Total Air Solution Provider

http://www.lg.com/vn/business
http://partner.lge.com |
Ha Long Shophouse, Lot D2 -06, Ha Long Marine Plaza, Bai Chay - Tel: 02033900369

ÐIỀU HÒA TRUNG TÂM LG LG Vietnam


10 ADVANTAGES
OF MULTI V

5 SMART
CONTROLS 6 BUSINESS
SUPPORT
MULTI V responds to diverse building - Engineering Tools & Support
environments with LG ThinQ-based - LG Air Conditioning Academy
AI control and individual/central - Asia Regional HQ
integrated control solutions.

1 ULTIMATE
EFFICIENCY 3 SUPERIOR
DURABILITY 4 DESIGN
FLEXIBILITY

7 9 10
Ultimate Energy Saving with LG’s exclusive “Black Fin” Flexible Installation with
Dual Sensing Control. heat exchanger is designed Large Capacity Outdoor Unit. DIVERSE
to perform even in corrosive
Environments.
MULTI V 5 enables easy type PRODUCT
change-over to suit the purpose
of any building.
LINE UP MADE IN BRAND
Hydrophilic film
LG offers a specialized product
KOREA RELIABILITY
Acryl + Epoxy +
Melamine resin lineup suited for various
business environments, perfectly LG MULTI V line-up emphasizing Global production sites facilitate
Humidity Temperature Aluminum fin
responding to the unique high quality and durability with world-class customer service.
conditions no matter the use case. Korea made products.

2
Certified protection

INNOVATIVE
TECHNOLOGIES
8 DIVERSE
INTEGRATED
SOLUTION
MULTI V 5 Integrated solution optimized for
- Ultimate Inverter Compressor Verification of corrosion resistance performance various business environments,
- Declared by TUV Rheinland
- Biomimetics Technology Fan - Test Method B of ISO9227.2017 including hot water, AHU, BMS,
- Test condition : Salt contaminated condition
+ seve re in d u stria l/tra ffic
environment
and EMS.
Scroll Compressor

001 / 002
WHY LG MULTI V

MULTI V BRAND HISTORY INFRASTRUCTURE IN ASIA

2017 ~

· Dual Sensing Control


2013 · U lt im a t e In v e r t e r
Compressor
· O n e U n if ie d P l a tf o r m
· A c t iv e R e f r ig e ra n t
2010 Control
Heat pump & Heat
recovery
· Va ria b le H e a t E x c h a n g e r LG Vietnam Air Conditioning Academy LG Whisen Park
· Black Fin
Circuit
· High Pressure Oil Return LG academy is supposed of LG showroom which LG home appliance LG Air conditioning Academy is a key infrastructure for the
· Smart Load Control and air conditioning projects are displayed and LG practice room company’s Total Climate Control business. HVAC business
2008 · Vapor Injection
· Smart Oil Return which we instruct LG HVAC product knowledge and software as differs from ordinary air conditioning businesses in that as a B2B
· Continuous Heating well by using directly with LG displayed materials. sector, the three elements of sales, installation and service must
· Va p o r In je c t io n
(Advanced)
come together to create good results.
· Ø7.0 Wide louver
2006 · LGDC Inverter

· Heat Recovery
· Ø7.0 Corrugate
· Fuzzy Algorithm
· AC Inverter
· R410A

Since the time when LG launched Korea’s first residential air MULTI V’s wide range of VRF solutions satisfies various building
conditioner in 1968, the company has worked to continuously types and sizes. MULTI V S’s size discharge was designed Germany
Canada
UK Poland
enhance its technological innovation and reliability. As a for small to mid-sized buildings while MULTI V Water is a Russia

result of sustained improvement, LG VRF launched the first water-cooled VRF solution with variable water flow control Italy Hungary
Korea
USA
France
generation of MULTI V in 2006 and achieved significant technology. Kazakhstan
China
development. With the best-in-class compressor technology
and innovation applied to every part and control solution, In 2017, the ultimate VRF solution was introduced with MULTI V 5. Jordan

MULTI V has evolved to be on of the world’s most efficient This generation has fully improved its technological potential
and reliable VRF solutions. with the powerful and reliable yet economical Ultimate Inverter GF
Vietnam
Panama
Compressor, effective corrosion resistance with the Ocean
Thailand
India

The first and second generations of MULTI V boasted inverter Black Fin coating and enlarged fans. Dual Sensing Control Philippines

Nigeria
technology and non-ozone depleting technology, while MULTI V III was offers the most pleasant indoor environment while minimizing Singapore
Colombia

produced with cutting edge tech like oil return with HiPOR TM unnecessary energy loss by sensing both temperature and
and double compression features with mid-pressure refrigerant humidity to efficiently manage cooling, heating and part load. Kenya
Indonesia

allowed by Vapor Injection. The innovative technologies of


MULTI V’s fourth generation brought about product leadership MULTI V 5 has been designed for the ultimate efficiency, Hub
in efficiency. Its Smart Load Control adjusts with the outdoor performance, flexibility, comfort and control, ensuring the most Brazil

Regional
temperature, while optimizing refrigeration management and pleasant indoor experience.
South Africa
heat exchange for both cooling and heating.
Local
Australia

Branch

003 / 004
WHY LG MULTI V

ENGINEERING TOOLS & SUPPORT


From planning to service & maintenance and then to de-construction, an architectural project goes through many stages from 01 Draft Energy Estimation
the beginning to the end of its lifecycle. Along those stages, various engineering tools are applied to solve the diverse issues
happening in each stage, with the most optimal solution possible. Given the usage of such tools, buildings are effectively LATS Energy
designed, built, supervised, and maintained throughout their lifecycle. LATS Energy is a program developed by LG to estimate energy consumption and
Dedicated to provide the best HVAC engineering support, LG Electronics Air Solution Business Unit offers several engineering analyze the life cycle cost of LG commercial air conditioning systems during a
tools and solutions focused on HVAC, during the overall lifecycle of a building, related to the three categories. Among them, the project's early stages.
LATS* Program series has been developed to offer the best tool for LG HVAC systems, providing our customers with a solution
that allows for faster, easier and more accurate model selection, draft energy estimations and more.
* LATS : LG Air-conditioner Technical Solution
02 Building Energy Modeling
eQuest, EnergyPro, Trace700 and More
These are certified commercial programs which assess the HVAC system efficiency
and building’s annual energy savings for building standards or certifications,
like LEED. LG HQ supports these programs for the project stages of Design
Development and Construction Design where in the overall designing is finished.

03 Model Selection
I II III LATS HVAC
LATS HVAC is a model selection program that accurately and quickly selects the
Energy Estimation Model Selection Installation most suitable LG commercial air conditioning systems for each design.
In addition to model selection, faster estimation on refrigerant piping diameter
& Energy Modeling & Design Environment
and additional refrigerant is possible, along with auto printing of reports.
Simulation

04 Design
LATS CAD
01 Planning LATS CAD enables faster and more accurate 2D design of LG commercial air
conditioning systems. It also enables modules for quotation and installation
LATS review that minimize inherent problems during installation and commissioning.
Energy
AutoCAD program is required.

02 Schematic Design LATS REVIT


LATS REVIT allows BIM users to have an attractive 3D design of LG commercial
LATS air conditioning systems with embedded calculations for refrigerant and efficiency
HVAC features.
AutoCAD Revit program is required.

