Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Source Control Document.

Preliminary
Model: BAP 319-125/48F4T-U5119
COSD: XXXX
Summary description: 400W Industrial Quality DC/DC Converter
125Vdc to -48Vdc/8.3A
Customer Name: Ferney Gutierrez ltda / Colombia
Customer Part Number: Same as above

Product Description:
This rugged, industrial-quality power converter utilizes field-proven technology to generate the required output power. It is a mature design
with a track record in numerous applications. Cooling is by conduction via baseplate. Additional cooling is achieved by natural convection
through the cooling slots. All heat-generating components are installed on aluminum heatsink blocks which are thermally connected to the
base plate. This also provides exceptional mechanical ruggedness. Conformal coating provides protection against humidity and airborne
contaminants. Full electronic protection, low component count, large design headrooms and the exclusive use of components with established
reliability contribute to a high MTBF. The unit is manufactured at our plant under strict quality control.
Special features: Conformal coating.

SPECIFICATIONS
Input Voltage Line/Load Regulation Shock/Vibration
125Vdc nominal ±1% combined from zero load to full IEC 61373 Cat 1 A&B
90-145Vdc operating range load including redundancy diode
Humidity
Input Current: 6.6A max
5-95% non-condensing
Dynamic Response
Input Protection Max 5% voltage deviation for 10% to MTBF
Inrush current limiting 50% load step, with better than 1msec 150,000 hours @ 45ºC
Varistor recovery time Demonstrated MTBF is significantly
Reverse polarity protection higher
Internal safety fuse Output Ripple/Noise
Lower voltage than the specified Better than 80mVrms or 400mVpp Indicators
minimum input will not damage the unit (@ 20MHz BW) Green OUTPUT ON LED visible through
the cooling slots
Isolation Output Overload Protection Control Input
1500Vdc input to chassis Rectangular current limiting with None
2250Vdc input to output hiccup-type short-circuit protection
700Vdc output to chassis Current Limit: 10A ± 1.0A Alarm Outputs
None
Standards Output Overvoltage Protection Package/Dimensions (WxHxL)
Designed to meet EN62368-1 and The second regulator loop is F4: 130 x 64 x 353mm
related standards completely stable and independent of (5.1” x 2.5” x 13.9”)
the main regulator loop Mounting holes are clear
EMI OVP setting: 54V ± 3V
EN55022 Class A with margins
Weight
Efficiency 2.2kg (4.9 lbs)
Switching Frequency 85% at full load
55kHz ±3kHz
Connections
Operating Temperature Range 12-pole, barrier type terminal block
0ºC to +50ºC for full specification 3/8” spacing
Output Voltage/Current
-48Vdc ± 0.3V/8.3A Temperature Drift RoHS Compliance
Output is floating, either terminal 0.03% per ºC over operating Not required, but accepted
can be grounded temperature range Warranty
Redundancy diode Two years subject to application
Cooling within good engineering practice
Not installed Conduction via a base plate and
natural air convection

Environmental Protection Drawn by Date


Terminal Block Pin-out Basic ruggedizing TS/lp February 23, 2024
Conformal coating
Checked by Drawing No./ Rev.
TS SCD U5119-A
Approved by
This document is the property of Absopulse Electronics Ltd. Its contents are proprietary and may neither be copied,
reproduced, nor its contents disclosed to others without prior written agreement from Absopulse Electronics Ltd.
TS
Absopulse Electronics Ltd. Tel: (613) 836-3511; Fax: (613) 836-7488; 110 Walgreen Rd; Carp; ON. K0A 1L0

You might also like