GENERAL: CONCRETE SLAB:

1. CONSTRUCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS OTHERWISE SHOWN OR NOTED MODIFY TYPICAL DETAILS 1. ALL REINFORCEMENT SHALL BE .019M CLEAR MINIMUM FROM TOP AND BOTTOM OF SLAB.
AS DIRECTED TO MEET SPECIAL CONDITIONS. 2. FOR TWO-WAY SLAB ALONG THE LONGER SPAN SHALL BE PLACED BELOW BARS NEAR THE SUPPORT UNLESS OTHERWISE INDICATED OR
2. SHOP DRAWINGS WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL STEELS. MISCELLANEOUS IRON, PRE-CAST CONCRETE, DETAILING
SHOWN IN DETAILS THE SPACING OF THE BARS AT THE COLUMN STRIPS CAN BE APPROXIMATELY 131 OF THE MIDDLE STRIP IN NO CASE HOOK (A OR G) L
ETC. SHALL BE SUBMITTED FOR ENGINEER'S APPROVAL PRIOR TO PURCHASE, FABRICATION AND INSTALLATION. DIMENSION
GREATER THAN 231 TIMES THE SLAB THICKNESS.
3. CONTRACTOR SHALL VERIFY ALL DIMENSIONS BEFORE ALL WORK IS TO BEGIN. CHECK WITH SANITARY, MECHANICAL AND ELECTRICAL 3. UNLESS OTHERWISE DETAILED IN CONDITIONING SLAB HAVING SAME REINFORCEMENT RUNNING IN ONE DIRECTION, REINFORCING SHALL
CONTRACTORS FOR CONDUITS, PIPE SLEEVES, ETC., TO BE EMBEDDED IN CONCRETE.

d
BEND, EXTENDED OR CUT AS FOLLOWS:
4. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE ADEQUATE SHORING AND BRACING OF THE STRUCTURE FOR ALL LOADS 4. TEMPERATURE BARS FOR SLAB SHAL BE GENERALLY PLACED NEAR THE TENSION FACE AND SHALL NOT BE LESS THAN 0.025 BT.
THAT MAYBE IMPOSED DURING CONSTRUCTION.

J
5. UNLESS OTHERWISE NOTED, ALL BEDDED SLAB BE REINFORCED WITH 10mmØ BAR AT .25M O.C. B.W. AT CENTER OF SLAB. CONSTRUCTION D

JOINT FOR SLAB SHALL NOT BE MORE THAN 3.00M APART.

EMBEDMENT
FOOTING: L1/4
6. PROVIDE EXTRA REINFORCEMENT L1/4
AT CORNERL2/4 L2/4 DISCONTINOUS
SLAB (TWO ADJACENT L3/4 L3/4
EDGE) AS SHOWN BELOW.
4d OR 65 MM MIN DEPTH
1. FOOTINGS WERE DESIGNED TO REST ON SOIL WITH AN ASSUMED BEARING CAPACITY OF 5000psf.

0.30MIN
2. NO FOOTING SHALL REST ON FILL.

WIDTH
180 DEG

t
3. MINIMUM CONCRETE PROTECTION SHALL BE .075M CLEAR FOR CONCRETE DEPOSITED AGAINST THE GROUND AND 0.05M FOR

W
CONCRETE DEPOSITED AGAINST THE FRAMEWORK.
DETAILING

DEPTH
DIMENSION
CONCRETE MIXES AND PLACINGS:
1. UNLESS OTHERWISE SPECIFIED, THE MINIMUM 28 DAYS CYLINDER COMPRESSIVE STRENGHT OF CONCRETE ARE AS FOLLOWS: L1/5 L1/5 L2/5 L2/5 L3/5 L3/5
L1 SPAN
EXTERIOR L2 SPAN
INTERIOR L3 SPAN
INTERIOR .
CANTILEVER

A OR G
LOCATION STREGHT AGGREGATE SIZE MAX. SLUMP
D

FOUNDATION, PILE CAP 3000 psi 3 4 IN (100mm)

