Professional Documents
Culture Documents
Bu1 Week 3
Bu1 Week 3
Bu1 Week 3
The size of service pipe connecting the main and the house being
served is governed by the:
A. Maximum demand and the
B. Probable demand or peak load
Example:
One urinal has 5 fixtures (see table below)
5 x 8 gallons = 40 gallons - the maximum demand of water supply per minute.
Determine the maximum demand and the probable demand of water for the
following fixtures installed:
Solution:
Solving for the total fixture units as base on the table above.
6 x 3 water closets = 18 units
2 x 3 lavatories = 6 units
2 x 1 kitchen sink = 2 units
2 x 3 shower = 6 units
--------------------
Total 32 fixture units
20 89.0 300 240 200 160 150 140 130 120 110 100
30 133.4 300 300 240 200 180 160 150 140 140 130
40 178.0 300 300 280 240 220 200 180 160 160 150
50 222.4 300 300 300 280 240 220 200 200 180 160
Notes
A. Doubling the diameter of pipe line increases its capacity up to 4 times.
B. A 20 mm service pipe can supply 2 branches at 13 diameter each it
could deliver up to 10 gals/min. Sufficient enough to served up to 10 fixtures.
C. A 25 mm service pipe can supply 2 branches at 20 diameter. It can
deliver up to 18 gals/min and serve 20 fixtures.
C. CHECK VALVE - are used when it is desired that the flow through a
pipe be always in one direction and there is a probability of a flow taking place
in the opposite direction.
SWING CHCEK VALVE - has a pivoted flap which is readily pushed open by
the pressure of water from one side but is tightly closed by the force of a
reverse flow.
FAUCETS:
The normal water pressure for residential houses ranges from 133 to
178 newtons (30 to 40 psi) . lower than this value may result in insufficient
flow of water particularly during simultaneous use of fixtures, likewise, water
pressure higher than 222 newtons (50 psi) may cause pipe hammering or
even bursting of the pipe connection.
1. An upfeed supply riser with the return circulation taken at a point just
below the highest fixture connection. For building of moderate height.
ZONING
When the water supply of very tall buildings is design as a unit, the
required capacities of tanks, pumps, and piping become unduly large and
excessive pressures are develop in lower portion of the down-feed risers. The
building therefor is divided into horizontal section or by zones and to design
the hot and cold water supply system separately for each zones.