Professional Documents
Culture Documents
Sheet (6) Differential Protection
Sheet (6) Differential Protection
The current ratios of the current transformers on the 132 kV side are 250/5A while
those on the 33 kV side are 600/5A. If the impedance of the transformer is 9% and a
3-phase fault occurs on the 33 kV side of the transformer outside its zone of protection,
a. Determine the currents, Ir & Is. Ignore the impedances of the cables.
b. Determine the average restraint current and operating current in the relay.
c. The bias characteristic of the relay is y = mx where y is operating current, x is
average restraint current and m is slope. Draw a neat sketch of the characteristic
curve of this relay if m is 10%. Mark the scales used for both the x-axis and y-
axis neatly on the sketch.
d. Mark the operating point of the relay due to this fault on the sketch. Will the
relay operate?
1/4
Dept.: Electr. Power & M/Cs 4th Year Electr. Power & M/Cs
Course: Power System Protection Differential Protection
Code: EPE426 Zagazig University Sheet (6)/4 Pages
Faculty of Engineering
of protection by marking the operating point the relay due to this fault on the
sketch. Ignore the impedances of the source and cables.
(CT ratios available: 500/5 A, 600/5 A, 800/5 A, 900/5 A, 1000/5 A, 1500/5 A, 2000/5
A & 3000/5 A)
Question 4: For the above transformer in Q3, determine if the relay will operate for a
fault outside the zone of protection on the 33 kV side of the transformer. The relay has
a bias characteristic of 10%. Draw the relay's operating characteristic curve indicate
the operating points on it.
2/4
Dept.: Electr. Power & M/Cs 4th Year Electr. Power & M/Cs
Course: Power System Protection Differential Protection
Code: EPE426 Zagazig University Sheet (6)/4 Pages
Faculty of Engineering
Question 10: A 3-Φ Generator, 11 kV has 12.5% reactance and rated power of 2.5
MVA at 0.8 p.f. It is equipped with circulating current system of protection which is
set to operate at fault currents not less than 150A. Find the value of NER required for
protecting 90% of the stator winding.
3/4
Dept.: Electr. Power & M/Cs 4th Year Electr. Power & M/Cs
Course: Power System Protection Differential Protection
Code: EPE426 Zagazig University Sheet (6)/4 Pages
Faculty of Engineering
400 A 20 A 420 A
Restrains
Operating
Fig. Q4
Question 12: A 6.6 kV, 5 MVA Y-connected synchronous generator has a reactance
of 1.5 Ω/ph and negligible resistance. A Merz-prize differential protection scheme is
used which operates when the out of balance current exceeds 25% of the full load
current. The neutral of the generator is grounded through a resistance of 8 Ω.
Determine the portion of winding which remains unprotected against earth fault. Show
that the effect of alternator reactance can be neglected.
4/4