Professional Documents
Culture Documents
Handover Docs
Handover Docs
CATALOGUE &
SPECIFICATION
Compressor Damper
Thermostat
Insulation
Butterfly valve
Gate valve
Y strainer
Balancing valve
Ball valve
Thermometer
Pressure gauge
Air vent
uPVC pipe
AHU
TECHNICAL REPORT
GENERAL
Unit Height : 1200 mm Unit Height (Top) : 0 mm
Unit Width : 1650 mm Door Type : Hinged
Fresh Air App. : Yes
DESIGN CONDITIONS
Air Flow Supply Air : 6563 m³/h
Return Air : 5807 m³/h
Filter Face Velocity Limit: 2.50 m/s Coil Face Velocity Limit : 2.00 m/s
Av.Face Velocity : 1.64 m/s Av. Face Velocity : 1.57 m/s
PROFILE
Inner Skin Material : GI Outer Skin Material : GI
Skin Thickness : 0.5 mm Skin Thickness : 0.5 mm
Surface Painted : Yes Surface Painted : Yes
1 MIXING BOX
Damper Selection : Top & Front User Define Temp: No Dry Bulb Temp. :
Blade Type : Opposed Pressure Drop : 23 Pa Wet Bulb Temp. :
GUIDE
TOP FRONT LEFT RIGHT
3 SECONDARY FILTER
4 DX COOLING COIL
5 COOLING COIL
7 SUPPLY FAN
GENERAL
Unit Height : 1200 mm Unit Height (Top) : 0 mm
Unit Width : 1450 mm Door Type : Hinged
Fresh Air App. : Yes
DESIGN CONDITIONS
Air Flow Supply Air : 5634 m³/h
Return Air : 4259 m³/h
Filter Face Velocity Limit: 2.50 m/s Coil Face Velocity Limit : 2.00 m/s
Av.Face Velocity : 2.11 m/s Av. Face Velocity : 1.62 m/s
PROFILE
Inner Skin Material : GI Outer Skin Material : GI
Skin Thickness : 0.5 mm Skin Thickness : 0.5 mm
Surface Painted : Yes Surface Painted : Yes
1 MIXING BOX
Damper Selection : Top & Front User Define Temp: No Dry Bulb Temp. :
Blade Type : Opposed Pressure Drop : 25 Pa Wet Bulb Temp. :
GUIDE
TOP FRONT LEFT RIGHT
TECHNICAL REPORT
2 PRIMARY FILTER
3 SECONDARY FILTER
4 DX COOLING COIL
5 COOLING COIL
7 SUPPLY FAN
GENERAL
Unit Height : 900 mm Unit Height (Top) : 0 mm
Unit Width : 1200 mm Door Type : Hinged
Fresh Air App. : Yes
DESIGN CONDITIONS
Air Flow Supply Air : 3316 m³/h
Return Air : 3024 m³/h
Filter Face Velocity Limit: 2.50 m/s Coil Face Velocity Limit : 2.00 m/s
Av.Face Velocity : 1.65 m/s Av. Face Velocity : 1.68 m/s
PROFILE
Inner Skin Material : GI Outer Skin Material : GI
Skin Thickness : 0.5 mm Skin Thickness : 0.5 mm
Surface Painted : Yes Surface Painted : Yes
1 MIXING BOX
Damper Selection : Top & Front User Define Temp: No Dry Bulb Temp. :
Blade Type : Opposed Pressure Drop : 12 Pa Wet Bulb Temp. :
GUIDE
TOP FRONT LEFT RIGHT
3 SECONDARY FILTER
4 COOLING COIL
5 SUPPLY FAN
GENERAL
Unit Height : 1200 mm Unit Height (Top) : 0 mm
Unit Width : 2280 mm Door Type : Hinged
Fresh Air App. : Yes
DESIGN CONDITIONS
Air Flow Supply Air : 7214 m³/h
Filter Face Velocity Limit: 2.50 m/s Coil Face Velocity Limit : 2.00 m/s
Av.Face Velocity : 1.83 m/s Av. Face Velocity : 1.76 m/s
PROFILE
Inner Skin Material : GI Outer Skin Material : GI
Skin Thickness : 0.5 mm Skin Thickness : 0.5 mm
Surface Painted : Yes Surface Painted : Yes
GUIDE
TOP FRONT LEFT RIGHT
2 PRIMARY FILTER
Type : Flat ( 2" Washable ) FILTER QUANTITY AIR PRESSURE DROP
Grade : G4 (>90% Arr) 295 x 595 mm : 2 Initial : 40 Pa
Latch : - Not Applicable - 595 x 595 mm : 2 Final : 250 Pa
Frame : 2" Rail Design : 125 Pa
3 SECONDARY FILTER
Type : Box FILTER QUANTITY AIR PRESSURE DROP
Grade : F8 (90-95% Eff) 295 x 595 mm : 2 Initial : 190 Pa
Latch : - Not Applicable - 595 x 595 mm : 2 Final : 500 Pa
Frame : Aluminum Design : 350 Pa
4 DESICCANT WHEEL
Process Air flow: 5400 m³/h Regen. Air flow: 1800 m³/h Type PSS-S 850x200 - 1/3
Pressure Drop: 303 Pa Pressure Drop: 318 Pa Dimension Height x Length x Width
Drive equipment: 3Ph/380V/90W Dehumidification cap: 27.4 kg/h 1050 x 1050 x 297 mm
5 COOLING COIL
COIL SPECIFICATIONS AIR SIDE WATER SIDE
Rows : 4 Entering Entering Temp. : 7.0 °C
Fin Per Inch : 12 Dry Bulb : 31.6 °C Leaving Temp. : 12.1 °C
Tube Height : 26 Wet Bulb : 15.1 °C Water Velocity: 2.44 m/s
Fin Length : 1219 mm Relative Humidity : 13.8 % Flow Rate : 2.3 L/s
Fin Height : 953 mm Leaving Pressure Drop : 155.05 kPa
TPC : F Dry Bulb : 11.6 °C Glycol : 0 %
Tube Type : Plain Wet Bulb : 6.5 °C
Tube Material : Copper Relative Humidity : 47.0 %
Fin Material : Aluminium
Drain Pan : Yes COIL PERFORMANCE
Drain Pan Material : SS201 Air Velocity : 1.76 m/s Sensible Capacity : 49.12 kW
Coil Header Size: 1¼'' Total Capacity : 57.8 kW Pressure Drop : 41 Pa
Tube Diameter : 1/2"
6 SUPPLY FAN
Air volume flow rate: 7214 m³/h Manufacturer Ziehl_Abegg
ESP : 780 Pa Fan Count: 2 pcs
TSP : 1577 Pa Model: GR35C-ZID.DG.CR
Total Pressure : 1618 Pa Efficiency: 61.96 %
Speed: 3124 rpm
Power: 2750 W
Max.Power: 3700 W
Current rated: 4.03 A
Input source 3~400Vac 50/60Hz
Maximum Speed: 3400 rpm
7 PRIMARY FILTER (REGENERATION AIR)
Type : Flat ( 2" Washable ) FILTER QUANTITY AIR PRESSURE DROP
Grade : G4 (>90% Arr) 295 x 595 mm : 0 Initial : 40 Pa
Latch : - Not Applicable - 595 x 595 mm : 1 Final : 250 Pa
Frame : Aluminium Design : 125 Pa
9 HEATING COIL
COIL SPECIFICATIONS AIR SIDE WATER SIDE
Rows : 4 Entering Entering Temp. : 140.0 °C
Fin Per Inch : 10 Dry Bulb : 36.0 °C Leaving Temp. : 90.0 °C
Tube Height : 25 Wet Bulb : 30.0 °C Water Velocity: 0.08 m/s
Fin Length : 480 mm Relative Humidity : 64.9 % Flow Rate : 0.2 L/s
Fin Height : 794 mm Leaving Pressure Drop : 0.07 kPa
TPC : B Dry Bulb : 10.8 °C Glycol : 0 %
Tube Type : Plain Wet Bulb : 40.8 °C
Tube Material : Copper Relative Humidity : 3.6 %
Fin Material : Aluminium
Drain Pan : No COIL PERFORMANCE
Drain Pan Material : SS201 Air Velocity : 1.29 m/s Sensible Capacity : 39.56 kW
Coil Header Size: '' Total Capacity : 40.04 kW Pressure Drop : 37 Pa
Tube Diameter : 1/2"
10 REGENERATION FAN
FAN MOTOR
Brand : YILIDA Recom. Power : 1.1 kW
Model : SYW Absorbed Power : 0.99 kW
Fan Size : 280 Electrical Supply : 380-415V/3Ph
Absorbed Power : 0.83 kW Frequency : 60 Hz
Speed : 2845 rpm Type : Standard
ESP : 100 Pa Speed : 2840 rpm
TSP : 768 Pa Pole : 2
Total Pressure : 791 Pa Frame Number : 80
Blade Type : Plug Fan Inverter : No
Fan Frame : R Qty: 1
Service Factor : 20.0 %
Discharge Velocity : 6.19 m/s
Orientation : Rear
Disch. Opening : 400 x 410 mm
Total Efficiency : 47.8 %
TECHNICAL REPORT
GENERAL
Unit Height : 800 mm Unit Height (Top) : 0 mm
Unit Width : 1100 mm Door Type : Hinged
Fresh Air App. : Yes
DESIGN CONDITIONS
Air Flow Supply Air : 2600 m³/h
Return Air : 2340 m³/h
Filter Face Velocity Limit: 2.50 m/s Coil Face Velocity Limit : 2.00 m/s
Av.Face Velocity : 1.30 m/s Av. Face Velocity : 1.87 m/s
PROFILE
Inner Skin Material : GI Outer Skin Material : GI
Skin Thickness : 0.5 mm Skin Thickness : 0.5 mm
Surface Painted : Yes Surface Painted : Yes
1 MIXING BOX
Damper Selection : Top & Front User Define Temp: No Dry Bulb Temp. :
Blade Type : Opposed Pressure Drop : 8 Pa Wet Bulb Temp. :
GUIDE
TOP FRONT LEFT RIGHT
3 SECONDARY FILTER
4 DX COOLING COIL
5 COOLING COIL
7 SUPPLY FAN
9 HEPA FILTER
10 EXTRACT FAN
GENERAL
Unit Height : 1200 mm Unit Height (Top) : 0 mm
Unit Width : 2280 mm Door Type : Hinged
Fresh Air App. : Yes
DESIGN CONDITIONS
Air Flow Supply Air : 7348 m³/h
Filter Face Velocity Limit: 2.50 m/s Coil Face Velocity Limit : 2.00 m/s
Av.Face Velocity : 1.83 m/s Av. Face Velocity : 1.76 m/s
PROFILE
Inner Skin Material : GI Outer Skin Material : GI
Skin Thickness : 0.5 mm Skin Thickness : 0.5 mm
Surface Painted : Yes Surface Painted : Yes
GUIDE
TOP FRONT LEFT RIGHT
2 PRIMARY FILTER
Type : Flat ( 2" Washable ) FILTER QUANTITY AIR PRESSURE DROP
Grade : G4 (>90% Arr) 295 x 595 mm : 2 Initial : 40 Pa
Latch : - Not Applicable - 595 x 595 mm : 2 Final : 250 Pa
Frame : 2" Rail Design : 125 Pa
3 SECONDARY FILTER
Type : Box FILTER QUANTITY AIR PRESSURE DROP
Grade : F8 (90-95% Eff) 295 x 595 mm : 2 Initial : 190 Pa
Latch : - Not Applicable - 595 x 595 mm : 2 Final : 500 Pa
Frame : Aluminum Design : 350 Pa
4 DESICCANT WHEEL
Process Air flow: 5400 m³/h Regen. Air flow: 1800 m³/h Type PSS-S 850x200 - 1/3
Pressure Drop: 303 Pa Pressure Drop: 318 Pa Dimension Height x Length x Width
Drive equipment: 3Ph/380V/90W Dehumidification cap: 27.4 kg/h 1050 x 1050 x 297 mm
5 COOLING COIL
COIL SPECIFICATIONS AIR SIDE WATER SIDE
Rows : 4 Entering Entering Temp. : 7.0 °C
Fin Per Inch : 12 Dry Bulb : 31.6 °C Leaving Temp. : 12.1 °C
Tube Height : 26 Wet Bulb : 15.1 °C Water Velocity: 2.44 m/s
Fin Length : 1219 mm Relative Humidity : 13.8 % Flow Rate : 2.3 L/s
Fin Height : 953 mm Leaving Pressure Drop : 155.05 kPa
TPC : F Dry Bulb : 11.6 °C Glycol : 0 %
Tube Type : Plain Wet Bulb : 6.5 °C
Tube Material : Copper Relative Humidity : 47.0 %
Fin Material : Aluminium
Drain Pan : Yes COIL PERFORMANCE
Drain Pan Material : SS201 Air Velocity : 1.76 m/s Sensible Capacity : 49.12 kW
Coil Header Size: 1¼'' Total Capacity : 58.4 kW Pressure Drop : 41 Pa
Tube Diameter : 1/2"
6 SUPPLY FAN
Air volume flow rate: 7348 m³/h Manufacturer Ziehl_Abegg
ESP : 780 Pa Fan Count: 2 pcs
TSP : 1577 Pa Model: GR35C-ZID.DG.CR
Total Pressure : 1618 Pa Efficiency: 61.96 %
Speed: 3124 rpm
Power: 2750 W
Max.Power: 3700 W
Current rated: 4.03 A
Input source 3~400Vac 50/60Hz
Maximum Speed: 3400 rpm
7 EXTRACT FAN
Air volume flow rate: 735 m³/h Manufacturer Ziehl_Abegg
ESP : 1100 Fan Count: 1 pcs
TSP : 1100 Model: GR35C-ZID.DG.CR
Total Pressure : 1100 Efficiency: 26.63 %
Speed: 2505 rpm
Power: 880 W
Max.Power: 3700 W
Current rated: 1.42 A
Input source 3~400Vac 50/60Hz
Maximum Speed: 3400 rpm
8 PRIMARY FILTER (REGENERATION AIR)
Type : Flat ( 2" Washable ) FILTER QUANTITY AIR PRESSURE DROP
Grade : G4 (>90% Arr) 295 x 595 mm : 0 Initial : 40 Pa
Latch : - Not Applicable - 595 x 595 mm : 1 Final : 250 Pa
Frame : Aluminium Design : 125 Pa
10 HEATING COIL
COIL SPECIFICATIONS AIR SIDE WATER SIDE
Rows : 4 Entering Entering Temp. : 140.0 °C
Fin Per Inch : 10 Dry Bulb : 36.0 °C Leaving Temp. : 90.0 °C
Tube Height : 23 Wet Bulb : 30.0 °C Water Velocity: 0.08 m/s
Fin Length : 480 mm Relative Humidity : 64.9 % Flow Rate : 0.2 L/s
Fin Height : 730 mm Leaving Pressure Drop : 0.07 kPa
TPC : B Dry Bulb : 10.8 °C Glycol : 0 %
Tube Type : Plain Wet Bulb : 40.8 °C
Tube Material : Copper Relative Humidity : 3.6 %
Fin Material : Aluminium
Drain Pan : No COIL PERFORMANCE
Drain Pan Material : SS201 Air Velocity : 1.29 m/s Sensible Capacity : 39.56 kW
Coil Header Size: '' Total Capacity : 39.56 kW Pressure Drop : 37 Pa
Tube Diameter : 1/2"
11 REGENERATION FAN
FAN MOTOR
Brand : YILIDA Recom. Power : 1.1 kW
Model : SYW Absorbed Power : 0.99 kW
Fan Size : 280 Electrical Supply : 380-415V/3Ph
Absorbed Power : 0.83 kW Frequency : 60 Hz
Speed : 2845 rpm Type : Standard
ESP : 100 Pa Speed : 2840 rpm
TSP : 768 Pa Pole : 2
Total Pressure : 791 Pa Frame Number : 80
Blade Type : Plug Fan Inverter : No
Fan Frame : R Qty: 1
Service Factor : 20.0 %
Discharge Velocity : 6.19 m/s
Orientation : Rear
Disch. Opening : 400 x 410 mm
Total Efficiency : 47.8 %
TECHNICAL REPORT
GENERAL
Unit Height : 1180 mm Unit Height (Top) : 0 mm
Unit Width : 2200 mm Door Type : Hinged
Fresh Air App. : Yes
DESIGN CONDITIONS
Air Flow Supply Air : 5709 m³/h
Filter Face Velocity Limit: 2.50 m/s Coil Face Velocity Limit : 2.00 m/s
Av.Face Velocity : 1.73 m/s Av. Face Velocity : 1.76 m/s
PROFILE
Inner Skin Material : GI Outer Skin Material : GI
Skin Thickness : 0.5 mm Skin Thickness : 0.5 mm
Surface Painted : Yes Surface Painted : Yes
GUIDE
TOP FRONT LEFT RIGHT
2 PRIMARY FILTER
Type : Flat ( 2" Washable ) FILTER QUANTITY AIR PRESSURE DROP Pa
Pa Grade : G4 (>90% Arr) 295 x 595 mm : 2 Initial : 40
Latch : - Not Applicable - 595 x 595 mm : 1 Final : 250
Frame : 2" Rail Design : 125 Pa
3 SECONDARY FILTER
Type : Box FILTER QUANTITY AIR PRESSURE DROP
Grade : F8 (90-95% Eff) 295 x 595 mm : 2 Initial : 190 Pa
Latch : - Not Applicable - 595 x 595 mm :1 Final : 500 Pa
Frame : Aluminum Design : 350 Pa
4 DESICCANT WHEEL
Process Air flow: 4709 m³/h Regen. Air flow: 1570 m³/h Type PSS-S 770x200 - 1/3
Pressure Drop: 328 Pa Pressure Drop: 339 Pa Dimension Height x Length x Width
Drive equipment: 3Ph/380V/90W Dehumidification cap: 25.2 kg/h 956 x 956 x 297 mm
5 COOLING COIL
COIL SPECIFICATIONS AIR SIDE WATER SIDE
Rows : 5 Entering Entering Temp. : 7.0 °C
Fin Per Inch : 12 Dry Bulb : 35.4 °C Leaving Temp. : 12.0 °C
Tube Height : 26 Wet Bulb : 15.8 °C Water Velocity: 1.43 m/s
Fin Length : 914 mm Relative Humidity : 9.1 % Flow Rate : 1.9 L/s
Fin Height : 826 mm Leaving Pressure Drop : 40.96 kPa
TPC : E Dry Bulb : 10.8 °C Glycol : 0 %
Tube Type : Plain Wet Bulb : 5.2 °C
Tube Material : Copper Relative Humidity : 40.1 %
Fin Material : Aluminium
Drain Pan : Yes COIL PERFORMANCE
Drain Pan Material : SS201 Air Velocity : 1.73 m/s Sensible Capacity : 38.72 kW
Coil Header Size: 2'' Total Capacity : 39.1 kW Pressure Drop : 50 Pa
Tube Diameter : 1/2"
6 SUPPLY FAN
Air volume flow rate: 5709 m³/h Manufacturer Ziehl_Abegg
ESP : 780 Pa Fan Count: 1 pcs
TSP : 1661 Pa Model: GR45C-ZID.GG.CR
9 HEATING COIL
COIL SPECIFICATIONS AIR SIDE WATER SIDE
Rows : 3 Entering Entering Temp. : 140.0 °C
Fin Per Inch : 10 Dry Bulb : 36.0 °C Leaving Temp. : 90.0 °C
Tube Height : 18 Wet Bulb : 30.0 °C Water Velocity: 0.08 m/s
Fin Length : 680 mm Relative Humidity : 64.9 % Flow Rate : 0.2 L/s
Fin Height : 572 mm Leaving Pressure Drop : 0.07 kPa
TPC : B Dry Bulb : 100.94 °C Glycol : 0 %
Tube Type : Plain Wet Bulb : 41.1 °C
Tube Material : Copper Relative Humidity : 3.76 %
Fin Material : Aluminium
Drain Pan : No COIL PERFORMANCE
Drain Pan Material : SS201 Air Velocity : 1.29 m/s Sensible Capacity : 32.2 kW
Coil Header Size: '' Total Capacity : 32.2 kW Pressure Drop : 28 Pa
Tube Diameter : 1/2"
10 REGENERATION FAN
FAN MOTOR
Brand : YILIDA Recom. Power : 1.1 kW
Model : SYW Absorbed Power : 0.91 kW
Fan Size : 280 Electrical Supply : 380-415V/3Ph
Absorbed Power : 0.79 kW Frequency : 50 Hz
Speed : 2819 rpm Type : Standard
ESP : 100 Pa Speed : 2819 rpm
TSP : 798 Pa Pole : 2
Total Pressure : 818 Pa Frame Number : 80
Blade Type : Plug Fan Inverter : yes
Fan Frame : R Qty: 1
Service Factor : 20.0 %
Discharge Velocity : 5.43 m/s
Orientation : Rear
Disch. Opening : 400 x 410 mm
Total Efficiency : 32.6 %
TECHNICAL REPORT
GENERAL
Unit Height : 1200 mm Unit Height (Top) : 0 mm
Unit Width : 2100 mm Door Type : Hinged
Fresh Air App. : Yes
DESIGN CONDITIONS
Air Flow Supply Air : 6563 m³/h
Return Air : 6156 m³/h
Filter Face Velocity Limit: 2.50 m/s Coil Face Velocity Limit : 2.00 m/s
Av.Face Velocity : 2.45 m/s Av. Face Velocity : 1.88 m/s
PROFILE
Inner Skin Material : GI Outer Skin Material : GI
Skin Thickness : 0.5 mm Skin Thickness : 0.5 mm
Surface Painted : Yes Surface Painted : Yes
GUIDE
TOP FRONT LEFT RIGHT
2 PRIMARY FILTER
Type : Flat ( 2" Washable ) FILTER QUANTITY AIR PRESSURE DROP
Grade : G4 (>90% Arr) 295 x 595 mm : 2 Initial : 40 Pa
Latch : - Not Applicable - 595 x 595 mm : 1 Final : 250 Pa
Frame : 2" Rail Design : 125 Pa
3 SECONDARY FILTER
Type : Box FILTER QUANTITY AIR PRESSURE DROP
Grade : F8 (90-95% Eff) 295 x 595 mm : 2 Initial : 190 Pa
Latch : - Not Applicable - 595 x 595 mm : 1 Final : 500 Pa
Frame : Aluminum Design : 350 Pa
4 DESICCANT WHEEL
Process Air flow: 4500 m³/h Regen. Air flow: 1500 m³/h Type PSS-S 770x200 - 1/3
Pressure Drop: 308 Pa Pressure Drop: 323 Pa Dimension Height x Length x Width
Drive equipment: 3Ph/380V/90W Dehumidification cap: 20.4 kg/h 956 x 956 x 297 mm
5 COOLING COIL
COIL SPECIFICATIONS AIR SIDE WATER SIDE
Rows : 5 Entering Entering Temp. : 7.0 °C
Fin Per Inch : 12 Dry Bulb : 29.6 °C Leaving Temp. : 12.0 °C
Tube Height : 27 Wet Bulb : 14.1 °C Water Velocity: 0.65 m/s
Fin Length : 1016 mm Relative Humidity : 14.5 % Flow Rate : 1.9 L/s
Fin Height : 857 mm Leaving Pressure Drop : 6.01 kPa
TPC : C Dry Bulb : 11.4 °C Glycol : 0 %
Tube Type : Plain Wet Bulb : 6.1 °C
Tube Material : Copper Relative Humidity : 44.5 %
Fin Material : Aluminium
Drain Pan : Yes COIL PERFORMANCE
Drain Pan Material : SS201 Air Velocity : 1.88 m/s Sensible Capacity : 39.85 kW
Coil Header Size: 2'' Total Capacity : 54.4 kW Pressure Drop : 59 Pa
Tube Diameter : 1/2"
6 SUPPLY FAN
Air volume flow rate: 6563 m³/h Manufacturer Ziehl_Abegg
ESP : 780 Pa Fan Count: 1 pcs
TSP : 1650 Pa Model: GR45C-ZID.GG.CR
Total Pressure : 1528 Pa Efficiency: 62.86 %
Speed: 2469 rpm
Power: 4870 W
Max.Power: 5200 W
Current rated: 6.79 A
Input source 3~400Vac 50/60Hz
Maximum Speed: 2570 rpm
7 PRIMARY FILTER (REGENERATION AIR)
Type : Flat ( 2" Washable ) FILTER QUANTITY AIR PRESSURE DROP
Grade : G4 (>90% Arr) 295 x 595 mm : 1 Initial : 40 Pa
Latch : - Not Applicable - 295 x 595 mm : 0 Final : 250 Pa
Frame : Aluminium Design : 125 Pa
9 HEATING COIL
COIL SPECIFICATIONS AIR SIDE WATER SIDE
Rows : 4 Entering Entering Temp. : 140.0 °C
Fin Per Inch : 10 Dry Bulb : 36.0 °C Leaving Temp. : 90.0 °C
Tube Height : 14 Wet Bulb : 31.0 °C Water Velocity: 0.20 m/s
Fin Length : 460 mm Relative Humidity : 70.2 % Flow Rate : 0.2 L/s
Fin Height : 445 mm Leaving Pressure Drop : 0.54 kPa
TPC : D Dry Bulb : 102.6 °C Glycol : 0 %
Tube Type : Plain Wet Bulb : 41.6 °C
Tube Material : Copper Relative Humidity : 3.8 %
Fin Material : Aluminium
Drain Pan : No COIL PERFORMANCE
Drain Pan Material : SS201 Air Velocity : 2.15 m/s Sensible Capacity : 33.37 kW
Coil Header Size: '' Total Capacity : 33.37 kW Pressure Drop : 92 Pa
Tube Diameter : 1/2"
10 REGENERATION FAN
FAN MOTOR
Brand : YILIDA Recom. Power : 1.1 kW
Model : SYW Absorbed Power : 0.89 kW
Fan Size : 280 Electrical Supply : 380-415V/3Ph
Absorbed Power : 0.75 kW Frequency : 50 Hz
Speed : 2775 rpm Type : Standard
ESP : 100 Pa Speed : 2840 rpm
TSP : 791 Pa Pole : 2
Total Pressure : 814 Pa Frame Number : 80
Blade Type : Plug Fan Inverter : yes
Fan Frame : R Qty: 1
Service Factor : 20.0 %
Discharge Velocity : 5.16 m/s
Orientation : Rear
Disch. Opening : 400 x 410 mm
Total Efficiency : 44.7 %
TECHNICAL REPORT
GENERAL
Unit Height : 1100 mm Unit Height (Top) : 0 mm
Unit Width : 1200 mm Door Type : Hinged
Fresh Air App. : Yes
DESIGN CONDITIONS
Air Flow Supply Air : 5166 m³/h
Return Air : 4633 m³/h
Filter Face Velocity Limit: 2.50 m/s Coil Face Velocity Limit : 2.00 m/s
Av.Face Velocity : 1.93 m/s Av. Face Velocity : 1.90 m/s
PROFILE
Inner Skin Material : GI Outer Skin Material : GI
Skin Thickness : 0.5 mm Skin Thickness : 0.5 mm
Surface Painted : Yes Surface Painted : Yes
1 MIXING BOX
Damper Selection : Top & Front User Define Temp: No Dry Bulb Temp. :
Blade Type : Opposed Pressure Drop : 18 Pa Wet Bulb Temp. :
GUIDE
TOP FRONT LEFT RIGHT
3 SECONDARY FILTER
4 COOLING COIL
5 SUPPLY FAN
7 HEPA FILTER
GENERAL
Unit Height : 880 mm Unit Height (Top) : 0 mm
Unit Width : 1100 mm Door Type : Hinged
Fresh Air App. : Yes
DESIGN CONDITIONS
Air Flow Supply Air : 1904 m³/h
Return Air : 1660 m³/h
Filter Face Velocity Limit: 2.50 m/s Coil Face Velocity Limit : 2.00 m/s
Av.Face Velocity : 0.95 m/s Av. Face Velocity : 1.37 m/s
PROFILE
Inner Skin Material : GI Outer Skin Material : GI
Skin Thickness : 0.5 mm Skin Thickness : 0.5 mm
Surface Painted : Yes Surface Painted : Yes
1 MIXING BOX
Damper Selection : Top & Front User Define Temp: No Dry Bulb Temp. :
Blade Type : Opposed Pressure Drop : 5 Pa Wet Bulb Temp. :
GUIDE
TOP FRONT LEFT RIGHT
3 SECONDARY FILTER
4 DX COOLING COIL
5 COOLING COIL
7 SUPPLY FAN
GENERAL
Unit Height : 1000 mm Unit Height (Top) : 0 mm
Unit Width : 1200 mm Door Type : Hinged
Fresh Air App. : Yes
DESIGN CONDITIONS
Air Flow Supply Air : 3574 m³/h
Return Air : 3240 m³/h
Filter Face Velocity Limit: 2.50 m/s Coil Face Velocity Limit : 2.00 m/s
Av.Face Velocity : 1.78 m/s Av. Face Velocity : 1.81 m/s
PROFILE
Inner Skin Material : GI Outer Skin Material : GI
Skin Thickness : 0.5 mm Skin Thickness : 0.5 mm
Surface Painted : Yes Surface Painted : Yes
1 MIXING BOX
Damper Selection : Top & Front User Define Temp: No Dry Bulb Temp. :
Blade Type : Opposed Pressure Drop : 14 Pa Wet Bulb Temp. :
GUIDE
TOP FRONT LEFT RIGHT
3 SECONDARY FILTER
4 DX COOLING COIL
5 COOLING COIL
7 SUPPLY FAN
9 EXTRACT FAN
GENERAL
Unit Height : 980 mm Unit Height (Top) : 0 mm
Unit Width : 1200 mm Door Type : Hinged
Fresh Air App. : Yes
DESIGN CONDITIONS
Air Flow Supply Air : 3085 m³/h
Return Air : 2534 m³/h
Filter Face Velocity Limit: 2.50 m/s Coil Face Velocity Limit : 2.00 m/s
Av.Face Velocity : 1.54 m/s Av. Face Velocity : 1.56 m/s
PROFILE
Inner Skin Material : GI Outer Skin Material : GI
Skin Thickness : 0.5 mm Skin Thickness : 0.5 mm
Surface Painted : Yes Surface Painted : Yes
1 MIXING BOX
Damper Selection : Top & Front User Define Temp: No Dry Bulb Temp. :
Blade Type : Opposed Pressure Drop : 11 Pa Wet Bulb Temp. :
GUIDE
TOP FRONT LEFT RIGHT
3 SECONDARY FILTER
4 DX COOLING COIL
5 COOLING COIL
7 SUPPLY FAN
GENERAL
Unit Height : 1200 mm Unit Height (Top) : 0 mm
Unit Width : 1650 mm Door Type : Hinged
Fresh Air App. : Yes
DESIGN CONDITIONS
Air Flow Supply Air : 7247 m³/h
Return Air : 6523 m³/h
Filter Face Velocity Limit: 2.50 m/s Coil Face Velocity Limit : 2.00 m/s
Av.Face Velocity : 1.81 m/s Av. Face Velocity : 1.73 m/s
PROFILE
Inner Skin Material : GI Outer Skin Material : GI
Skin Thickness : 0.5 mm Skin Thickness : 0.5 mm
Surface Painted : Yes Surface Painted : Yes
1 MIXING BOX
Damper Selection : Top & Front User Define Temp: No Dry Bulb Temp. :
Blade Type : Opposed Pressure Drop : 23 Pa Wet Bulb Temp. :
GUIDE
TOP FRONT LEFT RIGHT
3 SECONDARY FILTER
4 DX COOLING COIL
5 COOLING COIL
7 SUPPLY FAN
9 EXTRACT FAN
Movement by Perfection
Product documentation
Type
GR35C-ZID.DG.CR
Article number
116169/A01
Article number
116169/A01
Product documentation
Customer ZIEHL-ABEGG Contact
B&A Karl Ng
..