12d
4 IN (19mm) REINFORCING STEEL BARS
BEAMS, GIRDERS 3000 psi 3
4 IN (19mm) 4 IN (100mm)
1. ALL REINFORCING STEEL SHALL BE NEW BILLET, HOT ROLLED, WELDABLE, DEFORMED BARS CONFORMING
COLUMN, STAIR 3000 psi 3 4 IN (100mm)
SUSPENDED SLAB 3000 psi
4
3
IN (19mm)
IN (19mm) 4 IN (100mm)
TO THE SPECIFICATIONS OF PNS 49; 1986 (ASTM 615), Fy= 60,000 psi (413.79 Mpa) FOR SIZES >12 AND
Fy = 40,000 psi (275.86 Mpa) FOR SIZES ≤12.
90 DEG
2 TYPICAL COLUMN FOOTING DETAIL
4 2. ALL CONCRETE REINFORCEMENT SHALL BE DETAILED, FABRICATED, LABELED, SUPPORTED, AND SPACED S-01 Scale: 1:30
SHEARWALL/RET. WALL 3000 psi 3
4 IN (19mm) 4 IN (100mm) IN FORMS, SECURED IN THE REQUIRED LOCATION IN ACCORDANCE WITH THE PROCEDURES AND
REQUIREMENTS OUTLINED IN THE LATEST EDITION OF THE BUILDING CODE AND THE MANUAL OF STANDARD STANDARD HOOKS
SLAB ON GRADE 2500 psi 3
IN (19mm) 4 IN (100mm)
4 PRACTICE FOR DETAILED REINFORCED CONCRETE STRUCTURES.
CL
2. ALL CONCRETE MUST BE DEPOSITED, VIBRATED AND CURED ACCORDING TO THE ACI STANDARDS.
3. ALL REINFORCING STEEL BARS SHALL BE THOUROUGHLY CLEANED OF ALL LOOSE RUST, SOIL OR OTHER
CORROSIVE MATERIAL IMMEDIATELY PRIOR TO PLACING OF CONCRETE.
C
L
VERIFY
3. STRIPPING OF FORMS AND SHORES SHALL BE AS FOLLOWS: 12d FOR 25 MM CL
6d FOR 10, 12, 16 MM
DEVELOPMENT LENGTH, (Ld), IN TENSION FOR RC BEAMS LENGTH OF LAP COMPRESSION SPLICES (mm)

A OR G
FOUNDATION 1 DAY

HOOK
AND GIRDERS (PRISMATIC OR NON-PRISMATIC) BAR SIZE RC WALL
BEAMS, GIRDERS 21 DAYS fc'=21MPa fc'=28MPa fc'=34.5MPa
fc'=21MPa (3000psi) fc'=28MPa (4000psi) fc'=34.5MPa(5000psi) (mm) (3000psi) (4000psi) (5000psi)
COLUMN & WALLS 3 DAYS BAR SIZE
(mm) TOP BARS BOT BARS TOP BARS BOT BARS TOP BARS BOT BARS CHB WALL INTERIOR CHB
SUSPENDED SLAB 17 DAYS 16Ø 420 390 360

DETAILING DIMENSION
(mm) (mm) (mm) (mm) (mm) (mm) D

SHEARWALL/RET. WALL 3 DAYS 20Ø 540 510 450


16Ø 730 560 630 480 560 430
25Ø 720 600 540
RC STAIRS 17 DAYS
20Ø 1090 840 940 730 840 650 10Ø TRANSVERSE
28Ø 810 720 690 J
25Ø 1820 1400 1570 1210 1410 1080 U-BARS @ 300 O.C.
4. CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT SEGREGATION, RE-HANDLING, OR 4. 32Ø 900 780 720
FLOWING. PLACING OF CONCRETE SHALL BE DONE PREFERABLY WITH BUGGIES, BUCKETS, OR WHEEL 28Ø 2340 1800 1980 1520 1765 1360
36Ø 990 900 810
BARROWS. NO CHUTES WILL BE ALLOWED EXCEPT TO TRANSFER CONCRETE FROM HOPPERS TO BUGGIES, D

TENSION LENGTH
32Ø 2990 2300 2600 1985 2300 1780
WHELL BARROWS, OR BUCKETS IN WHICH CASE THEY SHALL NOT EXCEED 6.0M IN AGGREGATE LENGHT.
NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF VIBRATORS, UNLESS 36Ø 3770 2900 3280 2520 2930 2250

100
AUTHORIZED IN WRITING BY THE DESIGNERS AND ONLY FOR USUAL CONDITIONS WHERE VIBRATOR IS

600 (MINIMUM)
TENSION SPLICE CLASSIFICATION:
EXTREMELY DIFFICULT TO ACCOMPLISH. REFER TO DWG. NO. S-01
CLASS A = 1.00Ld 90 DEG 10Ø TRANSVERSE BARS
FOR NOTES ON PREPARATION @ 300 O.C.
CLASS B = 1.33Ld OF SOIL SUB-BASE.

