Features
Sensors
(B)
Super high-speed sampling with 50ms Fiber
Optic
Improved visibility with LCD display Sensors
:F
ree download the comprehensive device
(D)
management program (DAQMaster) Proximity
Sensors
SSR drive output / Current output selectable
SSRP output (standard/phase/cycle control selectable (E)
Pressure
Mounting space saving with compact design Sensors
:d
ownsized by approx. 30% in depth compared with
(F)
same size of other Series (panel back length: 45mm) Rotary
Encoders
Manual (H)
Temperature
Controllers
For the detail information and instructions of communication setting and Modbus mapping table, please refer to user
manual for communication, and be sure to follow cautions written in the technical descriptions (catalog, homepage). (I)
Visit our homepage (www.autonics.com) to download manuals. SSRs / Power
Controllers
Hard disk More than 1GB of free hard disk space (N)
Display
Units
VGA 1024×768 or higher resolution display
Others RS-232 serial port (9-pin), USB port (O)
Sensor
Controllers
(Q)
R Relay output Stepper Motors
Control output & Drivers
S SSR drive output & Controllers
(S)
1 Alarm output 1 Field
Network
Option output 2 Alarm output 1+Alarm output 2 Devices
S DIN W48×H48mm
Size M DIN W72×H72mm
H DIN W48×H96mm
L DIN W96×H96mm
Digit
4 9999 (4-digit)
Item
TX LCD display standard PID temperature controller
H-11
TX Series
Specifications
Series TX4S TX4M TX4H TX4L
Power supply 100-240VACᜠ 50/60Hz
Allowable voltage range 90 to 110% of rated voltage
Power consumption Max. 8VA
※1
Display method 11-segment (PV: white, SV: green), other display (yellow) with LCD method
Character PV(W×H) 7.2×14mm 10.7×17.3mm 7.2×15.8mm 16×26.8mm
size SV(W×H) 3.9×7.6mm 6.8×11mm 6.2×13.7mm 10.7×17.8mm
RTD DPt100Ω, Cu50Ω (permissible line resistance max. 5Ω)
Input type
TC K(CA), J(IC), L(IC), T(CC), R(PR), S(PR)
Display RTD ●At room temperature (23℃±5℃): (PV ±0.3% or ±1℃, select the higher one) ±1-digit
※2
accuracy TC ●Out of room temperature: (PV ±0.5% or ±2℃, select the higher one) ±1-digit
Relay 250VACᜠ 3A, 30VDCᜡ 3A, 1a
Control
SSR Max. 12VDCᜡ ±2V 20mA Max. 13VDCᜡ ± 3V 20mA
output
Current DC4-20mA or DC0-20mA (load resistance max. 500Ω)
Alarm output AL1, AL2 Relay: 250VACᜠ 3A 1a
Option output Trans. output DC4-20mA (load resistance max. 500Ω, output accuracy: ±0.3%F.S.)
Com. output RS485 Communication output (Modbus RTU method)
Control method ON/OFF control, P, PI, PD, PID control
Hysteresis 1 to 100℃/℉ (0.1 to 50.0℃/℉) variable
Proportional band(P) 0.1 to 999.9℃/℉
Integral time(I) 0 to 9999 sec
Derivative time(D) 0 to 9999 sec
Control period(T) 0.5 to 120.0 sec
Manual reset 0.0 to 100.0%
Sampling period 50ms
Dielectric strength 3,000VAC 50/60Hz for 1 min (between all terminals and case)
Vibration 0.75mm amplitude at frequency 5 to 55Hz (for 1 min) in each X, Y, Z direction for 2 hours
Relay Mechanical OUT, AL1/2: min. 5,000,000 operations
life cycle Electrical OUT, AL1/2: min. 200,000 (250VAC 3A resistance load)
Insulation resistance Over 100MΩ (at 500VDC megger)
Noise immunity Square shaped noise by noise simulator (pulse width 1㎲) ±2kV R-phase, S-phase
Memory retention Approx. 10 years (non-volatile semiconductor memory type)
Environ- Ambient temp. -10 to 50℃, storage: -20 to 60℃
ment Ambient humi. 35 to 85%RH, storage: 35 to 85%RH
Protection structure IP50 (front panel, IEC standards)
Insulation type Double insulation or reinforced insulation(mark: , dielectric strength between all terminals and case: 3kV)
Approval
※3 Approx. 146.1g Approx. 233g Approx. 214g Approx. 290g
Weight
(approx. 86.7g) (approx. 143g) (approx. 133g) (approx. 206g)
※1: When using the unit at low temperature (below 0℃), display cycle is slow.