03 Design Development
Energy
Modeling LATS CAD
- eQUEST
- TRNSYS
Ⓡ LATS REVIT
05 Environment Simulation
CFD CFD Analysis
04 Construction Design - FLUENT
CFD Analysis is applied in areas of estimating : indoor airflow and temperature
distribution while operating VRF products, outdoor airflow distribution, and
noise level. By running a simulation before construction, engineers estimate
possible issues and find optimal solutions for malfunctions that could occur after
construction.
05 Construction

06 Service & Maintenance


LGMV
LGMV offers real-time MULTI V cycle monitoring. During start-up, LGMV can
06 Service & Maintenance LGMV
check for normal operation as well as troubleshoot any errors. Also it helps to
find causes of errors and solve the problem faster.

005 / 006
WHY LG MULTI V

BENEFITS OF LG MULTI V

Benefits for Benefits for


Building Owners Consultants
Efficient Management & Cost Reduction Versatile Solutions
- Fault Detection Diagnosis enables easy maintenance - Air-cooled, Water-cooled, Heating, and Air Handing
- Requires no extra manpower for regular Unit interlocking solutions
maintenance
- With diverse control systems, maintenance cost is
Professional Design Support
minimized
- LATS (LG Air-conditioner Technical Solution) for
Reliability at Every Stage draft energy estimation, model selection, HVAC
- Ultimate Inverter Compressor developed and design and 3D designing
manufactured in Korea - CFD Analysis to ensure suitable solutions and
- Corrosion resistant Ocean Black Fin for harsh prevent malfunctions
conditions operation - Energy simulation offered to find the optimal
- Smart Oil management (Auto Oil Balancing and solution
Active Oil return) decreases compressor damage
Optimized Convenience with HVAC Design
Customized Comfort and Solution - F le x ib le a n d lo n g e r p ip in g le n g t h f a c ilit a t e s
- Compatible option between Heat pump and Heat HVAC designing process
recovery system is possible - M e e t s a n y t y p e o f c u s t o m e r re q u i re m e n t s o f
diverse environment, design conditions, and
building applications

Benefits for Benefits for


Developers & Construction Companies End-users

Green Solutions Cost Saving Operation


- Optimized for LEED/BREEAM certification - High efficiency guaranteed throughout product
- Renewable energy solution provided through line-up
geothermal application - Up to 31% cost savings with MULTI V's Smart
Load Control*
Maximizing Space Utilization
- Large capacity in compact size enhances space
utilization Comfort Cooling & Heating
- Smart Load Control maximizes indoor comfort level
- Dual Sensing Control offers pleasant and
Smart Building Solutions comfortable cooling and heating environment
- Seamless integration with current Building - Duration time of Continuous Heating is 11%
Management Systems longer than previous model**
- Wi-Fi control available for anytime, anywhere
access (via the 'LG ThinQ' mobile app) Convenient Functions
- Energy management and control according to - Low-noise operation provides a pleasant
usage and planning is possible with LG’s centralized environment
control solution

* Dual Smart Load Control ESEER based, below 50% humidity, model ARUM260LTE5
** LG internal test result

007 / 008
WHY LG MULTI V

APPLICATION SOLUTIONS

Office Residential
Supporting efficiency with flexibility Creating a comfortable home

High Rise Office Building Small to Medium sized Office Building Apartments

• MULTI V WATER IV • High Static Duct • Va ria b le w a t e r f lo w


• MULTI V 5 / S • 4 Way CST** • PDI • MULTI V 5 • 1 Way CST • PDI
• DX AHU • PDI* control kit

The MULTI V series revitalizes the workspace by providing fresh air at all times. LG's intelligent control solutions add comfort MULTI V 5 HP with various IDU enables optimal solution, providing comfort to every space through individual zone control
to any space. and hot water solution.

Commercial Hospitality
Maximizing business, minimizing cost Meeting diverse needs

Shopping Mall Retail Quick Service Restaurant (QSR)

• MULTI V • MULTI V • H Y D R O K IT
• MULTI V 5 • DX AHU • M U LT I V 5 • DX A H U • H Y D R O K IT • L o w S t a t ic D u c t • R e m o t e c o n t ro l • R e f r ig e ra n t l e a k d e t e c t o r
• ERV • ERV • 4 W ay C S T

The highly efficient, energy saving MULTI V 5 and MULTI V reduces operation costs, and provides comfort that suits any The diverse applications that can be applied to MULTI V 5 helps bring just the right solution to a sophisticated hotel business.
purpose and any space, helping to invest the extra space and expense to your business.

* PDI : Power Distribution Indicator ** CST : Cassette

009 / 010
WHY LG MULTI V

DIVERSE INTEGRATED SOLUTION DIVERSE INTEGRATED SOLUTION


Air Handling Unit (AHU) Solution Refrigerant Leak Detection Solution Energy Management Solution Interlocking Solution
AHU is a suitable solution for cooling and heating in large space. Real-time refrigerant leak detection ensures a safe environment. Since HVAC systems use a significant portion of any building’s total by Using ACU Module
With an LG AHU Comm. Kit (for both return air / supply air control) When refrigerant concentration exceeds 6,000ppm for 5 seconds, amount of energy, the energy saving functions of a controller can make a
It is costly to introduce a BMS system to control multiple devices or
connected to the DX coil of the AHU, LG VRF system can be applied to the indoor unit will stop operation and alert users with a buzzer or big difference. The energy navigation function enables you to set target
systems in a small building. With the ACU module, various IO contact
deliver conditioned air. light switch (Dry contact option). values for energy consumption over a certain period of time. In addition,
points (DI, DO, UI, AO) can be interlocked and integrated, while control
to achieve that value, the administrator can set the energy saving logic
is possible from the LG central controller. This enables an efficient
MULTI V 5 in 7 steps and predict the expected usage relative to the target value.
Outdoor Unit ROOM management of lighting, pumps and other devices in the building in
Active self-management enables energy savings through out the building.
Buzzer Alarm conjunction with the HVAC system.
Card Key
MULTI V 5
Outdoor Unit Saving Engineering Cost

I/O Module
70% Pump Lighting Fan Sensor
Strengthen
Maintenance Efficiency
Compressor Capacity IDU Operation IDU Operation
Ball Valve Control Ratio Control Level
ACS IO Module
(Field supply)

Refrigerant Remote
Detector Controller
EEV Signal
Target
AC Smart (ACP)
Communication Regulation : EN378, BREEAM, ASHRAE Std. 15 & 34
Forecasting
Kit Indoor Unit
EEV Kit

