Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

NEW DEVELOPMENTS IN LOW VOLTAGE AIR CIRCUIT BREAKER TECHNOLOGY

Tom Craig

Terasaki Europe Ltd, UK

INTRODUCTION

Protection within the Low Voltage (L.V.) area of The majority of ACBs used are draw-out pattern to
power distribution is often not given the same provide easier access to the ACB and additional
coverage in technical publications as its medium and isolation which maintenance procedures may require.
high voltage relatives. This requires the use of isolating contacts for the
However, from the end user prospective, it is often interconnection between body and chassis.
regarded as perhaps the most critical area of the Transferring these isolating contacts from the
system due to its close proximity and effect on final chassis to the body and ‘directly connecting them to
loads. the ACBs fixed contacts, substantially reduces the
In low voltage networks one of the main items of depth of the ACB.
protection equipment, responsible for the safe As the name suggests, the interrupting medium of
distribution of electrical energy is the Air Circuit the ACB is air and therefore sufficient space is
Breaker (ACB). required between the contacts to ensure effective arc
This is the gatekeeper of the system, often referred extinction. Generally, due to space requirements, the
to as the incomer. It is the highest amp rated device majority of ACBs use one contact break per pole to
within the L.V. distribution network and is often used interrupt any short circuit.
on the secondary of distribution transformers, bus- However, introduction of a symmetrical
couplers and large feeder loads. ‘DoubleBreak contact system (figure one) provides
The main functions of the ACB are the protection and the opportunity to further elongate the arc to ensure
isolation of the supply source, be it transformer or even faster interruption of the short circuit. Due to the
generator. Typical ratings range from 800A to 6300A mass of the contacts the typical total interrupting time
with breaking capacities up to 120ka at 415v AC. of a conventional ACB is 7Omsec.This is the time it
takes for the protection relay to sense the fault,
ACB technology has remained relatively static over initiate a signal to the tripping coil, fully open the
the last decade but the latest products now coming contacts and fully extinguish the arc.

on to the market have dramatically altered this Utilisation of the double break system ensures total
situation. This paper will draw attention towards the clearing time of less than one and a half cycles i.e.
importance of advances in ACB technology and its 30msec.
integral protection relay. In doing so, it will also
explain how these new and innovate designs can add Arc chamber
true value to the protection of low voltage distribution
systems.

ELECTROMECHANICAL INNOVATION

Fixed contact
Modern ACBs, compared to their predecessors, now
occupy less than half the volume. This is derived
from the trend of smaller areas being allocated for
switchboards and the demand for higher packing
densities. To achieve this dramatic reduction, yet
increase its interrupting capacity, and maintain a safe
working temperature, requires major innovations in
contact technology. Figure one
TemPower2 ACB with
DoubleBreak system.

Developments in Power System Protection, Conference Publication No.479 0 IEE 2001. 51 9


An additional benefit of this contact design is that as unit cost, in build and commissioning times that are
the arc energy is ‘shared between two sets of often unaccounted for.
contacts so any contact surface erosion is greatly Firstly, CTs must be connected to the busbars and
reduced, minimising build up of contact resistance wired correctly to the protection relay. This in turn
and thus increasing its operational life. Sharing of the would have to be connected to an additional shunt
arc energy within the double arc chamber ensures trip within ACB. This also increases commissioning
any ionised gases are safely dissipated thus time due to additional components and wiring.
achieving required clearance distance to earthed Modern ACBs with integral relays are fitted with wire
metal of zero. In other words, no additional space is looms for the integral CTs and tripping coil.
required for arc clearance providing even more
possibilitiesto achieve higher packing densities.
Finally, a symmetrical double contact design ensures
higher reliability of short circuit interruption should a
fault occur when the ACB is reverse connected, such
as bottom entry switchboards.