Control output operates normally.
※2: At room temperature(23℃±5℃)
TC R(PR), S(PR), below 200℃: (PV ±0.5% or ±3℃, select the higher one) ±1-digit
, over 200℃: (PV ±0.5% or ±2℃, select the higher one) ±1-digit
TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±2℃, select the higher one) ±1-digit
Out of room temperature range
TC R(PR), S(PR): (PV ±1.0% or ±5℃, select the higher one) ±1-digit
TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1-digit
※3: The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.
H-12
LCD Display PID Control
(D)
67.5
Proximity
Sensors
44.8
(E)
Pressure
Sensors
(F)
Rotary
Encoders
(G)
TX4H TX4L Connectors/
51 51 Connector Cables/
Sensor Distribution
48 6 45 96 6 45 Boxes/Sockets
(H)
Temperature
Controllers
(I)
SSRs / Power
Controllers
(J)
Counters
91.5
96
96
(K)
Timers
(L)
Panel
Meters
(M)
Tacho /
Speed / Pulse
Meters
Bracket (N)
Display
Units
ᆞ TX4S Series ᆞTX4M/H/L Series
31 (O)
3.5
Sensor
48.6 20 Controllers
45 5
(P)
Switching
4
Mode Power
Supplies
44.9
36
16
46 8.5 (Q)
Stepper Motors
& Drivers
& Controllers
15
55 21 (R)
33
Graphic/
Logic
Panels
11.9 (S)
Field
23.9 Network
56 Devices
(T)
Software
Panel cut-out
A (unit: mm)
Size A B C D
Model
B TX4S Min. 65 Min. 65 45+00.6 45+00.6
TX4M Min. 90 Min. 90 68+00.7 68+00.7
D
TX4H Min. 115 Min. 65 45+00.6 92+00.8
C TX4L Min. 115 Min. 115 92+00.8 92+00.8
H-13
TX Series
Terminal cover (sold separately)
ᆞRSA-COVER(48×48mm) ᆞRMA-COVER(72×72mm)
22
3 48.4 13 4 70 10
41
45
68.5
64
18
22
13
ᆞRHA-COVER(48×96mm) ᆞRLA-COVER(96×96mm)
91.5
86
86
13
13
Product Mounting
TX4S(48×48mm) series Other series
(-) driver
※Mount the unit on the panel. Push the bracket with tools to fix the unit as the figure.
H-14
LCD Display PID Control
Connections (A)
Photoelectric
※Shaded terminals are standard model. Sensors
TX4S series
OUT (E)
Pressure
SSR Sensors
12VDC±2V 20mA Max.