Power Consumption Distribution Solution Interlocking Solution Using Dry Contact


In case of shared power consumption in a building, a solution to 3 rd party thermostats can be used to control LG air conditioners in a
Ref. pipe (Liquid) distribute the power consumption amount per tenant might be room by using a multi point dry contact. The dry contact enables basic
Ref. pipe (Gas)
necessary. Electricity charges can be billed to each tenant by using control of air conditioners as well as making it possible to report the
Communication
output from the LG Power Distributor Indicator (PDI). An administrator status and any errors impacting the indoor unit.
AHU
is able to check the power usage for each space and date as needed. Integration Solution with BMS The Standard III remote control has a DO port. With this DO port, it
If the PDI is used in conjunction with an LG central controller, the results
There are many BMS protocols used for the control of buildings’ various is possible to interlock the indoor unit with 3 rd party devices such as
can be exported to Excel.
B Office systems such as HVAC, lighting, power and security. LG has a wide lighting, a fan, or a radiator, based on things like operation mode or
20 kWh
WHM range of gateway products for different protocols such as BACnet, current temperature.
C Office
(Watt Meter)
30 kWh D Office Modbus, and LonWorks. In addition, LG gateways include Stand-alone
Total Control of Any Device
Pulse Signal The indoor unit can be interlocked with various types of input such as
A Office
20 kWh central control capability to act as a back-up controller of the BMS if
30 kWh card key-tag, door sensor, human detection sensor etc. so that the air
In order to manage multiple spaces and multiple buildings, needed. conditioner is automatically operated. In addition, the dry contact
the administrators should be able to control systems from wherever option settings enable operation of air conditioner to maintain proper
they are. The LG central controller can be controlled from any web PDI
Small - Medium size building Medium - Large size building temperature when the occupant is absent. This solution makes sure
Power
browser that supports HTML5. Now through the implementation of that the room does not overheat or become too cold when unoccupied
100 kWh
HTML5, the interface will look great and perform well on any device. IDU ~64 : ACP LonWorks so that energy cost can be saved.

IDU ~128 : AC Smart 5


IDU 16~64 : Modbus RTU
(BACnet IP/Modbus TCP)

IDU ~256 : ACP 5


(BACnet IP/Modbus TCP)

Management office Library Main administration building BMS Protocol


BMS System
PC Tablet Mobile

011 / 012
LINE-UP

OUTDOOR UNITS LINE-UP


Unit : HP / ● 380V, 3Ø

Features Appearance 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 .... 104

● ● ●

● ● ● ● ● ● ●

● ● ● ● ● ● ● ● ● ● ● ● ● ●
• Dual Sensing Control
• Large capacity ODU (Up to 96HP)
• Continuous Heating
• Black Fin heat exchanger ● ● ● ● ● ● ● ● ● ● ● ●
• Heat pump function
• For large space, high rise building and
individual control building

● ● ● ● ● ● ● ● ● ● ● ●

013 / 014
OUTDOOR UNITS _ MULTI V 5 _ KEY FEATURES

INNOVATIVE TECHNOLOGIES INNOVATIVE TECHNOLOGIES


Dual Sensing Smart Load Control (SLC) Energy Savings with Dual Sensing Control Comfort Cooling Extended Compressor Speed
Enhanced energy saving & increased indoor comfort (Temperature & Humidity) Increased indoor comfort & enhanced operating efficiency from 10 Hz to 165 Hz
Cooling loads vary according to both temperature and humidity. Case study First reference use Indoor Unit (IDU) is operating in a season when
With Dual Sensing SLC, work exerted to meet the load depends its load is less than the design load, the comfort cooling algorithm
Weather characteristics of Warsaw, Poland
on both temperature and humidity. As a result, less capacity will be controls the indoor unit’s coil superheat, thus raising the discharged
The portion of cooling operation hours at low humidity condition (Below
required in lower humidity conditions. air temperature as the space temperature is approaching set point.
50% RH) is big. The cooling load of this condition is less than the load at 165 Hz
MULTI V 5’s comfort control algorithm monitors the outdoor air
It influences the VRF system main processor’s decision on where to standard (50 ~ 70% RH) or high (over 70% RH) humidity condition even in
temperature and humidity conditions. When changing weather
set the system’s target high or low system pressure values. the same outdoor air temperature. MULTI V 5 raises the evaporating Temp
up at low load (Low humidity) condition to enable energy saving and prevent conditions are deteriorating and there is a high potential the indoor
over-cooling which can happen when the system is controlled only by using unit’s load will remain stable or may increase, comfort cooling delays 10 Hz
Smart Load Control responds to : outdoor air Temp. or abandons raising the target superheat as the room temperature
1) Outdoor ambient dry bulb temperature approaches set-point. When changing weather conditions are 15 Hz
Warsaw weather in Summer
2) Outdoor ambient relative humidity (when enabled) favorable to raising target superheat, target superheat is moderated. Previous
Cooling Indoor Units - adjusts target low pressure
90% Model
150 Hz
What are the benefits?
80% High Humidity
Raises the target low pressure value as cooling load falls and/or ambient temperature falls.
70% ~ 100%
Lowers the target low pressure value as cooling load rises and/or ambient temperature rises.
70%
Increased indoor comfort

Relative Humidity
Heating Indoor Units - adjusts target high pressure
Lowers the target high pressure as heating load falls and/or ambient temperature rises.
60%
Mid Humidity
50% ~ 70%
SLC
Dual
Sensing
If comfort cooling is turned off, and the temperature of the leaving air is not
Enhanced Bearing with PEEK Material
for Increased Durability and Reliability
SLC
Raises the target high pressure as heating load rises and/or ambient temperature falls. 50%
raised, when the fan speed is reduced to low speed, there is a potential that
Low Humidity
40% 0% ~ 50% occupants located directly under a cassette IDU or supply air registers could
What are the benefits? feel cold air falling on them resulting in a lower overall comfort experience.
30% (Polyetheretherketone) bearing used for aero engine
Enhanced energy savings With comfort cooling turned on, the discharged air temperature is controlled.
20%
When the IDU controller reduces the fan speed, the potential for cold air falling
- Cooling Mode 23°C 25°C 27°C 29°C 31°C 33°C 35°C
on occupants located under the cassette IDU or supply air registers is reduced.
By raising the target low pressure during off-peak cooling operation, the Source : Outdoor Air Temperature
https://energyplus.net/weather
compressor lift is reduced. This slows compressor’s speed which leads to a
Time Portion of Relative Humidity in Summer
Enhanced operating efficiency
decrease in compressor’s power consumption.
(Warsaw, Poland) Raising superheat reduces refrigerant volume flowing through the coil.
- Heating Mode
RH (%) Portion As flow decreases, demand on the compressor decreases and the
By lowering the target high pressure during off-peak heating operation, the
compressor speed will be reduced, thus saving energy.
compressor lift is reduced. This slows compressor’s speed which leads to a 70% ~ 100% 8%
decrease in compressor’s power consumption. 50% ~ 70% 45%
Previous Model
0% ~ 50% 47%
Increased indoor comfort
Smart Load Control uses one (or two) sensors to measure changing outdoor
weather conditions and prepares the VRF system for operation under
the revised weather conditions before changing conditions impact indoor
Energy Consumption in Cooling Season Repeated on & off
Comfort &
Continuous Cooling
comfort. When we compared the energy consumption between SLC (Outdoor air
Temp sensing only) and Dual sensing SLC (Outdoor air Temp and humidity
Cooling load according to Cooling load according to
temperature change humidity change sensing), Dual sensing SLC control can save 6% more energy compared to
SLC. So dual sensing control is more efficient than SLC.
Cooling Load

Cooling Load

Cooling Mode Fan Mode Cooling Mode

EER Indoor unit set up available with Standard III Remote Controller.
MULTI V 5 SLC
MULTI V 5 Dual Sensing SLC 9 .4 9 .4
9.2
9.0 Preventing cold draft & repeated turn On / Off
8.1 8.6
25°C 30°C 35°C Temperature 40% 60% 80% Relative 7.9
Humidity Improved Indoor Comfort
Latent heat load Sensible heat load 6.9 6.9
Constant indoor temp condition 6.0
Indoor temp
Cooling Load
Previous Cooling Capacity

