Professional Documents
Culture Documents
Electric Fire Pump 20Lps@1500kPa - Grundfos
Electric Fire Pump 20Lps@1500kPa - Grundfos
Multistage centrifugal pump with inlet and outlet port on same level (inline). Support plates on pump base and drive
end enables horizontal mounting. The pump head and base are in cast iron – all other wetted parts are in stainless
steel. The Grundfos cartridge shaft seal ensures high reliability, safe handling, and easy access and service. Power
transmission is via a rigid split coupling. Pipe connection is via DIN flanges.
The pump is fitted with a 3-phase, fan-cooled asynchronous motor.
Liquid:
Pumped liquid: Water
Liquid temperature range: -20 .. 120 °C
Selected liquid temperature: 20 °C
Density: 998.2 kg/m³
Technical:
Pump speed on which pump data are based: 2950 rpm
Actual calculated flow: 20 l/s
Pump with motor (Yes/No): Y
Resulting head of the pump: 15.91 bar
Pump orientation: Horizontal
Shaft seal arrangement: Single
Code for shaft seal: HQQE
Rotating seal face material: Q, SiC
Stationary seal face material: Q, SiC
Elastomer in shaft seal: E, EPDM
Approvals: CE,EAC,UKCA,SEPRO
Approvals for drinking water: ACS,WRAS
CE approved (Yes/No): Y
cURus approved: N
USA MEPS (CC marking): No
China MEPS (CEL): No
South Korea MEPS (Kemco): No
Curve tolerance: ISO9906:2012 3B
Electropolished: No
Pump cleaned and dried: No
Colour of the pump: RAL 9004
Report, vibration: No
Report, motor test: No
Report, cleaned pump: No
Report, electropolished pump: No
Report, material quality: No
Materials:
Base: Ductile cast iron
EN 1563 EN-GJS-500-7
ASTM A536-84 65-45-12
Base plate: Ductile cast iron
Impeller: Stainless steel
EN 1.4301
AISI 304
Pump flange material: Ductile cast iron
Bearing: WC/WC
Support bearing: Graflon
Material certified according to: European standards
Installation:
Maximum operating pressure: 25 bar
Max pressure at stated temp: 25 bar / 120 °C
Electrical data:
Motor standard: IEC
IE efficiency class: IE3
Rated power - P2: 45 kW
Over/undersize motor: Standard motor size
Mains frequency: 50 Hz
Rated voltage: 3 x 380-420D/660-725Y V
Service factor: 1
Number of poles: 2
Built-in motor protection: PTC
Controls:
Frequency converter: NONE
Pressure sensor: N
Others:
Air vent position: 9 o'clock
Terminal box position: 9
Minimum efficiency index, MEI ≥: 0.7
Net weight: 532 kg
Gross weight: 678 kg
Shipping volume: 2.04 m³
Thrust handling device: N
CR 95-6 H-F-A-E-HQQE 50 Hz
H CR 95-6, 3*400 V, 50Hz eta
[bar] [%]
18
16
14
12
10 100
8 80
6 60
4 40
2 20
150 % Q
Q = 30 l/s
H = 11.7 bar
0 0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 Q [l/s]
Q = 20 l/s H = 15.91 bar
Pumped liquid = Water Liquid temperature during operation = 20 °C
Density = 998.2 kg/m³ Eta pump = 77.5 %
P2 NPSH
[kW] [bar]
40 2.0
30 1.5
20 1.0
10 0.5
0 0.0
P2 = 41.05 kW
NPSH = 0.25 bar
CR 95-6 H-F-A-E-HQQE 50 Hz
235
22
190
8x
150
573.4
100
419
350
40
18.5
4x
4 X G 1/2
G 1/2
450
225
380
449
275
338
G 1/2
N/A
140
708 1238
CR 95-6 H-F-A-E-HQQE 50 Hz
1238
290
177
60
172
Ø14
65
256
482
370
311
640
23
354
Ø19,5