OCP24 F08 Daily Check List For Fire Suppression System

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Document Number: OCP 24 F08

EMBASSY REIT Issued Date: 01/04/2021


Integrated Management System Rev.00
Daily Check list for Fire Suppression System Revision Date: NA

Block: Wing: Date:

Sl. No. Description Spec Status/record Remarks

Hydrant System

>8Kg/cm2 / as
1 Header Pressure
specified

2 Check all the line valves are open Should be open

3 Check all drain & priming valves are close Should be closed

4 Test run the booster, Main & DG pumps. Normal operation

5 Check all pumps are in auto Auto mode

6 DG pump Auto mode

7 Battery Voltage >24 V

8 Lube oil level Medium

9 Fuel oil level >75%

10 Coolant level Up to the brim

Sprinkler System

>8Kg/cm2 / as
1 Header Pressure
specified

2 Check all the line valves are open Should be open

3 Check all drain & priming valves are close Should be closed

4 Test run the booster, Main & DG pumps. Normal operation

5 Check all pumps are in auto Auto mode

6 DG pump Auto mode

7 Battery Voltage >24 V

8 Lube oil level Medium

9 Fuel oil level >75%

10 Coolant level Up to the brim

General

Check for meter


1 Power supply to the panel is normal.
parameter

2 Check for any gland leakage No Leak

3 Main fire tank level - Ground floor 100% filled

4 Terrace fire tank level 100% filled

Fireman Sign. Fire Officer Sign. Maintenance Sup. Sign.


Document Number: OCP 24 F08
EMBASSY REIT Issued Date: 01/04/2021
Integrated Management System Rev.00
Daily Check list for Fire Suppression System Revision Date: NA

Block: Wing: Date:

Sl. No. Description Spec Status/record Remarks

Hydrant System

>8Kg/cm2 / as
1 Header Pressure
specified

2 Check all the line valves are open Should be open

3 Check all drain & priming valves are close Should be closed

4 Test run the booster, Main & DG pumps. Normal operation

5 Check all pumps are in auto Auto mode

6 DG pump Auto mode

7 Battery Voltage >24 V

8 Lube oil level Medium

9 Fuel oil level >75%

10 Coolant level Up to the brim

Sprinkler System

>8Kg/cm2 / as
1 Header Pressure
specified

2 Check all the line valves are open Should be open

3 Check all drain & priming valves are close Should be closed

4 Test run the booster, Main & DG pumps. Normal operation

5 Check all pumps are in auto Auto mode

6 DG pump Auto mode

7 Battery Voltage >24 V

8 Lube oil level Medium

9 Fuel oil level >75%

10 Coolant level Up to the brim

General

Check for meter


1 Power supply to the panel is normal.
parameter

2 Check for any gland leakage No Leak

3 Main fire tank level - Ground floor 100% filled

4 Terrace fire tank level 100% filled

Fireman Sign. Fire Officer Sign. Maintenance Sup. Sign.