EPCC :

OWNER PMC DOC. NO. :KE3-DST-ELC-0908-6040


PHASE III UPSTREAM SURFACE
PROJECT
FACILITIES PROJECT

REV.
PAGE 2 OF 3

DATA SHEET FOR LV MOTOR UPTO 250 KW Engg. Sub-Contractor :


REV. 0
(TAG NO: PM-6931 A/B)
1
2 SERVICE
3 MANUFACTURER MODEL SERIAL NO.
4 NO. REQUIRED DRIVEN EQUIPMENT
5
6 MOTOR DESIGN DATA
7 APPLICABLE SPECIFICATIONS VIBRATION
8 IEC60034 NEMA STANDARD IEC 60034
9 OTHER GEN-SPC-ELC-6110 VIBRATION MONITORING
10 SITE DATA PROBE TYPE
11 ALT (m) 520 AMB TEMP (C) MAX 50 MIN 13 PROVISION FOR PROBES
12 RELATIVE HUMIDITY (%) MAX 68 MIN 14 SWITCH
13 INDOORS OUTDOORS WINTERIZATION NOISE
14 DUST FUMES TROPICALIZATION NEMA STANDARD GEN-SPC-MEQ-4050
15 OTHER THRUST
16 DRIVE SYSTEM MAX MOTOR THRUST (lb.)
17 DIRECT CONNECTED GEAR
18 OTHER
19 MOTOR ACCESSORY EQUIPMENT
20 SQUIRREL CAGE INDUCTION NEMA DESIGN B(equivalent) BASE PLATE SOLE PLATE STATOR SHIFT
21 SYNCHRONOUS MFG STD FANS NON-SPARKING FANS

22 POWER FACTOR REQ'D


23 BRUSHLESS SLIP RING
24 FIELD DISCHARGE RESISTOR BY MOTOR MFG
25 WOUND ROTOR INDUCTION
26 OTHER ENCLOSED COLLECTOR RINGS
27 ENCLOSURE PURGED MEDIUM PRESS (psig)
28 ZONE 2 GROUP IIA / IIB, T3 EXPLOSION RESISTANT, NONPURGED
29 TEFC EXPLOSION PROOF FORCED VENTILATION
30 WEATHER PROTECTED - I WEATHER PROTECTED - II FLOW (cfm) PRESS DROP (in. H2O)
31 FORCED VENTILATION OPEN DRIP PROOF BEARING TEMPERATURE DEVICES
32 TEWAC REQ'D NOT REQ'D
33 OTHER Minimum EEx-"e" LOCATION
34 FOR HAZARDOUS AREA CLASSIFICATION REFER MECHANICAL DESCRIPTION
O
35 DATA SHEET ALARM SET @ (OC) SHUTDOWN SET @ ( C)
36 DEGREE OF PROTECTION : IP55 (MINIMUM) SPACE HEATERS (FOR MOTORS RATED 30 KW & ABOVE)
37 BASIC DATA POWER (kW) VOLTS 230 PH 1 Hz 50
38 VOLTS 400+10% PHASE 3 HZ 50+ 5% MAX SHEATH TEMP (OC)
39 NAMEPLATE kW SERVICE FACTOR 1 WINDING TEMPERATURE DETECTORS
40 SYNCHRONOUS SPEED (rpm) THERMISTORS (no./phase)
41 INSULATION CLASS F TYPE TEMP COEFFICIENT: POSITIVE NEGATIVE
O O
42 TEMP RISE ( C) 70 ABOVE ( C) 50 BY Resistance TEMPERATURE SWITCH YES NO
43 STARTING RESISTANCE TEMP DETECTORS (no. / phase)
44 FULL VOLTAGE REDUCED VOLT (%) RESISTANCE MAT'L Platinum OHMS
45 LOADED UNLOADED SELECTOR SWITCH & INDICATOR BY:
46 VOLTAGE DIP (%) PURCHASER MANUFACTURER
47 SYS IMPED (R % + jX %) @ MVA VOLT MAXIMUM STATOR WINDING TEMPERATURES:
O O
48 XFORMER IMPED (Z %) @ MVA VOLT ALARM ( C) SHUTDOWN ( C)

49 PRIMARY VOLTAGE SECOND. VOLTAGE WINDING TEMPERATURE DETECTOR / SPACE HEATER LEADS

50 FEEDER TYPE Armoured Cables SIZE IN SAME TERMINAL BOX


51 NO./PHASE LENGTH (ft) IN SEPARATE TERMINAL BOXES
52 OTHER MOTOR ARRANGED FOR DIFFERENTIAL PROTECTION
53 Cable data to be advised after award of order SELF BALANCE PRIMARY CURRENT METHOD

54 C.T. DESCRIPTION
55 EXTENDED LEADS LENGTH (ft)
56 OTHER
57
58 REMARKS
59
60
61
EPCC :
OWNER PMC PHASE III UPSTREAM DOC. NO. : KE3-DST-ELC-0908-6040
1
PROJECT SURFACE FACILITIES

