Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

international journal of refrigeration 32 (2009) 800–808

available at www.sciencedirect.com

w w w . i i fi i r . o r g

journal homepage: www.elsevier.com/locate/ijrefrig

Performance optimization of a hybrid cooler combining


vapor compression and natural circulation cycles

Sunil Lee, Hoon Kang, Yongchan Kim*


Department of Mechanical Engineering, Korea University, Anam-Dong, Seongbuk-Gu, Seoul 136-713, Republic of Korea

article info abstract

Article history: A hybrid cooler combining vapor compression and natural circulation cycles was devel-
Received 13 November 2008 oped for the cooling of telecommunication equipment in the cabinet-type base station of
Received in revised form mobile communication. This hybrid cooler normally operates in the vapor compression
14 December 2008 mode at high ambient temperatures, but works in the natural circulation mode at low
Accepted 17 December 2008 ambient temperatures by the thermosiphon principle. The performance of the hybrid
Published online 30 December 2008 cooler was measured according to the refrigerant charge, outdoor temperature, heat
exchanger geometry, and the vertical distance between the condenser and the evaporator.
Keywords: The optimum design conditions for these variables are discussed with respect to the
Cooling performance of the hybrid cooler in both operating modes. The difference in the optimum
Component refrigerant charge between the two operating modes was solved by installing a liquid
Electronic receiver. The temperature difference between the indoor and ambient air was introduced
Telecommunications as a control parameter for use when changing the operating mode.
Cooling system ª 2008 Elsevier Ltd and IIR. All rights reserved.
Compression system
Thermosiphon
Experiment

Optimisation de la performance d’un refroidisseur hybride


alliant les cycles à compression de vapeur et les cycles à
circulation naturelle
Mots clés : Refroidissement ; Composant ; Électronique ; Télécommunication ; Système frigorifique ; Système à compression ; Ther-
mosiphon ; Expérimentation

1. Introduction electronic devices. In addition, since the electronic devices used


in mobile communication are vulnerable to dust and humidity,
The rapid performance enhancement of electronic components a cabinet-type base station, which is generally located
has increased the amount of heat generation per unit area of outdoors, should be tightly sealed and insulated from ambient

* Corresponding author. Tel.: þ82 2 3290 3366; fax: þ82 2 921 5439.
E-mail address: yongckim@korea.ac.kr (Y. Kim).
0140-7007/$ – see front matter ª 2008 Elsevier Ltd and IIR. All rights reserved.
doi:10.1016/j.ijrefrig.2008.12.008
international journal of refrigeration 32 (2009) 800–808 801

Nomenclature DH vertical distance between evaporator and


condenser (mm)
DB dry bulb temperature ( C)
DT temperature difference between indoor and
EER energy efficiency ratio
ambient air ( C)
m mass (kg)
NC natural circulation Subscripts
OD outside diameter (mm) a actual
Q cooling capacity (W) comp compressor
RH relative humidity (%) e evaporator
T air temperature ( C) fan fan
VC vapor compression i indoor
W power consumption (W) l liquid
x quality (%) o outdoor, ambient
v vapor

air. Therefore, ambient air cannot be used directly to cool expansion valve, and an evaporator. The evaporator absorbs
telecommunication equipment located inside the base station the heat from hot indoor air. The heat is rejected to the
in the winter season even though the temperature is signifi- ambient in the condenser. On the other hand, the natural
cantly lower than the indoor temperature of the base station. circulation mode activates when the ambient air temperature
Therefore, for the cooling of the telecommunication equipment becomes lower than a certain limit. The optimum tempera-
in the cabinet-type base station of mobile communication, ture limit activating the mode change from vapor compres-
a hybrid cooler combining vapor compression (VC) and natural sion to natural circulation can be determined by comparing
circulation (NC) cycles was developed. The refrigerant flow in the actual cooling capacity with the design value. The natural
the natural circulation cycle is produced by the temperature circulation cycle, which consists of an evaporator, a riser,
difference between the indoor and ambient air without the a condenser, and a downcomer, is based on the closed loop
operation of a compressor, and this type of refrigerant flow two-phase thermosiphon principle. It should be noted that the
yielded high performance and reliability of the system in the condenser is located at higher elevation than the evaporator.
winter season. However, proper system optimization between The terms ‘‘riser’’ and ‘‘downcomer’’ describe the flow direc-
the vapor compression and the natural circulation cycle are tion through the connecting pipes in the natural circulation
essential for developing a high efficient hybrid cooler used in mode. The loop flow in the natural circulation mode is driven
the cabinet-type base station of mobile communication. by the thermally generated density gradient between the
Fig. 1 shows the schematic diagram of a hybrid cooler. The condenser and the evaporator, generating a continuous
hybrid cooler has two operating modes of vapor compression unidirectional flow in the system. The application of the
and natural circulation. The hybrid cooler normally operates natural circulation cycle to the hybrid cooler can increase
in the vapor compression mode in the summer season. The system performance and reduce the possibility of compressor
compressor circulates the refrigerant through a condenser, an failure at low ambient temperatures.