Current
DC0/4-20mA AL1 OUT:
Load 500ΩMax. 1 13 7 250VAC 3A 1a
(F)
Rotary
Relay RESISTIVE LOAD Encoders
250VAC 3A 1a
30VDC 3A 1a 2 14 8 AL2 OUT:
RESISTIVE LOAD 250VAC 3A 1a (G)
Connectors/
+ + 3 +
RS485(A+) 15 9 RESISTIVE LOAD Connector Cables/
mA Sensor Distribution
mA
- - - A Boxes/Sockets
4 RS485(B-) 16 10
(H)
B
5 Communication Output 17 11 +
Temperature
Controllers
Transfer Output
DC4-20mA B' -
SOURCE 6 18 12
RTD TC (I)
100-240VAC SENSOR SSRs / Power
50/60Hz 8VA Controllers
(Q)
1 13 Stepper Motors
& Drivers
& Controllers
2 14
(R)
3 15 Graphic/
Logic
Communication Output Panels
Transfer Output
4 16 DC4-20mA
(S)
Field
5 17 RS485(A+)
+ Network
mA Devices
-
6 18
RS485(B-)
OUT OUT (T)
Current OUT 7 Relay 19 AL1 OUT: Software
H-15
TX Series
Sold Separately
Communication converter
SCM-WF48 SCM-US48I SCM-38I
(Wi-Fi to RS485·USB wireless (USB to RS485 converter) (RS232C to RS485 converter)
communication converter)
SCM-US EXT-US
(USB to Serial converter) (converter cable)
※Connect RS485 communication input type display unit (DS/DA-T Series) and RS485 communication output model of TX Series,
the display unit displays present value of the device without PC/PLC.
H-16
LCD Display PID Control
Parameter Group
RUN mode (K)
Timers
※If there is no key input for 30 sec while setting SV or the parameters, the new settings are ignored, and the unit will return to RUN mode
with previous settings. (O)
Sensor
※When returning to RUN mode by holding the key for over 3 sec, press the key within 1 sec to re-enter the first parameter of Controllers
● SV setting (Q)
※To change set temperature from 210℃ to 250℃ Stepper Motors
& Drivers
& Controllers
①RUN mode
(R)
Graphic/
Logic
Panels
(S)
Field
Network
Devices
Press any key among , , , once.
③Completes SV setting (T)
②SV setting mode Software
Change SV
by , , key
④Check SV
※If there is no key input for 3 sec while setting SV, the new setting is applied and the unit will return to RUN mode.
H-17
TX Series
● Parameter group 1 ※1: : Press any key among , , .
※2: Press the key once after changing the setting value, to save the setting value
and move to the next parameter
3 sec ※Hold the key for 3 sec to save the setting value and return to RUN mode after
RUN mode
changing the setting value.
2 sec ※ Dotted parameters may not appear by model type or other parameter settings.
PAR1
AL1 temperature
※1
AL1 1250
Setting range: D
eviation alarm(- [F.S] to [F.S]),
Absolute value alarm(temperature range)
※2 ※Does not appear when AL1/AL2 alarm operation [AL-1, AL-2] of parameter group 2 is
AL2 temperature set as AM)_/SBa /LBa .
※Only alarm output 2 models have [AL2].
AL2 1250
Auto-tuning ※When setting as ON, the unit starts auto-tuning. After completing,
OFF ON OFF is automatically set.
AT
※During auto-tuning, the auto-tuning indicator flashes
(every 1 sec).
Proportional
band
P 1)0 Setting range: 0.1 to 999.9℃/℉
Integral
time
Setting range: 0 to 9999 sec
I 0 ※Integral operation will be OFF
when the setting value is '0'
※Only appears when control method
[C-MD] of parameter group 2 is set as
Derivative PID.
time Setting range: 0 to 9999 sec
D 0 ※Derivative operation will be OFF
when the setting value is '0'
Manual reset
REST 5)0 Setting range: 0.0 to 100.0%
※Only appears in P, PD control.
Hysteresis
Setting range: 1 to 100℃/℉ (0.1 to 50.0℃/℉)
HYS 2 ※Only appears when control method [C-MD] of parameter group 2 is
set as ONOF.
H-18
LCD Display PID Control
● Parameter group 2 ※1: : Press any key among , , .
(A)
※2: Press the key once after changing the setting value, to save the setting value Photoelectric
RUN mode and move to the next parameter Sensors
※Hold the key for 3 sec to save the setting value and return to RUN mode after
(B)
4 sec changing the setting value. Fiber
3 sec Optic
※ Dotted parameters may not appear by model type or other parameter settings. Sensors
PAR2
(C)
Door/Area
※1 etting range: Refer to ' Input Type And Range'.
