Prepared By:
Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 4 0,685 No Sí
2 4 0,685 No Sí
3 4 1,100 No Sí
Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 A 0,390 D
Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 0,350 10 0
2 0,350 10 0
3 1,100 10 0
Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 1,018 1,100 0,700 2 0,700
2 1,000 1,000 0,400 1 0,400
3 1,000 1,000 0,600 1 0,600
Zone Input
Zone 1: MODULO DE CONECTIVIDAD 1 (345,6 sq.ft) (Group 0)
Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 32,00 Zone width (feet): 10,80
Lighting Watts: 968 Equipment Watts: 10.000
Number of people in zone: 4 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 8,50 Heating safety factor (%): 0
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 225
Cooling ventilation method: CFM/Pr Cooling ventilation value: 35,000
Cooling infiltration method: Direct Cooling infiltration value: 0,000
Heating ventilation method: Direct Heating ventilation value: 0,000
Heating infiltration method: AC/Hr Heating infiltration value: 0,000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 346 Exposed floor slab perimeter (ft): 0
Cooling loads only are calculated for this zone.
Check Figures
Total Building Supply Air (based on a 15° TD): 4.342 CFM
Total Building Vent. Air (3,22% of Supply): 140 CFM
Total Conditioned Air Space: 346 Sq.ft
Supply Air Per Unit Area: 12,5640 CFM/Sq.ft
Area Per Cooling Capacity: 85,0 Sq.ft/Ton
Cooling Capacity Per Area: 0,0118 Tons/Sq.ft
Heating Capacity Per Area: 0,00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 4,07 Tons
Check Figures
Total Air Handler Supply Air (based on a 15° TD): 4.342 CFM
Total Air Handler Vent. Air (3,22% of Supply): 140 CFM
Total Conditioned Air Space: 346 Sq.ft
Supply Air Per Unit Area: 12,5640 CFM/Sq.ft
Area Per Cooling Capacity: 85,0 Sq.ft/Ton
Cooling Capacity Per Area: 0,0118 Tons/Sq.ft
Heating Capacity Per Area: 0,00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 4,07 Tons
Building
Net Gain
48.811
Btuh
Equipment - 76,90%