a Hybrid cooler b Hybrid cooler

Condenser Condenser

Hot ambient air Cold ambient air

EEV Comp
Cabinet-type Cabinet-type
base station base station

High High
Power Power
PCB PCB
Indoor air Indoor air
Evaporator Evaporator

VC mode NC mode

Fig. 1 – Schematic diagram of the hybrid cooler.


802 international journal of refrigeration 32 (2009) 800–808

Outdoor chamber
DB WB P DB
P DB

ΔP
Condenser

DB
WB

P : Pressure sensor

Valve 3 ΔP : Differential pressure sensor


DB : Dry-bulb temperature sensor

WB : Wet-bulb temperature sensor


Valve 1 Valve 2

EE V Compressor
P Valve 4
DB

DB WB Indoor chamber

P DB ΔP
Evaporator

DB
WB

Fig. 2 – Schematic diagram of the experimental setup.

The vapor compression system has been studied exten- refrigerant charge, ambient temperature, heat exchanger
sively to find ways for cooling telecommunication equipment. geometry, and the vertical distance between the condenser
Schmidt and Shaukatullah (2003) reviewed the literature and the evaporator. The optimum design conditions for these
dealing with various aspects of telecommunication equip- variables are discussed with respect to the operating charac-
ment by experimental and numerical analysis of cooling teristics of the hybrid cooler in both the vapor compression
schemes, energy saving schemes, and other related areas. In and the natural circulation mode. In addition, the control of
addition, extensive research on the natural circulation system
has been conducted by several researchers. The natural
circulation system was utilized in various engineering Table 1 – Specifications of the heat exchangers.
systems such as a solar water heater (Zvirin et al., 1977),
Parameter Evaporator Condenser
nuclear power plants (Dimmick et al., 2002), a gas-cooled fast
reactor (Malo et al., 2006), and an integral type reactor (Chung Heat exchanger 8 Rows, 2 Steps 8 Rows, 3 Steps
et al., 2006). However, there is no study on hybrid coolers specification Length ¼ 250 mm Length ¼ 280 mm
Transverse tube Transverse tube
combining vapor compression and natural circulation cycles
pitch ¼ 22.2 mm pitch ¼ 22.2 mm
in open literature. In addition, previous studies (Cinato et al.,
Longitudinal tube Longitudinal tube
1998; McGlen et al., 2004) on telecommunication equipment pitch ¼ 25.4 mm pitch ¼ 25.4 mm
concentrated on system performance improvement at hot Tube size OD ¼ 9.52 mm OD ¼ 9.52 mm
ambient conditions. Therefore, the optimization of the hybrid Fin specification Flat fin: Thickness ¼ 0.2032 mm, Pitch ¼ 2.004 mm
cooler should be studied comprehensively to improve the Super slit fin:
performance and reliability of the hybrid cooler system in
both the vapor compression and the natural circulation mode 1.6 mm
for hot and cold climate conditions.
2 mm
The objective of this study is to investigate the perfor-
mance optimization of the hybrid cooler with consideration of
design parameters and operating conditions. The perfor-
mance of the hybrid cooler was measured according to the
international journal of refrigeration 32 (2009) 800–808 803