Project karl.ng@ziehl-abegg.com.sg
.
ZIEHL-ABEGG Subsidiary
Singapore
ZIEHL-ABEGG SEA Pte. Ltd.
33 Ubi Ave 3
#07-70 Vertex
SINGAPORE 408868
SINGAPORE
Phone +65 674 825 87
Fax +65 674 873 57
www.ziehl-abegg.sg
info@ziehl-abegg.com.sg
Type
GR35C-ZID.DG.CR
Article number
116169/A01
Contents
1. Recitals 4
2. Product specification - Technical data 5
3. Product specification – Applicable technical standards 6
4. Product specification – Lifetime 8
5. Product Specification - General product and handling description 9
6. Characteristic Curve 14
7. Drawing 15
8. Connection diagram 16
9. Aerodynamics and Acoustics 17
10. EU-Declaration of conformity 20
11. Deviation list 22
1. Recitals
The Product Specifications contained in this document are final, unless otherwise stated by a separate
provision in the "ZIEHL-ABEGG deviation list document" with respect to information provided by the
customer (cp. separate Chapter: Attachment).
Other regulations between the parties, regardless of time, form or content, are not part of the subject matter
of the contract and the agreement on characteristics/of features (Product Specifications) between the
parties.
Compliance with the following specifications is mandatory to ensure the functionality and safety of the
product. If the following specifications given especially but not limited for operating conditions, transport,
storage, mounting, start-up, maintenance and repair are not observed, the product may not operate safely
and may cause a hazard to the life and limb of users and third parties.
Deviations from the following requirements may therefore lead both to the loss of the statutory material
defect liability rights and to the liability of the buyer for the product that has become unsafe due to the
deviation from the specifications.
Environmental Conditions:
EN 60721-3-3:1995 “Classification of environmental conditions - Part 3: Classification of groups of
environmental parameters and their severities; section 3: Stationary use at weatherprotected locations” (IEC
60721-3-3:1994)
Climatic environmental conditions: class 3K2
Biological environmental conditions: 3B1
Chemical active substances: 3C1
Mechanical active substances: 3S1
Mechanical environmental conditions: 3M1
Corrosion protection:
Powder coating thickness
The total thickness of the standard powder coating as an average value of 10 measurements, distributed
evenly over the whole part must be between at least 80 and 160 µm (or 260 µm with double powder coating)
and may not drop below 60 µm at any measuring point. A total coating thickness of 160 µm (or 260 µm with
double powder coating) must not be exceeded.
The total thickness of a coating may not, however, be used as a measure of corrosion protection. The
corrosion protection of a coated part is composed of the pretreatment (e.g. zinc phosphatising), the type of
powder (e.g. mixed powder), the coating (single or dual layer), the material (bright / galvanised steel) and the
correct execution of the powder coating (cleaning/degreasing of the part)..
Properties of the powder coating
The ZIEHL-ABEGG standard powder coating uses a polyester-epoxy mixed powder.
Due to the polyester component in the mixed powder a medium UV resistance is given.
Generally the functional surfaces of all parts with threads, nuts and bolts or predefined functional surfaces
are uncoated to ensure the smooth running of the thread or the function (for example the grounding of the
part).
Painting thickness
Depending on the component or the design of the components, there may be deviations in the minimum
coating thickness or flaws. As a general rule, however, the total
coating thickness should not fall below 20 μm at any point.
The total coating thickness of the standard wet painting as an average value of 10 measurements distributed
evenly over the whole component must be between the
values specified in the following table.
However, the total coating thickness of wet painting may not be used as a measure of corrosion protection.
The corrosion protection of a coated component is made up of
the pretreatment (e.g. FEph) of the paint type/paint quality, the coating (one or two coat), the material
(bright/galvanized steel) and the correct application of the wet
painting (cleaning/degreasing of the component).
Operating conditions:
The product is designed for conveying non-aggressive, non-explosive, non-fluid, non-adherent, non-
abrasive, dust and particle-free gaseous media, air-like mixtures und air.
The fans/motors are not ready-to-use products, but are designed as components for refrigeration, air
conditioning and ventilation systems. The fans may not be operated until they are installed according to their
intended purpose.
Operating conditions, including the installation position of the fan, must be clearly specified by the customer,
especially in the case of special operating conditions such as a higher risk of condensate formation and
higher humidity or for outdoor use. These customer specifications form the basis for product design including
selection and assignment of suitable motors. ZIEHL-ABEGG cannot accept any liability for applications and
operating conditions not specified to us; the customer is then responsible for taking precautionary measures
against failure or damage to the fan.
To provide error-free operation and prevent damage to the product, the product may only be operated in the
admissible operating area according to the mentioned data sheets and air performance curves respectively
may only be used for the intended application.
The formation of small rusty spots during usage in accordance with the product specification and this general
product and handling description can occur. These do not affect the functionality of the product. In case of
sendzimir-galvanized components, corrosion at the cutting edges is possible.
The product must never be used in obviously damaged condition.
External magnetic fields are not allowed if their induced eddy currents would decelerate the fan respectively
these may lead to an increase in power consumption or to malfunctions in the electronics.
Temperature change speeds of a maximum of 1 K/min are permissible.
When used below -10 °C, it is a prerequisite that the fans are not subjected to any unusual external
influences such as impact-like mechanical loads.
The admissibility of operating the fan near of strong heat radiation sources must be checked and approved
by the device manufacturer. It must be ensured that the peak temperature of the radiant heat source does
not exceed the maximum ambient temperature of the fan (see rating plate). This applies in particular in the
event of a fault or when the fan is at a standstill.
The permissible relative humidity is indicated in the assembly and operating instructions.
Condensation in the drive must be excluded.
In case of longer downtimes in a humid atmosphere, the fans must be put into operation monthly for at least
2 hours, at least 80% of the rated speed, to allow any moisture that may have penetrated them or
condensation that has formed inside, to evaporate and to redistribute the bearing grease or to avoid
standstill markings / bearing rust respectively.
Applications in which the fan runs through several temperature and humidity phases at intervals must be
checked and released by the device manufacturer on a case-by-case basis.
Not permissible:
Blocking or slowing down the fan by inserting objects. The impeller may become unbalanced, be damaged
and may burst. Danger to life!
Loosening of the impeller and/or balance weights. The impeller becomes unbalanced and the motor bearing
life time decreases. Danger to life!
Continuous intentional change of direction of rotation. The motor and the impeller are overloaded.
Reverse current braking. The motor and impeller are overloaded.
AC fans on mains:
The fan is designed for continuous operation S1 according to DIN EN 60034-1:2011-02.
If switching operation (multiple switching per hour) is required, consult ZIEHL-ABEGG stating the planned
switching frequency.
Occasional starting between -40 °C and -25 °C is permissible.
Continuous operation below -25 °C only with special bearings for refrigeration applications on request.
The fan may only be operated within the permissible temperature range. Please refer to the technical
documentation of the product for the minimum and maximum ambient temperature valid for the respective
fan.
The maximum permissible ambient temperature is also indicated on the fan rating plate, with the following
exception: If special ball bearings with “cold grease” lubrication are installed in the fan, the maximum
permissible ambient temperature in continuous operation is + 20 °C.
Operation below -25 °C and partial load operation on frequency inverters for cold applications is
only possible with special bearings for refrigeration applications on request.
Permissible minimum ambient temperature for operation of 1~ fans with built-in operating capacitor: -25 °C.
For fans with protection class IP55 or higher (protection class according to DIN EN 60529 or DIN EN 60034-
4), the existing condensation drain hole must be opened at least every six months.
EC fans:
The fan is designed for continuous operation S1 according to DIN EN 60034-1:2011-02.
Occasional starting between -35 °C and -25 °C is permissible.
Continuous operation below -25 °C only with special bearings for refrigeration applications on request.
The fan may only be operated within the permissible temperature range. Please refer to the technical
documentation of the product for the minimum and maximum ambient temperature valid for the respective
fan.
Operation below -25 °C as well as partial load operation for refrigeration applications is only possible with
special bearings for refrigeration applications on request. If special bearings for refrigeration applications are
installed in the fan, please observe the permissible maximum temperatures in the technical documentation of
the product.
For safe operation up to the minimum permissible ambient temperature and to avoid condensation, a
continuous power supply must be ensured in refrigeration applications so that the condensation point does
not occur due to cooling-down.
Motor protection:
Implement the thermal motor protection depending on the design of the motor and observe the attached
wiring diagram.
A) For EC fans:
Relay: Please note the minimum switching voltage of 5 V as well as the minimum current of 100 mA at the
relay contact to ensure a reliable switching change.
The maximum voltage at the relay contact must not exceed 380 V AC / 220 V DC. The maximum switching
current is 5 A.
B) For AC fans:
The motors can be equipped with temperature sensors "TP" (PTC thermistor), internally connected
thermostat switches "TB", outgoing thermostat switches "TB" or can be delivered without thermal protection.
B1) Thermostat switch: Please observe the minimum current of approx. 50 mA at the thermostat switch so
that the contact switches permanently and safely. The maximum voltage at the thermostat switch must not
exceed 250 V AC or 60 V DC
(Note: all values and especially the maximum switching current of the TB depend on system parameters as
cycle of operation and the output current of the monitoring unit. For specific parameters contact our technical
support).
B2) PTC thermistor (PTC):
Standard internal rotor motors: Please observe the specifications and application limits, such as maximum
voltage, in the operating instructions of the respective motor manufacturer.
External rotor motors: The maximum voltage at the PTC thermistor must not exceed 2.5 V per PTC element.
Thermal motor protection is ensured exclusively by the use of temperature monitors, thermostat switches or
PTC thermistors. These motor protection devices must be connected.
If there are no temperature monitors, thermostat switches or PTC thermistors, a motor protection switch must
be used. However, motor protection switches do not provide temperature protection for the motors.
Assembly:
The assembly has to meet the requirements of the assembly instructions to enable error-free operation.
The fans may not be operated until they are installed according to their intended use. The included or
supplied guard grille of ZIEHL-ABEGG fans is usually designed according to EN ISO 13857 Table 4 (for
persons with a minimum age of 14 years). If the grilles are of a different design, the device manufacturer
must take further structural protective measures to ensure safe operation.
Commissioning:
Commissioning must be done by appropriately qualified technical personnel according to the specifications
in the operating and assembly instructions.
During start-up check the following:
1. Check the direction of rotation (see rotation direction arrow on the fan blade, impeller base plate or
support plates on suction side or rating plate).
2. Inspect the motor bearings for proper operation prior to installation. Check smooth, noiseless running
during commissioning, replace motor bearings if necessary.
3. Check for quiet, low vibration operation. Strong vibrations due to uneven running (imbalance), e.g. caused
by transportation damage or improper use, can lead to failure.
4. For variable speed fans: If resonance vibrations occur, it is possible to hide certain speed ranges.
5. A-rated sound power levels of over 80 dB(A) are possible.
6. Fans from ZIEHL-ABEGG SE are delivered balanced in accordance with DIN ISO 21940-11 for the
appropriate fan category in accordance with ISO 14694. Check the fan for mechanical vibrations after
installation. If the limit values of the corresponding fan category are exceeded in start-up, you must have the
motor/impeller unit checked by an expert and rebalanced if necessary before continuous operation is
permitted.
During commissioning, unexpected and hazardous conditions can arise in the entire installation due to
defective adjustments, defective components or incorrect electrical connections. Remove all persons and
objects from the hazardous area.
Do not start up the fan until you have read and understood all the safety instructions (DIN EN 50110, IEC
364), safety distances are observed (DIN EN ISO 13857 / EN 60335) and a hazard is excluded.
Acclimatize the fan to the permissible operating temperature range.
The device manufacturer must ensure low-vibration operation. The relevant standards must be observed e.g.
DIN ISO 10816.
In the case of applications with external vibrations, the device manufacturer must decouple the fan from the
vibration source.
The complete assembly must be checked for resonance by the device manufacturer when installed. For
variable-speed applications, the assembly must be checked for resonances over the entire speed range. If
excessive vibrations are detected, it must be avoided that the unit and the fan is operated in this resonance.
If the fan is operated with increased vibrations, service life will be considerably reduced or a failure can
occur.
Only for AC fans: For fans with protection class IP55 or higher (protection class according to DIN EN 60529
or DIN EN 60034-4), the existing condensation drain hole must be opened at least every six months.
Documentation:
In case of defective parts or products or in case of any warranty, it may be necessary to analyses the root
cause of the defect.
Therefore, ZIEHL-ABEGG may ask for documentation of proper life-cycle handling according to the
operating and assembly instructions and the general product and handling description. ZIEHL-ABEGG may
ask for appropriate documentation records in order to assess root cause of the defect.
Spare parts:
www.ziehl-abegg.com Movement by Perfection │ Bewegung durch Perfektion 12 │ 23
30/8/2022
© ZIEHL-ABEGG SE
All rights reserved. Confidential and proprietary document, not to be disclosed or used except in accordance with applicable agreements. No disclosure to third parties, if not
expressively agreed by ZA SE.
Article number
116169/A01
In all warranty cases repairs have to be carried out by ZIEHL-ABEGG. In all other cases spare parts shall
meet the specifications of the original installed parts to ensure error-free operation. Use of original ZIEHL-
ABEGG spare parts is recommended.
6. Characteristic Curve
Air performance
Acoustics
134323
Please note: It’s not allowed to use this fan in the stall area!*
*In doubt please ask your responsible ZIEHL-ABEGG sales contact.
7. Drawing
Dimensions in mm
The illustrations shown make no claim to completeness and are for orientation purposes only.
8. Connection diagram
Measurement method
The characteristic map display shows the pressure increase ∆psF in Pa
as a function of the volume flow rate qV in m3/h.
Technical conditions of supply
The specified performance data meet the respective requirements
for accuracy
- AN2 for centrifugal impellers without motor
- AN3 for centrifugal fans with standard motors
- AN2 for centrifugal impellers with ECblue motors (except EC055)
- AN3 for centrifugal impellers with ECblue motor EC055 (see type key)
- AN3 for axial fans with ECblue motors
- AN4 for axial fans with AC external rotor motors
in line with ISO 13348 and apply to the rated data and air performance
curves at the rated voltage. The continuous line in the characteristic
curve represents the optimum reliable operating range for fans.
Installation type A according to ISO
5801
Fan test bench
The fan characteristic curves are determined on a combined ventilation
and sound test bench.
The characteristic curves are measured in compliance with DIN EN ISO
5801 and AMCA 210-99. The sound power levels are measured in
compliance with DIN EN ISO 3745 and ISO 13347-3 using the
enveloping surface measuring method.
The figure below shows an example of the measuring setup. The fan is
installed in the measuring chamber at free inlet and free exhaust
Technology Centre (InVent)
(installation type A as per DIN EN ISO 5801 or AMCA 210-99).
Air density
The air density and humidity are conditioned during the measurement
using heat exchangers and kept largely constant. The characteristic
curves shown refer to the measuring density. The mean measuring
density is 1.16 kg/m³.
① Test fan
② pfs
③ Flow straightener
④ Nozzles
⑤ ∆p Differential pressure
⑥ Auxiliary fan
Because of the different weighting of the third-octave sound power Fig. Ib: Fan test-bench
level, the A-evaluation, which is typically carried out, takes into
account the subjective nature of human sound perception. The A-
tested sound power level is the standard variable used to assess
the sound characteristics of technical equipment.
No customer specification was available. Please note that ZIEHL-ABEGG does not confirm technical
requirements beyond this specification if they are not listed in a list of deviations.
The suitability of the product for sea atmosphere/dishwasher/offshore is beyond the influence of ZIEHL-
ABEGG.
ZIEHL-ABEGG can therefore neither guarantee nor prove the suitability of this product for this specific
application or the customer's intended use. The customer is responsible for testing and approving the
product for its intended use.
Please contact us. We would be pleased to design an individual solution for your requirements.
We would like to welcome you on our worldwide exhibitions. Please find our next exhibitions here.
Movement by Perfection
Product documentation
Type
GR45C-ZID.GG.CR
Article number
116177/A01
Article number
116177/A01
Product documentation
Customer ZIEHL-ABEGG Contact
B&A Karl Ng
..
Project karl.ng@ziehl-abegg.com.sg
enter here
ZIEHL-ABEGG Subsidiary
Singapore
ZIEHL-ABEGG SEA Pte. Ltd.
33 Ubi Ave 3
#07-70 Vertex
SINGAPORE 408868
SINGAPORE
Phone +65 674 825 87
Fax +65 674 873 57
www.ziehl-abegg.sg
info@ziehl-abegg.com.sg
Type
GR45C-ZID.GG.CR
Article number
116177/A01
Contents
1. Recitals 4
2. Product specification - Technical data 5
3. Product specification – Applicable technical standards 6
4. Product specification – Lifetime 8
5. Product Specification - General product and handling description 9
6. Characteristic Curve 14
7. Drawing 15
8. Connection diagram 16
9. Aerodynamics and Acoustics 17
10. EU-Declaration of conformity 20
11. Deviation list 22
1. Recitals
The Product Specifications contained in this document are final, unless otherwise stated by a separate
provision in the "ZIEHL-ABEGG deviation list document" with respect to information provided by the
customer (cp. separate Chapter: Attachment).
Other regulations between the parties, regardless of time, form or content, are not part of the subject matter
of the contract and the agreement on characteristics/of features (Product Specifications) between the
parties.
Compliance with the following specifications is mandatory to ensure the functionality and safety of the
product. If the following specifications given especially but not limited for operating conditions, transport,
storage, mounting, start-up, maintenance and repair are not observed, the product may not operate safely
and may cause a hazard to the life and limb of users and third parties.
Deviations from the following requirements may therefore lead both to the loss of the statutory material
defect liability rights and to the liability of the buyer for the product that has become unsafe due to the
deviation from the specifications.
Environmental Conditions:
EN 60721-3-3:1995 “Classification of environmental conditions - Part 3: Classification of groups of
environmental parameters and their severities; section 3: Stationary use at weatherprotected locations” (IEC
60721-3-3:1994)
Climatic environmental conditions: class 3K2
Biological environmental conditions: 3B1
Chemical active substances: 3C1
Mechanical active substances: 3S1
Mechanical environmental conditions: 3M1
Corrosion protection:
Powder coating thickness
The total thickness of the standard powder coating as an average value of 10 measurements, distributed
evenly over the whole part must be between at least 80 and 160 µm (or 260 µm with double powder coating)
and may not drop below 60 µm at any measuring point. A total coating thickness of 160 µm (or 260 µm with
double powder coating) must not be exceeded.
The total thickness of a coating may not, however, be used as a measure of corrosion protection. The
corrosion protection of a coated part is composed of the pretreatment (e.g. zinc phosphatising), the type of
powder (e.g. mixed powder), the coating (single or dual layer), the material (bright / galvanised steel) and the
correct execution of the powder coating (cleaning/degreasing of the part)..
Properties of the powder coating
The ZIEHL-ABEGG standard powder coating uses a polyester-epoxy mixed powder.
Due to the polyester component in the mixed powder a medium UV resistance is given.
Generally the functional surfaces of all parts with threads, nuts and bolts or predefined functional surfaces
are uncoated to ensure the smooth running of the thread or the function (for example the grounding of the
part).
Painting thickness
Depending on the component or the design of the components, there may be deviations in the minimum
coating thickness or flaws. As a general rule, however, the total
coating thickness should not fall below 20 μm at any point.
The total coating thickness of the standard wet painting as an average value of 10 measurements distributed
evenly over the whole component must be between the
values specified in the following table.
However, the total coating thickness of wet painting may not be used as a measure of corrosion protection.
The corrosion protection of a coated component is made up of
the pretreatment (e.g. FEph) of the paint type/paint quality, the coating (one or two coat), the material
(bright/galvanized steel) and the correct application of the wet
painting (cleaning/degreasing of the component).
Operating conditions:
The product is designed for conveying non-aggressive, non-explosive, non-fluid, non-adherent, non-
abrasive, dust and particle-free gaseous media, air-like mixtures und air.
The fans/motors are not ready-to-use products, but are designed as components for refrigeration, air
conditioning and ventilation systems. The fans may not be operated until they are installed according to their
intended purpose.
Operating conditions, including the installation position of the fan, must be clearly specified by the customer,
especially in the case of special operating conditions such as a higher risk of condensate formation and
higher humidity or for outdoor use. These customer specifications form the basis for product design including
selection and assignment of suitable motors. ZIEHL-ABEGG cannot accept any liability for applications and
operating conditions not specified to us; the customer is then responsible for taking precautionary measures
against failure or damage to the fan.
To provide error-free operation and prevent damage to the product, the product may only be operated in the
admissible operating area according to the mentioned data sheets and air performance curves respectively
may only be used for the intended application.
The formation of small rusty spots during usage in accordance with the product specification and this general
product and handling description can occur. These do not affect the functionality of the product. In case of
sendzimir-galvanized components, corrosion at the cutting edges is possible.
The product must never be used in obviously damaged condition.
