Professional Documents
Culture Documents
NFPA 59 Distancia Entre Tanques LPG
NFPA 59 Distancia Entre Tanques LPG
11 – 10 Oficina 802
Bogotá, D.C. Colombia – Suramérica
E-mail : noguera2@onc.com.co
Tel: (571) 3 47 66 01 Fax: (571) 2 12 98 14
División Control de Pérdidas
Seguridad Contra Incendio
Este extracto es tomado de la norma NFPA 59 para ilustración sobre las distancias mínimas
que deben separar tanques de almacenamiento de gas licuado de propano entre sí, y entre
ellos y otras construcciones o límites de la propiedad.
Preparado por: Germán Noguera Camacho para SICOLSA, por recomendación de Suratep
NFPA 59
Standard for the Storage and Handling of Liquefied Petroleum
Gases at Utility Gas Plants
1998 Edition
1-1.2 The term liquefied petroleum gases (LP-Gases), as used in this standard, shall mean and
include any material that has a vapor pressure that does not exceed that allowed for commercial
propane, which is composed predominantly of any of the following hydrocarbons, or mixtures of
them — propane, propylene, butanes (normal butane or isobutane), and butylenes.
1- 4 Definitions.
Containers. Vessels, such as tanks, cylinders, or drums, that are used for storing liquefied
petroleum gases.
Utility Gas Plant. A fuel gas distribution facility that is owned or operated by a utility, as
designated by the appropriate governing jurisdiction.
División
Control de Pérdidas
Seguridad Contra Incendio
2-4.1.2 Containers shall be located in accordance with Table 2-4.1.2 with respect to the distance
between containers, the distance between containers and the nearest important building or group
of buildings not associated with the LP-Gas plant, or a line of adjoining property that can be built
upon.
Table 2-4.1.2 Nonrefrigerated Container Installation Minimum Distances
Minimum Distances
From Container to Nearest
Water Capacity of Each Important Building or Group, of
Buildings Not Associated with the
Container Between Containers Utility Gas Plant, or a Line of
Adjoining Property That Can Be
Built Upon
gal (m3) ft (m) ft (m)
2001 to 30,000 (7.6 to 114) 5 (1.5 m) 50 (15)
1/4 of sum of diameters of
30,001 to 70,000 (114 to 265) 75 (23)
adjacent containers
1/4 of sum of diameters of
70,001 to 90,000 (265 to 341) 100 (30)
adjacent containers
1/4 of sum of diameters of
90,001 to 120,000 (341 to 454) 125 (38)
adjacent containers
1/4 of sum of diameters of
120,001 to 200,000 (454 to 757) 200 (61)
adjacent containers
200,001 to 1,000,000 (757 to 1/4 of sum of diameters of
300 (91)
3785) adjacent containers
1/4 of sum of diameters of
1,000,001 or more (over 3785) 400 (122)
adjacent containers
Note: The spacing of containers from buildings associated with utility gas plants shall be permitted to be reduced
to 50 percent of the distances in Table 2-4.1.2, with a minimum separation of 50 ft (15 m).
Página 2
División
Control de Pérdidas
Seguridad Contra Incendio
2-4.1.3 Multiple aboveground containers (or groups of containers) installed for use in a single
location shall be limited to the number of containers in one group, with each group separated
from the next group in accordance with the degree of fire protection provided in Table 2-4.1.3.
Containers shall be oriented so that their longitudinal axes do not point toward other containers,
aboveground liquefied natural gas tanks, and flammable liquid storage tanks on the same or
adjoining property.
2-4.1.4 All aboveground LP-Gas containers shall be located 100 ft (30.5 m) or more from
flammable liquids containers.
2-4.1.5 Nonrefrigerated LP-Gas containers shall not be located within dikes that enclose
flammable liquid tanks and shall not be located within dikes that enclose refrigerated LP-Gas
tanks.
2-4.1.6 Loose or piled combustible material and weeds and long, dry grass shall not be permitted
within 25 ft (7.6 m) of any container.
2-5.1.1 Every container shall be supported to prevent the concentration of excessive loads on the
supporting portion of the shell or heads.
2-5.1.2 Supports for containers shall be of solid masonry, concrete, or steel. Structural metal
supports shall be permitted to be employed where they are protected against fire in an approved
manner. Metal supports shall be protected against fire with a material that has a fire resistance
rating of at least 2 hours. Steel skirts that have only one opening that is 18 in. (462 mm) or less in
diameter shall be protected in accordance with the preceding, but fireproofing shall be required
to be applied only to the outside of the skirt …
Página 3