the mode change between vapor compression and natural modifications reduced flow restrictions in the refrigerant
circulation is discussed in terms of the design cooling capacity path. The inlet port of the condenser was located at higher
and the temperature difference between the indoor and elevation than the outlet port, while the inlet port of the
ambient air. evaporator was located at lower elevation than the outlet port.
The operating mode of the hybrid cooler was switched
from vapor compression to natural circulation by using four
2. Experimental setup and test procedure solenoid valves. The evaporator was exposed to indoor air,
while the condenser was exposed to ambient air. In the
2.1. Design of the hybrid cooler vapor compression mode, both Valve 3 and Valve 4 were
opened, and both Valve 1 and Valve 2 were closed. The
Fig. 2 shows the schematic diagram of the experimental setup. refrigerant discharged from the compressor was cooled in
The hybrid cooler tested in this study consists of an evapo- the condenser and then, the condensed refrigerant was
rator, a condenser, a compressor, an electronic expansion expanded in the EEV. The two-phase refrigerant entering the
valve (EEV), and four solenoid valves. The hybrid cooler was evaporator absorbed the heat from the indoor air and then
designed to operate effectively and reliably not only in the returned to the compressor. When the operating mode was
vapor compression mode but also in the natural circulation changed from vapor compression to natural circulation, both
mode. A major design concern was the establishment of Valve 3 and Valve 4 were closed, and both Valve 1 and Valve
stable refrigerant flow in the natural circulation mode by 2 were opened. In the natural circulation mode, the refrig-
increase of the refrigerant density gradient between the erant vaporized in the evaporator rose to the condenser
condenser and the evaporator and by reduction of the pres- directly bypassing the compressor. Then, the refrigerant,
sure loss in the flow loop. The condenser was installed in the which was condensed in the condenser by rejecting the heat
upper part of the hybrid cooler, while the evaporator was to the cold ambient air, returned to the evaporator directly
located in the lower part, to produce unidirectional refrigerant bypassing the EEV.
circulation. The refrigerant in the natural circulation mode The evaporator was designed to have a cooling capacity of
bypassed the compressor and EEV resulting in reduction of the 1.8 kW at an evaporating temperature of 7.2  C and an air
frictional pressure loss in the flow loop. In addition, the heat volume of 6.0 m3/min in the vapor compression mode. The
exchanger coil circuitries were modified to increase the condenser was designed to have a heating capacity of 2.4 kW
refrigerant flow rate in the natural circulation mode. These at a condensing temperature of 54.4  C and an air volume of

Table 2 – Heat exchanger coil circuitries tested in this study.