For low temperature, Adjusting capacity


to meet load
lower load and
Actually 31°C ~ 29 ~ 31°C 27 ~ 29°C 25 ~ 27°C 23 ~ 25°C Not cool
capacity are required External Load zone
Required
Cooling
Outdoor Air Temperature
Internal Load
Capacity
This energy simulation was performed in LG internally based on 16HP model.
Temperature & Humidity
Evaporation Temperature
Low Humidity
Power Consumption in Cooling Season
SLC
Yearly Power Input (kWh) - ODU
Lower load and Comfort
OAT MV4 (Fixed) MV5 SLC MV5 Dual SLC zone Set
capacity need High Humidity
temperature
higher evaporation 31 ~ 17 15 13
Outdoor
temperature Standard Temperature (°C) 29 ~ 31 91 73 62
(Non SLC)
Low Temperature High Temperature 27 ~ 29 183 136 124

Efficiency 25 ~ 27 243 170 165


Too cool
Low Humidity zone
23 ~ 25 155 110 109
SLC
Total 690 (137%) 503 (100%) 474 (94%)
Higher evaporation
High Humidity
temperature results 6% more energy saving
Standard compared to SLC Time
in higher efficiency (Non SLC) Previous Model
Outdoor
Temperature (°C)
Low Temperature High Temperature

015 / 016
OUTDOOR UNITS _ MULTI V 5 _ KEY FEATURES

INNOVATIVE TECHNOLOGIES INNOVATIVE TECHNOLOGIES


Variable Path Heat Exchanger Active Refrigerant Control HiPOR TM Sub-cooling & Vapor Injection
Optimized system efficiency & continuous heating Stable operation & sustaining most efficient operation Advanced compressor reliability & efficiency Increased heating performance
MULTI V 5 outdoor units (ODU) are manufactured with horizontally The accumulator in the outdoor unit has a storage tank mounted HiPOR™ is an LG trademark that stands for High Pressure Oil Return. MULTI V 5 is equipped with advanced sub-cooler and vapor injection
split ODU coil consisting of two independent circuit sections. inside known as the receiver tank. The receiver tank is equipped It consists of an oil separator, oil drain line between the separator and the control system. The sub-cooler algorithm sub-cools liquid refrigerant
Each half of the coil is independently controlled. with inlet and outlet valves that are electronically opened and compressor. HiPOR™ technology enables oil to return directly into the just enough so that it can travel to the farthest IDU in the system
This split coil feature makes it possible for MULTI V 5 to provide closed. Refrigerant is being passed between the accumulator compressor, instead of returning through the refrigerant suction pipe. operating in cooling mode without changing state. During low
continuous heating during defrost. The split coil and valve and the receiver tank on a continuous basis. MULTI V 5 active This prevents energy waste when oil flows between the separator ambient operation down to -25°C (Heating mode), the sub-cooler
arrangement also makes it possible for the MULTI V 5 to change refrigerant control algorithm goal is to minimize the amount of and the compressor. Because the operating pressure in the chamber provides medium temperature refrigerant gas to the compressor’s
the flow path of refrigerant through one of the two coils only, or refrigerant in circulation. The lower the volume in circulation the containing the oil sump of the compressor and the pressure in the oil vapor injection system. When injected into the compression
through both coils in either a series or parallel arrangement. lower the cost to move it around the system and the higher the separator are nearly equal, there is no loss in compressor efficiency. chamber, system mass flow increases which stabilizes the system’s
Based on system pressures, ambient temperature conditions, and stability of the refrigeration cycle. It accomplishes this by constantly suction pressure. In all cases the vapor injection increases the
monitoring the system operating pressures and temperatures and What are the benefits? compressors cycle efficiency and reduces operating cost.
mode of operation, the system controller may modify the selected
a variety of other vital control metrics of the refrigeration cycle. Maximizes reliability and efficiency of the compressor.
path at any time.
When the cycle is out of balance, an adjustment in the amount of Non HiPOR ™ HiPOR™ What are the benefits?
circulating refrigerant occurs. Compressor
1 Refrigerant Provides stable refrigeration cycle operation over a wide range of outdoor
What are the benefits? 3 ambient operating conditions.
4
Optimizes system efficiency regardless of operating modes as ambient weather Increases compressor efficiency when compared to systems without vapor
conditions change. What are the benefits? Efficiency Increase
Up to 33%
injection technology.
Customizes the used area of the outdoor unit’s heat exchange surface.
Widens the ambient temperature range at which stable operation occurs. 2

Oil Technology Mechanism


Low ambient cooling and / or light building load Sustains most efficient system operation regardless of outdoor weather 5

conditions, operating mode, or building load.


• Half active High-pressure
Non HiPOR ™ HiPOR™
• Lower idle Low pressure High pressure Oil Low pressure High pressure Oil Low-pressure
Cooling Heating Part Load refrigerant Compressor refrigerant Separator refrigerant Compressor refrigerant Separator
1 2 3 4 1 2 3 4

Amount of refrigerant
Full load cooling in receiver
• Upper & lower active 5 Energy loss in suction gas No energy loss in suction gas 5

• Series circuited • LG Internal Test result,


• High velocity refrigerant flow • Test condition - 15Hz Rating Condition : TC = 37.9°C, Te : 7.2°C

Heating - all conditions Smart Oil Management Mid-pressure


(Vapor injection port)
• Upper & Lower active Energy saving, enhanced heating & increased compressor reliability
• Parallel circuited
• Low velocity refrigerant flow MULTI V 5 performs oil return when needed under normal operating
IDU (Heating)
conditions. An oil level sensor is provided in every LG VRF compressor.
If the sensor indicates the compressor oil level is low, the main system
Efficiency
processor is notified that an oil return cycle is necessary. Oil balancing
EEV
Heating cycle occurs every hour and does not hinder system performance.
It balances the oil level deposit between both compressors in multi- High temp
discharge
compressor frames. Older VRF technology protects compressors from
Cooling Non-receiver tank
oil loss based on timed oil return logic because there was no way to
Fixed refrigerant amount Control optimized Refrigerant amount
Maximized efficiency know if the oil level in any one compressor was low. LG’s unique oil level MID-stage Injection
SC
Series Half Active Parallel measuring sensor actively monitors the oil level in each compressor. HEX
Low temp
Efficiency
Continuous Heating
What are the benefits? suction

Fixed refrigerant type Energy savings : fewer oil return cycles eliminate unnecessary energy
Heating performance
consumption.
Increases system heating run-time during winter operation.
Heating ODU Coil
efficiency 3% Increases compressor reliability.