S Sensors
Input sensor IN-T KCaH ※When changing the setting value, SV, [IN-B, H-SV/L-SV,
AL1, AL2, LBaB, AHYS] parameters of parameter group 2 are reset. (D)
※2 Proximity
Sensors
Temperature ※When changing the setting value, SV, [IN-B, H-SV/L-SV, AL1, AL2, (E)
unit
UNIT ?C ?F LBaB, AHYS] parameters of parameter group 2 are reset. Pressure
Sensors
(F)
Input Rotary
correction
IN-B 0 Setting range: -999 to 999℃/℉(-199.9 to 999.9℃/℉) Encoders
(G)
Connectors/
Connector Cables/
Input digital Sensor Distribution
filter
MAvF )1 Setting range: 0.1 to 120.0 sec Boxes/Sockets
(H)
Temperature
Controllers
SV low-limit Setting range: Within temperature range of each sensor [L-SV≤(H-SV-1-digit)]
value
L-SV -50 ※
When changing the setting value, and SV<L-SV, SV is reset as L-SV. (I)
SSRs / Power
Controllers
Control (K)
output mode
O-FT HEAT COOL Timers
(L)
Panel
Control ※When changing the setting value, [ErMV] is reset as )0, [DI-K] is Meters
method
C-MD PID ONOF
reset as OFF.
(M)
Tacho /
Speed / Pulse
Control Meters
※Appears only in selectable current output or SSR drive output
output OUT CURR SSR
selection model(TX4 - 4C). (N)
Display
Units
SSR drive
output SSrM STND CYCL PHAS ※Appears only in SSR drive output model (TX4 - 4S). (O)
method Sensor
Controllers
(P)
Current
oMA 4-20 0-20 ※Appears only when control output [OUT] is set as CURR. Switching
output range Mode Power
Supplies
(Q)
Setting range: 0.5 to 120.0 sec Stepper Motors
Control cycle T 2)0 ※Appears only when control method [C-MD] is PID. & Drivers
& Controllers
※Does not appear when SSR drive output is set as CYCL, or PHAS.
(R)
Graphic/
Logic
AL1 Panels
operation
AL-1 AM!A LBaA AM!A AM!B
(S)
Field
※Alarm operation ※ Alarm option Network
Devices
※When changing the setting
※Press the key to switch 'Alarm operation' 'Alarm option' setting. value, [AL1, AL2] parameter
(T)
of parameter group 1 is reset. Software
AL2
operation
AL-2 AM@A ※Set method is same as AL1 alarm operation [AL-1].
※Appears only in alarm output 2 models.
H-19
TX Series
Trans. output
low-limit FS-L -50
value
Setting range: Refer to ' Input Type and Range'.
※Appears only in transmission output model(TX4 -A4 ).
Trans. output
high-limit FS-H 1200
value
Comm.
ADRS 1 Setting range: 1 to 127
address
Comm.
parity-bit
PRTY NONE EVEN ODD
※Appears in RS485 communication output
model(TX4 -B4 ).
Comm.
stop-bit
STP 2 1
Comm.
response RSwT 20 Setting range: 5 to 99ms
waiting time
Comm.
write
COMW EnA DIsA
Digital input
DI-K STOP AlRE AT OFF
key
H-20
LCD Display PID Control
Alarm (A)
Set both alarm operation and alarm option by combining. Photoelectric
Sensors
OFF H ON OFF H ON
Deviation If deviation between PV and SV as high- (E)
Pressure
AM! high-limit SV PV PV SV limit is higher than set value of deviation Sensors
alarm 100℃ 110℃ 90℃ 100℃ temperature, the alarm output will be ON.