External magnetic fields are not allowed if their induced eddy currents would decelerate the fan respectively
these may lead to an increase in power consumption or to malfunctions in the electronics.
Temperature change speeds of a maximum of 1 K/min are permissible.
When used below -10 °C, it is a prerequisite that the fans are not subjected to any unusual external
influences such as impact-like mechanical loads.
The admissibility of operating the fan near of strong heat radiation sources must be checked and approved
by the device manufacturer. It must be ensured that the peak temperature of the radiant heat source does
not exceed the maximum ambient temperature of the fan (see rating plate). This applies in particular in the
event of a fault or when the fan is at a standstill.
The permissible relative humidity is indicated in the assembly and operating instructions.
Condensation in the drive must be excluded.
In case of longer downtimes in a humid atmosphere, the fans must be put into operation monthly for at least
2 hours, at least 80% of the rated speed, to allow any moisture that may have penetrated them or
condensation that has formed inside, to evaporate and to redistribute the bearing grease or to avoid
standstill markings / bearing rust respectively.
Applications in which the fan runs through several temperature and humidity phases at intervals must be
checked and released by the device manufacturer on a case-by-case basis.
Not permissible:
Blocking or slowing down the fan by inserting objects. The impeller may become unbalanced, be damaged
and may burst. Danger to life!
Loosening of the impeller and/or balance weights. The impeller becomes unbalanced and the motor bearing
life time decreases. Danger to life!
Continuous intentional change of direction of rotation. The motor and the impeller are overloaded.
Reverse current braking. The motor and impeller are overloaded.
AC fans on mains:
The fan is designed for continuous operation S1 according to DIN EN 60034-1:2011-02.
If switching operation (multiple switching per hour) is required, consult ZIEHL-ABEGG stating the planned
switching frequency.
Occasional starting between -40 °C and -25 °C is permissible.
Continuous operation below -25 °C only with special bearings for refrigeration applications on request.
The fan may only be operated within the permissible temperature range. Please refer to the technical
documentation of the product for the minimum and maximum ambient temperature valid for the respective
fan.
The maximum permissible ambient temperature is also indicated on the fan rating plate, with the following
exception: If special ball bearings with “cold grease” lubrication are installed in the fan, the maximum
permissible ambient temperature in continuous operation is + 20 °C.
Operation below -25 °C and partial load operation on frequency inverters for cold applications is
only possible with special bearings for refrigeration applications on request.
Permissible minimum ambient temperature for operation of 1~ fans with built-in operating capacitor: -25 °C.
For fans with protection class IP55 or higher (protection class according to DIN EN 60529 or DIN EN 60034-
4), the existing condensation drain hole must be opened at least every six months.
EC fans:
The fan is designed for continuous operation S1 according to DIN EN 60034-1:2011-02.
Occasional starting between -35 °C and -25 °C is permissible.
Continuous operation below -25 °C only with special bearings for refrigeration applications on request.
The fan may only be operated within the permissible temperature range. Please refer to the technical
documentation of the product for the minimum and maximum ambient temperature valid for the respective
fan.
Operation below -25 °C as well as partial load operation for refrigeration applications is only possible with
special bearings for refrigeration applications on request. If special bearings for refrigeration applications are
installed in the fan, please observe the permissible maximum temperatures in the technical documentation of
the product.
For safe operation up to the minimum permissible ambient temperature and to avoid condensation, a
continuous power supply must be ensured in refrigeration applications so that the condensation point does
not occur due to cooling-down.
Motor protection:
Implement the thermal motor protection depending on the design of the motor and observe the attached
wiring diagram.
A) For EC fans:
Relay: Please note the minimum switching voltage of 5 V as well as the minimum current of 100 mA at the
relay contact to ensure a reliable switching change.
The maximum voltage at the relay contact must not exceed 380 V AC / 220 V DC. The maximum switching
current is 5 A.
B) For AC fans:
The motors can be equipped with temperature sensors "TP" (PTC thermistor), internally connected
thermostat switches "TB", outgoing thermostat switches "TB" or can be delivered without thermal protection.
B1) Thermostat switch: Please observe the minimum current of approx. 50 mA at the thermostat switch so
that the contact switches permanently and safely. The maximum voltage at the thermostat switch must not
exceed 250 V AC or 60 V DC
(Note: all values and especially the maximum switching current of the TB depend on system parameters as
cycle of operation and the output current of the monitoring unit. For specific parameters contact our technical
support).
B2) PTC thermistor (PTC):
Standard internal rotor motors: Please observe the specifications and application limits, such as maximum
voltage, in the operating instructions of the respective motor manufacturer.
External rotor motors: The maximum voltage at the PTC thermistor must not exceed 2.5 V per PTC element.
Thermal motor protection is ensured exclusively by the use of temperature monitors, thermostat switches or
PTC thermistors. These motor protection devices must be connected.
If there are no temperature monitors, thermostat switches or PTC thermistors, a motor protection switch must
be used. However, motor protection switches do not provide temperature protection for the motors.
Assembly:
The assembly has to meet the requirements of the assembly instructions to enable error-free operation.
The fans may not be operated until they are installed according to their intended use. The included or
supplied guard grille of ZIEHL-ABEGG fans is usually designed according to EN ISO 13857 Table 4 (for
persons with a minimum age of 14 years). If the grilles are of a different design, the device manufacturer
must take further structural protective measures to ensure safe operation.
Commissioning:
Commissioning must be done by appropriately qualified technical personnel according to the specifications
in the operating and assembly instructions.
During start-up check the following:
1. Check the direction of rotation (see rotation direction arrow on the fan blade, impeller base plate or
support plates on suction side or rating plate).
2. Inspect the motor bearings for proper operation prior to installation. Check smooth, noiseless running
during commissioning, replace motor bearings if necessary.
3. Check for quiet, low vibration operation. Strong vibrations due to uneven running (imbalance), e.g. caused
by transportation damage or improper use, can lead to failure.
4. For variable speed fans: If resonance vibrations occur, it is possible to hide certain speed ranges.
5. A-rated sound power levels of over 80 dB(A) are possible.
6. Fans from ZIEHL-ABEGG SE are delivered balanced in accordance with DIN ISO 21940-11 for the
appropriate fan category in accordance with ISO 14694. Check the fan for mechanical vibrations after
installation. If the limit values of the corresponding fan category are exceeded in start-up, you must have the
motor/impeller unit checked by an expert and rebalanced if necessary before continuous operation is
permitted.
During commissioning, unexpected and hazardous conditions can arise in the entire installation due to
defective adjustments, defective components or incorrect electrical connections. Remove all persons and
objects from the hazardous area.
Do not start up the fan until you have read and understood all the safety instructions (DIN EN 50110, IEC
364), safety distances are observed (DIN EN ISO 13857 / EN 60335) and a hazard is excluded.
Acclimatize the fan to the permissible operating temperature range.
The device manufacturer must ensure low-vibration operation. The relevant standards must be observed e.g.
DIN ISO 10816.
In the case of applications with external vibrations, the device manufacturer must decouple the fan from the
vibration source.
The complete assembly must be checked for resonance by the device manufacturer when installed. For
variable-speed applications, the assembly must be checked for resonances over the entire speed range. If
excessive vibrations are detected, it must be avoided that the unit and the fan is operated in this resonance.
If the fan is operated with increased vibrations, service life will be considerably reduced or a failure can
occur.
Only for AC fans: For fans with protection class IP55 or higher (protection class according to DIN EN 60529
or DIN EN 60034-4), the existing condensation drain hole must be opened at least every six months.
Documentation:
In case of defective parts or products or in case of any warranty, it may be necessary to analyses the root
cause of the defect.
Therefore, ZIEHL-ABEGG may ask for documentation of proper life-cycle handling according to the
operating and assembly instructions and the general product and handling description. ZIEHL-ABEGG may
ask for appropriate documentation records in order to assess root cause of the defect.
Spare parts:
www.ziehl-abegg.com Movement by Perfection │ Bewegung durch Perfektion 12 │ 23
30/8/2022
© ZIEHL-ABEGG SE
All rights reserved. Confidential and proprietary document, not to be disclosed or used except in accordance with applicable agreements. No disclosure to third parties, if not
expressively agreed by ZA SE.
Article number
116177/A01
In all warranty cases repairs have to be carried out by ZIEHL-ABEGG. In all other cases spare parts shall
meet the specifications of the original installed parts to ensure error-free operation. Use of original ZIEHL-
ABEGG spare parts is recommended.
6. Characteristic Curve
Air performance
Acoustics
127881
Please note: It’s not allowed to use this fan in the stall area!*
*In doubt please ask your responsible ZIEHL-ABEGG sales contact.
7. Drawing
Dimensions in mm
The illustrations shown make no claim to completeness and are for orientation purposes only.
8. Connection diagram
Measurement method
The characteristic map display shows the pressure increase ∆psF in Pa
as a function of the volume flow rate qV in m3/h.
Technical conditions of supply
The specified performance data meet the respective requirements
for accuracy
- AN2 for centrifugal impellers without motor
- AN3 for centrifugal fans with standard motors
- AN2 for centrifugal impellers with ECblue motors (except EC055)
- AN3 for centrifugal impellers with ECblue motor EC055 (see type key)
- AN3 for axial fans with ECblue motors
- AN4 for axial fans with AC external rotor motors
in line with ISO 13348 and apply to the rated data and air performance
curves at the rated voltage. The continuous line in the characteristic
curve represents the optimum reliable operating range for fans.
Installation type A according to ISO
5801
Fan test bench
The fan characteristic curves are determined on a combined ventilation
and sound test bench.
The characteristic curves are measured in compliance with DIN EN ISO
5801 and AMCA 210-99. The sound power levels are measured in
compliance with DIN EN ISO 3745 and ISO 13347-3 using the
enveloping surface measuring method.
The figure below shows an example of the measuring setup. The fan is
installed in the measuring chamber at free inlet and free exhaust
Technology Centre (InVent)
(installation type A as per DIN EN ISO 5801 or AMCA 210-99).
Air density
The air density and humidity are conditioned during the measurement
using heat exchangers and kept largely constant. The characteristic
curves shown refer to the measuring density. The mean measuring
density is 1.16 kg/m³.
① Test fan
② pfs
③ Flow straightener
④ Nozzles
⑤ ∆p Differential pressure
⑥ Auxiliary fan
Because of the different weighting of the third-octave sound power Fig. Ib: Fan test-bench
level, the A-evaluation, which is typically carried out, takes into
account the subjective nature of human sound perception. The A-
tested sound power level is the standard variable used to assess
the sound characteristics of technical equipment.
No customer specification was available. Please note that ZIEHL-ABEGG does not confirm technical
requirements beyond this specification if they are not listed in a list of deviations.
The suitability of the product for sea atmosphere/dishwasher/offshore is beyond the influence of ZIEHL-
ABEGG.
ZIEHL-ABEGG can therefore neither guarantee nor prove the suitability of this product for this specific
application or the customer's intended use. The customer is responsible for testing and approving the
product for its intended use.
Please contact us. We would be pleased to design an individual solution for your requirements.
We would like to welcome you on our worldwide exhibitions. Please find our next exhibitions here.
+15°C + 5°C
Bananas
Lemon
+8°C Cucumber 0°C
Vegetables
Fruits
Others
Potatoes - Tomatoes
Fish
Mandarin
product
+3°C Green Been -5°C
Evaporating temperature °C
Beer
Milky
Milk
Orange – Cherry
Meat
Lamb- beef Cheese Flowers
Strawberry- Apple Ham - Veal Mushrooms – salad
Oil
Pear -Peach Butter Cauliflowers -asparagus Oysters
Room temperature °C
-10°C -18°C
Vegetables
-15°C beef -22°C
Meat
product
Milky
Fish
Strawberry- Cherry Ham - Veal Butter Asparagus - carrots Crustacean Bread
Fruits
Others
Peach Pork - Poultry Eggs
-18°C -25°C
Only 50Hz/400V
HP 2 7 10 *15
*kW 3.3 11.1 17.3 26.5
R22 R134a R448A PVE oil
R404A R507 R449A
MLZ series R407A R407F
POE oil
R452A R513A
R404A
VLZ series R448A
R449A
* EN12900 MBP 50Hz R22/R404A Te/Tc/RGT/SC: -10/45/20/0C
HP 4 10
**kW 2.8 6.5 PVE oil
LLZ series with R404A R507
NI/VI/LI R448A R449A R452A
POE oil
• Reliability built in …
• Self-aligning, compliant scroll design
• Teflon coated bearings
• Reduced complexity manufacturing
process (30% fewer parts and press-fit
manufacturing)
• Patented overload protection design
insures excellent motor protection while
eliminating nuisance trips
• Oil injection system insures adequate
lubrication in varying operating conditions
Benefits
Axial Compliance
Technique: Intermediate gas Radial Compliance
pressure Technique: Slider Block
Slider block
High
Pressure
Ratio
Very low
suction
pressure
Protector
- Yes, Of Course !!
- It helps with early detection of high discharge temp
hence increases compressor life
A relief valve
– based on temperature
Efficient
Quiet Reliable
ML
Z
Multi
Compact Refrigera
nt
Chúng tôi luôn chủ động Chúng tôi thích ứng nhanh Chúng tôi đặt ra tiêu chí về Tư duy win-win, bắt đầu từ
đưa ra những giải pháp tốt chóng và linh hoạt để thay sự công bằng trong mọi đích, chủ động và ưu tiên
hơn những gì đã hứa, đáng đổi, thay đổi để tốt hơn, mối quan hệ, nó giúp chúng những việc quan trọng,
tin cậy, tạo ra giá trị chia sẻ đổi mới và cải tiến không tôi hiểu nhau hơn và tạo chúng tôi là một tập thể Máy Bắn Ron Tự Động Hệ Thống Kiểm Tra Lưu Lượng & Chênh Lệch Áp Suất
và luôn chính trực. ngừng, từ đó tạo ra nhiều nên thành công. đoàn kết để rèn giũa những
sáng tạo hơn. cá nhân xuất sắc. Tất cả các ron làm kín bộ lọc của chúng tôi đều được tạo bởi EBRACO sở hữu hệ thống kiểm tra áp suất và lưu
một robot với hỗn hợp polyurethane đặc biệt để tạo ra miếng lượng không khí trong nhà theo tiêu chuẩn EN 779. Đường ống
đệm trên khung bộ lọc. Điều này nhằm đảm bảo tất cả bộ lọc cũng cho phép kiểm tra hiệu quả bộ lọc trong nhà đối với bộ lọc
Phạm Vi Tiếp Cận Toàn Cầu Của Chúng Tôi được kín hoàn toàn sau khi lắp đặt và mang lại hiệu suất tốt thô và bộ lọc tinh.
nhất cho khách hàng của chúng tôi.
Đội ngũ bán hàng và dịch vụ của EBRACO có mặt tại 8 quốc gia Singapore, Malaysia, Việt Nam, Thái Lan, Nhật Bản, Hàn Quốc,
Trung Quốc và Bangladesh. Đội ngũ chuyên gia của chúng tôi trên toàn cầu sẽ cung cấp cho bạn các giải pháp không khí theo yêu
cầu của bạn.
2 www.ebraco.net www.ebraco.net 3
TIÊU CHUẨN LỌC KHÍ
ASHRAE STANDARD 52.2-2012 ISO 16890:2016 EN EN779:2012 EN1822:2009
Hiệu
Hiệu Lượng Bụi suất Hiệu quả ban Phân số trung IEST Đặc trưng
Trung bình tổng hợp Trung bình của
quả Mức độ ngăn Tổng hợp Hiệu suất tối đầu (Ei) bình RP- Chất gây ô nhiễm được Ứng dụng Dòng sản phẩm EBRACO
Giá trị báo Hiệu quả kích thước hạt (Em) hiệu suất ban đầu
KIẾN TRÚC ban chặn ban Filter Class Thu giữ trung bình thiểu (tiêu biểu Hiệu quả CC001.3 kiểm soát
cáo hiệu % trong phạm vi kích thước, và xả
HOẶC HIỆU đầu đầu (Am) Trung bình (Ee) ở 0,4μm (Emin) 0,08 -
PHÂN LOẠI quả tối μm Em = (Ei + Ed) / 2
QUẢ PHÁT (Ei) (Aee) ở 0,15μm)
thiểu 0,4μm
HIỆN BỤI
Phạm Phạm ePM1 ePM2.5 ePM10 Test Final
Phạm vi 3 Coarse (%) Test Final dP 450Pa
vi 1 vi 2 (%) (%) (%) dP 250Pa
ISO Fine
(MERV) 0.3-1.0 1.0-3.0 3.0-10.0 0.3-1.0 0.3-2.5 0.3-10 % % % %
Dust
AFI <65 % MERV 1 Em<20 Am<50 G1 50≤Am≤65 Hạt lớn hơn 10.0µm Bộ lọc tổng, đồ dùng W-Roll
AFI 65%-70% MERV 2 Em<20 Final dP G2 65≤Am<80 (Phấn hoa) trong nhà và thương mại Paint Booth Ceiling Filter -
200 Pa (Rêu Tây Ban Nha) P600
AFI 70%-75% MERV 3 Em<20
(Mạt bụi) FG 50/75/100
AFI 75%-80% MERV 4 Em<20 (Bụi nhám) Paint Booth Plated Cardboard
(Phun bụi sơn) Paint Box
(Sợi dệt) Paint Booth HoneyComb -
AFI 80%-85% MERV 5 Em≥20 Am≥50 Final G3 80≤Am<90 Kích thước hạt trong Thương mại, PHH50
PRE FILTER
AFI 85%-90% MERV 6 Em≥35 dP 300 Pa khoảng 3.0µm-10.0µm công nghiệp, xưởng sơn Pura G
(G CLASS) (Khuôn) Pura D
NBS 25%- MERV 7 Em≥50 G4 Am≥90 Pura M
(Bào tử)
30% Pura Demister
(Keo xịt tóc)
NBS 30%- MERV 8 Em≥20 Em≥70 (Bụi xi măng) Oven Mat
35% (Snuff) Activated Carbon Media
(Sữa bột) Coal Granular Activated
Carbon
Activated Cacbon Pleated Air
Filter
NBS 40%- MERV 9 Em≥35 Em≥75 Ei>50 M5 40≤Em≤60 Kích thước hạt trong vòng IAQ liên quan đến Puracel I
45% 1,0µm-3,0µm thương mại & Puracel II
NBS 50%- MERV 10 Em≥50 Em≥80 (Bụi chì) công nghiệp, y tế Puracel V
55% (Bột xay) Pura Pak - S
(Bụi than) Pura Pak
NBS 60%- MERV 11 Em≥20 Em≥65 Em≥85 Em≥50 Ei>70 M6 60≤Em≤80
(Tự động phát thải) Puracel I HT
65%
(Máy phun sương rơi) Puracel I XT
NBS 70%- MERV 12 Em≥35 Em≥80 Em≥90 (Khói hàn) Puracel II HT
75% Activated Cacbon Bag Filter
MEDIUM
FILTER NBS 80%- MERV 13 Em≥50 Em≥85 Em≥90 Em≥50 Em≥65 Ei>80 F7 80≤Em≤90 Emin≥35 Kích thước hạt trong IAQ liên quan đến V-Bank Activated Cacbon
(F CLASS) 85% khoảng 0,3µm-1,0µm thương mại,
NBS 90%- MERV 14 Em≥75 Em≥90 Em≥95 Em≥70 Em≥80 Ei>90 F8 90≤Em≤95 Emin≥55 (Tất cả vi khuẩn) công nghiệp, y tế, thực
95% (dầu ăn) phẩm, v.v.
