VOLUME IV

SCHEDULE B3
TECHNICAL PARTICULARS AND GUARANTEES
B3.4 – 400/132 kV TRANSFORMERS
(To be Completed and Signed by the Tenderer)

400/132kV Transformers-TYPE A-GTP-1511106 -Rev 0


Item A- Main Transformers

Part-1: Major technical particulars and guarantees (Items to be fully completed for tender submission)

No. Item Unit Required Offered

1 1. Manufacturer’s name - - HYOSUNG Heavy Ind.

2. Country - - South Korea

3. Place of manufacture - - Chang-Won

2 Site conditions
55
1. Design maximum ambient temperature °C 55.0

2. Design average ambient temperature over °C 35.0 35

one year

3. Consideration for exposure to sunshine - Required Yes

4. Consideration for restricted air circulation - Required Yes

5. Altitude - Sea level Sea level

6. Consideration for fire protection system - Required It should be checked


by main contractor (L&T).
7. Consideration for highly corrosive - Required Yes(C4H as per spec)

environmental conditions

3 8. Type of the transformer - Type A Type A

9. Reference technical specification with - As per tender notification and/or


1.5.1.1.1.06-Rev 0
revision number special instructions

10. Type of transformer - Three phase, core or shell type, Three phase, core
type, mineral oil
mineral oil filled auto-transformer filled auto-transformer
with delta connected tertiary with delta connected
tertiary (stabilizing)
(stabilizing) winding housed in a winding housed in a
single tank. single tank

11. Reference standard - IEC 60076-1 IEC 60076-1

12. Rated voltage of the HV winding kV 400.0 400

13. Rated voltage of the LV winding kV 132.0 132

14. Rated voltage of the TRY winding kV Specify 33

15. Type of cooling - ONAN/ONAF/ODAF ONAN/ONAF/ODAF

16. Connection symbol - YNa0d1 YNa0d1

17. Number of phases - 3 3

Dubai Electricity & Water Authority Page 1 of 18 Tender RFX No.: 21323000xx
VOLUME IV
SCHEDULE B3
TECHNICAL PARTICULARS AND GUARANTEES
B3.4 – 400/132 kV TRANSFORMERS
(To be Completed and Signed by the Tenderer)

400/132kV Transformers-TYPE A-GTP-1511106 -Rev 0


Item A- Main Transformers

Part-1: Major technical particulars and guarantees (Items to be fully completed for tender submission)

No. Item Unit Required Offered

18. Um for HV winding kV 420.0 420

19. Um for LV winding kV 145.0 145

20. Um for TRY winding kV (Specify) 36

21. Installation requirement - Outdoor Outdoor

22. Rated frequency Hz 50.0 50

4 Rating / capacity (based on design ambient - - -


55°C)
1. HV/LV (ONAN/ONAF/ODAF) MVA 250/350/500 250/350/500

2. Tertiary winding (TRY) MVA 100 100

5 Usage of surge arresters on TRY winding Not Permitted No

6 Insulation level as per IEC 60076-3 - - -

1. HV line terminal kV SI 1175/LI 1425/LIC 1570/AC SI 1175 / LI 1425 /


LIC 1570 / AC 630
630
2. HVN kV LI 325/AC 140 LI 325 / AC 140

LI 650 / LIC 715 /


3. LV terminal kV LI 650/LIC 715/AC 275 AC 275
4. TRY line terminal (specify) kV LI ……./AC…….. LI 170 / AC 70

5. Is the Tap winding provided with any surge - Yes/No Yes


(Metal oxide ZnO)
protection device? (If ‘yes’, provide surge
Please refer to the
transfer characteristics) Attachment#3.

