Electrical A3

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

GENERAL NOTES :

1. ALL ELECTRICAL WORKS AND INSTALLATION SHALL COMPLY W/ THE PROVISIONS


A B C D A B C D OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE W/ THE RULES AND
REGULATION OF THE NATIONAL AND LOCAL AUTHORITIES CONCERN.
2. SERVICE VOLTAGE TO THE UNIT SHALL BE 230 VOLTS,60 HERTZ, SINGLE PHASE
3. SWITCHES SHALL BE INSTALLED 1.4MTS FROM FIN. FLOOR AND CONVENIENCE OUTLETS AT 0.30MTS
COUNTER TOP OUTLETS SHALL BE INSTALLED 0.20M IN HEIGHT FROM COUNTER TOP FINISH.
5 5 4. ALL MATERIALS TO BE USED SHALL BE NEW AND APPROVED TYPE APPROPRIATE FOR
LAUNDRY
LAUNDRY
AREA
BOTH LOCATION AND INTENDED USE.
AREA
5. ELECTRICAL INSTALLATION SHALL BE UNDER THE DIRECT SUPERVISION OF A DULY LICENSED
MASTER
MASTER BEDROOM
4
BEDROOM
4 ELECTRICAL ENGINEER OR A REGISTER MASTER ELECTRICIAN
KITCHEN
DINING
AREA
6. NO REVISION IN THE DESIGN SHALL BE DONE WHO THE PRIOR KNOWLEDGE & APPROVAL
KITCHEN DINING
AREA
T&B 1
T&B 1 OF THE DESIGNER AND THE OWNER ANY SUCH REVISION DONE W/O APPROVAL SHALL
CAUSE RESPONSIBILITY OF THE DESIGNER TO CEASE AS A WHOLE.
3 3
BEDROOM 1
BEDROOM 1 LIVING
LIVING AREA
AREA
SERVICE ENTRANCE
T&B 2
T&B 2
2 2 M kW-hr Meter
PORCH
PORCH BEDROOM 2
BEDROOM 2
2
2 - 14 mm THHN/ THWN Cu WIRE
1 1 2
IN 32 mm Ø IMC
MAIN PANEL
VALEROS' RESIDENCE MAIN:
VALEROS' RESIDENCE
POWER LAYOUT LIGHTING LAYOUT
SCALE: 1:100M
60 AT
SCALE: 1:100M
LIGHTING 15 AT 15 AT LIGHTING
1 2
15 AT 15 AT
LIGHTING 3 4 LIGHTING
20 AT 20 AT
C.O 5 6 C.O
30 AT 20 AT
ACU 7 8 KITCHEN OUTLET
20 AT 20 AT
SPARE 9 10 SPARE
NEUTRAL BUS
2
1 - 5.5 mm THHN
GROUND BUS
COPPER WIRE
GROUND
SINGLE LINE / RISER DIAGRAM
SCALE NTS
POWER LAYOUT -----------------------------
VALEROS' RESIDENCE LIGHTING LAYOUT E-01
LOAD SCHEDULE
PROFESSIONAL ELECTRICAL ENGINEER
LEGENDS & SYMBOLS
JONATHAN J. VALEROS
DES IGN + B UILD
----