NEW SENSOR TECHNOLOGY

Traditional protection current transformers (CTs)


have always been used as the input to the protection
relay system. Although a tried and tested solution,
they require additional space on the ACB, contribute
to overall heat dissipation and saturate between ten
and twenty times the full load current, depending if
they are 5P10 or 5P20 rated. Figure two
The replacement of bulky protection current TemPower2 ACB with
transformers with new sensor technology such as Integral protection relay.
Rogowski coils is one of the elements utilised to
reduce mass and minimise temperature on modern
ACBs. Reliability of the protection circuit is greatly increased
Rogowski coil technology is not new and was as the ACB and integral protection relay is ‘type
developed as far back as 1897. However, it is only in tested before it leaves the manufacturer. In addition,
the last ten years or so, with advanced unlike many conventional panel mount IDMT relays
microprocessor technology, that commercial that require a separate control voltage, the integral
applications for protection,have been established. protection relay utilises the power from the CTs to trip
Rogowski coils are similar to CTs but contain no iron the ACB.
core. This makes them smaller, lighter and emits a Another point also overlooked is that often the
lower AC watts loss. breaking capacity of the ACB is reduced to its short
They do not saturate like the conventional CT, thus time withstand value. For example an ACB may have
providing linearity and accuracy in protection settings. a breaking capacity of 65ka but a withstand of only
50ka.This is due to the length of time it takes a
separate relay to send the tripping signal to the
SEPARATE PANEL MOUNT VS. INTEGRAL external shunt trip coil. An integral protection relay
PROTECTION RELAYS however operates much quicker and would not suffer
from this reduction in breaking capacity.

The market trend over the last few years has Today s integral protection relays also provide
involved greater use of integral protection relays, protection beyond traditional over current protection.
which offer significant advantages over the separate Options include protection against restricted and
panel mounted IDMT relay (see figure two). unrestricted earth faults under-voltage and phase
ACBs connected to separate panel mount relays failure, reverse power flows, over-temperature and
require double the space within the main internal arcing faults.
switchboard.
There are many additional costs associated with the
separate panel mounted relays, apart from a higher

520
THE EVOLUTION OF OVERLOAD PROTECTION phases. Research is currently underway to produce
double rated switched neutrals for applications where
System protection requirements generally centre on high levels of harmonics cannot be economically or
overload and short circuit protection .So far we have effectively eliminated.
explained how modern ACB design has changed to
interrupt short circuits even faster, thus reducing
system damage and minimising down time. APPLICATION OF SELECTIVITY
An area of over current protection that has had to
become more refined is that of overload protection.
Earlier static protection relays did not posses today s Due to the higher frequency of faults in LV compared
‘thermal memory .If an overload condition to higher voltages, selectivity throughout the system
disappeared the timing element of the relay would is even more critical. The integral relay of modern
reset itself to zero. ACBs can posses in excess of 500,000 unique time
If the same or another overload condition were then current characteristics. This flexibility is often
generated while the conductor was still hot, the timing necessary as the ACB incomer will often have to
element of the relay would start again from zero. This grade with different protective devices such as the
could create a dangerous situation by allowing the upstream utility relay or the downstream fuse switch
conductor to reach a critical temperature before the or moulded case circuit breaker.
overload condition would cause the ACB to trip. A term associated with LV ACBs is ‘LSI
characteristics. This means Long time (overload
As the ACB must protect different sources, it must also be protection), Short time (selectivity zone) and
available with a choice of transformer or generator Instantaneous (short-circuit protection).
protection. Very often standard protection relays cannot It is important that the protection relay has fully
meet the overload protection requirements of generators adjustable LSI protection in order to provide
such as those dictated by marine regulations. A tripping maximum flexibility for selectivity.
time of less than 20secs for a 120% overload can only be In addition to full ‘ LSI flexibility one would also
achieved with generator, overload protection relays. require the option for time current characteristics to
The UK wiring regulations also give guidance comply with IEC60255-3.This provides even more
(regulation 433-01-01 of BS7671) by stating that flexibility by providing the traditional standard, very
systems should be designed so that “a small and extremely inverse curves often reserved for
overload of a long duration is unlikely to occur”. Most separate panel mounted IDMT relays only.
modern integral relays possess a PTA (Pre-Trip
Alarm) function that provides the facility to trip non- To overcome the drawbacks of a time based
essential load or start additional generator capacity selective system where one has larger time delays as
on detection of the system approaching an overload we approach the transformer or generator, attention
situation. is turning to zone interlock systems. This technique
usually reserved for medium voltage applications is
The increase of non-liner loads means today s LV also now being considered for LV application. This
network can have high magnitudes of harmonic technique ensures that full selectivity is achieved but
distortion. Many IDMT relays utilise a peak sensing with a maximum tripping time of less than 50msec.ln
overload element, which can result in nuisance order to achieve this the relays communicate to one
tripping of the ACB or under protection of the another and issue trip blocking or override time delay
conductor. signals where necessary.
Modern protection relays employ sampling an
integrating techniques to ensure the true r.m.s value
of the load current is measured .It is important that a END USER REQUIREMENTS
high sampling rate is chosen to ensure a wide
frequency spectrum is captured for the r.m.s
measurement. A sampling rate of 500psec would The demand from this area has forced the ACB
provide true r.m.s measurement up to the 1gth manufacture to consider added valued features
harmonic ensuring the system is future proof from throughout the design. A particular area of concern
further nuisance tripping. for many end users is the reliability of the switchgear
Overload protection of the neutral pole should also and what can be done to minimise downtime.
be catered for due to the accumulation of the Triple- Modular design ensures that all the main accessories
N harmonics in the neutral conductor. In this such as tripping and closing coils are field fit-able and
application, it is important to ensure that the neutral accessible from the front of the ACB, should they
conductor is rated to the same ampere as the main require replacement. Also all auxiliary, position and