Part load Heating Performance Smart Oil Return


Heating supply
efficiency 10% Performance Comparison
On On
Heating performance
Heating Heating Heating

Oil Oil
Non heating Non heating Non-Vapor Injection
Time
27 %
Timed oil return logic (Non-oil Sensor) Oil Level Sensor Oil
Effect of partial defrost
Increased heating operation time per day Auto Oil Balancing Up to
: Up to 12% -25°C
• LG Internal Test result,
Cooling
efficiency • Test condition
- without oil level sensor : -25 -20 -15 -10 -5 0 7 11 15
Time Active Refrigerant Control
Non-Partial defrost Refrigerant quantity (kg) every 8 hour oil recovery operation Oil Outdoor temp(°C)
- with oil level sensor : Improved heating performance by 27%.
non oil recovery operation Comparison tested on 10HP model.
Oil Level Sensor

017 / 018
OUTDOOR UNITS _ MULTI V 5 _ KEY FEATURES

INNOVATIVE TECHNOLOGIES DESIGN FLEXIBILITY


Corrosion Resistance Black Fin Biomimetic Fan Flexible Installation with Wider Operation Range
Improved durability Maximized performance Large Capacity Outdoor Units Able to operate at extreme conditions
The black coating with enhanced epoxy resin is applied on the heat The fans in MULTI V 5's outdoor unit have been upgraded to feature More flexible design potential & space saving With improved inverter cooling technology, sub-cooling and vapor
exchanger for strong protection from various corrosive external a moire pattern similar to that of a clam shell's exterior that help with injection, MULTI V 5 offers an extended range of heating and cooling
Large capacity outdoor units of MULTI V 5 minimize installation
conditions such as salt contamination and air pollution. noise reduction. At the same time, unlike the fans installed in previous operations. It can perform normal heating operations at temperatures
space that spares valuable floor space and significantly decreases
Moreover, the hydrophilic film keeps water from accumulating products that generate separation of flow due to absence of tubercles, as low as -25°C. Cooling operations function at temperatures as low as
total installed weight. This gives users more flexible design potential
on the heat exchanger’s fin, minimizing moisture buildup and the bumpy back design inspired by the bumps on the humpback -15°C or as high as 48°C making it an adequate solution for specialized
and better use of the saved space.
eventually making it even more corrosion resistant. whale’s flipper is applied as the tubercles on the back side of the fans, areas like technical rooms. Moreover, MULTI V 5’s cycle technology
LG Corrosion Resistance solution passed ISO 9227:2017 ASTM B117 increasing wind power by reducing flacking. In addition to the biomimetic with enhanced durability enables optimal cooling performance at high
accelerated corrosion test conducted by an independent test organization technology-based fans, extended shroud of MULTI V 5 allows more high temperature that increases up to 48°C.
and the result has been certified by prestigious global certification static pressure and helps fans to blow higher air volume for efficient
organization, TUV. operation. With wider air guide, discharged air current is stabilized and Previous Model
Outdoor air temp (°C WB)

noise level is reduced. 18°C


What are the benefits?
This improvement in durability prolongs the product’s lifespan and lowers both What are the benefits?
the operational and maintenance costs. Based on the biomimetic technology, the fans of MULTI V 5 increased air
flow rate by 10% in comparison to previous model and reduced its power
consumption up to 20% when compared with the fan blade design on
MULTI V IV. This eventually results in maximized performance with large capacity. 23 % 15 %
Reduction Reduction
-25°C
10°C 15°C 20°C 27°C

Heating Indoor air temp(°C DB)


12.25m 2
9.42m 2
3,640kg 3,100kg

Outdoor air temp (°C DB)


Previous Model Previous Model

Foot print area Product weight 48°C

Humpback 43°C
Comparison basis : 1 Rows of outdoor units 728kW (72.8kW x 10sets) installation case
Whale Design

Previous Model
Clam Shell
Pattern
-10°C

-15°C

10°C 14°C 25°C 27°C


Cooling Indoor air temp (°C WB)

Verification of corrosion resistance performance


- Declared by TUV Rheinland
- Test Method B of ISO 9227:2017
- Test condition : Salt contaminated condition
+ seve re in d u stria l/tra ffic
environment(NO 2 / SO 2 )

Hydrophilic film (Water flow)


The Hydrophilic coating minimizes moisture
buildup on the fin.
Acryl + Epoxy + Melamine resin
(Corrosion resistant)
The Black coating provides strong protection
from corrosion.
Aluminum fin
Air flow rate Power consumption

m /min
3
W

320 1,500
20%
10%
290

1,200

Previous Model Previous Fan Design

Comparison based on 20HP model Comparison based on air volume of 290m 3/min

019 / 020
Multi V 5 Outdoor Units

OUTDOOR UNITS _ MULTI V 5 _ KEY FEATURES 10. Sound


OUTDOOR UNITS Levels
_ MULTI V 5 _ TECHNICAL DATA

USER-FRIENDLY CONTROL 10.1 Sound Pressure Level


Multi
MultiV 5V 5 Outdoor
Outdoor
Units
Units
Position of Sound Pressure Level Measuring Cooling / Heating Operation
9.9.Operation
OperationLimits
Limits
Low-Noise Operation Simple Test Run via LGMV Note
Cooling
Cooling
Cooling / Heating
/ Heating
Operation
Operation Heating
For noise sensitive environment Increased overall efficiency in installation • Data is valid at free field condition
• Data
50°Cis valid at nominal operating condition
20°C
48°C
Unlike the previous model which enables Low-Noise Operation To make sure that the product functions properly, conducting a test run • Sound
18°C
45°C level will vary depending on a range of
15°C
only during night after judgment time, the Low-Noise Operation of is recommended. For previous product, professional engineer who is well- factors such as the construction(acoustic
40°C
MULTI V 5 can function regardless of the time at the noise sensitive aware of more than 40 different functional settings and more than 200 1m
absorption coefficient) of particular10°C
room in

Outdoor Temperature (°C WB)


Outdoor Temperature (°C DB)
35°C
areas. When used, the speed of the outdoor unit fans is restricted error codes had to check main parts in order to make sure that the test which the equipment is installed

Range for warming up operation


Range for continuous operation

Range for continuous operation


Range for pull down operation
30°C 5°C
during normal operation. run had succeeded. With Mobile LGMV of MULTI V 5, fast and accurate 1m
• Sound level can be increased in static
25°C
auto test run can be executed and the professional installer running the pressure mode or used air guide. 0°C
Previous Model test can receive test results via email, which shortens installation hours • Data is valid at free field condition.
20°C

15°C -5°C
and increases overall efficiency in installation processes. • Data is valid at nominal operating condition.
• Sound level will vary depending on a range of factors such as the
10°C Unit:dB(A)
-10°C
Previous construction (Acoustic labsorption
e d coefficient)
o M of particular room in g n i l 5°C o o C g n i t a e H
which the equipment is installed.
5 E T L 0 8 0 M 0U . R8 5A 0°C 0 . 9 5
-15°C

