PVsyst - Simulation report
Grid-Connected System

Project: PV
Variant: New simulation variant
No 3D scene defined, no shadings
System power: 4960 Wp

PVsyst TRIAL
Oulad Teïma - Morocco

PVsyst TRIAL

PVsyst TRIAL
Author

PVsyst TRIAL
Project: PV
Variant: New simulation variant

PVsyst V7.4.6
VC1, Simulation date:
15/05/24 10:22

PVsyst TRIAL
with V7.4.6

Project summary
Geographical Site Situation Project settings
Oulad Teïma Latitude 30.39 °N Albedo 0.20
Morocco Longitude -9.21 °W
Altitude 131 m
Time zone UTC

Weather data
Oulad Teïma
Meteonorm 8.1 (1996-2015), Sat=100% - Synthetic

System summary

PVsyst TRIAL
Grid-Connected System No 3D scene defined, no shadings

PV Field Orientation Near Shadings User's needs


Fixed plane No Shadings Unlimited load (grid)
Tilt/Azimuth 32 / 0 °

System information
PV Array Inverters
Nb. of modules 32 units Nb. of units 2 units
Pnom total 4960 Wp Pnom total 5.00 kWac
Pnom ratio 0.992

Results summary
Produced Energy 8652.44 kWh/year Specific production 1744 kWh/kWp/year Perf. Ratio PR 77.33 %

PVsyst TRIAL
Project and results summary

Main results
Loss diagram
Predef. graphs
Table of contents

General parameters, PV Array Characteristics, System losses


2
3
4
5
6
Single-line diagram 7

PVsyst TRIAL

PVsyst TRIAL
15/05/24 PVsyst Evaluation mode Page 2/7
Project: PV
Variant: New simulation variant

PVsyst V7.4.6
VC1, Simulation date:
15/05/24 10:22

PVsyst TRIAL
with V7.4.6

General parameters
Grid-Connected System No 3D scene defined, no shadings

PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 32 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate

Horizon Near Shadings User's needs


Free Horizon No Shadings Unlimited load (grid)

PVsyst TRIAL
PV Array Characteristics
PV module Inverter
Manufacturer Generic Manufacturer Generic
Model MN16/155 Model PVP 2500
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 155 Wp Unit Nom. Power 2.50 kWac
Number of PV modules 32 units Number of inverters 2 units
Nominal (STC) 4960 Wp Total power 5.0 kWac
Modules 4 string x 8 In series Operating voltage 140-450 V
At operating cond. (50°C) Pnom ratio (DC:AC) 0.99
Pmpp 4429 Wp
U mpp 247 V
I mpp 18 A

PVsyst TRIAL
Total PV power Total inverter power
Nominal (STC) 4.96 kWp Total power 5 kWac
Total 32 modules Number of inverters 2 units
Module area 41.0 m² Pnom ratio 0.99

Array losses
Thermal Loss factor DC wiring losses Module Quality Loss
Module temperature according to irradiance Global array res. 233 mΩ Loss Fraction 1.5 %
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s

Module mismatch losses Strings Mismatch loss IAM loss factor


Loss Fraction 2.0 % at MPP Loss Fraction 0.1 % ASHRAE Param.: IAM = 1 - bo (1/cosi -1)
bo Param. 0.05

PVsyst TRIAL

PVsyst TRIAL
15/05/24 PVsyst Evaluation mode Page 3/7
Project: PV
Variant: New simulation variant

PVsyst V7.4.6
VC1, Simulation date:
15/05/24 10:22

PVsyst TRIAL
with V7.4.6

Main results
System Production
Produced Energy 8652.44 kWh/year Specific production 1744 kWh/kWp/year
Perf. Ratio PR 77.33 %

Normalized productions (per installed kWp) Performance Ratio PR

PVsyst TRIAL
Balances and main results

GlobHor DiffHor T_Amb GlobInc GlobEff EArray E_Grid PR


kWh/m² kWh/m² °C kWh/m² kWh/m² kWh kWh ratio
January 113.3 30.66 13.42 173.5 170.1 728.8 684.0 0.795

PVsyst TRIAL
February 127.8 38.20 14.80 174.3 171.0 728.1 684.1 0.791
March 173.6 57.01 17.42 203.3 199.1 832.6 780.9 0.774
April 204.3 58.94 18.21 210.0 204.9 853.7 799.6 0.768
May 218.7 75.24 20.16 201.0 195.3 819.0 766.0 0.768
June 223.2 80.12 21.63 196.5 190.6 798.2 747.2 0.767
July 219.5 90.50 23.52 199.3 193.5 803.4 752.0 0.761
August 205.3 84.59 24.16 203.1 198.0 813.7 761.9 0.756
September 173.0 59.18 22.35 192.8 188.4 775.4 727.1 0.760
October 143.5 49.71 21.59 181.2 177.5 730.9 685.0 0.762
November 112.2 37.52 17.56 163.2 160.1 678.9 637.4 0.788
December 99.9 31.77 14.79 157.7 154.6 667.3 627.2 0.802
Year 2014.4 693.45 19.16 2255.9 2203.1 9230.1 8652.4 0.773

PVsyst TRIAL
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings

PVsyst TRIAL
15/05/24 PVsyst Evaluation mode Page 4/7
Project: PV
Variant: New simulation variant

PVsyst V7.4.6
VC1, Simulation date:
15/05/24 10:22

PVsyst TRIAL
with V7.4.6

Loss diagram
2014 kWh/m² Global horizontal irradiation
+12.0% Global incident in coll. plane

-2.34% IAM factor on global

2203 kWh/m² * 41 m² coll. Effective irradiation on collectors

efficiency at STC = 12.15% PV conversion

10967 kWh Array nominal energy (at STC effic.)

PVsyst TRIAL
-0.13% PV loss due to irradiance level

-11.61% PV loss due to temperature

-1.50% Module quality loss

-2.05% Mismatch loss, modules and strings

-1.19% Ohmic wiring loss


9230 kWh Array virtual energy at MPP

-6.22% Inverter Loss during operation (efficiency)

0.00% Inverter Loss over nominal inv. power


0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage

PVsyst TRIAL
-0.04% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
8652 kWh Available Energy at Inverter Output
8652 kWh Energy injected into grid

PVsyst TRIAL

PVsyst TRIAL
15/05/24 PVsyst Evaluation mode Page 5/7
Project: PV
Variant: New simulation variant

PVsyst V7.4.6
VC1, Simulation date:
15/05/24 10:22

PVsyst TRIAL
with V7.4.6

Predef. graphs
Daily Input/Output diagram

PVsyst TRIAL

PVsyst TRIAL System Output Power Distribution

PVsyst TRIAL

PVsyst TRIAL
15/05/24 PVsyst Evaluation mode Page 6/7
PVsyst V7.4.6
VC1, Simulation date:
15/05/24 10:22

PVsyst TRIAL
with V7.4.6

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL

You might also like