Coil no. Evaporator Condenser

Coil 1

Coil 2

Coil 3
804 international journal of refrigeration 32 (2009) 800–808

9 m3/min in the vapor compression mode. Table 1 shows the masses of the saturated vapor and liquid in the system at
specifications of the heat exchangers. Both flat fins and super room temperature of 25  C.
slit fins were applied to the heat exchangers. As shown in
ma  mv
Table 2, three evaporator coil circuitries were tested to obtain Normalized charge ¼ (2)
ml  mv
the optimum design data in the natural circulation mode. The
air flow direction in the heat exchangers was counter-cross The terms of mv and ml were determined by multiplying the
flow type. The compressor was a reciprocating type with total volume of the system with the densities of the saturated
a rated capacity of 2.1 kW. The EEV was used as a refrigerant vapor and liquid at the room temperature, respectively, which
flow control device in the vapor compression mode with an were calculated by using REFPROP 7.0 (2002).
orifice diameter of 1.4 mm. The refrigerant was R134a and all For all tests, the indoor air was maintained at 40  C DB/40%
tubes used in the system had an outside diameter of 9.52 mm. RH, which is the maximum temperature for the reliable
operation of electronic devices. The outdoor air in the vapor
compression mode was fixed at 35  C DB/40% RH, while that in
2.2. Experimental apparatus and test procedure
the natural circulation mode was varied from 0 to 15.0  C with
an interval of 2.5  C. The hybrid cooler was also tested by
As shown in Fig. 2, the hybrid cooler was tested in an air-
varying the evaporator coil circuitry, as shown in Table 2,
enthalpy type psychrometric calorimeter including indoor
having both flat fins and super slit fins. In addition, the hybrid
and outdoor chambers. Each chamber was designed for
cooler was tested by varying the vertical distance between the
controlled air temperature from 10 to 50  C and relative
condenser and the evaporator from 750 to 1250 mm.
humidity (RH) from 0 to 100%. Air temperature, relative
humidity, and air flow rate passing through the heat
exchanger were measured in each chamber. A resistance
temperature sensor (Pt 100 U) was used to measure the dry
and wet bulb temperatures of air to an accuracy of 0.15  C. 3. Results and discussion
The air flow rate was measured by using a nozzle with
a diameter of 76.2 mm according to ANSI/AMCA 210 (1985). 3.1. Effects of refrigerant charge
The pressure difference across the nozzle was measured by
using an electronic differential pressure transducer with an Fig. 3 shows the cooling capacity and EER of the hybrid cooler
uncertainty of 0.25%. The capacities of the evaporator and according to the variation of normalized refrigerant charge.
the condenser were calculated by using the air-enthalpy The evaporator used Coil 2 with flat fins, and the vertical
method according to ASHRAE Standard 116 (1993). The power distance between the condenser and the evaporator (DH ) was
inputs of the compressor and fan were measured by using 750 mm. The outdoor temperature in the vapor compression
a power meter with an uncertainty of 0.2%. (VC) mode was 35  C with 40% RH, while that in the natural
The energy efficiency ratio (EER) of the hybrid cooler was circulation (NC) mode was 5  C with 40% RH. The cooling
calculated by Eq. (1), in which the cooling capacity is divided capacity and EER of the hybrid cooler in both operating modes
by the power consumption of the compressor and fan. The (VC and NC) increased and then decreased slowly after their
estimated uncertainties of the capacity and EER of the system peak values with the increase of refrigerant charge. Therefore,
were 3.72% and 3.73%, respectively, by single-sample analysis each operating mode had an optimum refrigerant charge that
according to ASHRAE Guideline 2-1986 (1986). yielded the maximum cooling capacity and EER. Generally, the
 increase of the two-phase region in the evaporator reduces
EER ¼ Qe = Wcomp þ Wfan (1)
thermal resistance, resulting in the increase of the cooling
The performance of the hybrid cooler was measured capacity. The cooling capacities in both operating modes
according to the refrigerant charge, outdoor air temperature, decreased with the decrease of refrigerant charge from the
heat exchanger geometry including coil circuitry and fin, and optimum value due to the increase of the dry-out region at the
the vertical distance between the condenser and the evapo- evaporator outlet. Especially, the decrease of the cooling
rator. Table 3 shows test conditions used in the present study. capacity in the natural circulation mode was more significant
The normalized refrigerant charge into the system was varied as the refrigerant charge decreased from the optimum value
from 0.1 to 0.3 with an interval of 0.025 to investigate optimum because the refrigerant flow became unstable with lower flow
refrigerant charge for each operating mode. The refrigerant rate. On the other hand, the cooling capacities in both oper-
charge amount was normalized between 0 and 1 by the ating modes decreased with the increase of refrigerant charge

Table 3 – Test conditions.


Parameter Vapor compression mode Natural circulation mode
 
Indoor air (DB/RH) 40 C/40% 40 C/40%
Outdoor air (DB/RH) 35  C/40% 15  C/40%, 12.5  C/40%, 10  C/40%, 7.5  C/40%, 5  C/40%, 2.5  C/40%, 0  C/40%
Normalized charge 0.1, 0.125, 0.15, 0.175, 0.2, 0.225, 0.25, 0.275, 0.3
Vertical distance (mm) 750, 1000, 1250
international journal of refrigeration 32 (2009) 800–808 805

2600 24 receiver was installed at the condenser outlet. Table 4 shows


Q in VC mode EER in VC mode the design process of the liquid receiver. The difference in the
2400
Q in NCmode EER in NC mode
20 optimum refrigerant charge was 187 g, and the required
Cooling capacity, Q (W)