High-limit deviation: Set as 10℃ High-limit deviation: Set as -10℃ (F)
Rotary
ON H OFF ON H OFF Encoders
Deviation If deviation between PV and SV as low-
AM@ low-limit PV SV SV PV limit is higher than set value of deviation (G)
Connectors/
alarm 90℃ 100℃ 100℃ 110℃ temperature, the alarm output will be ON. Connector Cables/
Sensor Distribution
Low-limit deviation: Set as 10℃ Low-limit deviation: Set as -10℃ Boxes/Sockets
ON H OFF H ON (H)
Deviation If deviation between PV and SV as high/ Temperature
AM# high/low-limit PV SV PV low-limit is higher than set value of deviation Controllers
alarm 90℃ 100℃ 110℃ temperature, the alarm output will be ON.
High, Low-limit deviation: Set as 10℃ (I)
SSRs / Power
Controllers
OFF H ON H OFF
Deviation If deviation between PV and SV as high/
AM$ high/low-limit PV SV PV low-limit is higher than set value of deviation (J)
reserve alarm 90℃ 100℃ 110℃ temperature, the alarm output will be OFF. Counters
sequence 1 operates.
(T)
First alarm condition is ignored and from second alarm condition, standard alarm operates. When re-applied Software
Standby
AM .E standby sequence and if it is alarm condition, alarm output does not turn ON. After clearing alarm condition,
sequence 2
standard alarm operates.
Alarm latch and Basic operation is same as alarm latch and standby sequence1. It operates not only by power ON/OFF, but also
AM .F standby alarm setting value, or alarm option changing. When re-applied standby sequence and if it is alarm condition,
sequence 2 alarm output does not turn ON. After clearing alarm condition, alarm latch operates.
※Condition of re-applied standby sequence for standby sequence 1, alarm latch and standby sequence 1: Power ON
Condition of re-applied standby sequence for standby sequence 2, alarm latch and standby sequence 2: Power ON,
changing set temperature, alarm temperature [AL1, AL2] or alarm operation [AL-1, AL-2], switching STOP mode
to RUN mode.
H-21
TX Series
● Sensor break alarm
The function that alarm output will be ON when sensor is not connected or when sensor's disconnection is detected during temperature
controlling. You can check whether the sensor is connected with buzzer or other units using alarm output contact. It is selectable between
standard alarm [SBaA] or alarm latch [SBaB].
● Loop break alarm(LBA)
It checks control loop and outputs alarm by temperature change of the subject. For heating control(cooling control), when control output MV
is 100%(0% for cooling control) and PV is not increased over than LBA detection band [LBaB] during LBA monitoring time [LBaT], or when
control output MV is 0%(100% for cooling control) and PV is not decreased below than LBA detection band [LBaB] during LBA monitoring
time [LBaT], alarm output turns ON.
Time
When control output MV is 100%, PV is increased over than LBA detection band [LBaB] during LBA monitoring time
Start control to
[LBaT].
to The status of changing control output MV (LBA monitoring time is reset.)
When control output MV is 0% and PV is not decreased below than LBA detection band [LBaB] during LBA monitoring
to
time [LBaT], loop break alarm (LBA) turns ON after LBA monitoring time.
to Control output MV is 0% and loop break alarm (LBA) turns and maintains ON.
to The status of changing control output MV (LBA monitoring time is reset.)
When control output MV is 100% and PV is not increased over than LBA detection band [LBaB] during LBA monitoring
to
time [LBaT], loop break alarm (LBA) turns ON after LBA monitoring time.
When control output MV is 100% and PV is increased over than LBA detection band [LBaB] during LBA monitoring time
to
[LBaT], loop break alarm (LBA) turns OFF after LBA monitoring time.
to The status of changing control output MV (LBA monitoring time is reset.)
※When executing auto-tuning, LBA detection band [LBaB] and LBA monitoring time are automatically set based on auto tuning value. When
alarm operation mode [AL-1, AL-2] is set as loop break alarm(LBA) [LBa ], LBA detection band [LBaB] and LBA monitoring time [LBaT]
parameter is displayed.
H-22
LCD Display PID Control
Functions (A)
Photoelectric
Sensors
● Input correction [IN-B]
Controller itself does not have errors but there may be error by external input temperature sensor. This function is for correcting this error. (B)
Fiber
E.g.) If actual temperature is 80℃ but controller displays 78℃, set input correction value [IN-B] as '2' and controller displays 80℃. Optic
※As the result of input correction, if current temperature value (PV) is over each temperature range of input sensor, it displays HHHH or Sensors
LLLL.