7 Rated Line current on HV/ LV at ODAF - - -

1. HV at highest voltage tap A Specify 674.5

2. HV at nominal voltage tap A Specify 721.7

3. HV at lowest voltage tap A Specify 867.4

4. LV A Specify 2186.9

8 Maximum rated current of Tertiary winding A Specify 1749.5

9 No-load loss at rated voltage, normal ratio and kW Specify 67

rated frequency (maximum)

Dubai Electricity & Water Authority Page 2 of 18 Tender RFX No.: 21323000xx
VOLUME IV
SCHEDULE B3
TECHNICAL PARTICULARS AND GUARANTEES
B3.4 – 400/132 kV TRANSFORMERS
(To be Completed and Signed by the Tenderer)

400/132kV Transformers-TYPE A-GTP-1511106 -Rev 0


Item A- Main Transformers

Part-1: Major technical particulars and guarantees (Items to be fully completed for tender submission)

No. Item Unit Required Offered

10 Load loss at 75°C, rated frequency & rated current - -


at (500 MVA base)
1. Highest tap kW Specify 1474 kW (428-132kV)

2. Rated tap kW Specify 1494 kW

3. Lowest tap kW Specify 1832 kW (332.8-132kV)

4. Tap number at which maximum load loss Tap Specify No.18(332.8-132kV)


1832kW
occur and the corresponding loss No./kW

11 Auxiliary loss - - -
1. Cooling fan loss excluding standby kW Specify 19

(maximum)

2. Cooling pump loss excluding standby kW Specify 16

(maximum)

12 Total loss at 75°C(maximum) - - -

1. ODAF rating –H tap kW Specify 1541 kW

2. ODAF rating –R tap kW Specify 1561 kW

3. ODAF rating –L tap kW Specify 1899 kW

13 Impedance voltage at 75°C and 500 MVA base - - (indicate


between HV&LV windings tolerance)

1. At Highest tap (Tap 1) % 42 (min) 42% (Tol. +10%)

2. At rated tap (Tap 6) % 45.2 (min) 45.2% (Tol. +10%)

3. At Lowest tap (Tap 18) % ** 53% (Tol. +10%)

** Impedance shall have an increasing


pattern from tap 1 to 18 and at Tap 18, the
Impedance shall be maximum

14 Impedance voltage at 75°C and 500 MVA base - -


between HV& TRY windings (Not Guaranteed value)

1. At Highest tap (Tap 1) % Specify 84.8%

2. At rated tap (Tap 6) % Specify 86.8%

Dubai Electricity & Water Authority Page 3 of 18 Tender RFX No.: 21323000xx
VOLUME IV
SCHEDULE B3
TECHNICAL PARTICULARS AND GUARANTEES
B3.4 – 400/132 kV TRANSFORMERS
(To be Completed and Signed by the Tenderer)

400/132kV Transformers-TYPE A-GTP-1511106 -Rev 0


Item A- Main Transformers

Part-1: Major technical particulars and guarantees (Items to be fully completed for tender submission)

No. Item Unit Required Offered

3. At Lowest tap (Tap 18) % Specify 95.0%

15 Impedance voltage at 75°C and 500 MVA base % Specify 29.8%

between LV & TRY windings

16 Equivalent circuit zero sequence impedance at % Specify (Reference)


40.7% at Rated tap
normal ratio between HV/LV at 500 MVA
base

17 Short circuit capacity of the windings - - -

1. HV winding kA/3s Specify 1.6

2. LV winding kA/3s Specify 6.3

3. TRY winding kA/3s Specify 6.2

18 Temperature limits at CMR ( IEC 60076-2) - -


1. Top oil rise (thermometer method) K 45.0 45

2. Windings rise (resistance method) K 50.0 50

3. Hot spot winding rise (resistance method) K 63.0 63

4. Hot spot of core, metallic parts and adjacent °C 118.0 118

parts in contact with oil (reference ambient


of 55 °c)
5. Design winding hotspot factor (HV & LV) - Minimum 1.3 Min 1.3

(For Reference)
19 Loading beyond name plating rating (large - As per IEC 60076-7 (all types of 1. Long-time
*Ambient : 35 Deg
power transformer category) loading)
*Pre-load : 100%
1. Overloading Characteristic with varying - For reference *Overloading : 130%
2. Short-time
ambient, load and duration to be provided with *Ambient : 35 Deg
*Pre-load : 100%
calculation *Overloading : 150%

20 Guaranteed maximum sound pressure level

1. No-load with Fans and Pumps running dBA 85.0 (maximum) 85

2. Full load with Fan and Pumps running dBA Information 91(For reference)

21 On-load tap changer - - -


1. Make and country of origin - Specify ABB(Sweden)

Dubai Electricity & Water Authority Page 4 of 18 Tender RFX No.: 21323000xx
VOLUME IV
SCHEDULE B3
TECHNICAL PARTICULARS AND GUARANTEES
B3.4 – 400/132 kV TRANSFORMERS
(To be Completed and Signed by the Tenderer)