(Hầu hết khói)
NBS>95% MERV 15 Em≥85 Em≥90 Em≥95 Em≥70 F9 95≤Em Emin≥70
(Mực máy photocopy)
MERV 16 Em≥95 Em≥95 Em≥95 (Hầu hết các loại bột phủ)
(Hầu hết các chất màu sơn)
E10 Ei≥85 at Em≥95 at 0.3µm N/A Kích thước hạt lớn hơn Tất cả các loại phòng Hepatec Macro
MPPS 0,3µm sạch Hepatec Gel
E11 Ei≥95 at Em≥98 at 0.3µm (Virus) Hepatec V
MPPS (Bụi carbon) Hepatec II
Em≥99.97 at TYPE A
(Muối biển) Hepatec I
0.3µm
HEPA FILTER (Tất cả khói cháy) Hepatec I HT
N/A N/A N/A N/A N/A N/A N/A N/A E12 Ei≥99.5 at Em≥99.99 at TYPE C
(H CLASS) (Các nguyên tố phóng xạ) Hepatec I XT
MPPS 0.3µm
H13 Ei≥99.95 at Em≥99.995 at
MPPS 0.3µm
H14 Ei≥99.995 at Em≥99.999 at TYPE D
MPPS 0.3µm
U15 Ei≥99.9995 at Em≥99.9995 at TYPE F Kích thước hạt lớn hơn Phòng siêu sạch
MPPS 0.12µm 0,12µm
ULPA FILTER U16 Ei≥99.99995 Em≥99.99995 at
N/A N/A
(U CLASS) at MPPS 0.12µm
U17 Ei≥99.999995 Em≥99.999995
at MPPS at 0.12µm
Chú Thích
1. AFI: Viện lọc Hoa Kỳ 2. NBS: Cục tiêu chuẩn quốc gia 3. ASHRAE: Hiệp hội kỹ sư hệ thống sưởi ấm & điều hòa không khí Hoa Kỳ 4. MERV: Giá trị Báo cáo Hiệu quả Tối thiểu 5. MPPS: Kích thước hạt thâm nhập nhất 6. HEPA: Bộ lọc không khí dạng hạt hiệu quả cao 7.ULPA: Bộ lọc không khí có độ thâm nhập cực thấp
8. IEST: Viện Khoa học và Công nghệ Môi trường 9. Am : Hiệu quả bắt giữ trung bình cho các bộ lọc thô 10. Em : Hiệu quả Trung bình cho Bộ lọc trung 11. Emin: Hiệu quả tối thiểu 12. Ed: Hiệu quả xả 13. Ei: Hiệu quả ban đầu
4 www.ebraco.net www.ebraco.net 5
W-Roll Paint Booth Ceiling Filter Pura G Rod Pura G Pleat 1F
Ứng dụng: Đa ngành công nghiệp Ứng dụng: Công nghiệp ô tô Ứng dụng: Đa ngành công nghiệp Ứng dụng: Đa ngành công nghiệp
EN779 G2, G3, G4, M5 EN779 M5 EN779 G2, G3, G4, M5 EN779 G4
ISO 16890 Coarse 40%, 50%, 65%, 85% ISO 16890 Coarse 80% ISO 16890 Coarse 40%, 50%, 65%, 85% ISO 16890 Coarse 65%
Kích Thước Cuộn (m) 2x20 Kích Thước Cuộn (m) 2x20 Vật Liệu Lọc Sợi tổng hợp Vật Liệu Lọc Sợi tổng hợp
Vật Liệu Lọc Sợi tổng hợp Vật Liệu Lọc Sợi tổng hợp Vật Liệu Khung Nhôm
Vật Liệu Khung Nhôm
Độ Dày (mm) 5, 10, 15, 20, 22 Độ Dày (mm) 20 Độ dày khung (mm) 46
Độ dày khung (mm) 90
Áp Khuyến Nghị Thay Lọc (Pa) 250 Áp Khuyến Nghị Thay Lọc (Pa) 450 Áp Khuyến Nghị Thay Lọc (Pa) 250
Áp Khuyến Nghị Thay Lọc (Pa) 250
Nhiệt Độ (oC)/ Độ Ẩm (% RH) 100/100 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 100/100 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 100/100 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 100/100
Pre-filter
Ứng dụng: Công nghiệp ô tô Ứng dụng: Công nghiệp ô tô Ứng dụng: Đa ngành công nghiệp Ứng dụng: Đa ngành công nghiệp
EN779 G2, G3, G4 Hiệu Suất Lọc Trung Bình (%) ≥ 90 EN779 G2, G3, G4, M5 EN779 G2, G3, G4, M5
ISO 16890 Coarse 50%, 60%, 65% Kích Thước Cuộn (m) 1x10 ISO 16890 Coarse 40%, 50%, 65% ISO 16890 Coarse 40%, 50%, 65%, 85%
Kích Thước Cuộn (m) 2x20 Vật Liệu Lọc Carton đục lỗ xếp li Vật Liệu Lọc Sợi tổng hợp Vật Liệu Lọc Sợi tổng hợp
Vật Liệu Lọc Sợi thủy tinh Độ Dày (mm) 50, 60 Vật Liệu Khung Nhôm Vật Liệu Khung Nhôm, Kẽm
Độ Dày (mm) 50, 75, 100 Tốc độ định mức (m3/h/Pa) 0.5-1.0 / 20-40 Độ dày khung (mm) 46 Độ dày khung (mm) 21
Áp Khuyến Nghị Thay Lọc (Pa) 250 Áp Khuyến Nghị Thay Lọc (Pa) 450 Áp Khuyến Nghị Thay Lọc (Pa) 250 Áp Khuyến Nghị Thay Lọc (Pa) 250
Nhiệt Độ (oC)/ Độ Ẩm (% RH) 250/100 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 80/80 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 100/100 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 100/100
Khả năng giữ lại (kg/m3) 12-15 Khả năng giữ lại (kg/m3) 12-15
Hiệu suất lọc trung bình (%) ≥ 98 Kích Thước Cuộn (m) 1x10
Vật Liệu Lọc Giấy tổ ong nhiều lớp Vật Liệu Lọc Giấy tổ ong nhiều lớp
Vật Liệu Khung Carboard Độ Dày (mm) 100, 180
Tốc độ định mức (m3/h/Pa) 0.75-1.5 / 8-22.5 Tốc độ định mức (m3/h/Pa) 0.75-1.5 / 8-22.5
Áp khuyến nghị thay lọc (Pa) 500 Áp khuyến nghị thay lọc (Pa) 500
Nhiệt độ (oC)/ Độ ẩm (% RH) 80/80 Nhiệt độ (oC)/ Độ ẩm (% RH) 80/80
6 www.ebraco.net www.ebraco.net 7
Pura G Plank 2F Pura D Pura Pak S Puracel II
Ứng dụng: Thực phẩm, Điện tử, Sản xuất chất bán dẫn, Sức khỏe & bệnh viện Ứng dụng: Khu thương mại, Thực phẩm, Chất bán dẫn, Sức khỏe & bệnh viện Ứng dụng: Công nghiệp ô tô Ứng dụng: Thực phẩm, Điện tử,Sản xuất chất bán dẫn, Sức khỏe & Bệnh Viện
EN779 G2, G3, G4 EN779 M5 EN779 G4, M5, M6 EN779 F7, F8, F9
ISO 16890 Coarse 40%, 50%, 65% ISO 16890 Coarse 65%, 85% ISO 16890 Coarse 65%, ePM10 50% ISO 16890 ePM1 50%, 65%, 80%
Vật Liệu Lọc Sợi thủy tinh (Hotmelt separator)
Vật Liệu Lọc Sợi tổng hợp Vật Liệu Lọc Sợi tổng hợp không dệt Vật Liệu Lọc Sợi tổng hợp
Vật Liệu Khung Nhôm, Kẽm Vật Liệu Khung Nhôm, Giấy Vật Liệu Khung Nhôm, Kẽm, Nhựa Vật Liệu Khung Nhôm, Kẽm, Inox
Độ dày khung (mm) 21 Độ dày khung (mm) 46, 94 Độ dày (mm) 300, 380, 530, 630 Độ dày khung (mm) 70, 90
Áp Khuyến Nghị Thay Lọc (Pa) 250 Áp Khuyến Nghị Thay Lọc (Pa) 250 Áp Khuyến Nghị Thay Lọc (Pa) 450 Áp Khuyến Nghị Thay Lọc (Pa) 500
Nhiệt Độ (oC)/ Độ Ẩm (% RH) 100/100 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 80/100 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 80/100 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 80/100
Medium-Filters
Pre-filters
Ứng dụng: Thực phẩm, Điện tử,Sản xuất chất bán dẫn Ứng dụng: Thực phẩm, Điện tử,Sản xuất chất bán dẫn Ứng dụng: Thực phẩm, Điện tử, Dược phẩm, Sản xuất chất bán dẫn Ứng dụng: Thực phẩm, Điện tử, Dược phẩm, Sản xuất chất bán dẫn
EN779 G2, G3 EN779 G2, G3 EN779 M5, M6, F7, F8, F9 EN779 F7, F8, F9
ISO 16890 Coarse 40% ISO 16890 Coarse 40%, 50% ePM1 50%, 65%, 80% ISO 16890 ePM1 50%, 65%, 80%
ISO 16890
ePM10 50%, 65% Sợi thủy tinh (Hotmelt separa-
Vật Liệu Lọc Nhôm, Inox Vật Liệu Lọc Nhôm, Inox Vật Liệu Lọc
Vật Liệu Lọc Sợi tổng hợp tor)
Vật Liệu Khung Nhôm, Inox Vật Liệu Khung Nhôm, Inox Vật Liệu Khung Nhôm, Kẽm, Nhựa Vật Liệu Khung Nhựa
Độ dày khung (mm) 21, 25, 46, 90 Độ dày khung (mm) 21, 25, 46, 90 Độ dày (mm) 300, 380, 530, 630 Độ dày khung (mm) 292
Áp Khuyến Nghị Thay Lọc (Pa) 250 Áp Khuyến Nghị Thay Lọc (Pa) 250 Áp Khuyến Nghị Thay Lọc (Pa) 450 Áp Khuyến Nghị Thay Lọc (Pa) 500
Nhiệt Độ (oC)/ Độ Ẩm (% RH) 250/100 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 250/100
Nhiệt Độ ( C)/ Độ Ẩm (% RH)
o
80/100 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 80/100
Puracel I
Ứng dụng: Thực phảm, Điện tử, Dược phẩm, Sản xuất chất bán dẫn
Thông Số Kỹ Thuật
8 www.ebraco.net www.ebraco.net 9
Hepatec Macro Hepatec II Oven Mat
Puracel I HT 250
Ứng dụng: Thực phẩm, Điện tử, Dược phẩm, Sản xuất chất bán dẫn Ứng dụng: Thực phẩm, Điện tử, Dược phẩm, Sức khỏe & bệnh viện Ứng dụng: Công nghiệp ô tô Ứng dụng: Công nghiệp ô tô, Thực phẩm, Dược phẩm
EN1822 H13, H14, U15 EN1822 H13, H14, U15, U16, U17 EN779 G4 EN779 M6, F7, F8, F9
Sợi thủy tinh (Hotmelt separa- Sợi thủy tinh (Hotmelt separa- ISO 16890 Coarse 65% ePM1 50%, 65%, 80% | ePM10
Vật Liệu Lọc Vật Liệu Lọc ISO 16890
tor) tor) Kích Thước Cuộn (m) 1x20 65%
Vật Liệu Khung Nhôm, Kẽm, Inox Vật Liệu Khung Nhôm Sợi thủy tinh (Aluminum
Vật Liệu Lọc Sợi thủy tinh Vật Liệu Lọc
separator)
Độ dày khung (mm) 150 Độ dày khung (mm) 70, 90, 110
Độ Dày (mm) 5, 10, 18, 20, 22 Vật Liệu Khung Nhôm, Kẽm, Inox
Ron PU foam Ron PU foam
Độ dày khung (mm) 150, 292
Áp Khuyến Nghị Thay Lọc (Pa) 750 Áp Khuyến Nghị Thay Lọc (Pa) 750 Áp Khuyến Nghị Thay Lọc (Pa) 250
Áp Khuyến Nghị Thay Lọc (Pa) 500
Nhiệt Độ ( C)/ Độ Ẩm (% RH)
o
80/100 Nhiệt Độ ( C)/ Độ Ẩm (% RH)
o
80/100 Nhiệt Độ ( C)/ Độ Ẩm (% RH)
o
100/100 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 250/100
HT Filters
Ứng dụng: Thực phẩm, Điện tử, Dược phẩm, Sức khỏe & bệnh viện Ứng dụng: Sản xuất chất bán dẫn Ứng dụng: Ô tô, Thực phẩm, Điện tử, Dược phẩm, Sản xuất chất bán dẫn Ứng dụng: Điện tử, Sản xuất chất bán dẫn
EN1822 H13, H14, U15, U16, U17 EN1822 H13, H14 EN1822 H13, H14 EN779 M6, F7, F8, F9
Sợi thủy tinh (Aluminum Sợi thủy tinh (Aluminum ePM1 50%, 65%, 80%
Vật Liệu Lọc Sợi thủy tinh (Hotmelt separator) Vật Liệu Lọc Vật Liệu Lọc ISO 16890
separator) separator) ePM10 65%
Vật Liệu Khung Nhôm Sợi thủy tinh (Aluminum
Vật Liệu Khung Nhôm Vật Liệu Khung Nhôm, Kẽm, Inox Vật Liệu Lọc
Độ dày khung (mm) 93 separator)
Độ dày khung (mm) 150, 292 Độ dày khung (mm) 150, 292
Vật Liệu Khung Nhôm, Kẽm, Inox
Ron Gel Seal Ron PU foam Ron Ron chịu nhiệt
Độ dày khung (mm) 150, 292
Áp Khuyến Nghị Thay Lọc (Pa) 750 Áp Khuyến Nghị Thay Lọc (Pa) 750 Áp Khuyến Nghị Thay Lọc (Pa) 750 Áp Khuyến Nghị Thay Lọc (Pa) 500
Nhiệt Độ (oC)/ Độ Ẩm (% RH) 80/100 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 100/100 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 250/100 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 350/100
Ứng dụng: Thực phẩm, Sản xuất chất bán dẫn Ứng dụng: Lọc không khí Ứng dụng: Công nghiệp ô tô, Dược phẩm Ứng dụng: Công nghiệp ô tô, Dược phẩm
EN1822 H13, H14, U15 EN1822 H13, H14 EN1822 H13, H14 EN779 M6, F7, F8, F9
Sợi thủy tinh (Hotmelt separa- Vật Liệu Lọc Sợi thủy tinh, sợi tổng hợp Sợi thủy tinh (Aluminum ISO 16890 ePM1 50%, 65%, 80%
Vật Liệu Lọc Vật Liệu Lọc
tor) separator)
Vật Liệu Khung Giấy, Nhựa Vật Liệu Lọc Sợi thủy tinh (Hotmelt separator)
Vật Liệu Khung Nhôm, Kẽm Vật Liệu Khung Nhôm, Kẽm, Inox
Độ dày khung (mm) 292 Độ dày khung (mm) 30 Độ dày khung (mm) 150, 292 Vật Liệu Khung Nhôm, Kẽm, Inox
Ron PU foam Ron Sponge foam Ron Ron chịu nhiệt Độ dày khung (mm) 70, 120
Áp Khuyến Nghị Thay Lọc (Pa) 750 Áp Khuyến Nghị Thay Lọc (Pa) 250 Áp Khuyến Nghị Thay Lọc (Pa) 750 Áp Khuyến Nghị Thay Lọc (Pa) 500
Nhiệt Độ (oC)/ Độ Ẩm (% RH) 80/100 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 80/80 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 350/100 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 250/100
10 www.ebraco.net www.ebraco.net 11
Activated Carbon Media Activated Carbon Bag Filter Chemical Cassette Filter Chemical Cartridge Filter
Ứng dụng: Loại bỏ mùi và khí cho nhiều ngành công nghiệp Ứng dụng: Loại bỏ mùi và khí cho nhiều ngành công nghiệp Ứng dụng: Loại bỏ mùi và khí cho nhiều ngành công nghiệp Ứng dụng: Loại bỏ mùi và khí cho nhiều ngành công nghiệp
EN779 G2, G3, G4 EN779 F7, F8, F9 Hiệu quả >90% Hiệu quả >90%
ISO 16890 Coarse 40%, 50%, 65%, 85% ISO 16890 ePM1 40%, 65%, 80% Than hoạt tính dạng hạt, Bộ lọc Than hoạt tính dạng hạt, Bộ lọc
Kích thước cuộn(m) 2x20 Vật Liệu Lọc Than hoạt tính Vật Liệu Lọc Vật Liệu Lọc
hóa học dạng hạt hóa học dạng hạt
Vật Liệu Lọc Than hoạt tính Vật Liệu Khung Nhôm, Inox Vật Liệu Khung ABS Vật Liệu Khung ABS
Độ dày khung (mm) 3, 5, 10 Độ dày khung(mm) 21
Kích thước (WxHxD) mm 300x300x292, 145 x 300 x 440 Kích thước (WxHxD) mm 145x600, 145x450
Áp Khuyến Nghị Thay Lọc (Pa) 250-450 Áp Khuyến Nghị Thay Lọc (Pa) 450
Nhiệt Độ (oC)/ Độ Ẩm (% RH) 80/80 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 80/80 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 80/80 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 80/80
Granular Carbon V Bank Activated Carbon V Bank Polyester Cartridge Filter Nano Cellulose Cartridge Filter
Chemical Filters
Cartridge Filters
Ứng dụng: Loại bỏ mùi và khí cho nhiều ngành công nghiệp Ứng dụng: Loại bỏ mùi và khí cho nhiều ngành công nghiệp Ứng dụng: Lọc bụi trong phun bột, phun cát, sơn, gỗ, nhà máy xi măng Ứng dụng: Lọc bụi trong phun bột, phun cát, sơn, gỗ, nhà máy xi măng
Efficiency 90% EN779 F7, F8, F9 Hiệu quả >90% ASHRAE 52.2-2007 Up to MERV 15
ISO 16890 ePM1 40%, 65%, 80% ISO 16890 ePM1 40%, 65%, 80% Vật Liệu Lọc Polyester Vật Liệu Lọc Nano cellulose
Than hoạt tính dạng hạt, Bộ lọc Vật Liệu Lọc Than hoạt tính
Vật Liệu Lọc Vật Liệu Khung Mạ kẽm Vật Liệu Khung Mạ kẽm
hóa học dạng hạt Vật Liệu Khung Nhựa
Vật Liệu Khung Nhựa, Inox Đường kính tổng thể (Φ) mm 324, 352 Đường kính tổng thể (Φ) mm 324, 352
Độ dày khung(mm) 292
Độ dày khung(mm) 292 Độ dài (mm) 660, 750, 1000 Độ dài (mm) 660, 750, 1000
Áp Khuyến Nghị Thay Lọc (Pa) 450
Áp Khuyến Nghị Thay Lọc (Pa) 450 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 135/100 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 135/100
Nhiệt Độ (oC)/ Độ Ẩm (% RH) 80/80 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 80/80 Khả năng tẩy rửa Có Khả năng chống cháy Có
Activated Carbon Pleated Air Filter Coal Granular Activated Carbon High Temperature Resistance Cartridge Oval Cartridge Filter
Ứng dụng: Loại bỏ mùi và khí cho nhiều ngành công nghiệp Ứng dụng: Loại bỏ mùi và khí cho nhiều ngành công nghiệp Ứng dụng: Lọc bụi trong phun bột, phun cát, sơn, gỗ, nhà máy xi măng Ứng dụng: Lọc bụi trong dược phẩm, Thực phẩm, Phun bột
EN779 G2, G3, G4 Model A B C ASHRAE 52.2-2007 Up to MERV 15 ASHRAE 52.2-2007 Up to MERV 15
Hydrocarbons Sulphur Sulphur Dioxide
ISO 16890 Coarse 40%, 50%, 65%, 85% Chlorine Nitric OxideNitric Hydrogen Vật Liệu Lọc PPS, NOMEX Vật Liệu Lọc Ultra Web
Vật Liệu Lọc Than hoạt tính Dioxide Organic Oxide sulfide Vật Liệu Khung Mạ kẽm, In Vật Liệu Khung Mạ kẽm
Gas xử lý
gas Formaldehyde
Vật Liệu Khung Nhôm, Inox, Giấy Organic Gas Đường kính tổng thể (Φ) mm 142, 156, 178 Đường kính tổng thể (Φ) mm 324, 352, 365
Độ dày khung(mm) 21, 25, 46, 90 H2S Độ dài (mm) 660, 750, 1000 Độ dài (mm) 660, 750
Hiệu quả 99.5% 99.5% 99.5%
Áp Khuyến Nghị Thay Lọc (Pa) 250-450 Hoạt động tối Nhiệt Độ ( C)/ Độ Ẩm (% RH)
o
190, 232 /100 Nhiệt Độ (oC)/ Độ Ẩm (% RH) 135/100
10-95% 10-95% 10-95%
đa
Nhiệt Độ (oC)/ Độ Ẩm (% RH) 80/80 20-51°C 20-51°C 20-51°C Khả năng tẩy rửa Có Khả năng chống cháy Có
Nhiệt độ
12 www.ebraco.net www.ebraco.net 13
YÊU CẦU THIẾT KẾ ĐỐI VỚI PHÂN LOẠI PHÒNG SẠCH
TIÊU CHUẨN PHÒNG SẠCH YÊU CẦU THIẾT KẾ ĐỐI VỚI PHÂN LOẠI PHÒNG SẠCH
P
hòng sạch đang trở thành một không gian không thể Class 10 Class 100 Class 1000 Class 10,000 Class 100,000
thiếu của nhiều ngành, lĩnh vực sản xuất khác nhau. Tiêu CRITERIA
ISO 4 ISO 5 ISO 6 ISO 7 ISO 8
chuẩn phòng sạch ra đời nhằm nâng cao chất lượng sản
phẩm, xây dựng môi trường sản xuất sạch, đảm bảo các tiêu Không khí thay
500-600/8 to 10 300-480/5 to 8 180/3 60/1 20/0.33
chuẩn an toàn. Tiêu chuẩn phòng sạch lần đầu tiên được quy đổi mỗi HR / Min
định vào năm 1963 ở Mỹ. Đây là tiêu chuẩn được xây dựng
dựa trên các quy định về hàm lượng bụi trên một đơn vị thể Độ phủ của lọc % 90-100 60-70 20-30 7-15 4-5
tích không khí, nhiệt độ, độ ẩm và áp suất. Từ đó đến nay, tiêu
chuẩn này từng bước được cải tiến, hoàn thiện và trở thành CFM trên mỗi
tiêu chuẩn áp dụng cho toàn thế giới. 85-90 36-65 18-32 9-16 4-8
square foot
ISO 1 10 2
ISO 2 100 24 10 4
ISO 6 1,000,000 237,000 102,000 35,200 8,320 293 Class 1,000 A 3,520 20 3,520 20
ISO 8 3,520,000 832,000 29,300 Class 100,000 C 352,000 2,900 3,520,000 29,000
ISO9 35,200,000 8,320,000 293,000 Room Air D 3,520,000 29,000 not defined not defined
14 www.ebraco.net www.ebraco.net 15
The Laminar Airflow (LAF) Fan Filter Unit (FFU)
Ứng dụng: Công nghiệp hóa chất, Dược phẩm, Dinh dưỡng, Công nghệ sinh học Ứng dụng: Bán dẫn & Điện tử
Thân thiết bị SUS 304; Thép mạ kẽm sơn tĩnh điện (PCGI)
Thân thiết bị SUS304; SUS403; Nhôm; Thép mạ kẽm sơn tĩnh điện (PCGI)
Chất Liệu Tường Vách mềm nhựa vinyl, Acrylic, SUS 304
Bộ khuếch tán SUS 304 đột lỗ; Lớp màng Membrane Vận tốc không khí (m / s) 0.36-0.54
Cấu hình (Vị trí) Treo; Đứng Thiết bị điêu khiển tôc độ Cài đặt tốc độ duy trì và biến thiên, Bộ kiểm soát nhóm định tuyến
Bộ điều khiển Vi điều khiển với chức năng điều khiển quạt riêng lẻ; Bộ điều khiển cơ
Độ ồn (dB) <55 dB tại 0.45 m/s (không có bộ khuếch tán)
Cấp phòng sạch Class 100, 1k, 10k, 100k (Class A,B,C,D)
Tùy chọn khác Cổng áp suất, Cổ gió, Bảo trì từ khu vực làm việc
Tùy chọn khác Cổng PAO, Đồng hồ áp suất, Đèn UV, Tấm phủ mặt trước
Ứng dụng: Thực phẩm, Bán dẫn & Điện tử, Công nghiệp Hóa chất, Dược phẩm, Dưỡng sinh, Công Ứng dụng: Điện tử & Bán dẫn, Công nghiệp hóa chất, Dược phẩm, Thực phẩm, Công
nghệ Sinh học, Bệnh viện & Chăm sóc sức khỏe nghệ sinh học
Thiết bị điêu khiển tôc độ Điều khiển thủ công, Bộ vi điều khiển thông minh.
Bộ khuếch tán Bộ khuếch tán 5 chiều; Phẳng Độ ồn (dB) <55 dB
16 www.ebraco.net www.ebraco.net 17
OT Laminar Dispensing Booth (RLAF)
Ứng dụng: Bệnh viện & Chăm sóc sức khỏe Ứng dụng: Công nghiệp hóa chất, Dược phẩm, Dinh dưỡng, Công nghệ sinh học
Cung cấp bộ lọc không khí 99.995% tại 0.3 Microns (H14); 99.9995% tại 0.12 Microns (U15) Vận tốc không khí (m / s) 0.3-0.5
Phụ kiện Cổng PAO Bộ khuếch tán SUS 304 đột lỗ; Màng Membrane
Tùy chọn khác Hệ thống xả BIBO
Cấu hình (Vị trí) Đứng; Treo
Human Protection
Air Treatment
NFS-90351 (area risk 3&4)
Ứng dụng: Công nghiệp hóa chất, Dược phẩm, Thực phẩm, Công nghệ sinh học Ứng dụng: Đa ngành công nghiệp
Cổng kiểm tra rò rỉ, Đồng hồ đo áp suất, Máy quét kiểm tra rò rỉ, Túi Tùy chọn khác Đèn/còi báo, Quạt gió, Ống dẫn & Mặt bích
Phụ kiện
thay thế, Dụng cụ niêm phong
Độ ồn (dB) <55 dB tại 0.45 m/s (không có máy khuếch tán)
Tùy chọn khác Khả năng di chuyển được
Tùy chọn khác Cổng áp suất, Cổ gió, Thay lọc từ bên trong
Cấu hình (Vị trí) Treo
18 www.ebraco.net www.ebraco.net 19
Air Shower Static Pass Box
Vận tốc không khí (m / s) 20-25 Khóa liên động Điện từ; Khóa cơ học
90-92% (G4); 99.995% tại 0.3 Microns (H14); 99.9995% tại 0.12
Pre-filter/Hepa-Filter Đèn báo hiệu Có
Microns (U15)
Mặt thổi Một mặt; 2 mặt; 3 mặt
Bộ điều khiển Bộ vi điều khiển thông minh Tùy chọn khác Đèn UV, Đèn/Còi báo, Điện thoại liên lạc nội bộ, Chân đế
• Thích hợp cho quá trình chuyển giao nguyên liệu thô và thành phẩm
trong phòng sạch hoặc môi trường được kiểm soát.
Ứng dụng: Công nghiệp hóa chất, Dược phẩm, Dinh dưỡng, Công nghệ sinh học,Thực Ứng dụng: Dược phẩm, Công nghệ sinh học
phẩm, Chất bán dẫn & điện tử, Phòng sơn
90-92% (G4); 99.995% tại 0.3 Microns (H14); 99.9995% tại 0.12 Microns 90-92% (G4); 99.995% tại 0.3 Microns (H14); 99.9995% tại 0.12
Pre-filter/Hepa-Filter Pre-filter/Hepa-Filter
(U15) Microns (U15)
Vận tốc không khí (m / s) 0.36-0.54
Bộ điều khiển Bộ vi điều khiển thông minh
Đèn chiếu sáng LED
Mặt thổi Dọc / Ngang (Một mặt)
Tùy chọn khác Đèn UV, Đèn/Còi báo, Điện thoại liên lạc nội bộ, Chân dế
Độ ồn (dB) <55
20 www.ebraco.net www.ebraco.net 21
Mist Shower Kết Quả Của Chúng Tôi
Mô tả sản phẩm Chúng tôi cố gắng phục vụ khách hàng bằng các sản phẩm chất lượng và giải pháp đổi mới. Chúng tôi phục vụ hàng nghìn khách
• Thiết bị để ngăn ngừa sự lây nhiễm chéo của các hạt nguyên liệu dược hàng trong những năm qua. Ngày nay, hầu hết các khách hàng hợp tác với chúng tôi đều là những tập đoàn nổi tiếng đẳng cấp
phẩm nguy hiểm sang các cơ sở phòng sạch khác. thế giới.
• Vòi phun sương phun ra một lớp sương mù mịn đến quần áo của người
dùng và ngăn chúng khuếch tán ra ngoài. Điều này tạo nên sự bảo vệ
cần thiết cho hệ thống hô hấp của người vận hành, bảo vệ người vận
hành khỏi nguy cơ hít phải. Vòi phun sương làm ướt bề mặt áo bảo hộ Nhà Thầu
của người vận hành bằng một lớp sương nước mịn khiến bột dính vào
bề mặt thay vì bay vào không khí. Sau đó, bột được thổi bằng không khí
đã qua lọc HEPA với tốc độ cao 25 m / s để bay ra khỏi quần áo của con
người.
• Thiết bị đi kèm với khay thoát nước và đường ống với mục đích làm sạch
thường xuyên.
• Thích hợp cho việc làm sạch quần áo của người vận hành khi ra khỏi cơ
Điện Tử
sở sản xuất trong ngành sản xuất dược phẩm.
Thông Số Kỹ Thuật
Dược Phẩm
ID Thiết bị Ebraco - Mist Shower
HÀNG
Khí tuần hoàn / khí thả BIBO 3 giai đoạn
Mô tả sản phẩm
Ô tô
• Máy lọc không khí được khuyến khích sử dụng trong các cơ sở y tế, văn
phòng và gia đình.
• Máy lọc không khí có khả năng lọc các hạt bụi trong không khí, loại bỏ
mùi, khói thuốc lá, vi sinh vật và vi-rút lên đến 99,97%.
• Máy lọc không khí này được trang bị bộ lọc HEPA dùng trong y khoa, bộ
ion hóa và tia UV để loại bỏ các hạt độc hại.
• Bộ thiết bị này đi kèm với cảm biến hạt và tự động điều chỉnh lưu lượng
khí lọc để tối ưu hóa chất lượng không khí trong nhà. Tòa nhà thương mại
Ứng dụng: Phòng hồi sức bệnh nhân, phòng trẻ sơ sinh, văn phòng, nhà ở
Specification
Diện tích hoạt động (m2) / Lưu lượng không khí sạch (CMH) 20 - 60 / 800
Độ ồn dB (A) 50
Hospital
Kích thước sản phẩm (LxWxH) mm 590x410x995
22 www.ebraco.net www.ebraco.net 23
Để biết thêm thông tin, truy cập:
www.ebraco.net
Email : sales.admin@ebraco.net
www.ebraco.net
DESICCANT
DEHUMIDIFIER
Excellent supplier of products and solutions in global air-handling area
DESICCANT
ROTORS
Product introduction
ankie@puresci.com www.purescirotors.com
With the value of respecting science, humanity and engineering
research, and the motivation on products innovation, Puresci is devoted
to build a better future together with customers, employees and
partners.
Baikal Lab Dynamic Test Lab Mariana Lab Material R&D Lab
PSC PSL
Desiccant Rotor Characteristic
·Cost effective
Composed of inorganic fiber, silicate and coating. Inorganic fiber and silicate
a r e b o n d e d to ge t h e r i n t h e f o r m o f C h e m i c a l B o n d ,w i t h st r o n ge r
microstructure and excellent durability. Inorganic coating is used as the surface
cover due to its smooth and high-temperature resistance. Add other elements
to rotor material on the basis of silica gel, improving the strength of the
material spoke, the temperature resistance and the affinity for water molecules.
O rd i n a r y d e s i cc a n t r oto r c a n b e u s e d f o r b ot h o r d i n a r y h u m i d i t y
dehumidification and low dew point dehumidification. The dehumidification
performance of PSS is equivalent to that of industry average with a lower cost.
90°
270°
rotor
·Upgraded Material
·Saving cost
Through the control of material pore diameter and the addition of new
elements , the adsorption performance of is better than that of PSS.
Compared with ordinary rotors, the dehumidification capacity of PSS-S
will increase about 6% under the same dehumidification conditions;
Under the same dehumidification demand, the energy consumption can
be saved by about 8%. In low dew point condition, the energ y
consumption can be saved by about 15%. The dehumidification
performance of PSS-S is higher than that of industry average and the cost
is almost equal, that's why PSS-S is the most cost effective product.