2200
volume to store this refrigerant at liquid state was 172 mL at
2000
16 the condenser outlet temperature of 54.4  C. Therefore, the
1800
volume of the liquid receiver was selected as 344 mL by

EER
1600 12 assuming that 50% of the volume was filled with liquid
1400 VC mode : Ti=40°C,T =35°C
° refrigerant. It should be noted that the volume of the liquid
1200 NC mode : Ti=40°C,T =5°C 3 receiver was approximately 8.4% of the total volume of the
°
H=750 mm, Coil 2 with flat fin hybrid cooler.
1000
800
Fig. 4 represents the effects of refrigerant charge on the
2
performance of the modified hybrid cooler with the liquid
600
0.10 0.15 0.20 0.25 0.30 receiver. The modified hybrid cooler showed the optimum
Normalized charge normalized refrigerant charge of 0.2 in both operating modes.
The liquid receiver works like a capacitor in an electronic
Fig. 3 – Effects of refrigerant charge on the performance of circuit. Excessive refrigerant was stored in the liquid receiver.
the hybrid cooler without a liquid receiver. At the optimum normalized refrigerant charge of 0.2, the
optimum capacity and EER of the modified hybrid cooler in the
vapor compression mode were 2.49 and 1.88 kW, respectively,
from the optimum value due to the increase of the subcooled while those in the natural circulation mode were 19.42 and
liquid region at the evaporator inlet. 1.77 kW, respectively. In the vapor compression mode, the
In this study, the optimum normalized refrigerant charges cooling capacity of the system remained nearly constant at
in the vapor compression and the natural circulation mode, the peak value with the increase of normalized refrigerant
which were determined based on the maximum EER, were charge from 0.2. However, in the natural circulation mode, the
0.125 and 0.175, respectively. At each optimum refrigerant cooling capacity slightly decreased with the increase of
charge, the optimum capacity and EER of the hybrid cooler in normalized refrigerant charge beyond the optimum value
the vapor compression mode were 2.52 and 1.92 kW, respec- because excessive refrigerant entered the evaporator without
tively, while those in the natural circulation mode were 19.36 being stored in the liquid receiver; therefore, this cooling
and 1.80 kW, respectively. The natural circulation cycle capacity behavior was very close to the trend observed in the
showed significantly higher EER than the vapor compression original system without the liquid receiver.
cycle due to the use of the cold outdoor air as a driving force
for refrigerant circulation instead of the compressor. In addi- 3.2. Effects of outdoor temperature
tion, the natural circulation cycle required more refrigerant
charge than the vapor compression cycle to achieve stable Fig. 5 represents the cooling capacity of the modified hybrid
natural refrigerant circulation with an appropriate density cooler with the variation of the temperature difference
gradient. Therefore, the performance of the hybrid cooler between the indoor and outdoor air (DT ). The tested hybrid
degraded significantly when it did not operate at the optimum cooler adopted the liquid receiver, and the normalized
refrigerant charge in each operating mode. When the hybrid refrigerant charge was fixed at the optimum value of 0.2. The
cooler was operated at the normalized refrigerant charge of cooling capacity was measured in each operating mode with
0.125, which was the optimum value in the vapor compression the indoor temperature fixed at 40  C and the outdoor
mode, the cooling capacity and EER of the hybrid cooler in the temperature decreased from 15.0 to 0  C. The DT increased
natural circulation mode were 1.50 kW and 16.08, respec-
tively, which were 16.9% lower than those obtained when the
hybrid cooler was operated at the optimum refrigerant charge. 2600 24
In order to compensate the difference in the optimum Q in VC mode EER in VC mode
2400
Q in NC mode EER in NC mode
refrigerant charge between the two operating modes, a liquid 20
Cooling capacity, Q (W)