400/132kV Transformers-TYPE A-GTP-1511106 -Rev 0


Item A- Main Transformers

Part-1: Major technical particulars and guarantees (Items to be fully completed for tender submission)

No. Item Unit Required Offered

2. Manufacturer’s type number - Specify VUCGRT 750

3. DS type and number - Vacuum tap /- Vacuum tap / -

4. Rated voltage / Um kV/kV Suitable for Specified test levels 325

of Transformer

5. Rated current of the tap changer at design A Minimum 1.2 times through 1200

maximum ambient current in the winding at highest


current tap.

6. Voltage variation to be provided on - HV winding HV winding

7. Range of voltage variation % +7.0 to -16.8 +7.0 to -16.8

8. Step Voltage % 1.4 1.4

9. Number of taps - 18 18

10. Insulation level kV Specify in LI/AC 750/325

11. AC withstand test voltage - Specify -


a) Between first and last contact of selector kV Specify 350/140 (LI/AC)

switch

b) Between any adjacent contact kV Specify N/A

c) Between open diverter switch contact kV Specify N/A

d) Between live parts of diverter switch and kV Specify 350/140

ground
12. Change over selector recovery voltage kV Specify 35kV rms

13. Recovery voltage limiting device - Specify Not necessary


Please refer to the
14. Type test certificate reference - Required Attachment#4.

15. Motor drive unit type number - Specify BUE2

22 AVR relay (Out of HYOSUNG's scope) - - -


1. Manufacturer’s name - Specify A-eberle

2. Country of origin - Specify Germany

3. Hardware / software version - Specify 100.0030.TBD.156

Dubai Electricity & Water Authority Page 5 of 18 Tender RFX No.: 21323000xx
VOLUME IV
SCHEDULE B3
TECHNICAL PARTICULARS AND GUARANTEES
B3.4 – 400/132 kV TRANSFORMERS
(To be Completed and Signed by the Tenderer)

400/132kV Transformers-TYPE A-GTP-1511106 -Rev 0


Item A- Main Transformers

Part-1: Major technical particulars and guarantees (Items to be fully completed for tender submission)

No. Item Unit Required Offered

23 Magnetic core - - -

1. Type of core material - CRGO Silicon Steel CRGO Silicon Steel

2. Grade - Specify 23PHD085

3. Thickness of the lamination mm Specify 0.23


0.85W/kg
4. Specific loss at design flux density W/kg Specify
at 1.7T, 50Hz
24 Construction of core - -

1. Magnetic circuit - Core type or shell type Core type

2. Number of main limbs - Specify 3

3. Number of side limbs Specify 0

4. Yoke area ( % of main limb) Specify 100%

5. Side limb area ( % of main limb) - Specify N/A

6. Is magnetic shunt provided on core - Yes/ No Yes

clamping structure?

7. Is design incorporate metallic shield on - Yes/ No No

clamping parts?

25 Flux density in the core at nominal voltage and - - -


frequency and at normal ratio - (no load)
1. Limb T Specify 1.7

2. Yoke T Specify 1.7

3. Side limb T Specify N/A

26 No-load magnetizing current (approx.) at - -


rated frequency, normal ratio at:

1. 0.9 PU voltage - % 0.05 +/- IEC tolerance

2. 1.0 PU voltage - % 0.09 +/- IEC tolerance

3. 1.1 PU voltage - % 0.43 +/- IEC tolerance

4. 1.2 PU voltage - % 1.2 +/- IEC tolerance

27 Regulation at 75°C and normal ratio - - -

Dubai Electricity & Water Authority Page 6 of 18 Tender RFX No.: 21323000xx
VOLUME IV
SCHEDULE B3
TECHNICAL PARTICULARS AND GUARANTEES
B3.4 – 400/132 kV TRANSFORMERS
(To be Completed and Signed by the Tenderer)

400/132kV Transformers-TYPE A-GTP-1511106 -Rev 0


Item A- Main Transformers

Part-1: Major technical particulars and guarantees (Items to be fully completed for tender submission)