16% Inorganic Fiber
2% Surface Coating
Heater
Single rotor & low dew point
High temperature regeneration air
conditioning system
Cooling Coil Cooling Coil Cooling Coil
Workshop
45° 45°
90°
270° 270°
Performance test record of PSS-S in low dew point air condition
Regen Inlet Air Process Inlet Air Process Outlet Air Purge Outlet Air
Rotor
Process RPH
Velocity (m/s) (r/h )
Thickness
(mm)
Temperature Velocity Temperature Moisture
Temperature(°C) Moisture (g/kg) Dew Point (°CDP) Temperature (°C)
(°C) (m/s) (°C) (g/kg)
Regen Inlet Air Process Inlet Air Process Outlet Air Purge Outlet Air
Process Rotor
Velocity RPH (r/h) Thickness
(m/s) (mm)
Temperature Velocity Moisture Temperature Moisture Dew Point
Temperature (℃) Temperature (℃)
(℃) (m/s) (g/kg) (℃) (g/kg) ( ℃DP)
·Patented product
efficiency
·Energy Saving25%
Farther improve process technology on the basis of PSS-S to achieve
more uniform channel distribution, which can increase the specific
surface area,resulting in a stronger saturation adsorption capacity.
The best product for low dew point condition at present.
One of Puresci's patented products. Compared with PSS-S, under the
same demand of low dew point, the energy consumption can be saved
by about 15%. In the case of double rotor system with low dew point
requirements, it can be used with PST and heat pumps to achieve
medium temperature (70-90° C) regeneration, reducing energy
consumption by 40%-60%.
PSS
120-130℃ PST
70-90℃
13℃ 13℃
·Especially designed for low dew point inlet air condition, so the energy
·Without security risks of high temperature when the ma- chine is in operation
Adopt a variety of adsorption materials to achieve a strong polarity and Cou-
lomb field of the crystal hole, achieving stronger adsorption capacity for
water molecules and better performance in ultra-low dew point conditions.
The best product for low dew point condition at present.
One of Puresci's patented products. Compared with PSS-S, under the same
demand of low dew point, the energy consumption can be saved by about
15%. In the case of double rotor system with low dew point requirements, it
can be used with PST and heat pumps to achieve medium temperature (70-
90° C) regeneration, reducing energy consumption by 40%-60%.
12% Inorganic Fiber
2% Surface Coating
MTR™ Medium Temperature Regeneration
High Efficiency & Energy Saving Product
PST+PSC
The research and development of the medium
temperature regeneration system is based on the limit
points of the current refrigeration system (physical
limits, mathematics, chemistry), rotor materials and
process and logic control.
The MTRTM product is specially developed by Puresci
for the new energy battery industry. This product is
designed on the basis of the steam throttling heating
method and the heat pump hot water station with
high performance heat pump hot water unit.
80-90℃ 70-90℃
MTR™ Medium Temperature Regeneration
High Efficiency & Energy Saving Product
PST+PSC
Why pre rotor is PST?
1.With regen.temp.90 C, high demand on dehumidification performance of pre rotor
2. Processed by special chemical, PST can maintain excellent desorption capacity when regen. temp. is 90 C
3. PST is the "timely help" in double-rotor system
20-30%
Energy Saving
(VS High Temperature Steam) 15-20% Energy Saving
(VS Electric Heating Tube)
Mainly used in industrial fields with energy saving requirements like
Lithium Battery Manufacturing.
PSL Low Energy Consumption
Desiccant Rotor
·Adopt special production process, the odor is removed after drying and
curing
Adsorbent
PSL is a new and low-temperature regeneration desiccant rotor,
which is compounded with inorganic silicate and organic
Adsorbate
hydrophilic material through complex technology.
Adsorbate It retains the adsorption capacity and VDW force which can keep
Physical Adsorption Chemisorption performance for a long cycle time.
PSL is suitable for low regeneration temperature
rangingfrom 40℃ to 60 ℃, the main feature is to make full
use of low-grade energy.
Full Heat
Exchanger
PSL-B 1:1
A Condenser Pre Filter
Regenerative Fan
Pre Filter
A Evaporator B1 Evaporator Processed Fan B2 Evaporator Natatorium
Water Heating
B Compressor
Heat Dissipation
B Condenser
① Post Evaporator + Regenerative Condenser
Driving motor controller for rotor Special data acquisition instrument for dehumidifier
Specially developed for rotor driving DC motor, convenient to adjust and The acquisition card contains interface of 4G and RS485, through which the
remote control. Equipped with DC motor controller, the rotor RPH can be collected data can be transmitted to PC for real-time monitoring and
directly displayed. The controller can automatically adjust RPH to 0.1rad/h analysis. reducing maintenance cost and improving after-sales service.
1.Display of airflow
Manufacturing
Visitors from different countries
Technical Support
As a company focusing on R&D and application, wve have a
professional team, technical personnel can provide online
technical support and on-site technical services. When
customers encounter problems during use, our team will
timely provide professional solutions to solve problems for
customers.
Lead Time
For common size rotor, we have over 2000
rotors in stock.
Thank You
DIFFENRENTIAL
PRESSURE
SWITCH
Symaro
Functions
Function diagram
Switching
state
XD = Switching difference
Dp = Pressure difference
W = Switching point high
Switching points
QBM9903-3
Switching
points high
[Pa]
1552D01_01
2
Siemens A6V10935160_en--_b
Building Technologies 2018-04-11
Switching points
QBM9903-5
Switching
points high
1552D02_01
[Pa]
1552D03_01
[Pa]
Technical design
The differential pressure switches QBM9903-.. consist of three parts:
● Housing and cover
● Trapezoidal bead diaphragm
● 1 sheet steel mounting bracket
The connection set supplied includes:
● 2 sensor tubes, straight
● 4 attachment screws
● Plastic tubing, 2 m long, dia. 5/8 mm
3
Siemens A6V10935160_en--_b
Building Technologies 2018-04-11
Technical design
The differential pressure between the two pressure connections actuates the spring-loaded
diaphragm. The trapezoidal bead diaphragm ensures the long-term stable switching points.
Type summary
Ordering
When ordering, please specify the quantity, name, type designation, and stock number.
The minimum order quantity is 100 items or a multiple thereof.
Example: 100 differential pressure switches QBM9903-3 S55720-S430
The accessories comprising a connection set are added.
Notes
Safety
CAUTION
Mounting
The mounting instructions are included with the differential pressure switch.
The differential pressure switch is intended for mounting in air ducts or on walls.
Vertical orientation is recommended, but any orientation is possible in principle.
Horizontal orientation changes the switching point of the differential pressure switch (see
"Commissioning [➙ 5]").
The pressure connection tubes can be any length. Tubing longer than 2 m increases the
response time.
Mount the differential pressure switch above the duct pressure connection points.. To
prevent condensation, route the tubing at a gradual incline from the sensor tubes to the
differential pressure switch.
Installation
WARNING
4
Siemens A6V10935160_en--_b
Building Technologies 2018-04-11
Commissioning
Set the desired switching point using the switching point setting knob [5] (see "Dimensions
[➙ 8]") under the cover.
Factory calibration occurs in vertical orientation. For horizontal orientation, note the change
of switching point, i.e. adjust the switching point as follows:
● Cover facing upward: Switching point is 11 Pa higher than scale.
● Cover facing downward: Switching point is 11 Pa lower than scale.
Disposal
5
Siemens A6V10935160_en--_b
Building Technologies 2018-04-11
Technical data
WARNING
Electrical interface
Switching system EPU, multi-layer contact
Contact rating AC/DC 24 V, ≥0.01 A
AC 250 V Max. 5 A res.
Max. 3 A ind., cos φ > 0.6
(0.8 A at 6-fold starting current, cos φ >
0.6)
Voltage against earth Max. AC 250 V
External supply line fusing ● Max. T 10 A non-renewable fuse or
● Max. C 13 A circuit breaker
Tripping characteristic B, C, D as per EN 60898
Switching differential Factory set
Reset Automatic
Service life > 1,000,000 switching cycles
Function data
Measuring range See "Type summary [➙ 4]"
Max. unilateral overload -30…75 °C 7500 Pa
-30…85 °C 5000 Pa
Permissible media Air, non-corrosive gases
Reproducibility for range 30…300 Pa <±2.5 Pa
50…500 Pa <±5 Pa
100…1000 Pa <±5 Pa
Setting accuracy ≤±15 %
Materials
Housing PC, fiber-glass reinforced
Cover PC
Diaphragm Silicone LSR, emission-free
Mounting bracket Steel-sheet
Sensor tubes ABS
Plastic tube PVC, soft
6
Siemens A6V10935160_en--_b
Building Technologies 2018-04-11
Ambient conditions
Temperature ranges:
● Operation ● –30... +85 °C
● Storage ● –40... +85 °C
Ambient humidity <90 % r.h., non-condensing
Fire classes
As per UL94
Pressure housing / Housing V-0
Cover HB
Plastic tube V-2
Sensor tubes HB
Weight
Device (1 item) 116 g
Connection set 1 item) 54 g
Weight (with packaging) (100 items) 18.5 kg
Connection diagrams
Connection diagram
1 = Phase
1 max. 13 A
2 2 = Switch position 1-2: Lower pressure
Dp 40692_01
7
Siemens A6V10935160_en--_b
Building Technologies 2018-04-11
Application examples
Dimensions
58,4
42
40 6
65
81
88
8
Siemens A6V10935160_en--_b
Building Technologies 2018-04-11
Sensor tube
9
Siemens A6V10935160_en--_b
Building Technologies 2018-04-11
Issued by © Siemens Switzerland Ltd, 2016
Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.
Building Technologies Division
International Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 724 2424
www.siemens.com/buildingtechnologies
10
Siemens A6V10935160_en--_b
Building Technologies 2018-04-11
Document ID A6V10935160_en--_b
Edition 2018-04-11
FCU
42CFS Series
42CFS
42CFS
400 2,000
4 motor
BLDC Motor for optional
o o o
*Norminal Capacity based on : EAT 80 Fdb / 67 Fwb, CHWT 44 / 54 F
190.0
E
D
F
B
60.0 A 270
C
D
E
190.0
F
G
60.0 A B
&)6:
&)6:
&)6:
&)6:
&)6:
&)6:
&)6:
&)6:
&)6:
&)6:
&)6:
&)6:
&)6:
&)6:
&)6:
&)6:
REM A RK ( * )
Ent./Lvg. Water Temp. at delta T = 10 F
&/@5=#JI/A./÷'/<I#4M#.?= ©ÇØØÏËغÎÇÏÒÇÔʲÚÊ
=R% ÚÎ ÚÎ ÕÕØ
¬Ò
"I#*/=!%-J3&>%>L!ô ªËÈÇØÇÚÔǸÕÇʱӨÇÔÍÔǺÇÏ YOUR CARRIER MAN :
I!&>%>/DI#*; ¨ÇÔÍÔǨÇÔÍÑÕѺÎÇÏÒÇÔÊ
K#/J+÷ ºËÒ¬ÇÞ
Carrier reserves the right to make changes in specifications without prior notice.
42CFS/12/19
THERMOSTAT
T6865 Series Large LCD Digital Thermostat
24 VAC
2-pipe fan coil control
Data sheet
Features
• Super modern appearance design, suitable
for office, hotel and residential building
• Slim design, direct installation on 86×86mm
box or 3×3inch box
• Stylish and elegant green/blue backlight with
white colour ring
• 2-pipe integrated into one unit with easy
configuration
• Big LCD display with English and icons
• Easy to install and set-up
• Time on/off function
Application • Selectable room temperature or setpoint
application of 3-speed fan and modulating valves • Manual or automatic fan speed selection
1
Mechanical design Fan Operation
Thermostat appearance
Temperature display
Time on/off
Heat/Cool/Vent
Backlight
2
Keypad lock Freezing protection mode
The default status of ‘Keypad Lock’ is all keys Freezing protection can be disabled (default) or
available and it can be changed in ISU mode. enabled. If freezing protection is enabled (It is not
Keypad lock has the following settings: available in cool only application) and thermostat is in
All keys are available (Default) OFF mode while the room temperature is below 6 ℃,
System button is locked out the thermostat will open heating device before the
Fan and System button are locked out temperature rises to 8℃.
All buttons are locked
Operating modes
The following operating modes are available:
Comfort mode
Installation:
3
• Drafts or dead spots behind doors and in corners
Terminal Designations • Hot or cold air from ducts
• Sunlight or radiant heat from appliances
No Terminal Description • Concealed pipes or chimneys
• Unheated/uncooled areas such as an outside wall
1 R 24VAC power
8 SB Remote setback
Wiring diagrams
Step 2
Push the Power box into the junction box.
4
Step 4 System Test System Status
Insert the cable into connector on circuit board of
thermostat.
Step 5
Align the 4 tabs on the Back cover with
corresponding slots on the back of the
thermostat, and then push it until the thermostat
snaps in place.
Installer set up
Press and simultaneously for 3 seconds to
enter ISU as below:
Press or to change settings
Press to advance to next function
Press and hold and buttons 3 seconds to exit
and save settings
Installer test
Follow the procedure below to test the heating and
cooling and fan system.
Number
Setting
System
test No.
System
status
5
Setup Function Settings & Options Troubleshooting Tips
6
BLACK WELDED
STEEL PIPE
INSULATION
BUTTERFLY
VALVE
GATE VALVE
CONTROL BALL
VALVES
Specification Sheet schneider-electric.com | 1
Actuator Specifications
Rated torque 10, 15, 20, 50 N-m Main Construction Materials
Operating Voltage Actuator Cover PC
BV -…A 24 Vac ± 15%, 24 Vdc ± 15% Actuator Housing ASTM B85 Pressure die-cast aluminum,
anti-corrosion coating
Frequency 50 Hz or 60 Hz
Agency Approvals and CE PED directive 2014/68 / EU
Power Requirements (24 V) EMC directive 2014/30 / EU
10 N-m Running 8 VA, max. 12 VA Low voltage directive 2014/35 / EU
15 N-m Running 10 VA, max. 12 VA Machinery directive 2006/42 / EC
20 N-m Running 15 VA max. 20 VA
50 N-m Running 27 VA, max. 30 VA
Valve Specifications
Timing
Default 60s / 90° Size DN15…DN150
Optional 30s / 90° Pressure
Sensitivity (proportional control only) 1.00% DN15…DN50 PN25
DN65…DN150 PN16
Dead zone 3%
Flow Characteristic Equal Percentage
Actuator location protection class IP65
Rangeability >100:1
Impedance (proportional control only)
Voltage input impedance > 100K Leakage Rate ≤0.01% Kvs
Current input impedance <0.125K Medium Temperature* -15…+120 °C
Load requirement (proportional control only) Connection Standard
Voltage output load > 1K DN15…DN50 Female threaded connection ISO 7/1
Current output load <0.5K DN65…DN150 Flanged connection ISO 7005-2
Control signal 2…10 Vdc, 4…20 mA Main Construction Materials
Feedback signal 2…10 Vdc, 4…20 mA Valve Body
Environmental DN15…DN50 Brass
Operational Temperature -15…+ 55 °C DN65…DN150 Ductile Iron
Shipping Temperature -25…+ 70 °C Valve Core and Stem Stainless Steel
Storage Temperature -15…+ 55 °C Sealing Ring FKM
Humidity ≤95% RH * When medium temperature in valve is below 0 °C such as refrigerant (R12, R22, R134a,
R202) glycol etc., valve stem should be protected by stem heater (type THOT) to avoid con-
nection parts of the valve body and stem from frosting and icing.
www.schneider-electric.com
© 2019 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March, 2019 tc
Document Number: F-28110-1
2 | schneider-electric.com Specification Sheet
Valve Principal
ce
an
rm To ensure excellent stable control in the HVAC system, the flow
rfo
Pe characteristics of the control valve should compensate for the non-linear
Coil
output characteristics of the heat exchanger. To achieve a linear heat
al output relationship between the heat exchanger and the valve, an equal
tu
Ac percentage flow characteristic is optimal.
Flow Rate
l%
ua
Eq
% Open
Control over the output
characteristics of the water system
Conventional ball valves that do not have the “V” type core will exhibit large
increases in flow with very little actuator travel. Heat transfer output is
directly affected and uncontrollable. The HVAC control system will hunt to
find the proper heat transfer output to satisfy the room temperature.
al
tu
Ac
all
al B
ition
Flow Rate
Trad
e
Vavl
% Open
Traditional ball valve flow
characteristics
Conventional ball valves are not suitable for temperature control for the
following reasons:
ut
ns
O
• Larger flow coefficient than equal percentage valves allow for coil
ra
tT
al
m
ea
rH
Th
l%
equal percentage flow curve. The new “V” type core is used, which not
Ac
ua
only greatly improves the valve’s rangeability but also matches the heat
Eq
Flow Rate
actuators, the valve is precisely controlled, eliminating the need for water
% Open pipe reductions to ensure good control.
Schneider Electric Ball valve
Characteristic
March, 2019 tc © 2019 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
Document Number: F-28110-1
Specification Sheet schneider-electric.com | 3
Assembly Ordering
BV 2 15 M A
Actuator Type
A: 24V
Dimensions
© 2019 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March, 2019 tc
Document Number: F-28110-1
4 | schneider-electric.com Specification Sheet
24V Proportional
2 3
Control
Signal
Valve
Position
Feedback
Wiring Instructions 2 3
OPEN CLOSE
1. Disconnect power to the actuator. Control
2. Open the top cover to the terminal: do not disassemble other components. Signal +
Feedback
3. − must be handled
Please check carefully before connecting the supply voltage, the product + and wired in accordance with
− Signal
safety requirements and regulations.
4. After wiring is completed replace cover.
24 V Floating
24V Proportional
2 3 2 3
CLOSE OPEN
Control
Signal + −
Valve
Position
Feedback
24V
DIP switch
DIP switch
2 3
2 3 Proportional
Proportional
Floating Dry Contact
Floating
OPEN CLOSE
FeedbackDry Contact
Terminals Feedback
OPEN CLOSE
Terminals
Control
Signal +
Feedback
− + − Signal
+DIP switch
RS485
March, 2019 tc © 2019 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
DIP switch Document Number: F-28110-1
RS485
24 V Floating
5 | schneider-electric.com Specification Sheet
Actuator Indicators
Indicator Lamp Normal (green)
Self-Stroking (orange)
LED Color Status Description
Error (red)
Green Steady Normal operating mode
Yellow Flicker (frequency~ 1Hz) Self-stroking mode of opera- No Power (not illuminated)
tion
Red light Flicker (frequency~ 2Hz) Error alarm Reset Button/Indicator Lamp
ON
OFF
DIP Switches 1 2 3 4 5 6 7 8 9 10
DIP Function Setting Description
S1 Control/Valve position feedback ON 20%: control/Starting point for the valve position feedback signal 20% (Suitable for con-
signal to set the starting point trol/Feedback signal 4…20mA or 2…10)
OFF 0: control/Starting point for the valve position feedback signal 0 (Suitable for control/
Feedback signal 0…20mA or 0…10)
S2 Control signal setting ON The control signal is a current type
OFF The control signal is a voltage type
S3 Impedance match control signal ON The control signal is a voltage type
OFF The control signal is a current type
S4 Feedback signal setting ON Valve position feedback signal is a current
OFF Valve position feedback signal is a voltage type
S5 Direct/Reverse Acting ON Direct Acting: When the control signal increases, the actuator to “1” Running direction
OFF Reverse Acting: When the control signal increases the actuator to “0” Running direction
S6 Mode setting off signal ON If the control signal is cut off, inside the actuator control automatically provides a mini-
mum signal
OFF 1) When the control signal is a voltage-type, if the control signal is cut off, inside the
actuator control automatically provides a maximum signal
2) When the control signal is a current-type, if the control signal is cut off, inside the
actuator control automatically provides a minimum signal
S7 Calibration/Self-Stroke ON Each time actuator is powered runs full stroke cycle
OFF Full stroke cycle only initiated via reset button
S8 Control mode (when S9 for ON Floating control
OFFTime)
OFF Modulating proportional control
S9 OFF Modulating and Floating control
S10 Actuator Speed setting ON 60s / 90°
OFF 30s / 90°
Application Notes
Ensure actuator is installed correctly to valve body.
1. Once the assembly is installed, connect power and control signal cable according to the wiring diagram.
2. Set DIP switches for the desired functionality (DIP switches can also be set while the actuator has power). On power up, the
selections take effect immediately (this step for the purpose of the actuator and valve body to match)
3. Turn on the power (DIP switches can be changed with power on).
a. If Calibration/Self-Stoke is set to ON (S7=ON), the actuator indicator lamp will flash yellow. The actuator will run to the
“OPEN” position (valve fully open), and then run to the “Close” position (valve fully closed). Once complete, the actuator
indicator lamp will change from flashing yellow to solid green. The actuator will now follow control signal.
b. If Calibration/Self-Stroke is set to OFF (S7=OFF), actuator will follow control signal.
Note: If actuator indicator lamp is flashing red, actuator will need to be reset. Press Indicator lamp button for >5 seconds to
initiate reset.
Note: Factory default setting is for automatic self-stroking (S7 is ON), i.e., each time after power off, the actuator will automatically
run a full stroke cycle.
March, 2019 tc © 2019 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
Document Number: F-28110-1
Specification Sheet schneider-electric.com | 6
© 2019 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March, 2019 tc
Document Number: F-28110-1
Y STRAINER
REV.07/02/20
3 80 240.0 182.0
Specifications
CLASS 150(10K) CAST BRONZE Y TYPE STRAINER SCREWED ENDS
End to End : KITZ STANDARD,End Connection : JIS B0203,Wall
Tchickness : KITZ STANDARD,Test Standard : KITZ STANDARD,Sizes :
21/2-inch(65-mm),,KITZ Fig : Y
BALANCING
VALVE
STAD
Balancing valves
DN 10-50, PN 25
IMI TA / Balancing valves / STAD
STAD
The STAD balancing valve delivers accurate hydronic performance
in an impressive range of applications. Ideally suited for use on
the secondary side in heating and cooling systems, and tap water
systems.
Key features
>> High accuracy for all settings >> Self-sealing measuring points
Ensure accurate balancing and flow For simple, accurate balancing.
reading.
>> AMETAL®
>> Handwheel Dezincification resistant alloy that
Equipped with a digital read-out, the guarantees a longer valve lifetime and
handwheel ensures accurate and lowers the risk of leakage.
straightforward balancing. Positive
shut-off function for easy maintenance.
Technical description
Media:
Water or neutral fluids, water-glycol
mixtures (0-57%).
2
Measuring points Draining
Measuring points are self-sealed. Remove the cap and insert the Valves with draining for G3/4 hose connection.
probe through the seal.
,
Sizing
When Δp and the design flow are known, use the formula to
calculate the Kv value or use the diagram.
Kv values
Turns DN 10 DN 15 DN 20 DN 25 DN 32 DN 40 DN 50
0.5 - 0.136 0.533 0.599 1.19 1.89 2.62
1 0.091 0.226 0.781 1.03 2.09 3.40 4.10
1.5 0.134 0.347 1.22 2.13 3.36 4.74 6.76
2 0.264 0.618 1.95 3.64 5.22 6.25 11.4
2.5 0.461 0.931 2.71 5.26 7.77 9.16 15.8
3 0.799 1.46 3.71 6.65 9.82 12.8 21.5
3.5 1.22 2.07 4.51 7.79 11.9 16.2 27.0
4 1.36 2.56 5.39 8.59 14.2 19.3 32.3
NOTE: In softwares (HySelect, HyTools) and balancing instrument (TA-SCOPE) the STAD, PN 25 version, is named STAD*.
Measuring accuracy
The zero position is calibrated and must not be changed. Fig. 1
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 *)
Fig. 2
2D 5D 2D 10 D
D = Valve DN
3
IMI TA / Balancing valves / STAD
Correction factors
The flow calculations are valid for water (+20°C). For other a flow deviation that increases with small valves, low settings
liquids with approximately the same viscosity as water and low differential pressures. Correction for this deviation can
(≤20 cSt = 3°E=100S.U.), it is only necessary to compensate for be made with the software HySelect or directly in our balancing
the specific density. However, at low temperatures, the viscosity instruments.
increases and laminar flow may occur in the valves. This causes
Setting
Setting of a valve for a particular pressure drop, e g To check the setting: Close the valve, the indicator shows 0.0.
corresponding to 2.3 turns on the graph, is carried out as Open it to the stop position. The indicator then shows the set
follows: value, in this case 2.3 (Fig. 2).
1. Close the valve fully (Fig 1). Diagrams showing the pressure drop for each valve size at
2. Open the valve 2.3 turns (Fig. 2). different settings and flow rates are available to help determine
3. Using a 3 mm Allen key, turn the inner spindle clockwise until the correct valve size and pre-setting (pressure drop).
stop.
4. The valve is now set. Four turns corresponds to fully opened valve (Fig. 3). Opening it
further will not increase the capacity.
Diagram example
Wanted: NOTE:
Presetting for DN 25 at a desired flow rate of 1,6 m3/h and a If the flow rate is out of the scale in the diagram, the reading can
pressure drop of 10 kPa. be made as follows:
Starting with the example above, we get 10 kPa, Kv=5.06 and
Solution: flow-rate 1.6 m3/h.
Draw a straight line joining 1,6 m3/h and 10 kPa. This gives At 10 kPa and Kv=0.506 we get the flow-rate 0.16 m3/h, and at
Kv=5,06. Now draw a horizontal line from Kv=5,06. Kv=50.6, we get 16 m3/h. That is, for a given pressure drop, it is
This intersects the bar for DN 25 which gives 2,44 turns. possible to read 10 times or 0.1 times the flow and Kv-values.
4
Diagram
10 100 0.1 1
70
2 7
50
40
5 0.2 2
4
4.5 30
3.5
4 25
1 3.5 3
20 4 0.3 3
3 3.5 2.5
15
4
2.5 3 0.4 4
3.5 2
10 3
2 2.5 0.5 5
4
0.5 3.5 2.5
7 3 1.5
2
1.5
0.4 4 2.5 2 0.7
5
3.5 1.5
4 1
3 2
0.3 1.5 1
1 1.0 10
3
2.5 0.5
2.5 4
3.5 1.5 1
0.2 2 2
0.7 0.5
1.5
1.5 3
4
3.5 1.5 0.5
0.5 2.0 20
1 1
0.45 2.5
0.4 3 1 2.5
0.1 0.7
0.35
2 0.5 3.0 30
0.3 0.5
0.5
2.5
0.25 0.4 4.0 40
1.5
0.3
0.2 5.0 50
2
0.05 0.25
1
0.2
0.15
0.04
0.15
1.5 0.5
0.03
0.1 0.1 10.0 100
1
0.07
0.02 0.07
15
0.05
NOTE: In softwares (HySelect, HyTools) and balancing instrument (TA-SCOPE) the STAD, PN 25 version, is named STAD*.