2200
2000
16
1800
EER

Table 4 – Design process of the liquid receiver. 1600 12


1400 VC mode : Ti=40°C,T =35°C
Optimum Optimum charge in VC mode ¼ 467 g °
NC mode : Ti=40°C,T =5°C
refrigerant charge (Normalized charge ¼ 0.125) 1200 ° 3
Optimum charge in NC mode ¼ 654 g H=750 mm, Coil 2 with flat fin
1000
(Normalized charge ¼ 0.175)
800 2
Difference of the optimum charge ¼ 187 g
Density at the Density at T ¼ 54.4  C and x ¼ 0%: 1.082 g/mL 600
0.10 0.15 0.20 0.25 0.30
condenser outlet
Size selection Volume of liquid: 187 g/1.082 g/mL ¼ 172 mL Normalized charge
Portion of liquid in the liquid receiver ¼ 1/2
Volume of the liquid receiver ¼ 172  2 ¼ 344 mL
Fig. 4 – Effects of refrigerant charge on the performance of
the hybrid cooler with a liquid receiver.
806 international journal of refrigeration 32 (2009) 800–808

VC mode at H=750 mm 3.3. Effects of heat exchanger geometry


2000
NC mode at H=750 mm, NC mode at H=1000 mm
As mentioned, the heat exchangers had unique coil circuit-
Cooling capacity, Q (W)

1800
ries designed for the natural circulation cycle. Fig. 6 repre-
1600 sents the effects of the tube length per each path on the
Target capacity cooling capacity of the modified hybrid cooler. Coil 1, Coil 2,
1400 and Coil 3, which are shown in Table 2, had the tube lengths
per each path of 1 m, 2 m, and 4 m, respectively. The hybrid
1200 cooler with the liquid receiver was tested at the normalized
Ti=40°C,Coil 2 with flat fin refrigerant charge of 0.2 and DH ¼ 750 mm. The indoor
1000 Normalized charge = 0.2 temperature in both operating modes was fixed at 40  C. The
T=Ti-T
° outdoor temperature in the vapor compression mode was
800
35  C, while that in the natural circulation mode was 7.5  C.
24 28 32 36 40 The cooling capacity in the vapor compression mode
Temperature difference, T (°C) increased slowly with the increase of the tube length per
each path. In the natural circulation mode with the adoption
Fig. 5 – Effects of outdoor temperature on the cooling
of flat fins, the cooling capacity increased by 10.7% with the
capacity of the hybrid cooler.
increase of the tube length per each path from 1 to 2 m
because of the increase of the two-phase region in the
evaporator. However, the cooling capacity decreased by 2.2%
with the increase of the tube length per each path from 2 to
with the decrease of the outdoor temperature. The cooling 4 m because of the pre-existence of dry-out in the evapo-
capacity in the vapor compression mode decreased slightly rator. There is an optimum tube length per each path that
with the decrease of the outdoor temperature. On the other will yield the optimum cooling capacities, in both operating
hand, the cooling capacity in the natural circulation mode modes. Especially, the cooling capacity of the natural
increased significantly with the decrease of the outdoor circulation cycle was more strongly affected by the coil
temperature due to the increase in refrigerant flow rate. The circuitry than that of the vapor compression cycle. There-
maximum cooling capacity in the natural circulation mode fore, the coil circuitry should be optimized as priority based
was 1.84 kW at the DT of 35  C and vertical distance (DH ) of on the cooling capacity in the natural circulation mode. In
1000 mm; this capacity was consistent with the cooling this study, the optimum tube length per each path was 2 m,
capacity of 1.84 kW in the vapor compression mode at the which yielded the maximum cooling capacities of 1.61 kW
same DT. However, as the DT increased from 35  C (To ¼ 5  C) and 1.71 kW for flat fins and super slit fins, respectively, in
to 40  C (To ¼ 0  C), the cooling capacity decreased slightly due the natural circulation mode.
to the increase of the subcooled region at the evaporator inlet The super slit fins enhanced the airside heat transfer
resulting from excessive liquid return from the condenser. coefficient of the heat exchangers, resulting in the increase
As shown in Fig. 5, the cooling capacity in the natural of the cooling capacity. The cooling capacities in the vapor
circulation mode was strongly dependent on the DT. When the compression and the natural circulation mode increased by
DT is large enough, the designed cooling capacity can be 1.7% and 5.9% on average, respectively, when the flat fins
obtained with stable system operations. Therefore, the DT can were replaced with super slit fins in the heat exchangers.
be used as a control parameter to determine the switching Therefore, the performance of the natural circulation cycle
point of the operating mode. If the designed cooling capacity is
1.60 kW at DH ¼ 750 mm, DT ¼ 32.5  C (To ¼ 7.5  C) can be the
point for switching the mode from vapor compression to 2100
natural circulation. In addition, as shown in Fig. 5, the VC mode : Ti=40°C,T =35°C Normalized charge = 0.2
°
2000 NC mode : Ti=40°C,T =7.5°C ΔH=750 mm
increasing slope of the cooling capacity with respect to DT at °
DH ¼ 1000 mm was higher than that at DH ¼ 750 mm. At larger 1900
Cooling capacity, Q (W)