100
BEAMS AND GIRDERS:

DETAILING DIMENSIONA OR G
MASONRY AND CONCRETE BLOCKS:

HOOK

200
3-10Ø LONGITUDINAL BARS REFER TO DWG. NO. S-01
1. UNLESS OTHERWISE NOTED IN THE PLANS OR SPECIFICATIONS, CAMBER ALL BEAMS AT LEAST 6mm FOR 1. ALL NON-LOAD BEARING TYPE CONCRETE BLOCKS SHALL HAVE A UNIT WEIGHT NOT TO EXCEED 80 PCF. FOR LOAD BEARING TYPE TIE BEAM FOR NOTES ON PREPARATION
CONCRETE BLOCKS, A MINIMUM COMPRESSIVE STRENGHT OF 6.90 Mpa SHALL BE DEVELOPED. (CONT.) WITH TENSION SPLICE
EVERY 3.0M OF SPAN EXCECPT FOR CANTILEVERS FOR WHICH THE CAMBER SHALL BE AS NOTED IN THE OF SOIL SUB-BASE.

6D
PLANS OR AS ORDERED BY THE STRUCTURAL ENGINEER BUT IN NO CASE LESS THAN 19mm FOR EVERY 3.0M 2. PROVIDE 1-16Ø VERTICAL BARS AT CORNERS, INTERSECTIONS, END OF WALLS AND EACH SIDE OF MASONRY WALL OPENING.
100 500 100 300
OF FREE SPAN. 3. LINTEL BEAMS SHALL BEAR AT LEAST 8 INCHES (200mm) ON EACH SIDE OF MASONRY WALL OPENING.

H
4. UNLESS OTHERWISE INDICATED IN THE PLANS, WALL REINFORCEMENT SHALL BE AS FOLLOWS: REFER TO DWG. NO. S-01
2. IF THERE ARE TWO OR MORE LAYERS OF LONGITUDINAL REINFORCING BARS IN A BEAM OR ORDER, USE D

REFER TO DWG. NO. S-01 FOR NOTES ON PREPARATION 3-10Ø LONGITUDINAL BARS
SEPERATORS OF A SIZE NOT LESS THAN 25mm BARS SPACED ABOUT 0.90M ON CENTER. IN NO CASE SHALL FOR NOTES ON PREPARATION OF SOIL SUB-BASE.
THERE LESS THAN TWO (2) SEPERATORS BETWEEN LAYERS OF BARS. CONCRETE HOLLOW BLOCKS REINFORCEMENT (CONTINUOUS) WITH TENSION SPLICE
OF SOIL SUB-BASE.
3. LONGITUDINAL REINFORCING BARFS SHALL BE PLACED SYMMETRICALLY ABOUT THE VERTICAL CENTER
D

DET. OF CHB ON SLAB THICKENING


LINE OF THE BEAM OR GIRDER SECTION WHERE POSSIBLE WITH UPPER LAYER BARS PLACED DIRECTLY REINFORCEMENT NOTES
DET. OF CHB ON TIE BEAM DETAIL OF WALL FOOTING
ABOVE THOSE IN THE BOTTOM LAYER. t (mm) A.MIN. LAP SPLICE = 0.25M
HORIZONTAL VERTICAL
4. MINIMUM CONCRETE PROTECTION OF REINFORCING BARS SHALL BE 38mm, B. PROVIDE RIGHT ANGLE REINFORCEMENT AT CORNER (FOR INTERIOR WALL)
5. BEAM REINFORCING BARS BOTH TOP AND BOTTOM TERMINATING IN A WALL SHALL EXTEND AT THE MOST 75 10Ø @ 0.60m O.C. 10Ø @ 0.60m O.C. 0.90M LONG. 135 DEG
50mm FROM THE FAR FACE OF THE WALL AND SHALL TERMINATE IN A STANDARD 90° HOOK. C. WHERE CHB WALLS ADJOINING COLUMN, R.C. BEAM,
100 10Ø @ 0.60m O.C. 10Ø @ 0.60m O.C.
6. BEAM REINFORCING BARS BOT TOP AND BOTTOM TERMINATING IN A COLUMN, SHALL EXTERND TO THE WALL DOWEL W/ SAME SIZE AS VERTICAL OR HORIZONTAL STIRRUP AND TIE-HOOKS
FAR FACE OF THE CONFINED CONCRETE CORE OF THE COLUMN AND TERMINATED BY A STANDARD 90°
150 10Ø @ 0.60m O.C. 10Ø @ 0.60m O.C.
REINFORCEMENT SHALL BE PROVIDED. 3 WALL FOOTING DETAILS
HOOK. S-01 Scale: 1:20
7. GENERALLY NO LAP SLPLICE SHALL BE PERMITTED ON BEAMS AND GIRDERS AT POINTS WHERE CRITICAL 200 10Ø @ 0.60m O.C. 10Ø @ 0.60m O.C.
BENDING STRESSES OCCUR. IN ADDITION, FOR GIRDERS, NO LAP SPLICE SHALL BE LOCATED WITHIN THE
JOINTS OR WITHIN THE DISTANCE EQUAL TO TWICE THE DEPTH OF THE MEMBER FROM THE FACE OF THE
JOINT.
8. PROVIDE LAP SPLICES ON GIRDER WITH HOOP REINFORCEMENT OVER THE LENGHT OF THE LAPPED BARS CONCRETE WALLS:
SPACED NO FARTHER THAN ONE-FOURTH OF THE NOMINAL DEPTH OR 100mm. UNLESS OTHERWISED INDICATED IN THE PLANS, WALL REINFORCEMENT
9. SEE MECHANICAL, PLUMBING, ELECTRICAL, AND FIRE PROTECTION DRAWINGS FOR ALL SUSPENDED PIPE SHALL BE FOLLOWED ACCORDING TO THE FOLLOWING SCHEDULE
AND EMBEODED PIPINGS, CONDUITS, DUCTWORKS, ETC.
REINFORCEMENT
WALL VERTICAL
STANDARD HOOKS STIRRUP AND TIE-HOOKS THK. REMARKS SECTION