No. Item Unit Required Offered

1. At unity power factor % Specify Approx. 12.21

2. At 0.8 power factor (lag) % Specify Approx. 37.1

28 Maximum current density in windings at CMR - - -

1. HV winding (main) A/mm2 Specify Max. 3

2. HV regulating winding (coarse) A/mm2 Specify N/A

2
3. HV regulating winding (fine) A/mm Specify Max. 3

4. LV winding A/mm2 Specify Max. 3

5. TRY winding A/mm2 Specify Max. 3

29 Winding resistance at 75°C - - -

1. HV- main winding Ω/phase Specify Approx. 0.36

2. HV-course tap winding Ω/phase Specify N/A

3. HV-fine tap winding Ω/phase Specify Approx. 0.06

4. LV Ω/phase Specify Approx. 0.07

5. TRY winding Ω/phase Specify Approx. 0.03

30 Oil/ mass schedule - - -

1. Total volume of oil required to fill the l Specify 145,800

transformer (including cooling plant) up to


1/3rd level of the conservator– at 35°C

2. Total volume of the conservator- main tank l Shall be approximately 10% of the 12,000
volume of oil in the tank
3. Volume of oil in main conservator between l Specify 8,280
MIN and MAX levels – main tank
4. Total volume of the conservator- OLTC l 250.0 (approx.) 250
5. Total volume of oil in the conservator l Shall be sufficient NOT to 230
between MIN and MAX levels – OLTC
generate MIN alarm signal during
periodic oil sampling
31 Mass schedule - - -

1. Mass of assembled core kg Specify 73,900

Dubai Electricity & Water Authority Page 7 of 18 Tender RFX No.: 21323000xx
It can be slightly changed after detailed design.
VOLUME IV
SCHEDULE B3
TECHNICAL PARTICULARS AND GUARANTEES
B3.4 – 400/132 kV TRANSFORMERS
(To be Completed and Signed by the Tenderer)

400/132kV Transformers-TYPE A-GTP-1511106 -Rev 0


Item A- Main Transformers

Part-1: Major technical particulars and guarantees (Items to be fully completed for tender submission)

No. Item Unit Required Offered

2. Mass of winding kg Specify 71,900

3. Mass of core and winding assembly kg Specify 170,200


4. Total mass of complete transformers, kg Specify 384,900
including cooling plant, all fittings, accessories
and oil
5. Mass of the main shipping body kg Specify 220,000 (Without oil)

32 Type and grade oil - - -


1. Manufacturer name and country of origin - Specify ERGON & USA

2. Reference standard - IEC60296 IEC60296

3. Type of oil - Type-A: Unused, fully inhibited Type A, Unused, fully


inhibited high grade
high grade mineral oil mineral oil
4. Manufacturer’s type reference - Specify Hyvolt III

5. Type of the oil used for active part - Specify Uninhibited type
impregnation and factory testing.
6. If offered in A32.5 is different from A32.3, - Test report to be furnished Yes(Miscibility report
compatibility and mix-ability of the test oil will be provided)
with actual oil shall be proved by necessary
test
33 Short circuit withstand requirement. - - -
1. Brief description of transformer subjected to - Test reference and/ or calculation Please refer to the
short-circuit test or for which short-circuit Attachment#1.
calculations are available. required
2. Thermal / dynamic withstand capability of - Must be proved by necessary Please refer to the
the offered transformer. Attachment#2.
calculation.
34 For below items, refer specification, relevant IEC or other International Standards. Voltage / Current Rating shall be
commensurate with the specific application. Items shall be offered from approved vendor list. New makes are acceptable
subject to approval separately. Type and features shall be agreed separately. Where items NOT Applicable Mark “NA”
or “-“. The Country Of Origin including sub-assembly items shall be from Western Europe or Japan or other DEWA
approved origin.