• Sound level can be increased in static pressure mode or used air guide. -5°C
Load 5 E T L 0 0 1 M 0U . R8 5A 0 .-20°C9 5
-10°C
5 E T L 0 2 1 M 0U . R9 5A 0 .-25°C0 6
-15°C
5 E T L 0 4 1 M 0U . R0 6A 10°C 14°C 15°C 20°C 25°C 27°C 30°C 0 . 110°C 6 15°C 20°C 25°C27°C 30°C
Sound level Off Outdoor Units Function
5 E T L 0 6 1 M 5U . R0 6A Indoor Temperature (°C WB) 5 . 1Indoor6Temperature (°C DB)
Category Functions MULTI V 5 Note
Note
(Judgment time) Low-noise operation time 5 E T L 0 8 1 M 0U . R1 1. 1.These
6AThesefiguresfigures
assume
assumethethe following
following
operating
operatingconditions:
conditions: 0 . 2 6
Variable Path of Outdoor Unit HEX ○ Note
5 E T L 0 0 2 M 0U . R2 1.Equivalent
6A Equivalent piping
piping
length:7.5m
length:7.5m
These figures assume the following operating conditions 5 . 4 : 6
HiPOR TM (High Pressure Oil Return) ○ Level
Leveldifference:0m
difference:0m
Equivalent piping length : 7.5m
Humidity5 SensorE T L 0 2 2 ○M 5U . R4 6ALevel difference : 0m 5 . 5 6
On Key Refrigerant 2. 2.
RangeRange of pull
of pull
down
downoperation:
operation:
Components If the
If the
relative
relative
humidity
humidityis too
is too
high,
high,
cooling
cooling
capacity
capacity
cancan
be be
decreased
decreasedby by
thethe
sensible
sensible
heat
heat
reduction.
reduction.
6:00 12:00 13:00 18:00 21:00 0:00 6:00 Corrosion5Resistance
E Black
T Fin L 0 4 2 ○M 0U . R5 2.6ARange of pull down operation :
If the relative humidity is too high, cooling capacity 0 can. be7decreased 6 by the sensible heat
Highest Start End
outdoor temp Oil Sensor5 E T L 0 6 2 ○M 0U . R5 3.6AWarming
reduction.
0 . 7 6
up operation means that the outdoor unit operates to reach the range
5 E T L 1
Dual Sensing 2 2 ○M 5U . R1 6Aof continuous operating, however it may not operate 5 .continuously
2 6 due to safety or
protection logic.
Low Noise Operation
5 E T L 1 4 2 ○M 0U . R2 6A 0 . 3 6
High Static Mode of Outdoor Unit Fan ○
5 E T L 1 6 2 M 5U . R2 6A 5 . 3 6
Partial Defrosting ○ Multi
Multi V 5V 5 Outdoor Units
5RemovalE of TOutdoor
L Unit0 8 2 M 8U . R2 6A 8 . 3 6 Outdoor Units
Auto Dust Simultaneous
9. Operation Cooling
Limits / Heating Operation
R3 9.6A Operation Limits

Useful Function 5 rotation)
(Fan reverse E T L 0 0 3 M 1U . 1 . 4 6
Indoor Cooling Comfort Mode Based Simultaneous
Cooling Cooling / Heating Operation
Outdoor 5 E T L 0
Temperature 2 3 ○M 8U . R3 6A Simultaneous Cooling / Heating Operation
8Heating
. 5 6
5 Control
Smart Load E (SLC)
T L 0 4 3 M 6U . R5 6A 30°C 6 . 20°C6 6
Load (Changing indoor discharge air ○
5 E T L 0
temperature according to load) 6 3 M 0U . R6 6A 8 . 7 6
25°C
5 Control
Outdoor Unit E Refer
T to Humidity
L 0 8 3 ○M 2U . R6 6A 8 0 6. 16°C 15°C
675675

Defrost /5DeicingE T L 0 0 4 ○M 3U . R6 6A 20°C 1 . 8 6

Outdoor Temperature (°C WB)


Outdoor Temperature (°C DB)
Sound level Scheduled setting available
High Pressure
5 SwitchE T L 0 2 4 ○M 5U . R6 6A 15°C 2 . 10°C8 6

Range for continuous operation

Range for pull down operation

Range for warming up operation


Phase Protection ○

Range for continuous operation


Low-noise Low-noise 5 E T L 0 4 4 M 8U . R6 6A 9 . 8 6
operation operation Wi-Fi MV Module Reliability Restart Delay (3-minutes) ○ 10°C
5 E T L 0
Self Diagnosis
6 4 ○M 8U . R7 6A 3 . 5°C9 6
Soft Start5 E T L 0 8 4 ○M 0U . R8 6A 5°C 0 . 0 7
On Off On

6:00 12:00 18:00 6:00 Test Run 5 E T L 0


Function 0 5 ○M 0U . R7 6A 0°C 6 . 0°C8 6
Start End Start End
5 E T L 0
AC Ez (Simple Controller) 2 5 M
PQCSZ250S0 1U . R7 6A -5°C 7 . 8 6
AC Ez Touch
5 E T L 0 4 PACEZA000
5 M 2U . R7 6A 8 . -5°C8 6
Indoor setting available
AC Smart IV PACS4B000 -10°C
5 E T L 0 6 5 M 4U . R7 6A 5 . 9 6
Central Controller AC Smart 5 PACS5A000
5 E T L 0
ACP (Advanced Control Platform) IV
8 5 M
PACP4B000
3U . R8 6A -15°C10°C 14°C 15°C 20°C 25°C 27°C 30°C 8 .-10°C9 6
5 EControlTPlatform)
ACP (Advanced L 50 0 6 M
PACP5A000 5U . R8 6A 4 . 010°C 7 15°C 20°C 25°C27°C 30°C
5
AC Manager 5 E T L 0 2 6 M
PACM5A000 6U . R8Note 6A
Note
Indoor Temperature (°C WB) 5 . 0Indoor7Temperature (°C DB)
BNU (Building ACP 5 E T L 0
Lonworks 4 6 M
PLNWKB000 7U . R8 Note
1. 6AEquivalent piping length:7.5m
1. These
These figures
figures assume
assume the the following
following operating
operating conditions:
conditions: 6 . 0 7
Network Unit) Equivalent piping length:7.5m
ACP BACnet
5 E T L 0 6 PQNFB17C0
6 M 8U . R8 Level6ALevel
1. These figures assume the following operating conditions
difference:0m
difference:0m 6 . 0 : 7
Cycle Monitoring Diagnosis Installation Smart Management Refrigerant Charging Kit PRAC1 2. Range
Equivalent
2. Range of pull
of pull down
piping
down length : 7.5m
operation:
operation:
Installation 5 E T L 0 8 6 M 0U . R9 If 6 AIfLevel
the the
relative
difference
relative humidity
humidity
: 0m
is toois too
high,high, cooling
cooling capacity
capacity cancan be1decreased
be decreased. by1the
by the 7
sensible
sensible heatheat reduction.
reduction.
Variable Water Flow Valve Control Kit - 2. Range of pull down operation :
5 E T L 0 0 7 M 6U . R9 6AIf the relative humidity is too high, cooling capacity 3 can. be1decreased 7 by the sensible heat
LGMV PDI (Power Standard PPWRDB000
reduction.
Distribution Indicator) Premium5 E T L 0 2 7 M
PQNUD1S40 8U . R9 6A 8 . 1 7
Cool / Heat Selector 5 E T L 0 4 7PRDSBM
M 1U . R9 6A 9 . 0 7
Low Ambient Kit 5 E T L 0 6 7 M
PRVC2 2U . R9 6A 9 . 0 7
IO Module (ODU Dry Contact) PVDSMN000
Cycle Monitoring LGMV PRCTIL0
677
Device Mobile LGMV PLGMVW100

○ : Applied, - : Not Applied

676676

021 / 022
OUTDOOR UNITS _ MULTI V 5 _ Q&A

MULTI V 5 Q&A MULTI V 5 Q&A

Q1 What are the differences between MULTI V IV and MULTI V 5? Q3 How does MULTI V 5 operate when humidity reference of the dual sensing SLC is that of the outdoor?
A1 Category MULTI V IV H/P (ARUN***LTE4) MULTI V 5 H/P (ARUN***LTE5) A3 During dual sensing SLC, outdoor unit changes target pressure of the system referring to temperature and humidity in cooling mode.
- When the humidity of outdoor side is higher than that of indoor side, outdoor unit will lower target pressure to remove humidity, thus
Vapor Injection ◯ ◯
outdoor unit will consume more energy and indoor will be more cooled compared to SLC operation but more efficiency than normal operation.
HiPOR TM ◯ ◯