REV.
PROJECT PAGE 3 OF 3
2
Engg. Sub-Contractor :
DATA SHEET FOR LV MOTOR UPTO 250 KW
REV. 0
3
(TAG NO: PM-6931 A/B)
4
5 SERVICE
6 ACCESSORY EQUIPMENT (continued) MANUFACTURER'S DATA (continued )
7 SURGE CAPACITORS YES NO EXCITATION FIELD RHEOSTAT FIXED RESISTOR REQ'D.
8 LIGHTNING ARRESTORS YES NO SUPPLIED BY
9 CURRENT TRANSFORMER FOR AMMETER YES NO BEARINGS TYPE LUBRICATION GREASE
10 DESCRIPTION LUBE OIL REQ'D (USgpm) @ (psig)
11 MAIN TERMINAL BOX SIZED FOR: (During detail engineering) TOTAL SHAFT END FLOAT (mm)
12 MAIN MOTOR FEEDER SIZE NO. / PH. LIMIT END FLOAT TO (mm)
13 WIRING METHOD MOTOR ROTOR SOLID SPLIT
14 CT's FOR DIFF. PROTECT MTD BY MOTOR HUB SOLID SPLIT
15 SURGE CAPACITORS MTD BY FOR TEWAC & TEIGF MOTORS
16 LIGHTNING ARRESTORS MTD BY COOLING WATER REQ'D (USgpm)
17 CT FOR AMMETER MOUNTED BY C.W. TEMP RISE ( OC) PRESS DROP (psig)
18 SPACE FOR STRESS CONES AIR/GAS REQ'D (scfm) PRESS MAINT (in. H2O)
19 AIR FILTER CURVES REQ'D BASED ON MOTOR SAT. @ RATED VOLTAGE

20 MFG TYPE SPEED vs TORQUE (also @ 80 and 100 % RATED VOLT)


21 SPEED vs POWER FACTOR ACCELERATION
22 MANUFACTURER'S DATA SPEED vs CURRENT DAMAGE (cold & hot)
23 MANUFACTURER EQUIPMENT WEIGHTS
24 FRAME NO. FULL LOAD RPM (ind) NET WT (kg) SHIPPING WT (kg)

25 EFFICIENCY (full load) (3/4 L) (1/2 L) ROTOR WT (kg) MAX ERECT WT (kg)
26 POWER FACTOR (ind)(FL) (3/4 L) (1/2 L) MAX MAINT. WT (IDENTIFY) (kg)
27 CURRENT (rated volt)(FL) LOCKED ROTOR EQUIPMENT DIMENSIONS
28 LOCKED ROTOR POWER FACTOR LENGTH (m) WIDTH (m) HEIGHT (m)
29 LOCKED ROTOR STALL TIME (cold)
30 TORQUE (kg-m)(full load) SHOP INSPECTION AND TESTS
31 LOCKED ROTOR STARTING (syn) REQUIRED WITNESS
32 PULL-UP (ind) PULL-IN (syn) SHOP INSPECTION
33 BREAK DOWN (ind) PULL-OUT (syn) TESTING
34 OPEN CIRCUIT TIME CONSTANT (Sec) MFG STD SHOP TESTS
35 SYMMETRICAL CONTRIBUTION TO 3 PH TERMINAL FAULT AT: IMMERSION TEST
36 (1/2 cycles) (5 cycles)
37 REACTANCE X''d X'd Xd
O
38 AC STATOR RESISTANCE (ohms) @ C
39 RATED KVA
40 KVA INRUSH @ FULL VOLTAGE and LOCKED ROTOR (syn)(%)
41 KVA @ FULL VOLTAGE & 95 % SPEED (%)
42 MAX LINE CURRENT IN STATOR ON 1st SLIP CYCLE @ PULL-OUT (syn) 1 COUPLING
43 SUPPLIED BY EQUIPMENT VENDOR
44 ACCELERATION TIME (motor only @ rated voltage)(seconds) MFG MODEL
45 ACCELERATION TIME (motor & load @ 85 % rated volt)(sec) MOUNTED BY MOTOR MFG PURCHASER
46 ROTOR / FIELD WR2 @ MOTOR SHAFT (kg m 2) MANUFACTURER OF DRIVEN EQUIPMENT
47 ROTATION FACING COUPLING END PAINTING
48 MAX. NO. OF STARTS PER HOUR MANUFACTURER'S STANDARD
49 FIELD DISCHARGE RESISTOR (ohms) GEN-SPC-MEQ-8200
50 RATED EXCITATION FIELD VOLTAGE(volts DC)
51 RESISTANCE OF EXCITATION FIELD @ 77 OF (ohms) SHIPMENT
52 EXCITATION FIELD @ FULL LOAD & RATED P.F.(amps) DOMESTIC EXPORT EXPORT BOXING REQ'D
53 EXCITATION FIELD (MAX)(amps) (MIN)(amps) OUTDOOR STORAGE OVER 6 MONTHS
54 RECOMM MAX POWER FACTOR CORRECTION CAPACITOR (kvar) OTHER
55 MOTOR GD2
56

57 REMARKS
58 1. VENDOR TO COMPLETE THE DATA SHEET AND SUBMIT ALONG WITH BID DOCUMENTS.
59 2. VENDOR TO FURNISH THE MAXIMUM POSSIBLE CABLE SIZE THAT CAN BE ACCOMMODATED IN THE MOTOR TERMINAL BOX. INCREASED SIZE OF
60 TERMINAL BOX, IF REQUIRED, SHALL BE INFORMED DURING TECHNICAL EVALUATION.
61 3.THE STARTING CURRENT OF MOTOR SHALL NOT EXCEED 7 TIMES THE RATED CURRENT FOR THE MOTORS RATED 37KW AND BELOW,
62 FOR THE MOTORS RATED ABOVE 37 KW THE STARTING CURRENT SHALL NOT EXCEED 6 TIMES THE RATED CURRENT
63
64
65
66
67
68
69
70
71
72
73
74
75
76