A. HV bushing Unit Required Offered


1. Manufacturer - Specify HSP

2. Country of Origin - Specify Germany

3. Type - RIP RIP

Dubai Electricity & Water Authority Page 8 of 18 Tender RFX No.: 21323000xx
VOLUME IV
SCHEDULE B3
TECHNICAL PARTICULARS AND GUARANTEES
B3.4 – 400/132 kV TRANSFORMERS
(To be Completed and Signed by the Tenderer)

400/132kV Transformers-TYPE A-GTP-1511106 -Rev 0


Item A- Main Transformers

Part-1: Major technical particulars and guarantees (Items to be fully completed for tender submission)

No. Item Unit Required Offered


4. Application - Oil to SF6 Oil to SF6

5. Mounting - Double flange Double flange

6. Conductor Material - Copper Copper

7. Manufacturer's type reference - Specify EKTG 1425-420


1200
8. Rated voltage kV Minimum 420 kV 420kV

9. Rated current A Specify 1200A

10. Coating of SF6 end terminal (Sn or Ag) - Specify Ag (Silver plated)

11. Mass of the bushing kg Specify 250

12. Type of test tap - (non-self earthing preferred) Non-self earthing type

13. Dry lightning impulse voltage withstand level kV Specify 1425

14. Switching impulse voltage withstand level kV Specify 1175

15. Power frequency AC voltage withstand Level kV Specify 695(Dry)

16. Dynamic current / duration kA/s Specify 75kA / 2s

17. Short time thermal withstand current / kA/s Specify 30kA / 2s

duration

18. Cantilever strength kN Specify 4kN

B. LV bushing
1. Manufacturer - Specify HSP

2. Country of Origin - Specify Germany

3. Type - RIP RIP

4. Application - Oil to SF6 Oil to SF6

5. Mounting - Double flange Double flange

6. Conductor Material (copper) - Copper Copper

7. Manufacturer's type reference - Specify EKTG 650-145-


3150
8. Rated voltage kV Min 145 kV 145

9. Rated current A Specify 3150

Dubai Electricity & Water Authority Page 9 of 18 Tender RFX No.: 21323000xx
VOLUME IV
SCHEDULE B3
TECHNICAL PARTICULARS AND GUARANTEES
B3.4 – 400/132 kV TRANSFORMERS
(To be Completed and Signed by the Tenderer)

400/132kV Transformers-TYPE A-GTP-1511106 -Rev 0


Item A- Main Transformers

Part-1: Major technical particulars and guarantees (Items to be fully completed for tender submission)

No. Item Unit Required Offered

10. Coating of SF6 end terminals (Sn or Ag) - Specify Ag (Silver plated)

11. Mass of the bushing kg Specify 160

12. Type of test tap - (non-self earthing preferred) Non-self earthing type

13. Dry lightning impulse voltage withstand level kV Specify 650

14. Dynamic current / duration kA/s Specify 196kA / 2s

15. Short time thermal withstand current / kA/s Specify 56kA / 2s


duration
16. Cantilever strength kN Specify 4kN

C. HVN bushing
1. Manufacturer - Specify HSP

2. Country of Origin - Specify Germany

3. Type - RIP or OIP RIP

4. Application - Oil to air Oil to Air

5. Mounting - Single flange Single flange

6. Type: Draw lead/rod type or Solid Type - Specify Solid Conductor

7. Conductor Material - copper Copper

8. Manufacturer's type reference - Specify SETFt 325-73-3150

9. Rated voltage kV Minimum 72.5 kV 72.5

10. Rated current A Specify 3150

11. Material for the external insulator - Specify Silicone

12. Coating of air end terminal (Sn or Ag) - Specify Ag (Silver plated)

13. Mass of the bushing kg Specify 140

14. Type of test tap - (non-self earthing preferred) Non-self earthing type

15. Dry lightning impulse voltage withstand level kV Specify 325

16. Power frequency AC voltage withstand Level kV Specify 155

17. Total creepage distance of outdoor shedding mm Specify 2383

18. Creepage length per kV mm/kV 31.5 mm/kV 31.5

19. Dynamic current / duration kA/s Specify 278 kA

Dubai Electricity & Water Authority Page 10 of 18 Tender RFX No.: 21323000xx
VOLUME IV
SCHEDULE B3
TECHNICAL PARTICULARS AND GUARANTEES
B3.4 – 400/132 kV TRANSFORMERS
(To be Completed and Signed by the Tenderer)

400/132kV Transformers-TYPE A-GTP-1511106 -Rev 0


Item A- Main Transformers

Part-1: Major technical particulars and guarantees (Items to be fully completed for tender submission)