(C)
● Input digital filter [MAvF] Door/Area
Sensors
If current temperature (PV) is fluctuating repeatedly by rapid change of input signal, it reflects to MV and stable control is impossible.
Therefore, digital filter function stabilizes current temperature value. (D)
For example, set input digital filter value as 0.4 sec, and it applies digital filter to input values during 0.4 sec and displays these values. Proximity
Sensors
Current temperature may be different by actual input value.
● SSR drive output method (SSRP function) [SSrM] (E)
Pressure
ㆍSSRP function is selectable one of standard ON/OFF control, cycle control, phase control by utilizing standard SSR drive output. Sensors
ㆍThis function parameter appears only in SSR drive output model (TX4 - 4S).
ㆍRealizing high accuracy and cost effective temperature control with both current output (4-20mA) and linear output(cycle control and phase (F)
Rotary
control) Encoders
ㆍSelect one of standard ON/OFF control [STND], cycle control [CYCL] , phase control [PHAS] at SSrM parameter of parameter group 2. For
cycle control, connect a zero cross turn-on SSR or random turn-on SSR. For phase control, connect random turn-on SSR. (G)
Connectors/
SSR voltage output Connector Cables/
(TX4S: 12VDC SSR module Sensor Distribution
TX4M/H/L: 13VDC) Load Boxes/Sockets
(I)
SSRs / Power
Controllers
Power
100-240VAC
(J)
50/60Hz Counters
※When selecting cycle or phase control mode, the power supply for a load and a temperature controller must be the same. (K)
※Control cycle [T] is able to set only when control method [C-MD]of parameter group 2 is set as PID and SSR drive output method [SSrM] Timers
is set as STND.
※In case of selectable current output or SSR drive output model(TX4 - 4C), this parameter does not appear. (L)
Panel
Standard ON/OFF control by SSR is only available. Meters
ON OFF ON OFF
(N)
Display
Units
2)Cycle control [CYCL]
Controls the load by repeating output ON / OFF according to (O)
AC
the rate of output within setting cycle based on certain period Sensor
Controllers
(50-cycle).
Control accuracy is almost the same with phase control’s. OUT
(P)
Switching
This control has improved ON/OFF noise than phase 50 Cycle 50 Cycle Mode Power
Supplies
control’s due to zero cross type which turns ON/OFF at zero
50% 80%
point of AC. (Q)
Stepper Motors
& Drivers
& Controllers
3)Phase control [PHAS]
AC (R)
Controls the load by controlling the phase within AC half cycle. Graphic/
Serial control is available. Logic
Panels
OUT
Must use random turn-on SSR for this mode.
10% 50% (S)
Field
● Current output range [oMA] Network
Devices
In case of selectable current output or SSR drive output model(TX4S- 4C), when control output [OUT] parameter group 2 is set as [CURR],
you can select high/low-limit range, 4-20mA [4-20] or 0-20mA [0-20] of current output.
(T)
Software
● Hysteresis [HYS]
Set interval between ON and OFF of control output for ON/OFF control.
If hysteresis is too narrow, hunting(oscillation, chattering) could occur due to external Heating operation
noise. Control
output
In case of ON / OFF control mode, even if PV reaches stable status, there still ON OFF
occurs hunting. It could be due to hysteresis Hysteresis
[HYS] setting value, load’s response characteristics or sensor’s location. In [HYS]
order to reduce hunting to a minimum, it is required to take into following factors Temp.
SV
consideration when designing temp. controlling; proper Hysteresis [HYS], heater’s
capacity, thermal characteristics, sensor’s response and location.