D
HORIZONTAL VERTICAL
180 DEG 90 DEG 90 DEG 135 DEG

VAR.
D D HOR. & CENTER VERT.
BAR SIZE BAR SIZE 0.102m 10Ø @ 0.25m O.C. 10Ø @ 0.30m O.C.
(MM) A OR G J A OR G (MM) A OR G A OR G H BARS STAGGERED OUTSIDE
B

VAR.
10Ø 60 125 60 150 10Ø 40 105 105 65 0.127m 10Ø @ 0.20m O.C. 10Ø @ 0.25m O.C. - DO -
12Ø 80 150 105 200 12Ø 50 115 115 80 12Ø @ 0.25m O.C. BOTH FACES HOR.
0.152m 12Ø @ 0.30m O.C. SHALL BE INSIDE
16Ø 95 175 130 250
0.178m 12Ø @ 0.23m O.C. 12Ø @ 0.25m O.C. - DO -

D
20Ø 125 225 175 350
12Ø @ 0.30m O.C. BOTH FACES HOR.
0.208m 12Ø @ 0.30m E.F.
25Ø
32Ø
155
275
275
425
205
335
425
550 0.229m 12Ø @ 0.20m O.C. 12Ø @ 0.25m O.C. E.F.
SHALL BE OUTSIDE
- DO -
7 DETAIL OF SLAB ON FILL / GRADE
S-01 Scale: 1:10
0.254m 12Ø @ 0.30m O.C. E.F. 12Ø @ 0.30m O.C. E.F. - DO -
COLUMN: 0.275m 12Ø @ 0.25m O.C. E.F. 12Ø @ 0.30m O.C. E.F. - DO -
6 TIE BEAM (TB) DETAIL
1. WHERE COLUMNS CHANGE IN SIZE, VERTICAL REINFORCEMENTS SHALL BE OFFSET AT A SLOPE NOT MORE THAN 1 IN 6. PROVIDE S-01 Scale: 1:20
TRANSVERSE REINFORCEMENT (JOINT HOOPS) AS PER FIGURE PROVIDED IN SHEET NO. 2. 0.305m 12Ø @ 0.23m O.C. E.F. 12Ø @ 0.27m O.C. E.F. - DO -
2. LAP SPLICES, WHEN REQUIRED, ARE PERMITTED ONLY WITHIN THE CENTER HALF OF TEH COLUMN LENGHT AND SHALL BE PROPORTIONED
AS TENSION SPLICES. IN NO CASE SHALL THE LAP SPLICE BE LOCATED CLOSER THAT A DISTANCE EQUAL TO THE MAXIMUM COLUMN 0.356m 12Ø @ 0.20m O.C. E.F. 12Ø @ 0.25m O.C. E.F. - DO -
DIMENSION FROM THE FACE OF THE BEAM-COLUMN JOINT. PROVIDE EXTRA TRANSVERSE REINFORCEMENT OF THE SAME SIZE ARRANGEMENT
0.406m 12Ø @ 0.25m O.C. E.F. 12Ø @ 0.30m O.C. E.F. - DO -
INDICATED IN THE COLUMN SCHEDULE SPACED AT MOST ONE-FOURTH OF THE MINIMUM COLUMN DIMENSION THROUGHOUT THE LENGHT
OF THE SPLICE OR 100mm.
3. FOR ALL TIED COLUMNS, PROVIDE TRANSVERSE REINFORCEMENTS OF THE SAME SIZE AND ARRANGEMENT INDICATED IN THE COLUMN
SECTION SCHEDULE AND SPACED NO GREATER THAN ONE QUARTER THE MINIMUM COLUMN SECTION DIMENSION NOR 100mm. OVER A
DISTANCE FROM EACH JOINT FACE OF LESS NOT LESS THAN THE LARGER OF THE MAXIMUM COLUMN SECTION DIMENSION, OR ONE SIXTH
OF THE CLEAR HEIGHT OF THE COLUMN OR 450mm.
4. UNLESS OTHERWISE DETAILED, TYPICAL BAR DETAILS FOR TIED COLUMNS ARE AS SHOWN IN FIGURE PROVIDED IN SHEET. NO. 2.

