SUKMA KELANTAN 2026 - PEMBINAAN ARENA TERTUTUP, KOMPLEKS SUKAN

BUKIT MERBAU, PASIR PUTEH, KELANTAN ( REKA DAN BINA )

Sprinkler System

The system proposed is designed in accordance to MS 1910 : 2017 based on Ordinary Hazard Group IV
(OH IV – 30 meter). The design capacity for the sprinkler tank is based on the OH occupancy where
tank is not dependent on inflow i.e 185 m3 (refer Table 9).

All pipework is in accordance with Table 30 & 31 for range pipe and distribution pipes size
respectively.

The selection of pump flow rate is in accordance with Table 16 which nominal pump rating are 3,050
L/min @ 2.4 bar with characteristic not less than 2,100 L/min @ 4.5 bar OR 1,800 L/min @ 5.0 bar.

The precalculated hydraulic calculation method has been carried out to determine the available pump
head can deliver the water up to furthest point in the way that from the design point for each array of
distribution pipes to the alarm valve maximum friction lost shall be not exceed 0.5 bar at a flow rate of
1000 L/min.

From the calculation (refer to table), it can be shown that all friction loss are less than 0.5 bar.

INTRO SPRINKLER SPRK1


Statement of Distribution Pipe Losses between the various design
points and the Installation Valves
(Based on MS 1910-2017)

HAZARD GROUP : OH IV - 30 M

PROJECT : SUKMA KELANTAN 2026 - PEMBINAAN ARENA TERTUTUP,


KOMPLEKS SUKAN BUKIT MERBAU, PASIR PUTEH, KELANTAN

LEVEL : ROOF

1 2 3 4 5 6 7
Run of
distribution Pipe Pipe No. Equiv. Total Pressure
pipe from size length of pipe equiv. loss at
valves to turns length length design
(letter) of turns of pipe flow rate*
(mm) (m) (m) (m) (mb)

DP/A - FS/1 65 0 0 1.89 0 0.00


80 8 0 2.37 8 128.00
100 20 1 1.43 21.43 94.29
150 76 2 2 80 52.00

FS/1- AV 150 35 4 2 43 27.95

Flow Switch 150 35.88 35.88 23.32


Butterfly Valve 150 6.38 6.38 4.15

Total = 329.71

Static Gain X= 0.00

Difference = 329.71

DP/B - FS/2 65 0 0 1.89 0 0.00


80 8 0 2.37 8 128.00
100 28 0 1.43 28 123.20
150 83 1 2 85 55.25

FS/2- AV 150 35 4 2 43 27.95

Flow Switch 150 35.88 35.88 23.32


Butterfly Valve 150 6.38 6.38 4.15

Total = 361.87

Static Gain X= 0.00

Difference = 361.87

* Including pressure losses across any orifice plate.

SPRINKLER
SPRK2

SPRINKLER
Pipe nom. Pressure
bore Loss

65 35
80 16
100 4.4
150 0.65
200 0.1

65 35
80 16
100 4.4
150 0.65
200 0.1

SPRINKLER
Statement of Distribution Pipe Losses between the various design
points and the Installation Valves
(Based on MS 1910-2017)

HAZARD GROUP : OH IV - 30 M

PROJECT : SUKMA KELANTAN 2026 - PEMBINAAN ARENA TERTUTUP,


KOMPLEKS SUKAN BUKIT MERBAU, PASIR PUTEH, KELANTAN

LEVEL : 1ST FLOOR

1 2 3 4 5 6 7
Run of
distribution Pipe Pipe No. Equiv. Total Pressure
pipe from size length of pipe equiv. loss at
valves to turns length length design
(letter) of turns of pipe flow rate*
(mm) (m) (m) (m) (mb)

DP/C - FS/3 65 0 0 1.89 0 0.00


80 7.5 0 2.37 7.5 120.00
100 14.5 1 1.43 15.93 70.09
150 112 9 2 130 84.50

FS/1- AV 150 30 4 2 38 24.70

Flow Switch 150 35.88 35.88 23.32


Butterfly Valve 150 6.38 6.38 4.15

Total = 326.76

Static Gain X= 0.00

Difference = 326.76

DP/D - FS/4 65 0 0 1.89 0 0.00


80 5 0 2.37 5 80.00
100 25 0 1.43 25 110.00
150 60 1 2 62 40.30

FS/2- AV 150 30 4 2 38 24.70

Flow Switch 150 35.88 35.88 23.32


Butterfly Valve 150 6.38 6.38 4.15

Total = 282.47

Static Gain X= 0.00

Difference = 282.47

* Including pressure losses across any orifice plate.

SPRINKLER
SPRK3

SPRINKLER
Pipe nom. Pressure
bore Loss

65 35
80 16
100 4.4
150 0.65
200 0.1

65 35
80 16
100 4.4
150 0.65
200 0.1

SPRINKLER