5
IMI TA / Balancing valves / STAD
Without drain
L Female threads.
D
Thread according to ISO 228. Thread length according to ISO 7/1.
With drain
L Female threads.
D
Thread according to ISO 228. Thread length according to ISO 7/1.
→ = Flow direction
Kvs = m3/h at a pressure drop of 1 bar and fully open valve.
*) Can be connected to smooth pipes by KOMBI compression coupling.
NOTE: In softwares (HySelect, HyTools) and balancing instrument (TA-SCOPE) the STAD, PN 25
version, is named STAD*.
With drain
L Male threads.
D Thread according to ISO 228. Thread length according to DIN 3546.
→ = Flow direction
Kvs = m3/h at a pressure drop of 1 bar and fully open valve.
NOTE: In softwares (HySelect, HyTools) and balancing instrument (TA-SCOPE) the STAD, PN 25
version, is named STAD*.
6
With smooth ends
L With drain
ØD
Smooth ends for connection to press coupling.
→ = Flow direction
Kvs = m3/h at a pressure drop of 1 bar and fully open valve.
NOTE: In softwares (HySelect, HyTools) and balancing instrument (TA-SCOPE) the STAD, PN 25
version, is named STAD*.
Accessories
Measuring point
Max 120°C (intermittent 150°C) L EAN Article No
AMETAL®/EPDM 44 7318792813207 52 179-014
103 7318793858108 52 179-015
Welding connection
Swivelling nut Valve D Pipe EAN Article No
Max 120°C DN DN
Brass/Steel 1.0045 (EN 10025-2) 10 G1/2 10 7318792748400 52 009-010
15 G3/4 15 7318792748509 52 009-015
20 G1 20 7318792748608 52 009-020
25 G1 1/4 25 7318792748707 52 009-025
32 G1 1/2 32 7318792748806 52 009-032
40 G2 40 7318792748905 52 009-040
50 G2 1/2 50 7318792749001 52 009-050
7
IMI TA / Balancing valves / STAD
Soldering connection
Swivelling nut Valve D Pipe Ø EAN Article No
Max 120°C DN
Brass/gunmetal CC491K (EN 1982) 10 G1/2 10 7318792749100 52 009-510
10 G1/2 12 7318792749209 52 009-512
15 G3/4 15 7318792749308 52 009-515
15 G3/4 16 7318792749407 52 009-516
20 G1 18 7318792749506 52 009-518
20 G1 22 7318792749605 52 009-522
25 G1 1/4 28 7318792749704 52 009-528
32 G1 1/2 35 7318792749803 52 009-535
40 G2 42 7318792749902 52 009-542
50 G2 1/2 54 7318792750007 52 009-554
Compression connection
D Max 100°C Valve D Pipe Ø EAN Article No
Brass/AMETAL® DN
Support bushes shall be used, for more 10 G1/2 8 7318793620002 53 319-208
information see catalogue leaflet FPL. 10 G1/2 10 7318793620101 53 319-210
10 G1/2 12 7318793620200 53 319-212
10 G1/2 15 7318793620309 53 319-215
10 G1/2 16 7318793620408 53 319-216
15 G3/4 15 7318793705006 53 319-615
15 G3/4 18 7318793705105 53 319-618
15 G3/4 22 7318793705204 53 319-622
8
Handwheel
Complete EAN Article No
Orange/grey 7318794043602 52 186-008
Identification tag
EAN Article No
7318792779206 52 161-990
Allen key
[mm] EAN Article No
3 Pre-setting 7318792836008 52 187-103
5 Draining 7318792836107 52 187-105
Insulation
For heating/cooling For L H D B EAN Article No
CFC-free polyurethane. Covered with grey DN
PVC. 10- 155 135 90 103 7318792839108 52 189-615
See catalogue leaflet “Prefab insulations” 20
for complete details. 25 175 142 94 103 7318792839306 52 189-625
32 195 156 106 103 7318792839504 52 189-632
40 214 169 108 113 7318792839702 52 189-640
50 245 178 108 114 7318792839900 52 189-650
9
FLEXIBLE
RUBBER JOINT
TWINFLEX Screwed Type
FLEXIBLE RUBBER JOINT
FEATURES
TWINFLEX Screwed Type Rubber Joint can afford large defletion that you can hardly imagine. It has various
functions and are highly reliable. Followings are the main features :
Withstandability
It can withstand a bursting pressure of over 5.39 MPa (55 kgf/cm2) and a maximum working pressure of
0.98 MPa (10 kgf/cm2) with the combination of excellent formative technique and strong chemical fibre.
Large Displacement Absorption for Eccentricity, Axial Movement and Angular Movement
Since it can absorb large displacement, TWINFLEX screwed type flexible rubber joint is most appropriate
for the protection of pipe line system. For example, it can prevent the destruction of connecting pipe due to
earthquake and subsidence of ground.
Highly Reliable
The packing parts are strengthened with steel reinforcing rings to prevent the rubber body from slipping out
of the fitting sides of flanges.
Convenient to install
When limited space is allowed for installation, the free type sockets can be screwed separately to pipe
before fitting in the joint.
APPLICATIONS
Vibration isolation for small pumps and circular pumps.
Sewage disposal purifier line.
Vibration isolation for air-conditioners and pipes.
STRUCTURE
No. Parts Materials
1 Flange-A FCD400
2 Flange-B FCD400
3 Nut SS400
4 Bolt SS400
5 Rubber Synthetic Rubber
6 Union Edge FCD400
7 Washer SS400
8 Reinforcing Cord Synthetic Fiber
TWFS-0105
Dimension and Allowable Movement
Size (mm) Allowable Movement (mm) Installation Allowance (mm)
Nominal Bore
A L l T.M. A.E. o
A.C. A.M.( ) T.M. A.E. A.C. A.M.( o )
15mm (1/2") 25 120 30 15 10 15 20 6 3 4 10
20mm (3/4") 25 120 30 15 10 15 20 6 3 4 10
25mm (1") 25 120 30 15 10 15 20 6 3 4 10
32mm (1 1/4") 40 175 35 20 10 20 30 8 3 6 10
40mm (1 1/2") 40 175 35 20 10 20 30 8 3 6 10
50mm (2") 50 175 40 20 10 20 30 8 3 6 10
T.M. = Transverse Movement
A.E. = Axial Elongation
A.C. = Axial Compression
A.M. = Angular Movement
Operating Condition
Notes
1. Information in the above table is for single displacement only. In case of complex displacement, follow the
below expression.
C.EL(C) = A.EL(C) x {1-(A.T.M.-T.M. x A.A.M.-A.M.)}
A.T.M. A.A.M.
C.EL(C) = Correct Elongation (Compression)
T.M. = Transverse Movement
A.EL(C) = Allowable Elongation (Compression)
A.A.M. = Allowable Angular Movement
A.T.M. = Allowable Transverse Movement
A.M. = Angular Movement
Ball Valves
Threaded ends to BS21 or solder joint ends.
CTH W.O.G. non-shock 4.14 MPa (600 psi), W.O.G. 150 ºC non-shock 0.69 MPa (100 psi)
TH W.O.G. non-shock 2.76 MPa (400 psi), W.O.G. 150 ºC non-shock 0.69 MPa (100 psi)
Materials
Parts Material
D
Body Brass
Body cap Brass
Stem Dezincification Resistant Brass
H Ball Brass*
Ball seat PTFE
O-ring FKM
*Nickel-Chrome Plated
Solder joint end valves should not be used in service
where the temperature of line fluid is higher than the
L softening point of solder.
Dimensions mm
inch 1/4 3/8 1/2 3/4 1 11/4 11/2 2 21/2 3
Nominal Size
mm 8 10 15 20 25 32 40 50 65 80
L 44 45 56 63 74 82 91 104 – –
Fig. TH Fig. CTH L1 Solder 47 47 54 73 88 98 113 135 147 177
• Threaded end to BS21 • Solder joint end to
H 41 41 45 48 54 58 63 74 89 103
ASME B16.18 D 60 60 80 80 110 110 110 140 200 300
*TH: 1/4 to 2
W.O.G. non-shock 2.76 MPa (400 psi), W.O.G. 150 ºC 0.69 MPa (100 psi)
Materials
Parts Material
D D1
Body Brass/Bronze*
Body cap Brass/Bronze*
Stem Dezincification Resistant Brass
H H1 Ball Brass**
Ball seat PTFE
O-ring FKM
*Size 4 only
**Nickel-chrome plated
L L
Dimensions mm
inch 1/4 3/8 1/2 3/4 1 11/4 11/2 2 21/2 3 4
Nominal Size
mm 8 10 15 20 25 32 40 50 65 80 100
Fig. T Fig. TT L 50 50 65 68 79 86 96 109 127 153 179
H 45 45 45 50 55 60 65 75 91 105 124
• Threaded end to BS21 • Threaded end to BS21
H1 41 41 44 48 55 61 66 80
Fig. AKT D 60 60 80 80 110 110 110 140 200 300 400
• Threaded end to ASME B1.20.1 D1 65 65 80 80 90 105 105 120
*TT: 1/4 to 2
W.O.G. non-shock 2.76 MPa (400 psi), W.O.G. 150 ºC 0.69 MPa (100 psi)
Materials
Parts Material
Body Brass
D
Body cap Brass
Stem Dezincification Resistant Brass
Ball Brass*
H Ball seat PTFE
O-ring FKM
*Nickel-chrome plated
Dimensions mm
inch 1/4 3/8 1/2 3/4 1
Nominal Size
mm 8 10 15 20 25
L 59 60 74 80 94
Fig. TO H 45 45 45 50 55
• Threaded end to BS21 D 60 60 80 80 110
27
THERMOMETER
Industrial Thermometers
DESIGN & OPERATION
Description
INDUSTRIAL THERMOMETERS
A thermometer is an instrument
designed to measure and indicate
the temperature of a specific
application or condition. An Industrial
Thermometer, commonly known as
a “Liquid-In-Glass” or Light-Powered
Digital Thermometer, is installed at the
point of measurement and is
usually read from that location.
Principles of Operation
Liquid-in-Glass
This thermometer is comprised of a
liquid-filled sealed glass tube and bulb,
which is affixed to the front of a metal
temperature scale, and extends into a
metal bulb chamber (stem). Flaked
graphite is used within the bulb chamber
to transfer the measured temperature to
the glass bulb. Temperature changes
cause the thermo-active fill to expand or
contract within the tube. This activity is
instantly visible in the tube against the
calibrated markings of the temperature
scale. For purposes of readability, the
tube is formed with a lens front to
create a magnified indicating column.
Light-Powered Digital
This thermometer is comprised of a
thermistor wire that extends into the
stem. Flaked graphite is used to transfer
the measured temperature to the
Liquid-in-Glass thermistor. Temperature change causes
a change in the output of the thermistor;
this output is translated through a
pre-programmed algorithm in the
microprocessor resulting in a digital
display of the temperature.
Selecting an Industrial
All Trerice Industrial Thermometers should be carefully selected to meet
the demands of the particular application. The information contained in
this catalog is offered only as a guide to assist in making the proper
selection. Improper applications may cause failure of the instrument,
resulting in possible personal injury or property damage. For applications
Light-Powered Digital where the process media may be corrosive or contained under pressure,
the use of a thermowell is required to prevent damage to the thermometer
and facilitate its removal from the process.
82
12950 W. Eight Mile Road • Oak Park, MI 48237-3288 • TEL:248/399-8000 • FAX: 248/399-7246 • www.TRERICE.com
Selecting an Industrial Thermometer (Liquid in-glass only)
INDUSTRIAL THERMOMETERS
Case
The case is durable, die cast aluminum with dark blue epoxy powder coating (Hydro-Therm is furnished with
Valox Case), and is available in scale sizes from 51/2 " through 12". Cases are available in adjustable angle,
rigid straight, and rigid 90° and 45° angle configurations. The adjustable angle case can be moved to any
viewing position for enhanced readability.
Stem
The stem is the sensitive portion of the instrument that is inserted into the process. Stems can be provided
in aluminum, brass, or stainless steel. Aluminum and brass stems include a brass coupling nut, while the
stainless steel stem includes a stainless steel coupling nut.
Aluminum stems must always be installed in a thermowell. Brass and stainless steel stems may be installed using a union
connection bushing in place of a thermowell. Trerice however, recommends the use of a thermowell to facilitate the removal
of the thermometer.
Window
Windows are supplied in clear acrylic (ranges through 300°F), or double-strength glass (standard on ranges
above 300°F).For direct sunlight applications, an ultraviolet protective plastic window is available. This window
helps prevent sunlight induced deterioration of thermoactive fills.
Accuracy
The accuracy of an industrial thermometer is expressed as a variance (plus or minus) in scale divisions.
All Trerice Industrial Thermometers are accurate to within one scale division of the temperature range.
Extreme ambient conditions above 120˚ F or below 30˚ F) may more than double the allowable accuracy tolerance of spirit filled
thermometers. This effect increases on thermometers operating at the high end of their scale, and decreases on thermometers
operating at the low end of their scale. Please consult factory for further information.
Thermoactive Fills
Trerice Industrial Thermometers are available with either of the following fill types:
• Spirit – A blue-colored, organic, spirit fill is standard. This proprietary fill is available for use with
temperatures of 500°F and below and can be supplied in alternate colors (consult factory).
• Mercury – Blue appearing mercury fill is only available for retort type thermometers as mercury
fill is specifically required.
Thermowells
For applications where the process media may be corrosive or contained under pressure, the use of a ther-
mowell is required to prevent damage to the thermometer and facilitate its removal from the process.
Thermowells are available in various lengths, connections, sizes, and materials. Please consult the
Thermowell Section of this catalog.
To ensure minimum response time, Trerice Heat Transfer Paste should be applied to the sensing portion of the stem
before installation into a thermowell. 1 oz. tube: Item No. 107-0001
83
12950 W. Eight Mile Road • Oak Park, MI 48237-3288 • TEL:248/399-8000 • FAX: 248/399-7246 • www.TRERICE.com
Econo-Therm
INDUSTRIAL THERMOMETERS
96
12950 W. Eight Mile Road • Oak Park, MI 48237-3288 • TEL:248/399-8000 • FAX: 248/399-7246 • www.TRERICE.com
Econo-Therm
All dimensions are nominal.
Dimensions in [ ] are in millimeters.
INDUSTRIAL THERMOMETERS
AIR-DUCT STEM
1.33 .82
[34] [21]
Ø.50
[13]
6.69
[170]
Ø.25
- 3 HOLES
Ø2.50 EQUALLY
[Ø64] SPACED
1.42
[36] U
.88 [22]
1.62
HEX
[41]
Ø1.50
[Ø38]
U
AIR-DUCT STEM
MOUNTING DIMENSIONS
Ø.53
[14]
Note: Shown with required thermowell (must be ordered separately. Refer to page 153.)
U Length Dimension
2" (Aluminum) 1.31 [33.3]
4" (Brass) 3.25 [82.6]
6" (Air-Duct) 6.00 [152.4]
12" (Air-Duct) 12.00 [304.8]
Standard Ranges
Fahrenheit Scale Celsius Scale Dual Scale Fahrenheit Celsius
Range Range Range Figure Minor Figure Minor
Code Range Code Range Code Range Intervals Divisions Intervals Divisions
01 –40° to 110°F 17 –40° to 40°C 41 –40° to 110°F & –40° to 40°C 20° 2° 10° 1°
03 30° to 130°F 25 0° to 55°C 43 30° to 130°F & 0° to 55°C 10° 1° 5° 1°
06 30° to 180°F 27 0° to 83°C 46 30° to 180°F & 0° to 83°C 20° 2° 10° 1°
07 30° to 240°F 19 0° to 115°C 47 30° to 240°F & 0° to 115°C 20° 2° 10° 1°
08 30° to 300°F 20 0° to 150°C 48 30° to 300°F & 0° to 150°C 30° 5° 10° 2°
09 50° to 400°F 28 10° to 205°C 49 50° to 400°F & 10° to 205°C 50° 5° 20° 2°
13 200° to 500°F 32 93° to 260°C 53 200° to 500°F & 93° to 260°C 25° 5° 10° 2°
Dual scale figure intervals may differ.
97
12950 W. Eight Mile Road • Oak Park, MI 48237-3288 • TEL:248/399-8000 • FAX: 248/399-7246 • www.TRERICE.com
Thermowells
All dimensions are nominal.
Dimensions in [ ] are in millimeters.
for 4350 Econo Thermometers
THERMOWELLS
(A)
STEM (A)
LENGTH STEM
LENGTH
.75
Ø.410 Ø.410
[19] LOCKING
[10] (P) [10]
.44 SET
SCREW EXTERNAL
[11] THREAD
LOCKING U
SET LENGTH Ø.53 Ø.53
SCREW 1.31 [33] [13] [13]
.44 (T)
(P) 1.00 U
EXTERNAL [11] [25]
LAGGING LENGTH
THREAD EXTENSION 1.25 [32]
1.81 [46]
Standard
4” Stem Length
(A)
STEM
LENGTH
.87
[22]
Ø.440
.44 [11]
[11]
Alternative materials and accessories are also available. Please consult the Options and Accessories Section for details.
Selection of the proper thermowell is the sole responsibility of the user. Temperature and pressure limitations must be considered.
Improper application may cause failure of the thermowell, resulting in possible personal injury or property damage.
Thermowell Style (P) External Thread (A) Stem Length (T) Lagging Extension Material
3- Econo 3 1/2 NPT C 2" Stem C 13/4 Extension (4" Stem only) 2 Brass
4 3/4 NPT G 4" Stem Omit if None 3 Steel
5 304SS
6 316SS
153
12950 W. Eight Mile Road • Oak Park, MI 48237-3288 • TEL:248/399-8000 • FAX: 248/399-7246 • www.TRERICE.com
PRESSURE
GAUGE
Pressure Gauges
DESIGN & OPERATION
Description
A pressure gauge is a mechanical
PRESSURE GAUGES
CASE
RING
Principles of Operation
Most Trerice Pressure Gauges are constructed
with a bourdon tube sensing element. When
WINDOW
SEAL
Case
Cases are available in a wide variety of materials and
All Trerice Pressure Gauges should be
Under normal operating conditions, only the tube and socket assembly (Wetted Parts) of a pressure gauge
will come into contact with the fluid being measured (Pressure Medium). The selection of the assembly will be
determined by the composition of the medium. Air, gas, steam, water and other non-corrosive media are usually
satisfied by a bronze or brass bourdon tube and brass socket assembly. Stainless steel or Monel wetted parts are
used when the medium contains corrosive elements or when high operating pressures or temperatures will be
encountered. A diaphragm seal is recommended for highly corrosive media or that which may solidify or deposit
solids within the tube and socket assembly of the gauge. (See the Diaphragm Seal section of this catalog.)
4
12950 W. Eight Mile Road • Oak Park, MI 48237-3288 • TEL:248/399-8000 • FAX: 248/399-7246 • www.TRERICE.com
Connection and Mounting
The socket connection provides an entrance port for the process medium as well as a means to mount
the gauge to a pipeline or vessel. Male connections can be provided with NPT, BSPT, or other thread styles,
PRESSURE GAUGES
in sizes from 1/8" through 1/2". A high-pressure, 9/16" LHT connection is also available. The mounting location
indicates where the connection protrudes from the case. Trerice Pressure Gauges are available with three
standard mounting locations: lower male (LM), lower back male (LBM), and center back male (CBM).
Other connection locations may be available on some models.
Pointer
There are essentially three types of pointers available on Trerice Pressure Gauges: a micro-adjustable
pointer (providing high quality and accuracy); a friction-type pointer (providing adjustability and durability);
and a plain, non-adjustable pointer (providing economic reliability).
Accuracy
The accuracy of a pressure gauge is expressed as a percentage (plus or minus) of the maximum scale
range. Please refer to Pressure Gauge Standard ASME B40.100.
The maximum operating pressure of the application should not exceed 75% of the
shut-down, system pres-
measurement range selected. Therefore, the specified range should be twice the
sures can greatly exceed
normal operating point of the gauge to avoid damage to the gauge internal. A wide
intended conditions.
psi pressure. Ranges are indelibly presented in black figures and markings upon
protected by appropriate
Environmental Conditions
Pressure gauge selection will be influenced by the environmental conditions
Pressure gauges provide an
Liquid Filling
closed loop systems, a safety
relief device must be used.
Liquid filling (glycerin, silicone or other fills) can prolong the life of a pressure
gauge by minimizing wear on the gauge internal resulting from vibration or
oscillation. Liquid filling also acts as a permanent lubricant to the moving parts
of the instrument.
5
12950 W. Eight Mile Road • Oak Park, MI 48237-3288 • TEL:248/399-8000 • FAX: 248/399-7246 • www.TRERICE.com
D80 Series
Dry or Liquid Filled • Stainless Steel Case
Specifications
Models Wetted Parts
D82B
D82LFB
(dry) Bronze tube,
(liquid filled) brass socket
UTILITY GAUGES
Lead-Free (PBF)
Meets NSF/ANSI
Standards 372 and 61
D83SS
D83LFSS
(dry) 316 Stainless steel
(liquid filled) tube & socket
Window Acrylic
14
12950 W. Eight Mile Road • Oak Park, MI 48237-3288 • TEL:248/399-8000 • FAX: 248/399-7246 • www.TRERICE.com
D80 Series
All dimensions are nominal. Dimensions in [ ] are in millimeters.
Dry or Liquid Filled • Stainless Steel Case
Standard Ranges
psi Ranges (A) D82 D83
UTILITY GAUGES
Range Specific Range Figure Minor Figure Minor
Code (psi) Intervals Divisions Intervals Divisions
010 30" Hg to 0 5 0.5 5 0.5
020 30" Hg to 15 psi 10/5 1/0.5 10/5 1/0.5
030 30" Hg to 30 psi 10/5 1/1 10/5 1/1
040 30" Hg to 60 psi 10/10 2/1 10/10 2/1
050 30" Hg to 100 psi 30/20 2/2 30/20 2/2
060 30" Hg to 150 psi 30/30 5/2 30/30 5/2
070 30" Hg to 300 psi 30/50 5/5 30/50 5/5
080 0 to 15 psi 3 0.2 3 0.2
090 0 to 30 psi 5 0.5 5 0.5
100 0 to 60 psi 10 1 10 1
110 0 to 100 psi 10 1 10 1
120 0 to 160 psi 20 2 20 2
130 0 to 200 psi 20 2 20 2
140 0 to 300 psi 50 5 50 5
150 0 to 400 psi 50 5 50 5
160 0 to 600 psi 100 10 100 10
180 0 to 1000 psi 100 20 100 20
190 0 to 1500 psi 300 20 300 20
200 0 to 2000 psi 200 20 200 20
210 0 to 3000 psi 500 50 500 50
1.18 [30]
220 0 to 5000 psi 1000 100 1000 100
Ranges over 5000 PSI are not available on D82LFB.
Dial Size C E F J M
11/2" D82 1.85 [47] 1.50 [38] 0.32 [8] 1.06 [27] 1.61 [41]
11/2" D83 1.85 [47] 1.50 [38] 0.32 [8] 1.06 [27] 1.61 [41]
2" D82 2.28 [58] 1.89 [48] 0.39 [10] 1.14 [29] 2.05 [52]
2" D83 2.28 [58] 2.05 [52] 0.35 [9] 1.18 [30] 2.05 [52]
21/2" D82 2.68 [68] 2.24 [57] 0.39 [10] 1.18 [30] 2.44 [62]
21/2" D83 2.68 [68] 2.32 [59] 0.51 [13] 1.38 [35] 2.44 [62]
4" D82 4.29 [109] 3.07 [78] 0.47 [12] 1.42 [36] 3.90 [99]
4" D83 4.29 [109] 3.94 [100] 0.75 [19] 1.93 [49] 3.94 [100]
15
12950 W. Eight Mile Road • Oak Park, MI 48237-3288 • TEL:248/399-8000 • FAX: 248/399-7246 • www.TRERICE.com
AIR VENT
The UL Series
Universal Air Release Valves
Compound Lever System
NPT Screwed or ANSI Class Flanges
Available
sales@crispinvalve.com
Universal Air Release
Valves
Universal Air Release Valve
Valve With Stainless Steel Trim or
T
Functio Bronze and Stainless Steel
UL SERIES
n Trim
• Allows air to escape he Universal Air Valve is designed to permit the automatic
a pipeline as it is escape of large quantities of air from a pipeline when the line
being filled is being filled, and to permit air to enter the pipeline when the
line is being emptied. It also allows accumulating air to escape
• Allows air to enter while the line is in operation and under pressure. This is accom-
a pipeline as it is plished with a compound lever system functioning in conjunction
being emptied with a large and small orifice in one integral body casting.
As the liquid rises into the valve, air escapes through the large
• Allows accumulating orifice to the atmosphere. Liquid entering the valve raises the float
air to escape while a and lever system, carrying with it the pressure plunger and the
line is in operation main valve.
and under pressure When the liquid has raised the float to its limit, the stainless
steel main valve rests against the seat. The pressure plunger also
Features rests against its seat, which is the main valve. In this position, the
valve is closed and no liquid can escape.
Include
• Meets AWWA
C-512
Air & Vacuum
• Compound lever Orifice
system Performance
• NPT screwed or ANSI Curves
Class Flanges
UL SERIES
line is in operation and
under pressure, it will
displace the liquid at the
top of the valve body and
the float will drop as the
For 6” and 8” liquid recedes. As this
dimension and weight occurs, the pressure valve
information, will open, permitting the
see the following page.
escape of the accumulated
Model Information air, after which the liquid
Size of Valve 1” 2” 3” 4” 6” 8” level will rise and the
Model No. UL10.1 UL20.1 UL30.1 UL40.1
valve will close.
Screwed Inlet UL10 UL20 UL30 UL40 Should the pipeline be
125#
UL21.1 UL31.1 UL41.1 drained through natural
Flanged Inlet UL21 UL31 UL41 C61 C81
processes or should a large
250#
UL22.1 UL32.1 UL42.1
break develop, the float
Flanged Inlet UL22 UL32 UL42 C62 C82
will drop all the way down
Discharge in SCFM as the liquid level drains
Operating ORIFICE SIZE from the valve body. The
Pressure valve will then stay in the
(PSIG) 3/32” 1/8” 5/32” 3/16” 1/4”
full open position permit-‐‑
150 13.8 24.4 37.9 54.6 98
ting the entrance of air
200 17.9 31.9 49.5 72 127
and eliminating the dan-‐‑
250 22.1 39.2 61.1 88 157
300 26.4 46.7 73 105 187 ger of pipeline collapse
due to vacuum.