1 STRUCTURAL NOTES
S-01 Scale: NTS

8 TYPICAL BEAM DETAIL


S-01 Scale: NTS

S-1
01
 



 





 



 

 

S-2
01
A B C D E A' A B C D E

1 1

2 2

3 3

3'

SECOND FLOOR

1 FOUNDATION PLAN 2 FRAMING PLAN


S-03 Scale: 1:100 S-03 Scale: 1:100

S-3
01
A' A B C D E A' A B C D E

1 1

2 2

3 3

3' 3'

THIRD FLOOR MEZZANINE

1 FRAMING PLAN 2 FRAMING PLAN


S-04 Scale: 1:100 S-04 Scale: 1:100

S-4
01
TRUSS 1 DETAILS

PURLINS (SEE ROOF FRAMING FOR


PURLINS SPACING)
Ø12 ROUND BARS AS SAGRODS WELDED
TO NEAR MID DEPTH OF PURLINS (TYP.)

L-50x50x3mm SEAT ANGLE WELDED TO


TRUSS TOP CHORD & LIGHT GAUGE
A' A B C D E PURLINS (TYP.)
STEEL TRUSS

2 TRUSS DETAILS
S-05 Scale: 1:75

1
CHB WALL

CHB WALL
10mmØ RSB @ 140mm O.C

LENGTH

150 125
275
25mm RAIN
LENGTH GROOVE

CHB WALL
2
WIDTH

3 TYPICAL DETAIL OF CANOPY/LEDGE


S-05 Scale: 1:20

15
0
10 MMØ NOSING BARS
3 10 MMØ TEMP. BAR 10 MMØ TEMP.
PLACE AS SHOWN 200 BAR @ 220MM O.C.
10 MMØ @ 12 MMØ @ 175MM O.C.
200MM O.C.

100
TOP & BOT. MAIN SEE SUSPENDED SLAB SCHED.
3'

600
E.F.

150
REBARS TYP.
10 MMØ NOSING BARS
12 MMØ @ 200MM O.C. E.F. 12 MM Ø @ 175 MM

300
10 MMØ TEMP. BAR @ O.C. B.W. TOP & BOT.
4-12 MMØ 12 MM Ø @ 200MM O.C. TO ALL 220 MM O.C. LANDING REBARS
CONTINUOUS 600 STAIRS

150
ROOF

1 FRAMING PLAN TYP. STAIR FOUNDATION DETAIL TYP. STAIR FLR LVL DETAIL
S-05 Scale: 1:100 Scale: NTS Scale: NTS

10 MMØ NOSING BARS 10 MMØ TEMP. BAR PLACE AS SHOWN

150
150
12 MM Ø @ 175 VERIFY 10 MMØ NOSING BARS
MM O.C. TOP & 12 MMØ @ 175 MM O.C. TOP & BOT.

150
BOT. MAIN MAIN REBARS TYP. TO ALL STAIRS
REBARS TYP. TO SEE SUSPENDED
ALL STAIRS SLAB SCHED.

115
12 MMØ @ 175 MM O.C. B.W. TOP &

150
BOT. LANDING REBARS

TYP. STAIR LANDING DETAIL TYP. STAIR START-UP DETAIL


Scale: NTS Scale: NTS

S-5
01