H-23
TX Series
● Manual reset [REST] ●Manual reset [REST] by control result
When selecting P/PD control mode, certain temperature difference
exists even after PV reaches stable status because heater's rising and Set below 50.0 as reset value
falling time is inconsistent due to thermal characteristics of controlled
objects, such as heat capacity, heater capacity. This temperature Offset
SV
difference is called offset and manual reset [REST] function is to set/ Offset
correct offset.
When PV and SV are equal, reset value is 50.0%. After control is Set over 50.0 as reset value
stable, PV is lower than SV, reset value is over 50.0% or PV is higher
than SV, reset value is below 50.0%.
Communication Setting
It is for parameter setting and monitoring via external devices (PC, PLC, etc.).
Applicable for models with RS485 communication output through option output(TX4 -B4 ).
Please refer to ' Ordering Information'.
● Interface
Comm. protocol Modbus RTU Comm. speed 4800, 9600 (default), 19200, 38400, 115200 bps
Connection type RS485 Response waiting time 5 to 99ms (default: 20ms)
Application standard EIA RS485 Compliance with Start bit 1bit (fixed)
Max. connection 32 units (address: 01 to 127) Data bit 8bit (fixed)
Synchronous method Asynchronous Parity bit None (default), Odd, Even
Comm. method Two-wire half duplex Stop bit 1bit, 2bit (default)
Comm. effective range Max. 800m
A(+)
※It is recommended to use Autonics communication converter; SCM-WF48 (Wi-Fi to RS485·USB wireless communication
converter, sold separately), SCM-US48I (USB to RS485 converter, sold separately), SCM-38I (RS232C to RS485
converter, sold separately).
Please use twisted pair wire, which is suitable for RS485 communication, for SCM-WF48, SCM-US48I and SCM-38I.
H-24
LCD Display PID Control
- 0 (C)
UNIT ?C LBaT 0 Door/Area
Sensors
IN-B 0 LBaB 2
Parameter group 1
MAvF )1 FS-L -50 (D)
Proximity
Parameter Factory default Sensors
L-SV -50 FS-H 1200
AL1
1250 H-SV 1200 ADRS 1 (E)
Pressure
AL2 Sensors
O-FT HEAT BPS 96
AT OFF
C-MD PID PRTY NONE (F)
P 1)0 Rotary
OUT CURR STP 2 Encoders
I
0 SSrM STND RSwT 20 (G)
Connectors/
D Connector Cables/
oMA 4-20 COMW EnA Sensor Distribution
Boxes/Sockets
REST 5)0
2)0(Relay) DI-K STOP
HYS 2 T (H)
@0(SSR drive) ErMV )0 Temperature
Controllers
(J)
Error Counters
(M)
Tacho /
Speed / Pulse
Meters
● Follow instructions in 'Cautions during Use'. Otherwise, It may cause unexpected accidents.
(O)
● Check the polarity of the terminals before wiring the temperature sensor. Sensor
Controllers
For RTD temperature sensor, wire it as 3-wire type, using cables in same thickness and length.
For thermocouple (CT) temperature sensor, use the designated compensation wire for extending wire. (P)
● Keep away from high voltage lines or power lines to prevent inductive noise. Switching
Mode Power
In case installing power line and input signal line closely, use line filter or varistor at power line and shielded wire at input signal line. Supplies
Do not use near the equipment which generates strong magnetic force or high frequency noise. (Q)
● Do not apply excessive power when connecting or disconnecting the connectors of the product. Stepper Motors
& Drivers
● Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power. & Controllers
● Do not use the unit for other purpose (e.g. voltmeter, ammeter), but temperature controller. (R)
Graphic/
● When changing the input sensor, turn off the power first before changing. Logic
Panels
After changing the input sensor, modify the value of the corresponding parameter.
● Do not overlapping communication line and power line. (S)
Field
Use twisted pair wire for communication line and connect ferrite bead at each end of line to reduce the effect of external noise. Network
Devices
● Make a required space around the unit for radiation of heat.
For accurate temperature measurement, warm up the unit over 20 min after turning on the power.
(T)
● Make sure that power supply voltage reaches to the rated voltage within 2 sec after supplying power. Software
H-25