Smart Oil Control (Oil Level Sensor) ◯ ◯


Outdoor humidity is higher than indoor unit Evaporation temperature & efficiency
Active Refrigerant Control ◯ ◯ Outdoor unit will consume more energy Dual Sensing SLC (RH 70% )
Variable Heat Exchanger Circuit ◯ ◯ Relative Humidity >70%

Continuous Heating ◯ ◯ Discharge


SLC under the high humidity condition
Temperature
Smart Load Control ◯ ◯ (˚C)

Dual sensing (Humidity Sensor) - ◯


Normal operation (non -SLC)
Comfort Cooling ◯ ◯
20°C 25°C 30°C 35°C
Black Fin - ◯ Discharge air will be more cold than normal or
SLC operation Efficiency SLC under the high humidity condition
(%)
Maximum Capacity (1 Unit / 4 Unit) 20 HP / 80 HP 26 HP / 96 HP

Height Difference (ODU ~ IDU / IDU ~ IDU) 110m / 40m 110m / 40m
Normal operation (non -SLC)
Cooling Operating Range (OAT, °CDB) -10 ~ 43 -15 ~ 48
20°C 25°C 30°C 35°C
Heating Operating Range (OAT, °CWB) -25 ~ 18 -25 ~ 18

1 Unit 50 ~ 200% 50 ~ 200% - When the humidity of outdoor side is lower than that of indoor side, outdoor unit will rise target pressure to save energy and keep
Combination ratio of
2 Unit 50 ~ 160% 50 ~ 160% comfort, but indoor humidity will be less removed compared to normal operation.
IDU
3 or 4 Units 50 ~ 130% 50 ~ 130%
Outdoor humidity is lower than indoor unit Evaporation temperature & efficiency
○ : Applied, - : Not Applied
Outdoor unit will consume less energy Dual Sensing SLC (Low Humidity)
30%< Relative Humidity<50%

Discharge
Q2 Can MULTI V 5 ODU be connected with the 2 series indoor unit?
SLC under the low humidity condition
Temperature
(°C)
A2 Yes, MULTI V 5 ODU can be connected with the 2 series indoor unit. In this case, the ODU DIP Switch No.3 should be “OFF” which is
default setting. Refer to the below table. Normal operation (non -SLC)

ODU IDU Compatibility ODU DIP Switch No. 3 If dip switch setting is not correct Ref. 20°C 25°C 30°C 35°C
Discharge air will be less cold than normal or
SLC operation. Efficiency SLC under the low humidity condition
Can not communicate between Indoor (%)
Must be OFF
Gen. 2 (ARNU*2) & Outdoor unit
(factory default)
(System will not be operated)

Normal operation (non -SLC)


When Dip Switch No.3 is OFF, 20°C 25°C 30°C 35°C
MULTI V IV Must be ON to enable
Gen. 4 (ARNU*4) System can be operated, but
MULTI V 5 gen. 4 functions
some function of Gen. 4 is not available
To maximize comfort and energy efficiency, the outdoor unit's humidity sensing can be turned off or a standard remote control can be
When Dip Switch No.3 is ON, installed to sense indoor humidity.
Must be OFF Can not communicate between Gen. Some functions of
Gen. 2 + Gen. 4
(factory default) 2 Indoor & Outdoor unit (Gen 2 units are not Gen.4 are not available
operated), only Gen 4 Units are operated. Sensing point SLC Setting
CASE 1. Dual Sensing SLC with Outdoor humidity sensor in ODU Setting
○ : Applied, - : Not Applied Outdoor humidity
by humidity sensor (ODU) DIP-SW01

ODU dip switch setting procedure (No.3) 7-Segment

ODU main PCB dip switch is all “OFF” at default state SW04C (X : cancel) Setting summary
SW03C ( : forward) DIP-SW01 #5 On
(1) Check and make sure that all connected indoor units are 4 series. (ARNU******4.) SW02C ( : backward) Func > Fn14 >
(2) Change Dip switch No. 3 from OFF ON Off, op1 ~ op3
SW01C ( : Confirm/
(3) Push the reset button. Automatic Addressing)
SW01D (reset)
Dip Switch 7 Segment
Indoor humidity CASE 2. D u a l S e n sin g S LC w ith In d o o r h u m id ity se n so r in N e w S ta n d a rd
ON ON R/C setting (PREMTB100)

Setting summary
Reset Function>
button Smart Load Control>
Off, op1 ~ op3
1 2 3 4 5 6 7 1 2 3 4 5 6 7
1 2 3 4 5 6 7 1 2 3 4 5 6 7
User can turn off humidity control in ODU Setting (humidity reference)
<Setting summary> ODU DIP-SW01 #5 On > Func > Fn16 > Off

023 / 024
OUTDOOR UNITS _ MULTI V 5 _ Q&A

MULTI V 5 Q&A MULTI V 5 Q&A

Q4 What is the principle and accuracy of humidity sensor? Other Questions


A4 Total Tolerance (%) = Sensor measurement tolerance (%) + Location of sensor tolerance (%) Upper electrode
Item Question Answer
The capacitive measurement principle established and proved itself as a standard in the past. Thin-film polymer
For this principle, the sensor element is built out of a capacitor. The dielectric is a polymer Lower electrode
Fan The static pressure of MULTI V 5 is max. 8 mmAq as MULTI V IV?? Yes, the static pressure of MULTI V 5 is the same as MULTI V IV.
which absorbs or releases water proportional to the relative environmental humidity, and thus Glass substrate

changes the capacitance of the capacitor. This change in capacitance can be measured by an
electronic circuit. For humidity sensors with CMOSens Ⓡ technology, a “micro-machined” finger
electrode system with different protective and polymer cover layers forms the capacitance for Is the limitation of Compressor max. Hz applied No, the limitation of comp Hz is not applied for default.
Compressor
the sensor chip, and, in addition to providing the sensor property, simultaneously protects the by the capacity of outdoor unit? But, it can be set by option for limitation of max. Hz (or current).
sensor from interference in ways previously not achieved.

Model Humidity Sensor of Outdoor Humidity Sensor of R/Controller


The optimal middle pressure for vapor injection is 1.2 P S *.
VI In case of vapor injection, how much is the middle pressure?
Size (mm) 3 x 3 x 1.1 2.5 x 2.5 x 0.9 *P S : Suction pressure of compressor.

Supply voltage range 2.1 to 3.6 V 2.4 to 5.5 V

RH operating range 0 ~ 100% RH 0 ~ 100% RH By how much is heating capacity increased


VI Generally, the heating capacity is increased up to 15 ~ 20%.
by vapor injection?
T operating range -40 to +125°C (-40 to +257°F) -40 to +125°C (-40 to +257°F)

RH response time 8 sec (tau 63%) 8 sec (tau 63%)

Humidity
Where is Indoor Humidity sensor? It is placed inside of the RS3 remote controller.
Sensor

Remote Does remote controller show the humidity information (Status) as Yes. It shows the current humidity information on screen.
Controller well? (for RS3 Only) But has no function to control the humidity.

Remote Is it possible to connect the local humidity sensor with Remote No. All of RS3 remote controller can not be connected
Controller controller (RS3)? with local humidity sensor.