DH, the DT for the operating mode switch becomes lower and
the operating period of the natural circulation mode 1800
increases, which can reduce system power consumption due
1700
to a significantly higher EER in the natural circulation mode.
Generally, the cooling capacity of the natural circulation mode 1600
is lower than that of the vapor compression mode. The
cabinet-type base station has less internal load in the winter 1500 Flat fin in VC mode
Flat fin in NC mode
season (natural circulation mode) than that in the summer 1400 Super slit fin in VC mode
season (vapor compression mode) due to heat loss to the cold Super slit fin in NC mode
ambient. Therefore, the reduction of the internal load in the 1300
1m (Coil 1) 2m (Coil 2) 4m (Coil 3)
winter season can partially contribute to compensate the lack
Tube length per each path (m)
of the cooling capacity in the natural circulation mode.
However, it is recommended to optimize the cooling capacity Fig. 6 – Effects of heat exchanger geometry on the cooling
based on that of the natural circulation mode. capacity of the hybrid cooler.
international journal of refrigeration 32 (2009) 800–808 807

VC mode : Ti=40°C, T =35°C Normalized charge = 0.2


1900 NC mode : Ti=40°C
° 4. Conclusions
Coil 2 with flat fin
Cooling capacity, Q (W)

The performance optimization of the hybrid cooler with


1800
consideration of design parameters and operating conditions
was carried out in this study. The performance of the hybrid
1700 cooler was measured for variations of the refrigerant charge,
outdoor temperature, heat exchanger geometry, and the
vertical distance between the condenser and the evaporator
1600
(DH ). The optimum normalized refrigerant charges in the vapor
VC mode
NC mode at T =7.5°C compression and the natural circulation mode were 0.125 and
°
1500 NC mode at T =5°C 0.175, respectively. The modified system with the liquid receiver
°
showed the optimum normalized refrigerant charge of 0.2 in
625 750 875 1000 1125 1250 1375 both operating modes because excessive refrigerant was stored
Vertical distance, H (mm) in the liquid receiver in the vapor compression mode. The
cooling capacity in the natural circulation mode increased
Fig. 7 – Effects of vertical distance on the cooling capacity of
significantly with the reduction of the outdoor temperature due
the hybrid cooler.
to the increase in the refrigerant flow rate. Therefore, the
temperature difference between the indoor and outdoor air (DT )
can be used as a control parameter for the change of the oper-
ating mode. The optimum tube length per each path and the
was more strongly dependent on the airside heat transfer
optimum vertical distance DH for the hybrid cooler to achieve
coefficient than that of the vapor compression cycle. In the
optimum cooling capacities in both operating modes were 2.0 m
natural circulation mode, the refrigerant flow rate was
(Coil 2 in Table 2) and 1000 mm, respectively. The performance
dominantly determined by the capacities of the evaporator
of the natural circulation cycle was more strongly affected by
and condenser; in the vapor compression mode, it was
the coil circuitry, fin type, and vertical distance DH than that of
more strongly affected by the capacities of the compressor
the vapor compression cycle. Therefore, these design parame-
and EEV.
ters should be optimized as priority based on the cooling
capacity in the natural circulation mode. In addition, the natural
3.4. Effects of vertical distance circulation cycle showed significantly higher EER than the vapor
compression cycle because natural refrigerant circulation was
