technical brochure 686
Mitigating the effects of arcs
in M.V. switchgear
Members
D. Fulchiron, Convenor (FR), G. Kachelrieβ, Secretary (DE), A. Brandt (DE),
L. Del Rio Etayo (ES), J. Douchin (FR), T. Du Plessis (ZA), A. Gardner (US), M. Grote (DE),
T. Hintzen (DE), J. Kjønås (NO), J. Meehan (CA), I. Ndiaye (US), M. Palazzo (CH),
S. Singh (DE), P. Skryten (NO), Y. Tits (BE), K. Tsuchiya (JP)
Figure 1 - Typical event sequence of an active arc mitigation system, arc extinguisher (AE)
results in the Brochure for the mitigation of arcs in MV 1. Gas flow as the main phenomenon during arcing,
switchgear. resulting in extremely hot and toxic gasses that
need to be vented out of the faulty compartment of
The survey was performed in May 2015 via the CIGRE the MV switchgear;
National Committees and 43 responses from 11 countries 2. Sound waves generated by the sudden expansion of
were received. The aim of the survey was to obtain the users the plasma volume of the arc;
experience feedback on arc events in MV switchgear, user 3. The radiated light from the arc;
requirements for arc resistance switchgear, the experience 4. Pressure rise and pressure release as a function of
on mitigating arc effects, and the impact on safe working the arc duration in the faulty compartment and
practices when using arc mitigation techniques. This survey MV switchgear room where applicable;
assisted the workgroup to understand the international 5. Arc burn through of steel enclosure walls;
application and consideration for arc mitigation systems. 6. Material vaporization and burning of materials due
to the arc;
Description of the technical 7. Pollution of the MV switchgear faulty compartment,
adjacent compartments and room due to the gas
brochure flow pollutants;
8. Switching room overpressure, contamination,
The Brochure consists of ten chapters and one annexure. toxicity exposure, and thermal damage;
The statistical results of the survey performed are not 9. People safety;
provided in this article, but makes an interesting study for 10. Distribution system interruptions and plant health.
comparing the international best practises implemented
thus far. The main outcome for the Brochure chapters can Defining these effects provides the basis for the
be summarised as follows: mitigation review and engineering considerations required
thereof in the next chapters of the Brochure.
Effects of arcs in mv switchgear
The chapter 3 covers the effects of arcs in MV switchgear. Active arcs mitigation strategies
Arcs in MV switchgear are known to be caused for The two main categories for arc effects mitigation
various reasons as described in the Brochure and article strategies are: Passive arc effect mitigation and Active arc
introduction, and the effects thereof may lead to the and arc effect mitigation. Passive arc mitigation is the
destruction of the MV switchgear and the endangering of MV switchgear equipment natural designed behaviour to
human lives. take care of or limit the arc effects when they occur, and
include also building design and ducting considerations
The following effects of arcs in MV switchgear are for the environment wherein it will be installed. Active
considered in this Brochure: arc mitigation strategies are the additional provision •••
Figure 2 - Typical current limitation by an active arc mitigation system, arc extinguisher (AE)
In this chapter the benefits and drawbacks are discussed Performance assessment
for both active and passive arc mitigation strategies. This The performance assessment of arc mitigation systems
informs and provides the user on the evaluation of which is not clear in any international standard at present. This
solution to select in order to obtain the optimal benefit chapter explore the options of component, system or
for mitigating the effects of arcs in MV switchgear. Special global solutions testing, to assess and rate the performance
caution shall always need to apply to ensure the solutions of various arc mitigation type solutions. Containerised
selected do not lead to an increased arc effects risk. See pressure test chambers are some of the latest developments
also chapter 8. identified in the global solution test field to analyse and
validate pressure behaviour during internal arc events and
the mitigation thereof. The four synthesis approaches •••
BROCHURE N° 686
(en anglais seulement)
www.e-cigre.org
Prix non-Membres / Non-Member Price:
150 e
Purchase (non-members)