Update Power Distruibution and circuit loadings

Circuit Voltage AC Amps Load Kw Available PV KW Installed PV kW verter out serv


Maternity 240-120 16 9,6 4 X 3.2KW 12,8 1
Maison 240-120 5
Emergency 240 3
Café 240-120 5
Surgery 240-120 20 5 5 X 2kW 10 1
Neo Natal 240-120 10 6,4 2 X 3.2kW 9,6 1
Clinic 120 4 1 X 3.5kW 3,5 2
Stock containe 240-120 3,4
Admin 240-120 1,5
Internal 240-120 2
Gen Room 120 2
Gen Room-Battery inverter mini grid 30 5 x 10kW 50 2
TOTAL 71,9 51 85,9 7

There is a 56% reduction in capacity of solar power generation.


The power demand is 71,9 Kw
In photo voltaic energy we have 85.9 kw installed, but of this, we use 35.9 as backup power

Budget
Description Cost $US
Automation and control with power transfer switches 3000
Thermal protections 500
Distribution panel-accessories 23500
Change of units inverte in faults 16500
Construction of a three-phase network with inverters and neutral to ground. 3000
Repair of investors to keep in reserves. 2500
Installation of a new generator to increase availability. 25000
Miscellaneous 5000
Testing and replacement of batteries for inverters 8500
Kit Generator repair 110Kw 4000

TOTAL 91500

July 21 2018