In the natural circulation mode, the driving force for the used instead of the compressor.
liquid refrigerant return to the evaporator was gravitational
force. The longer the vertical distance between the
condenser and the evaporator (DH ), the stronger the driving Acknowledgements
force. The hybrid cooler having Coil 2 with flat fins was
tested for the variation of the DH from 750 to 1250 mm at the This research was supported by a grant 2008NBLHME090000
optimum normalized refrigerant charge of 0.2. The indoor from the Korea Institute of Energy and Resources Technology
temperature in both operating modes was fixed at 40  C. The Evaluation and Planning.
outdoor temperature in the vapor compression mode was
35  C, and those in the natural circulation mode were 5  C
and 7.5  C. references
Fig. 7 shows the effects of the vertical distance DH on the
cooling capacity of the modified hybrid cooler. The cooling
capacity of the vapor compression cycle remained nearly ANSI/AMCA 210, 1985. Laboratory Methods of Testing Fans for
constant at 1.84 kW regardless of the vertical distance DH. Rating. ANSI, Arlington, VA.
However, the cooling capacity of the natural circulation cycle ASHRAE Guideline 2-1986, 1986. Engineering Analysis of
was the maximum at DH ¼ 1000 mm and then rapidly Experimental Data. ASHRAE, Atlanta, GA, USA.
decreased as DH deviated from the optimum value. The ASHRAE Standard 116, 1993. Methods of Testing for Seasonal
Efficiency of Unitary Air-Conditioner and Heat Pumps.
cooling capacity of the natural circulation cycle at To ¼ 7.5  C
ASHRAE Standard 116. ASHRAE, Atlanta, GA.
increased by 7.1% with the increase of DH from 750 to Chung, Y.J., Kim, H.C., Chung, B.D., Chung, M.K., Zee, S.Q., 2006.
1000 mm due to the rise of the driving force of refrigerant Two-phase natural circulation and the heat transfer in the
circulation. However, as DH increased from 1000 to 1250 mm, passive residual heat removal system of an integral type
the cooling capacity of the natural circulation cycle at reactor. Ann. Nucl. Energy, 262–270.
To ¼ 7.5  C decreased by 5.5% due to the rapid increase of the Cinato, P., Bianco, C., Licciardi, L., Pizzuti, F., Antonetti, M.,
Grossoni, M., 1998. An innovative approach to the
vapor pressure drop in the riser. Therefore, the optimum
environmental system design for TLC rooms in telecom Italia,
vertical distance for the present system was 1000 mm, which
INTELEC.
yielded the optimum cooling capacities of 1.84 kW and Dimmick, G.R., Chatoorgoon, V., Khartabil, H.F., Duffey, R.B., 2002.
1.67 kW at the outdoor temperatures of 5  C and 7.5  C, Natural-convection studies for advanced CANDU reactor
respectively. concepts. Nucl. Eng. Des. 215, 27–38.
808 international journal of refrigeration 32 (2009) 800–808

Malo, J.Y., Bassi, C., Cadiou, T., Blanc, M., Messie, A., Tosselo, A., REFPROP 7.0, 2002. National Institution of Standards and
Dumaz, P., 2006. Gas-cooled fast reactors-DHR systems, Technology Gaithersburg, MD, USA.
preliminary design and thermal-hydraulics studies. Nucl. Eng. Schmidt, R.R., Shaukatullah, H., 2003. Computer and
Technol. 38 (2), 129–138. telecommunications equipment room cooling; a review of
McGlen, R.J., Jachuck, R., Lin, S., 2004. Integrated thermal literature. IEEE Trans. Compon. Packag. Tech. 26 (1), 89–98.
management techniques for high power electronic devices. Zvirin, Y., Shitzer, A., Grossman, G., 1977. The natural circulation
Appl. Therm. Eng. 24, 1143–1156. solar heater-models with linear and nonlinear temperature
distributions. Int. J. Heat Mass Transfer 20, 997–999.

You might also like