52 1
relay connections should be accessible from the front This information can then be used for post fault
should any modifications need to be carried out to diagnosis and can be combined with detail on the
the switchboard. percentage contact wear and contact temperature.
The modular design also ensures that fixed and This can help the engineer plan preventative and
moving contacts can be replaced in approximately predictive maintenance programs.
ten minutes per pole should the need ever arise.
Integral protection relays on today s ACBs are
provided with ‘in built trip circuit supervision and CONCLUSION
calibration test facilities. Should the protection relay
or the tripping coil malfunction the user can be
informed locally or remotely. Integrated trip supervision and monitoring of the
The end user is increasingly looking for preventative temperature and erosion of the contacts, provide
maintenance oppoQunitiesthat will result in zero unparalleled preventative maintenance opportunities
unplanned downtime and where possible, reduce or that previously were impractical to implement.
eliminate any unnecessary maintenance. The movement from time based to condition based
A question often asked is when should the main maintenance programs compliment the additional I

contacts be inspected or even replaced? electrical parameters that can be measured and
Today s sophisticated relays can indicate percentage communicated to the BMS system. Maintenance
contact wear by taking into account the magnitude solutions can be provided over the Internet so the
and energy of the overcurrent. A new ACB would manufacturer can remotely diagnosis the pre and
have zero percentage contact wear while a figure post fault information to assist the end user in
approaching one hundred percent means that obtaining minimum downtime.
replacement of contacts is necessary. Integral protection relays offer reduced costs of
Over temperate is certainly one of the main problems installation time and testing, increased reliability and
associated with the failure of switchgear .The can assist in fault diagnosis of the ACB itself.
provision of indication of contact wear can greatly The ability to remotely change the protection settings
assist the user to plan maintenance more effectively. is an important considerationfor standby generator
However, over temperature is often not just due to applications where it is necessary to alter the settings
increased contact resistance. More often than not it is automatically to continue to obtain full selectivity with
due to inadequate or blocked ventilation or busbar essential loads.
fixing bolts not being at the correct torque. Additionally, the ability to transmit settings opens up
Thermographic surveys can of course detect these the possibility for communicating with output files of
hot spots but these can be costly and do not provide selectivity software so that the automatic
‘real time‘ monitoring of the situation. commissioning of the integral relays also takes place.
Recent developments in ACBs mean that thermistors Protection, monitoring and control have become
can now be fitted to individual phase contacts of the collective requirements.
ACB. Should the temperature increase for whatever
reason the user is alerted immediately of the situation Today s ACBs-are now beyond being classed as
so scheduled maintenance can be planned. intelligent, they have ‘self awareness .

BUILDING MANAGEMENT SYSTEMS

The traditional BMS system is usually connected to


the lift and fire system, lighting, HVAC and security
systems. Today many engineers are now taking
advantage of the data capability of intelligent ACBs,
after all if the ACB should fail the previous devices
would also suffer from main loss.
Advanced protection relays now offer power metering
facilities so that complete energy profiles can be
transmitted to the BMS or SCADA system.
The advantage over separate panel meters, apart
from space and cost savings, is the ability to gather
and transmit fault data. Rather than just get an
indication of a trip, the engineer can be informed as
to the type of fault, magnitude and ACB tripping time.

522

You might also like