Orifice Sizing These cycles will
Valve Information
MAXIMUM OPERATING PRESSURE IN PSI repeat automatically as
Size Max. 150 Max. 200 Max. 250 Max. 300 each condition presents
1” 3/16” 3/32” 3/32” 3/32” itself, and the valve will
2” 1/4” 3/16” 3/16” 1/8” function satisfactorily
3” 1/4” 3/16” 3/16” 1/8” with hot or cold water,
4” 1/4” 3/16” 3/16” 1/8” and in the presence of
6” 1/4” 3/16” 3/16” 1/8” many chemicals and oil-‐‑
8” 1/4” 3/16” 3/16” 1/8” base liquids.
3
Submittal Sheet for Crispin UL
Series
Universal Air Release Valve
Universal Valves
Parts List: 1”–4” Valves Dimensions and Weights
UL SERIES
PART ITEM MATERIAL MODEL INLET TRIM HEIGHT WIDTH LENGTH WT(LBS)
NO. UL10 1” NPT S/S 10 1/4” 6 7/8” 9 3/4” 27
1P* PROTECTOP Cast Iron
UL10.1 1” NPT S/S/BRASS 10 1/4” 6 7/8” 9 3/4” 27
1S* TOP Cast Iron
UL20 2” NPT S/S 13 1/2” 8 3/8” 12 3/8” 72
2 FLANGE Cast Iron
UL20.1 2” NPT S/S/BRASS 13 1/2” 8 3/8” 12 3/8” 72
3* BODY, SCREWED Cast Iron UL21 2” 125# Flg. S/S 17” 8 3/8” 12 3/8” 74
3F* BODY, 125 LB FLG. Cast Iron UL21.1 2” 125# Flg. S/S/BRASS 17” 8 3/8” 12 3/8” 74
3FH* BODY, 250 LB FLG Cast Iron UL22 2” 250# Flg. S/S 17 1/4” 8 3/8” 12 3/8” 75
4 A&V FULCRUM Stainless Steel UL22.1 2” 250# Flg. S/S/BRASS 17 1/4” 8 3/8” 12 3/8” 75
5&16 PRESSURE FULCRUM Stainless Steel UL30 3” NPT S/S 17 1/4” 10 1/4” 14 3/4” 111
6 VALVE LEVER Stainless Steel UL30.1 3” NPT S/S/BRASS 17 1/4” 10 1/4” 14 3/4” 111
7 LINK Stainless Steel UL31 3” 125# Flg. S/S 20 5/8” 10 1/4” 14 3/4” 131
8 BALL LEVER Stainless Steel UL31.1 3” 125# Flg. S/S/BRASS 20 5/8” 10 1/4” 14 3/4” 131
9 BALL FLOAT Stainless Steel UL32 3” 250# Flg. S/S 21” 10 1/4” 14 3/4” 133
10 BALL FULCRUM Stainless Steel UL32.1 3” 250# Flg. S/S/BRASS 21” 10 1/4” 14 3/4” 133
13 NUT Stainless Steel UL40 4” NPT S/S 20” 11 3/4” 16 3/4” 163
14 PRESSURE VALVE Rubber/S/S UL40.1 4” NPT S/S/BRASS 20” 11 3/4” 16 3/4” 163
PLUNGER UL41 4” 125# Flg. S/S 23” 11 3/4” 16 3/4” 180
15 PRESSURE SEAT Stainless Steel UL41.1 4” 125# Flg. S/S/BRASS 23” 11 3/4” 16 3/4” 180
17 SEAT CAGE Stainless Steel UL42 4” 250# Flg. S/S 23 5/16” 11 3/4” 16 3/4” 183
18 A&V SEAT Rubber UL42.1 4” 250# Flg. S/S/BRASS 23 5/16” 11 3/4” 16 3/4” 183
21 PRESS LIMIT STOP Stainless Steel C61 6” 125# Flg. S/S 16 1/4” 15” 22 7/8” 198
23 BEARING PIN Stainless Steel C62 6” 250# Flg. S/S 16 3/4” 15” 22 7/8” 222
23A BEARING PIN Stainless Steel C81 8” 125# Flg. S/S 18 1/8” 17 3/4” 25 3/8” 290
24 BEARING PIN Stainless Steel C82 8” 250# Flg. S/S 18 5/8” 17 3/4” 25 3/8” 320
25 BEARING PIN Stainless Steel
26 PIN CLIP Stainless Steel
28 SCREW Stainless Steel
29 DRAIN PLUG Steel
30 FULCRUM WASHER Fibre
31 FULCRUM WASHER Fibre
32 FLANGE GASKET Armstrong
33 FLANGE BOLT Steel
34 FLANGE NUT Steel
35 A&V FULCRUM NUT Steel
36 BALL FULCRUM NUT Steel
Orifice A
Size 24
23A
23 16
Specifications
MODEL INLET SIZE OUTLET SIZE A B WHT. 34 7 6 12 3
8 3W
UL10 1” NPT 1” NPT 9.75 10.75 27 25
UL10.1 1” NPT 1” NPT 9.75 10.75 27 25
B
25 9
Parts
ITEM
1S TOP
List CAST
DESCRIPTION MATERIAL
IRON
ASTM
A126 CL.B
2 FLANGE CAST IRON A126 CL.B
3 BODY CAST IRON A126 CL.B
3W LOCK WASHER STAINLESS STEEL A240
4 AIR & VAC FULCRUM STAINLESS STEEL A240
**6 VALVE LEVER STAINLESS STEEL A582
7 LINK STAINLESS STEEL A240
8 BALL LEVER STAINLESS STEEL A240 Specifications
9 FLOAT STAIN LESS STEEL A240
10 BALL FULCRUM STAINLESS STEEL A582 The valve(s) shall be installed at the high points in the system or
11 VALVE PLUNGER STAINLESS STEEL A193 at points selected by the engineer. This will permit discharging the
& BUNA-N RUBBER surge of air from an empty line when filling, and relieve the vacu-
12 PLUNGER NUT STAINLESS STEEL A194 um when draining the system. The valve(s) shall also release an
15 PRESSURE SEAT STAINLESS STEEL A582 accumulation of air when the system is under pressure. This shall
16 PRESSURE FULCRUM STAINLESS STEEL A240 be accomplished in a single valve body.
17 SEAT CAGE STAINLESS STEEL A240 The valve(s) shall operate through a compound lever system
18 AIR & VAC SEAT BUNA—N RUBBER N/A which will seal both the pressure orifice and the air and vacuum
23 BEARING PIN STAINLESS STEEL A582 orifice simultaneously. This lever system shall permit a
23A BEARING PIN STAINLESS STEEL A582 ” orifice to release an accumulation of air from the
24 BEARING PIN STAINLESS STEEL A582 valve body at a capacity of SCFM of air and pres-
25 BEARING PIN STAINLESS STEEL A582 sure of PSIG.
26 COTTER PIN STAINLESS STEEL A313
The function of the lever system shall also permit a positive dis-
29 DRAIN PLUG BRASS B505
engagement of the main valve from the large orifice, as the float
30 FULCRUM WASHER FIBER N/A
drops and pressure decreases. The disengagement shall be
32 FLANGE GASKET ARMSTRONG N—8092 N/A
immediate and not limited to the initial draw of a vacuum.
33 FLANGE BOLT STEEL A307
34 NUT STEEL A563 The valve(s) shall be Crispin Model Universal Air
50 INTERFERENCE PIN STAINLESS STEEL A582 Valve as manufactured by Multiplex Manufacturing Co., Berwick,
PA. The valve(s) shall be ” NPT screwed or ANSI
Class (125, 250) flanged inlet connection, and shall have a cast
iron body, top and inlet flange (where required), stainless steel
** Material for UL10.1 will be brass float and trim with Buna-N seat. Valves which operate the pres-
sure plunger via a single lever and fulcrum will not be acceptable.
Option: A protectop will be supplied to prevent debris from entering the outlet of the valve.
Option: (Where pressures are greater than 300 PSIG), the valve(s) shall be ANSI Class flanged inlet connection, and shall
have a (steel, stainless steel, or ductile iron) body, top and inlet flange.
Standard operating pressure for Crispin Air Valves is 20 to 150 PSIG. Please check one of the following if your operating needs differ:
2 to 40 PSIG 151 to 300 PSIG
5
Submittal Sheet for Crispin UL Series
Orifice Options
SUBMITTAL SHEET FOR UL SERIES
33 30
36 10 1S
18 50 2
DIAMETER MAX. PRESSURE DISCHARGE RATE
7 11
1/4” 150 PSIG 98 SCFM
4A
32 3/16” 250 PSIG 88 SCFM
34 6
13W 23 15 5B 1/8” 300 PSIG 46.7 SCFM
23B
Size Specifications
26 25 16 17 23B
26 12
3 23B
8
21
B
24 MODEL INLET SIZE OUTLET SIZE A B C WHT.
9A UL20 2” NPT 2” NPT 12.50 13.50
72
9
C
UL20.1 2” NPT 2” NPT 12.50 13.50
72
*UL21 2” 125# FLG 2” NPT 12.50
17.00 78
UL21.1 2” 125# FLG 2” NPT 12.50
17.00 78
29 UL22 2” 250# FLG 2” NPT 12.50
17.25 89
UL22.1 2” 250# FLG 2” NPT 12.50
17.25 89
* Includes ANSI Class 125 or 250 Companion FLG and NPL
CP1
CP2 Parts List
ITEM DESCRIPTION MATERIAL ASTM
Specifications
1S TOP CAST IRON A126 CL.B
2 FLANGE CAST IRON A126 CL.B
The valve(s) shall be installed at the high points in the system or at points 3 BODY CAST IRON A126 CL.B
selected by the engineer. This will permit discharging the surge of air from 4A CAP SCREW STAINLESS STEEL A193
an empty line when filling, and relieve the vacuum when draining the sys- 5B AIR & VAC FULCRUM STAINLESS STEEL A240
tem. The valve(s) shall also release an accumulation of air when the sys- **6 VALVE LEVER STAINLESS STEEL A582
tem is under pressure. This shall be accomplished in a single valve body. 7 LINK STAINLESS STEEL A240
8 BALL LEVER STAINLESS STEEL A240
The valve(s) shall operated through a compound lever system which 9 FLOAT STAINLESS STEEL A240
will seal both the pressure orifice and the air and vacuum orifice simul- 9A FLOAT ROD STAINLESS STEEL A582
taneously. This lever system shall permit a ” orifice to 10 BALL FULCRUM STAINLESS STEEL A582
release an accumulation of air from the valve body at a capacity of 11 VALVE PLUNGER STAINLESS STEEL A193
SCFM of air and pressure of PSIG. & BUNA-N RUBBER
12 PLUNGER NUT STAINLESS STEEL A194
The function of the lever system shall also permit a positive disen- 13W LOCK WASHER STAINLESS STEEL A240
gagement of the main valve from the large orifice, as the float drops and 15 PRESSURE SEAT STAINLESS STEEL A582
pressure decreases. The disengagement shall be immediate and not 16 PRESSURE FULCRUM STAINLESS STEEL A240
limited to the initial draw of a vacuum. 17 SEAT CAGE STAINLESS STEEL A240
The valve(s) shall be Crispin Model Universal Air Valve as man- 18 AIR & VAC SEAT BUNA—N RUBBER N/A
ufactured by Multiplex Manufacturing Co., Berwick, PA. The valve(s) shall 21 PRESSURE LIMIT STOP STAINLESS STEEL A240
be ” NPT screwed or ANSI Class (125, 250) flanged inlet connec- 23 BEARING PIN STAINLESS STEEL A582
tion, and shall have a cast iron body, top and inlet flange (where required), 23A BEARING PIN STAINLESS STEEL A582
stainless steel float and trim with Buna-N seat. Valves which operate the 23B BEARING PIN STAINLESS STEEL A582
pressure plunger via a single lever and fulcrum will not be acceptable. 24 BEARING PIN STAINLESS STEEL A582
25 BEARING PIN STAINLESS STEEL A582
Option: A protectop will be supplied to prevent debris from entering the 26 COTTER PIN STAINLESS STEEL A313
outlet of the valve. 29 DRAIN PLUG BRASS B505
30 FULCRUM WASHER FIBER D710
Option: (Where pressures are greater than 300 PSIG), the valve(s) shall
be ANSI Class flanged inlet connection, and shall have a 32 FLANGE GASKET ARMSTRONG N—8092 N/A
(steel, stainless steel, or ductile iron) body, top and inlet flange. 33 FLANGE BOLT STEEL A307
34 NUT STEEL A563
All Crispin Valves are hydrostatically tested at 150% of their maximum 36 BALL FULCRUM NUT STEEL A563
working pressure. Standard operating pressure for Crispin Air Valves is 50 INTERFERENCE PIN STAINLESS STEEL A582
20 to 150 PSIG. Please check one of the following if your operating
FLAN G E CO N N ECTIO N PARTS
needs differ: 2 to 40 PSIG 151 to 300 PSIG
CP1 NIPPLE STEEL A53
** Material for UL2_.1 will be brass CP2 COMPANION FLANGE CAST IRON A126 CL. B
6
UL
Submittal Sheet for Crispin UL
Series
3”–4” Universal Air Release
Valve
Manufactured in compliance with ANSI/AWWA C512 Date: October, 2001
Orifice Options A
Size Specifications 30
7 13W
12
23 4A
4
MODEL INLET SIZE OUTLET SIZE A B C WHT. 10 23A
UL30 3”NPT 3” NPT 14.75 18.00
114 25 25
8
B
UL31 3” 125# FLG 3” NPT 14.75
20.50 125 5
21 9A
UL32 3” 250# FLG 3” NPT 14.75
21.00 131 23
C
UL30.1 3” NPT 3” NPT 14.75 18.00
114 21
Parts
ITEM
1S TOP
ListMATERIAL
DESCRIPTION
CAST IRON
ASTM
A126 CLB Specifications
2 FLANGE CAST IRON A126 CLB
3 BODY CAST IRON A126 CLB The valve(s) shall be installed at the high points in the system or at points
4 AIR/VAC FULCRUM STAINLESS STEEL A240 selected by the engineer. This will permit discharging the surge of air from
4A FULCRUM BOLT STAINLESS STEEL A193 an empty line when filling, and relieve the vacuum when draining the sys-
5 PRESSURE FULCRUM STAINLESS STEEL A240 tem. The valve(s) shall also release an accumulation of air when the sys-
**6 VALVE LEVER STAINLESS STEEL A582 tem is under pressure. This shall be accomplished in a single valve body.
7 LINK STAINLESS STEEL A240
8 BALL LEVER STAINLESS STEEL A240 The valve(s) shall operate through a compound lever system which will
9 FLOAT STAINLESS STEEL A240 seal both the pressure orifice and the air and vacuum orifice simultane-
9A FLOAT ROD STAINLESS STEEL A582 ously. This lever system shall permit a ” orifice to release an
10 BALL FULCRUM STAINLESS STEEL A582
accumulation of air from the valve body at a capacity of
11 VALVE PLUNGER STAINLESS STEEL& A193/D2000 SCFM of air and pressure of PSIG.
BUNA-N RUBBER
12 PLUNGER NUT STAINLESS STEEL A194 The function of the lever system shall also permit a positive disengage-
13W LOCK WASHER STAINLESS STEEL A240
ment of the main valve from the large orifice, as the float drops and pres-
15 PRESSURE SEAT STAINLESS STEEL A582
17 SEAT CAGE STAINLESS STEEL A240 sure decreases. The disengagement shall be immediate and not limited
18 AIR & VAC SEAT BUNA-N RUBBER D2000 to the initial draw of a vacuum.
21 PRESSURE LIMIT STOP STAINLESS STEEL A240 The valve(s) shall be Crispin Model Universal Air Valve as
23 BEARING PIN STAINLESS STEEL A582
23A BEARING PIN STAINLESS STEEL A582 manufactured by Crispin-Multiplex Manufacturing Co., Berwick, PA. The
24 BEARING PIN STAINLESS STEEL A582 valve(s) shall be ” NPT screwed or ANSI Class (125, 250)
25 BEARING PIN STAINLESS STEEL A582 flanged inlet connection, and shall have a cast iron body, top and inlet
26 COTTER PIN STAINLESS STEEL A313 flange (where required), stainless steel float and trim with Buna-N seat.
29 DRAIN PLUG BRASS B505 Valves which operate the pressure plunger via a single lever and fulcrum
30 FULCRUM WASHER FIBER D710 will not be acceptable.
31 FULCRUM WASHER FIBER D710
31A FULCRUM WASHER FIBER D710 Option: A protectop will be supplied to prevent debris from entering the
32 FLANGE GASKET ARMSTRONG N-8092 N/A outlet of the valve.
33 FLANGE BOLT STEEL A307
34 NUT STEEL A563 Option: (Where pressures are greater than 300 PSIG), the valve(s) shall
35 AIR/VAC FULCRUM NUT STEEL A563 be ANSI Class flanged inlet connection, and shall have a
36 BALL FULCRUMNUT STEEL A563 (steel, stainless steel, or ductile iron) body, top and inlet flange.
37 ADJUSTING PLATE STAINLESS STEEL A240
38 BOLT STAINLESS STEEL A193 Standard operating pressure for Crispin Air Valves is 20 to 150 PSIG.
50 INTERFERENCE PIN STAINLESS STEEL A582 Please check one of the following if your operating needs differ:
** Material for UL30.1, UL.31.1, UL40.1, UL41.1, UL42.1 will be brass 2 to 40 PSIG 151 to 300 PSIG
7
uPVC PIPE
VENTILATION
FAN
CCE Series
IN-LINE FAN - DIRECT DRIVEN
In-Line Direct Driven Fan – CCE Series
• Cabinet is manufactured in
galvanized sheet steel. Dimension
• Incorporates a direct driven,
DIDW forward curved centrifugal
fan.
• Removable access panel on both
sides for easy access to fan and motor.
• Flanged inlet and outlet for easy
ductwork connection.
• Operating temperature -40°C to +40°C
Optional Features:
• Internal Insulation.
• Filter with throwaway media.
• Different discharge orientation.
Weight
Model A B C D E F G H J K
(kg)
CCE 140 403 316 268 198 111 210 160 441 25 233 11
Kruger Ventilation Industries Asia Co., Ltd
certies that the CCE series shown herein CCE 160 453 356 308 204 204 230 270 490 25 265 16
is licensed to bear the AMCA Seal. CCE 7-7 442 401 392 263 232 240 344 491 25 340 18
The ratings shown are based on tests and
procedures performed in accordance with CCE 8-8 502 451 442 291 260 291 384 549 25 379 21
AMCA Publication 211 and AMCA Publication CCE 9-7T 572 401 393 236 266 348 322 621 25 340 24
311 and comply with the requirements of
the AMCA Certied Ratings Program. CCE 9-7 573 451 442 236 266 348 382 619 25 378 27
CCE 9-9T 572 401 393 302 266 348 322 621 25 340 25
CCE 9-9 573 451 442 302 266 348 382 619 25 378 27
CCE 10-8 652 561 502 269 293 410 462 699 25 431 33
CCE 10-10 652 561 502 335 293 410 462 699 25 431 35
CCE 12-9 743 631 573 313 345 510 547 790 25 526 42
CCE 12-12 743 631 573 399 345 510 547 790 25 526 44
All dimension in mm.
Technical Data
Lp (A) at
Maximum Motor Maximum
Max Q Motor Voltage Capacitor Insulation 3m free Speed
Model Input Power Phase Hz Current
(m3/ h) Protection (V) (μF/ V) Class discharge (RPM)
(W) (A)
(dB (A))
CCE 140 4P-1 1SY 641 112 IP20 1 50 0.6 220 4.0/450 F 61 1450
CCE 160 4P-1 1SY 914 148 IP20 1 50 0.7 220 4.0/450 F 52 1400
CCE 7-7 4P-1 1SY 1577 255 IP20 1 50 1.1 220 7.5/450 F 52 1300
CCE 8-8 4P-1 1SY 1613 328 IP20 1 50 1.4 220 7.5/450 F 50 1300
CCE 9-7T 4P-1 3SY 1879 560/500/430 IP20 1 50 2.6/2.3/2.1 220 7.5/450 F 51 1200/1150/1100
CCE 9-7 4P-1 3SY 2084 590/500/430 IP20 1 50 2.7/2.5/2.0 220 7.5/450 F 47 1200/1150/1100
CCE 9-9T 4P-1 3SY 2426 780/520/360 IP20 1 50 3.5/2.5/1.8 220 12.5/450 F 56 1300/1100/800
CCE 9-9 4P-1 3SY 2574 800/520/360 IP20 1 50 3.6/2.4/1.7 220 12.5/450 F 51 1300/1100/800
CCE 10-8 4P-1 3SY 3639 1370/1120/940 IP20 1 50 6.3/5.2/4.5 220 16.0/450 F 59 1300/1250/1150
CCE 10-10 4P-1 3SY 3857 1420/1100/950 IP20 1 50 6.6/5.2/4.6 220 16.0/450 F 59 1300/1250/1150
CCE 12-9 6P-1 3SY 4547 1150/700/450 IP20 1 50 5.8/3.6/2.5 220 12.5/450 F 59 940/820/620
CCE 12-12 6P-1 3SY 5200 1220/700/450 IP20 1 50 6.2/3.7/2.5 220 12.5/450 F 62 940/820/620
- Values shown are for inlet Lwi(A) sound power levels for installation type D – Ducted inlet, Ducted outlet. The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.
Ratings include the effects of duct end correction.
- Performance certified is for installation type D – Ducted inlet, Ducted outlet.
- Performance ratings do not include the effects of appurtenances (accessories).
- Speed (RPM) shown is nominal. Performance is based on actual speed of test.
- Lp(A) at 3m free discharge dB(A) levels are not licensed by AMCA International.
Performance Data
200 CCE 140 4P-1 1SY 320 CCE 160 4P-1 1SY
150 240
100 160 76
84
74
83
50 80
83 73
82 73
0 0
0 150 300 450 600 750 0 200 400 600 800 1000
Flow Rate (m3/h) Flow Rate (m3/h)
300 450
200 300
76 72
75
71
100 150
74
70
73 71
0 0
0 400 800 1200 1600 2000 0 400 800 1200 1600 2000
Flow Rate (m3/h) Flow Rate (m3/h)
600 CCE 9-7T 4P-1 3SY 750 CCE 9-7 4P-1 3SY
600
Static Pressure (Pa)
Static Pressure (Pa)
450
450
300 72 72 72
71
300
69 71 72 66 68 69
150 65
150 67
68 70 73 65 68
66
68 70 72 0 64 66 68
0
0 400 800 1200 1600 2000 0 500 1000 1500 2000 2500
Flow Rate (m3/h) Flow Rate (m3/h)
- Values shown are for inlet Lwi(A) sound power levels for installation type D – Ducted inlet, Ducted outlet. The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.
Ratings include the effects of duct end correction.
- Performance certified is for installation type D – Ducted inlet, Ducted outlet.
- Performance ratings do not include the effects of appurtenances (accessories).
- Speed (RPM) shown is nominal. Performance is based on actual speed of test.
Performance Data
750 CCE 9-9T 4P-1 3SY 750 CCE 9-9 4P-1 3SY
600 600
450 450
75
72
300 72 73
300 71 72 74 71 71
74
69 70 75 66 68
150 150
63 69 76
61 68 77 0 58 64 72
0
0 500 1000 1500 2000 2500 3000 0 500 1000 1500 2000 2500 3000
Flow Rate (m3/h) Flow Rate (m3/h)
800
Static Pressure (Pa)
800
Static Pressure (Pa)
600 600
81
80 81 80 81
80 78 400
400 77 79
74 78 77
200 76 80 200 73 75 79
73
72 75 80
0 73 76 80 0
0 1000 2000 3000 4000 5000 0 1000 2000 3000 4000 5000
Flow Rate (m3/h) Flow Rate (m3/h)
600 CCE 12-9 6P-1 3SY 600 CCE 12-12 6P-1 3SY
500 500
Static Pressure (Pa)
Static Pressure (Pa)
400 400
74 75
300 300 75
72 76 74 77
73
71
200 200 75 76 79
71
100 68 80 100 81 81
78
0 0
0 1000 2000 3000 4000 5000 0 1000 2000 3000 4000 5000 6000
Flow Rate (m3/h) Flow Rate (m3/h)
- Values shown are for inlet Lwi(A) sound power levels for installation type D – Ducted inlet, Ducted outlet. The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.
Ratings include the effects of duct end correction.
- Performance certified is for installation type D – Ducted inlet, Ducted outlet.
- Performance ratings do not include the effects of appurtenances (accessories).
- Speed (RPM) shown is nominal. Performance is based on actual speed of test.
NOTES
THE KRUGER GROUP
• KOREA • MALAYSIA
NEOMATE CO. LTD KRUVENT INDUSTRIES (M) SDN BHD
2-1010, Ace High Tech City B/D, 775 Gyeongin-ro, Lot 850, Jalan Subang 7, Taman Perindustrian Subang,
Yeongdeungpo-gu, Seoul, Korea. Postal Code 07299 47500, Subang Jaya, Selangor D.E.
Tel. +82-2-2679-2052 - Fax. +82-2-2679-2174 Tel. +603 80743399 - Fax +603 80743388
Email: y7890@neomate.co.kr Email: mktg@kruger.com.my
• MYANMAR • PHILIPPINES
KRUGER VENTILATION (MYANMAR) CO.LTD KRUGER M&E INDUSTRIES CORPORATION
Room No. F21, Thiri Yadanar Whole Sale Market, (Htawunbe) FAPI Compound, E. Rodriguez Ave.