No. Item Unit Required Offered

20. Short time thermal withstand current / kA/s Specify 78.75kA/2s

duration
21. Cantilever strength kN Specify 4kN

D. TRY bushing TRY bushing will be submitted separately later.


1. Manufacturer - Specify CEDASPE

2. Country of Origin - Specify Italy

3. Type - Solid- composite type Solid-composite type

4. Application - Oil to air Oil to air

5. Mounting - Single flange Silinge flange

6. Conductor Material - Copper Copper

7. Manufacturer's type reference - Specify SBC 36-M48

8. Rated voltage kV Specify 36

9. Rated current A Specify 3150

10. Material for the external insulator - Specify Silicone

11. Coating of air end terminal - Sn or Ag Ag

12. Mass of the bushing kg Specify 30

13. Dry lightning impulse voltage withstand level kV Specify 170

14. Power frequency AC voltage withstand Level kV Specify 77

15. Total creepage distance of outdoor shedding mm Specify 1180

16. Creepage length per kV mm/kV Specify 31.5mm/kV

17. Dynamic current / duration kA/s Specify 196 kA / 2s

18. Short time thermal withstand current / kA/s Specify 78.7kA / 2s

duration
19. Cantilever strength kN Specify 3.15kN

35 For below items, refer specification and relevant IEC or other International Standards. Items shall be offered from
approved vendor list. New makes are acceptable subject to approval separately. The country of origin including sub-
assembly items shall be from Western Europe or Japan or other DEWA approved Origin. Type and features shall be
agreed separately. Where items NOT applicable mark “NA” or “-“.

Dubai Electricity & Water Authority Page 11 of 18 Tender RFX No.: 21323000xx
VOLUME IV
SCHEDULE B3
TECHNICAL PARTICULARS AND GUARANTEES
B3.4 – 400/132 kV TRANSFORMERS
(To be Completed and Signed by the Tenderer)

400/132kV Transformers-TYPE A-GTP-1511106 -Rev 0


Item A- Main Transformers

Part-1: Major technical particulars and guarantees (Items to be fully completed for tender submission)

No. Item Unit Required Offered

35A Accessories Make Country of origin

1. Buchholz relay EMB GERMANY

2. Oil surge relay for OLTC ABB SWEDEN

3. Air bag rupture relay EMB GERMANY

4. Pressure relief device QUALITROL USA

5. Air bag for conservator PRONAL FRANCE

6. Oil level indictors MESSKO GERMANY

7. Prismatic type oil level indicators MESSKO GERMANY

8. Oil temperature indicator MESSKO SWEDEN

9. Winding temperature indicator MESSKO SWEDEN

10. Maintenance free breather MESSKO GERMANY

11. Silicagel breathers TAIJIN KOREA

12. Radiator TTP INDIA

13. Cooling fan SCHORMANN GERMANY

14. Cooling pump KELVION GERMANY

15. Flexible compensator YOUNGJIN KOREA

16. Oil flow indicator TAIJIN KOREA

17. Bushing current transformer ENPAY TURKEY

18. Neutral current transformer


ITL UK
(outdoor type)
19. Current transformer (outdoor type
ITL UK
for TRY)
20. Anti-vibration pad KVT KOREA

21. Fiber optic sensor FISO CANADA

22. Butterfly type valve WON-KWANG KOREA

23. Gate and/ or ball valve OK-KWANG KOREA

Dubai Electricity & Water Authority Page 12 of 18 Tender RFX No.: 21323000xx
VOLUME IV
SCHEDULE B3
TECHNICAL PARTICULARS AND GUARANTEES
B3.4 – 400/132 kV TRANSFORMERS
(To be Completed and Signed by the Tenderer)

400/132kV Transformers-TYPE A-GTP-1511106 -Rev 0


Item A- Main Transformers

Part-1: Major technical particulars and guarantees (Items to be fully completed for tender submission)

No. Item Unit Required Offered

24. Oil flow check valve (Non-return


MPACO KOREA
Valve)
25. AVR panel (Out of HYOSUNG's scope)
35B Raw material Make Country of origin

1. Copper conductor SAM-DONG KOREA

2. CRGO POSCO KOREA

3. Insulating paper MUNKSJO SWEDEN

4. Press boards PUCARO GERMANY

5. Steel plate HYOSUNG KOREA