370 17 3.8 13

Depth of Sewer Pipe


Wd : 11600 lb/lin-ft 18 3.8 14
19 3.8 15
Allowance Load 20 3.8 16
17
Wc : (Lf x B x D-load)/Safety Factor 18
19
Where 20
21
Wc : Max Allowable load on pipe in pounds per linear foot 22
B : Internal pipe diameter, feet 23
D-load : Three - edge load for ultimate failure 24
Safety factor : 1.5 for concrete pipe 25
Lf : 1.9 Load factor for crushed stone bedding 26
27
D-load for Class I Sewer : 1200 lb/lin ft. ft diam 28
D-load for Class II Sewer : 1500 lb/lin ft. ft diam 29
D-load for Class III Sewer : 2000 lb/lin ft. ft diam 30
D-load for Class IV Sewer : 3000 lb/lin ft. ft diam 4.54 0.160651 31
D-load for Class V Sewer : 3750 lb/lin ft. ft diam 28.26 32
33
34
Wc for Class I Sewer : 6840 FAIL 35
Wc for Class II Sewer : 8550 FAIL 36
Wc for Class III Sewer : 11400 FAIL Max 13.9 IV
Wc for Class IV Sewer : 17100 OK

54 13.9
Diameter of RCC Pipe
9.0 12.0 15.0 18.0 21.0 24.0 27.0 30.0 33.0 36.0 42.0 48.0 54.0 60.0 66.0 72.0
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A
#N/A #N/A
#N/A
Vertical Load on Sewer Pipe
Kh Cd
Wd = CdwB d
2 0.8 0.73
1 1 1.0 2.0
Where 1.5 1.25 1 1.57
2 1.57
dist diff 1
Wd : Total vertical load on pipe in pounds per linear foot 2.5 1.85 level diff 0.57 15483
Cd : Load coefficient for trench installation 3 2.1 0.57 3
w : Weight per cubic foot of fill, pounds 4 2.5 0.401176 4
Bd : Trench width at top of pipe, feet 5 2.8 1.401 5
H : Heigth of fill over top of sewer, feet 6 3.03 6
7 3.23 7
w : 120 lb/ft3 For Lahore Only 8 3.4 8
Sewer Size : 66 inch 9 3.5 9
H : 16.4 ft 10 3.6 10
Bd : 9.6 ft 15 3.8 11
kh : 1.7 16 3.8 12
Cd : 1.400 17 3.8 13

Depth of Sewer Pipe


Wd : 15483 lb/lin-ft 18 3.8 14
19 3.8 15
Allowance Load 20 3.8 16
17
Wc : (Lf x B x D-load)/Safety Factor 18
19
Where 20
21
Wc : Max Allowable load on pipe in pounds per linear foot 22
B : Internal pipe diameter, feet 23
D-load : Three - edge load for ultimate failure 24
Safety factor : 1.5 for concrete pipe 25
Lf : 1.9 Load factor for crushed stone bedding 26
27
D-load for Class I Sewer : 1200 lb/lin ft. ft diam 28
D-load for Class II Sewer : 1500 lb/lin ft. ft diam 29
D-load for Class III Sewer : 2000 lb/lin ft. ft diam 30
D-load for Class IV Sewer : 3000 lb/lin ft. ft diam 4.54 0.160651 31
D-load for Class V Sewer : 3750 lb/lin ft. ft diam 28.26 32
33
34
Wc for Class I Sewer : 8360 FAIL 35
Wc for Class II Sewer : 10450 FAIL 36
Wc for Class III Sewer : 13933 FAIL Max 16.4 IV
Wc for Class IV Sewer : 20900 OK

66 16.0
66 16.4
66 15.9
66 16.1
Diameter of RCC Pipe
9.0 12.0 15.0 18.0 21.0 24.0 27.0 30.0 33.0 36.0 42.0 48.0 54.0 60.0 66.0 72.0
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A
#N/A #N/A
#N/A
Vertical Load on Sewer Pipe
Kh Cd
Wd = CdwB d
2 0.8 0.73
1 1 1.0 2.0
Where 1.5 1.25 1 1.57
2 1.57
dist diff 1
Wd : Total vertical load on pipe in pounds per linear foot 2.5 1.85 level diff 0.57 17728
Cd : Load coefficient for trench installation 3 2.1 0.57 3
w : Weight per cubic foot of fill, pounds 4 2.5 0.418823 4
Bd : Trench width at top of pipe, feet 5 2.8 1.419 5
H : Heigth of fill over top of sewer, feet 6 3.03 6
7 3.23 7
w : 120 lb/ft3 For Lahore Only 8 3.4 8
Sewer Size : 72 inch 9 3.5 9
H : 17.7 ft 10 3.6 10
Bd : 10.2 ft 15 3.8 11
kh : 1.7 16 3.8 12
Cd : 1.420 17 3.8 13

Depth of Sewer Pipe


Wd : 17728 lb/lin-ft 18 3.8 14
19 3.8 15
Allowance Load 20 3.8 16
17
Wc : (Lf x B x D-load)/Safety Factor 18
19
Where 20
21
Wc : Max Allowable load on pipe in pounds per linear foot 22
B : Internal pipe diameter, feet 23
D-load : Three - edge load for ultimate failure 24
Safety factor : 1.5 for concrete pipe 25
Lf : 1.9 Load factor for crushed stone bedding 26
27
D-load for Class I Sewer : 1200 lb/lin ft. ft diam 28
D-load for Class II Sewer : 1500 lb/lin ft. ft diam 29
D-load for Class III Sewer : 2000 lb/lin ft. ft diam 30
D-load for Class IV Sewer : 3000 lb/lin ft. ft diam 4.54 0.160651 31
D-load for Class V Sewer : 3750 lb/lin ft. ft diam 28.26 32
33
34
Wc for Class I Sewer : 9120 FAIL 35
Wc for Class II Sewer : 11400 FAIL 36
Wc for Class III Sewer : 15200 FAIL Max 17.7 IV
Wc for Class IV Sewer : 22800 OK

72 12.1 15.0
72 12.3 17.3
72 12.4 15.2
72 13.3 14.9
72 13.5 14.9
72 13.8 15.1
72 13.0 17.7
Diameter of RCC Pipe
9.0 12.0 15.0 18.0 21.0 24.0 27.0 30.0 33.0 36.0 42.0 48.0 54.0 60.0 66.0 72.0
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A #N/A #N/A
#N/A #N/A #N/A #N/A
#N/A #N/A
#N/A

You might also like