Toe Chae Ward, North Okkalapa Township, Yangon. Tunasan, Muntinlupa City 1773, Philippines
Tel. +959 763141081/2/3 Tel. +63 2-8622892/4/6/7, 5534059 - Fax +63 2-8622891
Email: htoon@krugermm.com Email: mktg@krugerph.net
• SINGAPORE • TAIPEI
KRUGER ENGINEERING PTE LTD KRUGER VENTILATION (TAIWAN) CO. LTD
No. 10 Buroh Street #06-06, West Connect Building, No. 157, Ping-an Rd, Hengfeng Village,
Singapore 627564 Dayuan Shiang Taoyuan County 337, Taiwan
Tel. +65 68631191 - Fax +65 68631151 Tel. +886 3-3859119 - Fax +886 3-3859118
Email: mktg@krugerasia.com Email: sales@krugertwn.com.tw
• THAILAND • VIETNAM
KRUGER VENTILATION IND. (THAILAND) CO. LTD KRUGER VENTILATION INDUSTRIES (VIETNAM) CO. LTD
30/105 Moo 1, Sinsakorn Industrial Estate, Lot A7. 2-4, C2 Road, Thanh Thanh Cong IZ,
Chetsadawithi Road, Khok Kham Mueng, Samuthsakorn 74000, Thailand Trang Bang Dist. Tay Ninh Province, Vietnam
Tel. +662 1050399 - Fax + 662 1050370-2 Tel. +84-276 3585200/01/02 - Fax +84-276 3585199
Email: mktg@kruger.co.th Email: mktg@krugervn.com
The company is always improving and developing its products, therefore the company reserves the right of making changes to the illustrated products.
Certified dimension can be provided upon request.
APN Series
Propeller Fans – APN Series
Propeller fan for wall or panel mounting with wall plate made of mild steel, with painted finish.
Impeller having blades made of Glass Reinforced Polypropylene(PPG), Glass Reinforced Polyamide
(PAG) or Aluminium.
Totally enclosed Class "F" motor, to a min. IP54 protection are fitted as standard. Standard motor up to
2.2 kW are usually supplied on DOL starting, motor 3.0 kW and above are star/delta starting. Motors of
other specification are available upon request.
Dimensions – 50Hz
Supply Exhaust
C C
Model □A □B C
The company is always improving and developing its products, therefore the company reserves the right of making changes to the illustrated products.
Certified dimension can be provided upon request.
Overview
The heating, ventilation and air–conditioning (HVAC) industry
is in the midst of a dynamic era, however air–distribution
ductwork remains virtually unchanged since the early 1900s.
Several factors have introduced the need to revolutionise
HVAC ductwork. Energy use has continued to escalate, and
thus the demand for energy reducing solutions has intensified.
Tiger Support & Wire
Requirements for clean air are becoming increasingly prevalent. Hanger Assembly
Speed of construction has become a valuable asset. Floor
space and headroom are under constant pressure.
Traditionally, HVAC ductwork is constructed from
galvanised sheet steel, which is installed first
and then insulated separately as a second
operation.
The Kingspan KoolDuctTM System Tiger Clip Coupling System
however, is an advanced and
innovative pre–insulated rectangular
HVAC ductwork system, which is
installed in a single–fix.
The Kingspan KoolDuctTM System
eliminates virtually all of the problems
Kingspan KoolDuctTM System
associated with galvanised sheet steel,
Plenum Box
mineral fibre duct board and pre–
insulated rigid polyisocyanurate (PIR)
ductwork systems whilst, at the same
time, offering additional advantages
to the specifying engineer, the architect,
the M&E contractor, the fabricator, the facilities
manager, the property developer and the building owner.
Ductwork fabricated from the Kingspan KoolDuctTM System
Aluminium Grip
can reduce air–leakage rates to a fraction of those typical of
Coupling System
rectangular sheet metal ductwork. This cutting edge System
thus offers the triple benefits of cutting energy use, cutting
operational carbon dioxide (CO2) emissions and cutting costs.
As a result, the Kingspan KoolDuctTM System should be
considered the ductwork system of choice, where low Volume Control
embodied environmental and low operational environmental Damper
impacts are key requirements.
2
What is The Kingspan KoolDuctTM
System?
The Kingspan KoolDuctTM System comprises premium
performance Kingspan KoolDuctTM panels, fabrication methods,
coupling systems and a complete line of accessories to produce
4–bolt Steel Channel Support & pre–insulated rectangular ductwork in sections up to 3.93 m long.
Coupling System Threaded Rods
Kingspan KoolDuctTM panels available in the following thicknesses
and corresponding installed R–values:
• 22 mm = R1.0;
• 30 mm = R1.4;
• 33* mm = R1.6; and
Fire Damper Access Panel
• 42 mm = R2.0.
*minimum order quantities apply
3
Benefits
UL Listed – the only premium performance pre–insulated ductwork in the world to be UL Listed as a Class 1 Air Duct, to
®
Standard for Safety UL 181 (Underwriters Laboratories: Factory Made Air Ducts & Air Connectors), when fabricated to a
specification clearly defined by UL.
Low weight – weighs up to 75% less than ductwork constructed from galvanised sheet steel and insulated with mineral fibre –
this makes it ideal for refurbishment projects, where existing building structures have insufficient load capacities for new service
loads.
Faster installation speeds – low weight ductwork fabricated in sections up to 3.93 m long, single–fix installation and no need
to install insulation as a second operation, reduces project scheduling periods for insulated ductwork.
Space saving – typically saves up to 150–200 mm in a single dimension, since the space required to manually install a separate
layer of insulation around the ductwork is eliminated – this allows ductwork to be installed flush to ceilings, walls and floors, as well
as to surfaces within confined enclosures.
Installed cost savings – reduced labour and materials, including fixings and first level support members, can provide an ideal
value engineered ductwork solution without compromising performance – over 15% less expensive.
Low air–leakage – rates can be reduced to a fraction of those typical of rectangular sheet metal ductwork – can easily achieve:
BS EN 1507: 2006 air–leakage Class D; BS EN 13403: 2003 Class C; and B&ES (HVCA) DW/144 Class C.
Reduced energy usage & running costs – low ductwork air–leakage can yield significant electrical consumption savings
because of reduced heating and cooling loads, and fan energy usage.
Class 0 – Kingspan KoolDuctTM panels faced with silver aluminium foil on one side and either silver or black coated aluminium
foil on the other, and their rigid thermoset insulation core, are Class 0, as defined by the Building Regulations in England.
Euroclass Bs1d0 – Kingspan KoolDuctTM panels faced with silver aluminium foil on one side and silver aluminium foil on the other,
are Euroclass Bs1d0, as defined by the European Fire Classification System.
Easily modified – ductwork configurations can be easily modified and adapted onsite to deal with unexpected changes to the
design, which may be required to circumvent unforeseen obstructions and other building design issues.
4
Green Guide Summary Rating of ‘A’ – an Ecoprofile, certified by BRE Certification to the the BRE Environmental Profiles
methodology, has been created for Kingspan KoolDuctTM panels produced at Kingspan Insulation’s Pembridge, UK,
manufacturing facility. BRE has assigned the panels a 2008 Green Guide Summary Rating of ‘A’.
Whole life cost saving – up to 20% over 30 years, compared with ductwork constructed from galvanised sheet steel and
insulated with mineral fibre.
Low embodied environmental impact – up to 65% less than that of rock mineral fibre insulated galvanised sheet steel
ductwork.
Reduced operational CO2 emissions – as a result of low ductwork air–leakage, and the subsequent reduction in operational
energy usage.
Reduced workshop–generated waste – computer aided fabrication can greatly reduce the volume of waste, compared with
manual fabrication.
Thin insulation – the low thermal conductivity (k–value / l–value) of Kingspan KoolDuctTM panels makes them the most
thermally efficient, and hence the thinnest, insulation product commonly used for pre–insulated HVAC ductwork.
A fibre-free rigid insulation core – minimises the risk of loose fibres entering the airstream through the
ductwork, since distributed air does not come into contact with an insulation material that produces loose
fibres.
Zero–ODP & Low GWP – the insulation core of Kingspan KoolDuctTM panels is manufactured with a CFC/HCFC–
free blowing agent that has zero Ozone Depletion Potential (ODP) and low Global Warming Potential (GWP).
LEED® & BREEAM – ductwork fabricated from The Kingspan KoolDuctTM System can contribute points towards achieving
credits, including pilot credits, in many of the LEED® rating systems. Contributions can also be made toward the achievement
of credits in the schemes within the building rating system BREEAM.
1
Manufactured to the highest standards – Kingspan KoolDuctTM panels are manufactured under a management system
900
ISO
BS
EN
EN
ISO
14001 certified to BS EN ISO 9001: 2008 (Quality management systems. Requirements), BS EN ISO 14001: 2004 (Environmental
BS
001
BS
OH
SAS
18
Management Systems. Requirements) and BS OHSAS 18001: 2007 (Health & Safety Management Systems. Requirements).
5
Applications
Application Suitability
The Kingspan KoolDuctTM System is designed for use in building services / HVAC applications. It is suitable for both new build and retrofit projects
in the residential, commercial, institutional, light industrial and leisure sectors. Moreover, it is especially suitable for use in non–ferrous applications
and on high specification projects where insulants with a fibre-free core may be preferred, for instance:
*For swimming pools, non–standard applications and project specific advice, please contact Kingspan Insulation.
Table 1: Operating Limits for Ductwork Fabricated from the Kingspan KoolDuctTM System
*These are maximum values and vary depending upon both the coupling system and the size of the ductwork. Refer to The Kingspan KoolDuctTM System Fabrication Manual series of
publications for details.
NB ‘Mean Air Velocity’ refers to the design airflow rate related to the cross sectional area of the ductwork. ‘Design Pressure’ relates to the actual total pressure of the relevant section of
ductwork and not the fan static pressure. ‘Total Pressure’ is a combination of both static and dynamic pressures.
Ductwork fabricated from The Kingspan KoolDuctTM System should not be used in the following applications:
● conveyance of solids;
● fire resistant ductwork;
● kitchen / grease hood exhaust systems;
● chemical, fume or smoke exhaust systems;
● where combustible matter readily collects inside the ductwork;
● adjacent to any mechanical / electrical sources of extreme heat;
● outdoor / underground use without mechanical and / or weather protection;
● where the failure of automatic control equipment may give rise to extreme temperatures; and
● with equipment of any type that does not include automatic maximum temperature controls.
6
Prestige Projects
7
Contact Details
General Enquiries
Email: info@kingspaninsulation.asia
Kingspan Insulation Pty Ltd reserves the right to amend product specifications without prior notice. Product thicknesses shown in this document should not be
taken as being available ex–stock and reference should be made to the current Kingspan Insulation Pty Ltd price list or advice sought directly from Kingspan
Insulation Pty Ltd. The information, technical details and fixing instructions etc. included in this literature are given in good faith and apply to uses described herein.
Recommendations for use should be verified as to the suitability and compliance with actual requirements, specifications and any applicable codes, laws and
regulations. For other applications or conditions of use, Kingspan Insulation Pty Ltd offers a Technical Advisory Service, the advice of which should be sought for
uses of Kingspan Insulation Pty Ltd products that are not specifically described herein. The fire tests referenced in this literature and the assigned results are not
intended to reflect hazards presented by the materials and products described herein under actual fire conditions. Please check that your copy of the literature is
current by visiting www.kingspaninsulation.asia
Local Supplier:
www.kingspaninsulation.asia
TM Kingspan, KoolDuct, the zo Device and the Lion Device are Trademarks of the Kingspan Group plc. © Kingspan Insulation Pty Ltd
AIR BOX
AIR GRILLE
DAMPER
HEPA FILTER
Clean Process Filters: E10 to U17 | HEPA Filters for high airflow
Absolute CE
Advantages
• Range of standard sizes • Very high efficiency
• Compact design • H13 are individually tested
1822
I N DIVID U A L LY
CE R T IFI E D
1400654 CEG11-305x610x292-P0 E11 305x610x292 950/125 7.2 7.2 As part of our program for continuous improvement, Camfil reserves the right to change specifications without notice.
96
Clean Process Filters: E10 to U17 | HEPA Filters for high airflow
97
G4 FILTER
Pre-Filtration G3 to M5 | Media
STED
TE
STED
TE
EN
ISO16890 779:2012
A CCO RDI N G A CC O RDI N G
TO TO
8850290001 MHF 24x24x2-G4 MERV 8 G4 Coarse 60% 592 x 592 x 48 3400/110 0.57 1.69
8850290002 MHF 12x24x2-G4 MERV 8 G4 Coarse 60% 287 x 592 x 48 1700/110 0.3 1.18
As part of our program for continuous improvement, Camfil reserves the right to change specifications without notice.
50
DUST
COLLECTOR
FARR GOLD SERIES®
Scan to see video about the making
of the Remembering Tree.
SERVICE
dust collector...guaranteed.
WOW
• We will clean dust, mist and fumes from factories,
the workplace, making them safer and more productive.
Power up your dust collector with HemiPleat! This statement comes from
the fact that with lower pressure drop HemiPleat filters, you can pull more
for today…
air with less energy, thus capturing pollutants better. Filtration
and tomorrow.
The air coming out of a Farr Gold Series dust
• We will ship collectors fast while still giving the customer what they want. collector with HemiPleat filters has been tested
to exceed the air quality required in most hospital
Saving energy and increasing production efficiency while
• We will be the most customer and rep friendly company in the
operating rooms!
controlling indoor air quality is a challenging aspect of plant air pollution control business.
Green Your Factory of the filter allowing a reduction in the number of filters by at least a third. The
design has also led to long filter life with low pressure drop.
Our goal at Camfil APC is to be green, starting with the environmental benefits of our
products. We help our customers go green by stopping thousands of different pollutants
from entering the workspace air and the outside air. We also build our equipment to last,
so less waste is created over time. Our HemiPleat technology has revolutionized the air
pollution control industry by delivering very high efficiency in a filter that lasts twice as
long as competitive products. It contributes to sustainability while saving energy. Even
the paint on our Farr Gold Series® collector is green, and not just the color: We use an
pleat
environmentally friendly powder painting process so no VOCs are emitted. Further- ®
more, premium efficiency motors are standard on the fans we supply. We are constantly
Getting Greener launching green initiatives. We look forward to working with you to “green” your factory.
Farr Gold Series Collectors Come ® The ultimate in a green filter! The DuraPleat is fully washable and
develop and maintain sustainable business practices.
reusable. We have customers that have 5-year-old DuraPleat filters and
AN
N G
• Fiberglass/Composites
UFAC T
Thermal spray with integrated HEPA and vertical explosion venting
• Food/Sugar
LEA
• Foundry
UR
ING
Indoor flameless explosion venting • Grinding
Ship abrasive blasting
Scan to see more Farr Gold Series® installations.
Pharmaceutical dust • Mining Pharmaceutical dust with bag-in bag-out (BIBO) filter change-out
Weld smoke ventilation
Thermal Spray with spark trap module
• Nuisance Dust Ventilation Ore crusher at major copper mine
Farr Gold Series with HEPA integrated Safety Monitoring Filter (iSMF) Paper shredding/recycling GS48 with skirting on plasma cutting Tunnel mining skid package OEM laser cutting fume Ore storage bin vent
6 7 8
®
The Heart of the Farr Gold Series
5,972,059
The HemiPleat cartridge uses optimal pleat spacing with synthetic glue beads to hold Scan to learn more about HemiPleat.
Gold Cone Double Seal Urethane Gasket
the pleats open. HemiPleat breathes more air with less energy and increases the
cleaning effectiveness of the reverse pulse, thus resulting in a lower pressure drop.
atent #
HemiPleat Green - proprietary blend of cellulose and polyester fibers with a moisture resistant silicone treatment
HemiPleat Flame Retardant - proprietary blend of cellulose and polyester fibers with a flame retardant treatment
•
Gold Cone P
HemiPleat Carbon Impregnated - proprietary blend of cellulose and polyester fibers impregnated with carbon for static dissipation Vertically mounted to shed dust readily for
HemiPleat Synthetic - 100% synthetic filter media for washability and moisture resistance over cellulose. efficient cleaning and longer service life.
Patent # US 7,722,699 B2
110 µm 1150x 60 µm 2050x
10 11
Easy Filter Farr Gold Series offers modular design
Change-out for optimum flexibility–delivered fast!
1 We are very happy with the Camfil APC dust collector. The dust
collection solution was purchased for our CNC plasma cutter to replace a
horizontal cartridge dust collector due to short filter life. The current filters
have been in for over a year and still look great and are operating on less
than 3” pressure drop. Also, the Camfil APC people have been a Powerful Cleaning
pleasure to do business with. System to Provide
— Dan Schuler, Schuler Manufacturing Long Filter Life
3 cleaning of dust
Individually Powder Coated
Farr Gold Series components are individually
powder coated prior to assembly for superior
corrosion resistance.
Low Boy
Low Pro
Standard
Other hopper options available include drawer kit, trough hopper with screw conveyor, and continuous liner discharge.
13
Farr Gold Series Models
®
# of cartridges
Model # Code
Gold Series
GS 24
Standard hopper arrangements shown. See opposite page for other hopper options.
16
NFPA COMPLIANT
Combustible Dust Collection Systems
Outlet Protection
Integrated Safety
Monitoring Filter (Patent Pending)
Inlet Protection The iSMF has been proven to isolate the
downstream equipment from the progression of
a flame front during an explosion. The Farr Gold
Fast-Acting Valve Series dust collector with an integrated Safety
Designed to close within milliseconds of detecting an explosion, the fast-acting valve Monitoring Filter allows you to recirculate exhaust
installs in either inlet and/or outlet ducting. The fast-acting valve creates a mechanical air back into the work space when your dust is
barrier within the ducting, which effectively isolates pressure and flame fronts (from explosive. The key advantage of this device is that
either direction) from being able to propagate further through the process. it prevents the transmission of explosive dust
(fuel) from the collector.
OR OR
Inlet/Outlet Chemical Isolation
Designed to react within milliseconds of detecting an explosion, a High Speed Abort Gates
chemical isolation system can be installed in either inlet and/or outlet High speed abort gates are designed to divert process air
ducting. The chemical isolation system creates a chemical barrier that and/or smoke to a safe location outside when a possible
suppresses the explosion within the ducting, reduces the propagation ignition source is detected entering the dust collection
of flame through the ducting and minimizes pressure increases within system or when a fire is detected. Its primary purpose is
connected process equipment. to protect the inside of the building from burning debris,
embers or smoke. Can be installed in either inlet and/or
outlet ducting.
OR
Explosion Venting
The Stinger was designed to be installed in the inlet
TM
Chemical Suppression OR
Designed to react within milliseconds of detecting an explosion, a chemical suppression
system is installed in the collectors dirty air section. The chemical suppression system prevents
expanding a deflagration by releasing a chemical agent. This system is often used in order to put
combustible dust collectors inside the factory where you can’t vent to the outside.
18
1 2 3 4 19
Farr Gold Series Controls ®
GoldLink
GoldLinkTM is your anytime access to
the diagnostics of your dust collection
system. GoldLink monitors 4 preset
analog inputs and 16 preset digital
inputs to keep you informed on your
operation. GoldLink sends multiple users
messages when critical set points are
reached insuring your manufacturing
facility is safer and more productive.
GoldLink can be included in any Camfil Smart Solenoid Controller
integrated control panel or retro-fit to Camfil APC introduces a new cost saving
systems already installed. innovation. The timer controls for pulsing
the solenoids are now embedded with the
solenoids so you no longer have to wire a
remote timer board to the solenoid tray.
The ON and OFF times of the solenoids are
easily adjusted through dials integrated
FDC Controller
into the solenoid tray.
This controller’s flexible design
allows it to be adapted to many
dust collector configurations.
VFD Controller
The timer controller with Variable Frequency
Drive (VFD) option provides complete control of
the blower during and after startup. It has all the
necessary functions for a controlled start of the
Farr Gold Series without the high current loads
typically associated with blowers during startup.
It also provides the ability to control the blower’s
speed resulting in the greatest energy savings
and process functionality.
Custom GS Controller Integrated Dust Collector (IDC) Controller with Smart Start
20
Bag-In Bag-Out (BIBO) Butterfly Valve Continuous Liner Discharge Low Pro Hopper Quick Seal GS Drum Kit with Slide Gate Pulse Header Silencer GS High Vacuum Fully Insulated Collector Stainless Steel
Pharmaceutical Options
Top Hand Rails UHMW Mining Inlet Baffle Slurry Tank for Conveying Dust Copper Tubing and Diaphragm GS Skirt Auger Screw Conveyor Self Dumping Hopper Clean Sweep Remote Safety Monitoring Filter Broken Bag Detector Collector Stiffening Compressed Air Regulator
Maintenance Valve
Mining Options
Mining Options
Extended Options
Extended Options
Green Moisture Resistant Media Fire Retardant Media Carbon Static Electricity Synthetic Washable Media Heavy Duty Cast Rotary Airlock Fabricated Flex Tip Airlock Cast Rotary Airlock Dust Briquetter Custom Structural Steel Quad Pulse Technology Custom OEM Designs Inspection View Port
Conductive Media for Fibrous Dust
Gold Cone Media Options
Inlet Options
GoldLink
Fire and Explosion Protection
Vertical Explosion Vent Flameless Explosion Vent Stinger Backdraft Damper Chemical Suppression System Top Mount Fan Side Mount Fan Ground Mount Fans Fan Silencer Ambient Weld Smoke Collection Source Fume Collection Source Capture Dust Source Capture Foundry
Ducting Designs
Ducting Designs
Fans
Fans
21 22 23
Typical Farr Gold Series® Shipment
Custom Preassembled
Skid Mounted Dust
Collection System
24
Camfil APC Farr Gold Series Product Overview
Farr Gold Series® Collectors GS Camtain® Collectors GS1QP Quad Pulse GS High Vacuum
Cyclone Separators GSM4 Mini Systems Zephyr® III Portables GSP Packaged Systems
• High efficiency centrifugal • Self-contained systems for • Three-stage filtration • Smoke and dust collector for
particulate separators 1,000 to 2,000 CFM applications • For welding fumes, grinding dusts CNC laser and plasma cutters
• Excellent as prefilters to large • Fully assembled and prewired • 700 CFM at capture hood • Fully assembled and prewired
cartridge collector systems in unit includes fan, controls, unit - just plug it in!
many applications motor starter, filters and • Heavy duty fume arm is free
of obstruction inside • Fan rated 2,500 CFM at 10” w.c.
cleaning system
• Single cartridge dust collector • Fan provided with premium • FDC Controller GoldLinkTM is your anytime access
• Mini solution for sub 500 CFM efficient “E” motor to the diagnostics of your dust
• Motor Starters
applications where you want a • Non-overloading backward collection system.
• VFD’s
dedicated dust collector for one inclined fan wheels with standard
process machine or as a bin vent supplied integrated damper • Custom Controls
• High performance filtration with • Lower pressure drop • Improves performance of existing • Handles difficult dust applications
Multiple media options dust collector
• Enhanced cleaning for more • Exceptionally rugged, long lasting
• State-of-the art pleat spacing efficient operation • Greater media utilization • Washable media may be reused
• Size for nearly all industrial • Excellent energy performance • More effective cleaning and lower in many applications
dust collector brands pressure drop
25
World’s Largest Dust, Mist and Fume Collector Factory
25 acres - 280,000 sq. feet of factory space!
TM
s c an t o v i s i t
www.camfilapc.com
C a m fi l A P C | 3 5 0 5 S. A irpo r t Ro ad, Jo ne s bo ro, A R 72401
8 7 0 - 9 3 3 - 8 0 4 8 | e- m a i l: f ilte r man@ far rapc.co m | 800-479-6801
8 7 6 5 4 3 2 1
ITEM NO. PART NUMBER QTY. UNITS DESCRIPTION
SALES ORDER
2 325325001 2 EA FLTR-GS-GR-325
974
FOOTPAD DETAIL
REMOVE TOP PANEL
TO CREATE OUTLET SECTION A-A
SEE DETAIL #4 ON
DWG #GS10002-M SPECIFICATIONS:
1152
1. MODULAR CONSTRUCTION FROM 3.5 & 4.6mm
HRCS
5. IMPORTANT NOTE:
FANS TYPICALLY EXPERIENCE
FOUR TO TEN TIMES THE FULL LOAD
AMPS DURING START-UP. CIRCUITS
67 AND FUSES MUST BE ADJUSTED
10 ACCORDINGLY.
2805 REF.
SHIPPING INFO:
TIMER CONTROLLER
2689
FIELD LOCATED EQUIPMENT END USER:
B B
(OUTLET) CL
(OPTIONAL)
CUSTOMER REP:
2356
FIELD BOLTED
W/ 3/8-16 THRD P.O.#:
CUTTING BOLTS FARR #:
(INLET) CL
1555
HOPPER/SUPPORT
W/ DRAWER LIFTER
762
C 12/12/2014 HE MBL
(225866002)
102X102X5
FORMED LEGS REV DATE REVISION DESCRIPTION SON DFT CK APP
TOLERANCES UNLESS OTHERWISE STATED MAC PAC DATA
DUST DRAWER MACHINED
CMDTY PRODUCT SUB UNIT OF
W/ BALL TRANSFERS OVER 0.00 30.00 100.00 300.00 CODE CLASS CLASS MEASURE
UP TO 29.99 99.99 299.99
A TOLERANCE +0.10 +0.15 + 0.20 +0.30 N/A 40 20 EA
A A FABRICATED A
OVER 0.00 30.0 100.0 500.0 2000.0 CROSS REFERENCE NONE
**THE CUSTOMER ASSUMES THE RESPONSIBILITY FOR CONTACTING THEIR INSURANCE UNDERWRITER
AND ADVISING CAMFIL/FARR IN REGARD TO SPECIFIC APPLICATION REQUIREMENTS OF EXPLOSION UP TO 29.9 99.9 499.9 1999.9
VENTING OR IF ADDITIONAL FIRE PROTECTION AND SAFETY EQUIPMENT MAY BE REQUIRED. THE TOLERANCE +0.5 + 1.0 + 1.5 + 2.0 +3.0 SCALE:1:12.5 SHEET 1 OF 1
BUYER IS ALSO CAUTIONED TO ADHERE TO PRESCRIBED OSHA, NFPA, FEDERAL, STATE AND LOCAL *ALL DRAWINGS & DIMENSIONS ARE SUBJECT TO
CODES AND REGULATIONS APPLICABLE TO INDUSTRIAL VENTILATION SYSTEMS, WHICH CAMFIL/FARR CHANGE WITHOUT NOTICE. STANDARD FARR GS2 TITLE
EQUIPMENT MAY BE APPLIED ON. SALES DRAWING. (NOT FOR CONSTRUCTION) GS2 DUST COLLECTION SYSTEM
DRAWING NO. REV.
SIZE
DO NOT SCALE PRINT A1 216723002-M C
8 7 6 5 4 3 2 1