OWNER PMC EPCC :
PHASE III UPSTREAM SURFACE FACILITIES
PROJECT – PKG-2: KEYI FPF
LIGHTING CALCULATIONS Engg. Sub-contractor
1.0 GENERAL
1.1 Purpose
The purpose of this calculation is to determine the number of indoor and outdoor lighting
fixtures necessary to meet required illumination levels for all designated areas.
1.2 Objective
The objective is to use Chalmlite version 4.0 lighting software to determine the number of
fixtures required for all areas. The Chalmlite printouts for representative areas are shown in
Attachment. 1
The lighting system shall provide adequate illumination to all necessary areas of the site.
Outdoor process lighting fixtures are EEx-“e”, IIA/IIB, T3, IP55 min, 1x400W flood lighting,
HPSV type mounted on 10m height poles.
Shelters, platforms and tank ladders lighting fixtures are EEx- “e”, IIA/IIB, T3 IP55 min, 2
x36W fluorescent type, bracket or 3m above platform pole mounting height.
Emergency generator shelter and fire water pump station request 30 min. battery backup
2x36W fluorescent lighting fixtures.
Associated gas compressors shelter lighting fixtures are EEx-“e”, IIA/IIB, T3, IP55 min
1x150W HPSV pendant mounted type.
Indoor lighting fixtures for maintenance shop are 1x250W HPMV pendant mounted type.
1.4 Definitions
Other Codes:
• IES Lighting Handbook
OWNER PMC EPCC :
PHASE III UPSTREAM SURFACE FACILITIES
PROJECT – PKG-2: KEYI FPF
LIGHTING CALCULATIONS Engg. Sub-contractor
5.0 CALCULATIONS
For indoor lighting calculation the Lumen (or Zone Cavity) method is used software to
estimate the number of lamps which give the illumination level requested.
Number of luminaires:
E•A
N=
F • MF • UF
Where:
E = required average illumination level in Lux
A = area considered in m2
F = initial lamp lumens
MF = maintenance factor
OWNER PMC EPCC :
PHASE III UPSTREAM SURFACE FACILITIES
PROJECT – PKG-2: KEYI FPF
LIGHTING CALCULATIONS Engg. Sub-contractor
UF = utilization factor
For outdoor lighting calculation the Point-by-Point method is used software to estimate the
number of lamps which give the illumination level requested.
F • MF
E= • cos 3 θ
h2
Where:
E = required average illumination level in Lux
F = initial lamp lumens for angle θ
MF = maintenance factor
h = mounting height (in metres)
cos θ = angle between vertical and point where illumination value must be calculated
cosinus
6.0 ATTACHMENTS
ATTACHMENT – 6.1
ATTACHMENT – 6.2
Engg. Sub-Contractor
DOC: KE3-CAL-ELC-0908-6078
PHASE III UPSTREAM SURFACE FACILITIES KEYI FPF PROJECT
ATTACHMENT 2 - Lighting Calculation Results Summary
Qty of
Required Designed
No. Location Type of Lighting Fixtures Lighting Remarks
Lux Level Lux Level
Fixtures
A INDOOR
1 Control Room 300 318 2 x 36W decorative, mirror optic, 10 Att. 6.1.1
fluorescent fixture
1 x 18W emergency lighting 4
equipped with 30min battery backup
2 Equipment room 200 240 2 x 36W decorative, mirror optic, 6 Att. 6.1.2
fluorescent fixture
1 x 18W emergency lighting 2
equipped with 30min battery backup
3 400V Switchgear room 200 212 2 x 36W fluorescent fixture 10 Att. 6.1.3
industrial type
1 x 18W emergency lighting 2
equipped with 30min battery backup
4 AC UPS room 200 220 2 x 36W fluorescent fixture industrial 4 Att. 6.1.4
type
5 Battery room 150 170 2 x 36W fluorescent fixture suitable 2 Att. 6.1.5
for Zone 2, IIC, T3 EEx-"e" type
8 Meeting room 200 234 2 x 36W decorative, mirror optic, 3 Att. 6.1.8
fluorescent fixture
1 x 18W emergency lighting 1
equipped with 30min battery backup
9 Prayer room 200 495 2 x 36W decorative, mirror optic, 2 Att. 6.1.9
fluorescent fixture
11 Mud room 150 328 2 x 36W decorative, mirror optic, 1 Att. 6.1.11
fluorescent fixture
1 of 3
Qty of
Required Designed
No. Location Type of Lighting Fixtures Lighting Remarks
Lux Level Lux Level
Fixtures
12 Changing room & toilet 200 376 2 x 36W decorative, mirror optic, 3 Att. 6.1.12
fluorescent fixture
13 Pantry & mess 150 186 2 x 36W decorative, mirror optic, 1 Att. 6.1.13
fluorescent fixture
16 Guard room 200 340 2 x 36W decorative, mirror optic, 3 Att. 6.1.16
fluorescent fixture
B OUTDOOR
1 Overall outdoor lighting 27 Att. 6.1.17
2 Tank farm area 5 - 10 20 flood light with 10m pole, SON-T 4 Att. 6.1.18
lamp 4 x 400W, suitable for Zone 2,
IIA/IIB, T3 EEx- "e" type
flood light with 10m pole, SON-T 2
lamp 3 x 400W, suitable for Zone 2,
IIA/IIB, T3 EEx- "e" type
3 Separators area 50 51 flood light with 10m pole, SON-T 1 Att. 6.1.19
lamp 4 x 400W, suitable for Zone 2,
IIA/IIB, T3 EEx- "e" type
flood light with 10m pole, SON-T 1
lamp 3 x 400W, suitable for Zone 2,
IIA/IIB, T3 EEx- "e" type
4 Inlet manifold area 50 73 flood light with 10m pole, SON-T 2 Att. 6.1.20
lamp 3 x 400W, suitable for Zone 2,
Eex- "e" type
5 Other outdoor areas flood light with 10m pole, SON-T 3+2 1. fire water
lamp 2 x 400W , suitable for Zone 2, area
IIA/IIB, T3 EEx- "e" type 2. emergency
flood light with 10m pole, SON-T generator area
lamp 4 x 400W , suitable for Zone 2, 3.flare knock
IIA/IIB, T3 EEx- "e" type out
4.heating
medium area
5. vent pit +
flare
6 Associated gas 150 147 1 x 150W SON-E fixture suitable for 14 Att. 6.1 21
compressors skids Zone 2, IIA/IIB, T3 EEx - "e" type
shelter
7 Crude oil export pumps 150 180 2 x 36W fluorescent fixture suitable 6 Att. 6.1.22
shelter for Zone 2, IIA/IIB, T3 EEx-"e" type
8 Fire water pumps 150 173 2 x 36W fluorescent fixture equipped 4 Att. 6.1.23
shelter with 30min battery backup suitable
for Zone 2, IIA/IIB, T3 EEx-"e" type
2 of 3
Qty of
Required Designed
No. Location Type of Lighting Fixtures Lighting Remarks
Lux Level Lux Level
Fixtures
3 of 3