From 15A NCAC 02T .0114 Average Daily Flow (gallons per day) 202,305
Design Pumping Flow Rate
Peak Factor = 18 + √P
4 + √P
Calculated Peak Factor = 2.0
Design Peak Factor = 2.5
"Only
Pressure Head at Proposed
Pressure Head Connection "Only Pump
at Connection Proposed Pump Static Head "All On" Station On" Pump Head
GPM "All On" (feet) Station On" (feet) (feet) TDH (feet) TDH (feet) Velocity (fps) (feet)
100 14 0 20 37 23 0.6 245
300 16.6 0.4 20 59 43 1.9 197
600 20.8 1.4 20 123 103 3.8 135
900 25.5 2.9 0 199 176 5.7 74
1200 30.5 5 0 326 301 7.7
Horsepower: 35