OWNER PMC
PKG-2 : KEYI FIELD PRODUCTION FACILITIES
TABLE OF COMPLIANCE REPORT FOR
230V AC UPS SYSTEM
Engg. Sub-Contractor
TBE DOCUMENT NO. : KE3-TBE-ELC-0908-6094 REV. C DATE : 28/03/10
BIDDER NAME :
S. NO. REFERENCE NO. : ENQUIRY REQUIREMENT Beijing Zhengzhuo Engg /Socomec REMARKS
DATE :
1 General
1.1 Service AC UPS Comply
1.2 Tag No. UPS -6801 Comply
1.3 Quantity 1 set Comply
2 Design Data
2.1 Make Vendor Data Socomec
Microprocessor based control system, Parallel
2.2 Type/Model Vendor Data Redundant configuration with active load sharing
(Model:DELPHYS DS)
2.3 Installation Indoor, non-hazardous air conditioned room Comply
2.4 Rating @ 0.8p.f 16 kVA 20kVA
2.5 Rated output voltage 230V ±1%, 1 Ph, 2W Comply
2.6 Rated output frequency 50Hz ± 1% Comply
2.7 Inverter Output voltage adjustment range at rated load Vendor Data 230V AC +/- 1%
2.8 Inverter Input voltage DC (Nominal/ Range) Vendor Data 306V - 451V C
2.9 Harmonic distortion at inverter output at rated load (For linear load) Vendor Data <2%
2.10 Harmonic distortion at inverter output at rated load (For non linear load) Vendor Data <3%
BIDDER NAME :
S. NO. REFERENCE NO. : ENQUIRY REQUIREMENT Beijing Zhengzhuo Engg /Socomec REMARKS
DATE :
2.11 Dynamic response under following conditions:
For 50% step load Vendor Data +/-2%
For 100% step load and unload Vendor Data -4% to +2% C
Power supply interruption & restoration Vendor Data <5msec
Load transferred to bypass line Vendor Data 0msec
One inverter gets faulty and load transfer to healthy inverter Vendor Data 0msec
2.12 Maximum recovery time to reach steady state after above disturbance Vendor Data 5msec
2.13 Isolation Transformer at invertor output Required Comply
2.14 Method of changeover (Load transfer) By static switch Comply
2.15 No. of static switch in each UPS Vendor data 1
2.16 Bypass regulated transformer Required Comply
2.17 Static switch for bypass circuit Required Comply
2.18 Maintenance Bypass switch Required Comply
2.19 Overall efficiency of UPS system
At 100% load Vendor Data 94.40%
At 75% load Vendor Data 94.00%
At 50% load Vendor Data 93.30%
At 0% load Vendor Data 90.80%
2.20 Overload capacity and duration Vendor Data 150% for 1 min, 125% for 10 min
2.21 Current rating of battery charger in A Vendor Data 106
2.22 Output voltage of battery charger under float / rapid charging condition in V Vendor Data 392/451
BIDDER NAME :
S. NO. REFERENCE NO. : ENQUIRY REQUIREMENT Beijing Zhengzhuo Engg /Socomec REMARKS
DATE :
Alarm, control, indication & metering requirements as per Datasheet for UPS
2.25 Required Comply
system (Doc.No.KE3-DST-ELC-0908-6062).
2.26 Type of cooling Vendor data Fan ( n+1)
2.27 Cable entries Bottom Comply
2.28 Colour shade Vendor data RAL7012
2.29 Overall dimensions(LXWXH) & Weight in mm x mm x mm, Kg
UPS Vendor data 3800x800x1930, 1680
Battery rack Vendor data 4200x720x1300 ( For each battery bank)
2.30 Battery bank weight in Kg Vendor data 2839(For each battery bank & associated racks)
3 Scope of Supply:
Design, manufacturing, assembly, painting, inspection & testing, packing &
3.1 Required Comply
shipping of 230VAC UPS system with battery
Vendor support for Supervision of installation, start up and commissioning on
3.2 Required Comply
per diem basis
3.3 Start up & Commissioning Spares Required Provided
3.4 Spare parts for two years continuous operation Recommended list with price Provided
3.5 Special Tools & Tackles Required (if any) Not required
3.6 Drawings / Documents as per MR Required Comply