SLC Does dual sensing SLC function control the humidity ratio? No. There is no control of humidity ratio.

Is SLC fully used on Eurovent? Isn’t humidity fixed


SLC Eurovent (RH 47%) and AHRI (RH 51%) have fixed humidity test condition.
for the test? What about AHRI?

Comfort cooling need super heating controlled and Comfort heating need sub
Comfort
Why is not the comfort heating applied in product? cooling controlled. In case of controlling EEV for sub cooling, noise and stable
Cooling
operation may be affected and critical.

Does the IDU – Central controller direct connection for


Installation No, it is not possible.
communication cable is possible? (Flat connection)

025 / 026
1,000m 225m
TOTAL PIPING LENGTH Longest Piping Length

- Air Cooled VRF Heat Pump

between ODU ~ IDU


- 22.4kW ~ 268.8kW (Cooling capacity based)

Height Difference
- 3Ø, 380 ~ 415V, 50Hz
- Top discharge outdoor unit

110m
TOTAL PIPING LENGTH

between IDU ~ IDU


Height Difference
40m
How does it work?
Dual Sensing

Energy savings

Partial Defrost
Reliability

Designed
Design
For
For
The Ultimate Low noise
The Ultimate

Advanced performance

027 / 028
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION

MULTI V 5 MULTI V 5
ARUN080LTE5 / ARUN100LTE5 ARUN160LTE5 / ARUN180LTE5
ARUN120LTE5 / ARUN140LTE5 ARUN200LTE5 / ARUN220LTE5

HP 8 10 12 14 HP 16 18 20 22
Combination Unit ARUN080LTE5 ARUN100LTE5 ARUN120LTE5 ARUN140LTE5 Combination Unit ARUN160LTE5 ARUN180LTE5 ARUN200LTE5 ARUN220LTE5
Model Name Model Name
Independent Unit ARUN080LTE5 ARUN100LTE5 ARUN120LTE5 ARUN140LTE5 Independent Unit ARUN160LTE5 ARUN180LTE5 ARUN200LTE5 ARUN220LTE5
kW 22.4 28.0 33.6 39.2 kW 44.8 50.4 56.0 61.6
Cooling (Rated) Cooling (Rated)
Btu/h 76,400 95,500 114,600 133,800 Btu/h 152,900 172,000 191,100 210,200
Capacity Capacity
kW 25.2 31.5 37.8 44.1 kW 50.4 56.7 63.0 69.3
Heating (Rated) Heating (Rated)
Btu/h 86,000 107,500 129,000 150,500 Btu/h 172,000 193,500 215,000 236,500
Cooling (Rated) kW 4.59 5.70 7.91 9.12 Cooling (Rated) kW 10.80 10.96 12.31 14.84
Input Input
Heating (Rated) kW 4.74 5.78 8.06 9.78 Heating (Rated) kW 11.59 12.06 15.52 17.54
EER (Rated) 4.88 4.91 4.25 4.30 EER (Rated) 4.15 4.60 4.55 4.15
COP (Rated) 5.32 5.45 4.69 4.51 COP (Rated) 4.35 4.70 4.06 3.95
Power Factor Rated - 0.93 0.93 0.93 0.93 Power Factor Rated - 0.93 0.93 0.93 0.93
Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Exterior Exterior
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K
Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus
Compressor Motor Output x Number W x No. 5,300 x 1 5,300 x 1 5,300 x 1 5,300 x 1 Compressor Motor Output x Number W x No. 5,300 x 1 5,300 x 1 + 4,200 x 1 5,300 x 2 5,300 x 2
Type Propeller fan Propeller fan Propeller fan Propeller fan Type Propeller fan Propeller fan Propeller fan Propeller fan
Motor Output x Number W 1,200 x 1 1,200 x 1 1,200 x 1 900 x 2 Motor Output x Number W 900 x 2 900 x 2 900 x 2 900 x 2
m 3 /min 240 x 1 240 x 1 240 x 1 320 x 1 m 3 /min 320 x 1 320 x 1 320 x 1 320 x 1
Air Flow Rate (High) Air Flow Rate (High)
Fan ft3 /min 8,476 x 1 8,476 x 1 8,476 x 1 11,301 x 1 Fan ft3 /min 11,301 x 1 11,301 x 1 11,301 x 1 11,301 x 1
External Static Pressure (Max, Pa) 80 80 80 80 External Static Pressure (Max, Pa) 80 80 80 80
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP TOP TOP Discharge Side / Top TOP TOP TOP TOP
Pipe Liquid Pipe mm (inch) 9.52 (3/8) 9.52 (3/8) 12.7 (1/2) 12.7 (1/2) Pipe Liquid Pipe mm (inch) 12.7 (1/2) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Connections Gas Pipe mm (inch) 19.05 (3/4) 22.2 (7/8) 28.58 (1-1/8) 28.58 (1-1/8) Connections Gas Pipe mm (inch) 28.58 (1-1/8) 28.58 (1-1/8) 28.58 (1-1/8) 28.58 (1-1/8)
Dimensions (W x H x D) mm x No. (930 x 1,690 x 760) x 1 (930 x 1,690 x 760) x 1 (930 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 Dimensions (W x H x D) mm x No. (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1
kg 199 x 1 199 x 1 199 x 1 221 x 1 kg 221 x 1 261 x 1 281 x 1 281 x 1
Net Weight Net Weight
lbs 439 x 1 439 x 1 439 x 1 487 × 1 lbs 487 × 1 575 × 1 619 × 1 619 × 1
Sound Cooling dB(A) 58.0 58.0 59.0 60.0 Sound Cooling dB(A) 60.5 61.0 62.0 64.5
Pressure Level Heating dB(A) 59.0 59.0 60.0 61.0 Pressure Level Heating dB(A) 61.5 62.0 64.5 65.5
mm 2 x No. mm 2 x No.
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
(VCTF-SB) (VCTF-SB)
Refrigerant name R410A R410A R410A R410A Refrigerant name R410A R410A R410A R410A
Precharged Amount kg 10.0 10.0 10.0 13.0 Precharged Amount kg 13.0 13.0 14.0 14.0
Refrigerant in factory lbs 22.0 22.0 22.0 28.7 Refrigerant in factory lbs 28.7 28.7 30.9 30.9
t-CO 2 eq 20.9 20.9 20.9 27.1 t-CO 2 eq 27.1 27.1 29.2 29.2
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50
Power Supply Ø, V, Hz Power Supply Ø, V, Hz
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 13 (20) 16 (25) 20 (30) 23 (35) Number of maximum connectable indoor units 26 (40) 29 (45) 32 (50) 35 (56)

Note Note
1. Due to our policy of innovation some specifications may be changed without notification. 1. Due to our policy of innovation some specifications may be changed without notification.
2 . W i r i n g c a b l e s i z e m u s t c o m p l y w i t h t h e a p p l i c a b l e l o c a l a n d n a t i o n a l c o d e s . A n d “ E l e c t r i c c h a r a c t e r i s t i c s ” c h a p t e r s h o u l d b e c o n s i d e re d f o r e l e c t r i c a l w o r k a n d d e s i g n . 2 . W i r i n g c a b l e s i z e m u s t c o m p l y w i t h t h e a p p l i c a b l e l o c a l a n d n a t i o n a l c o d e s . A n d “ E l e c t r i c c h a r a c t e r i s t i c s ” c h a p t e r s h o u l d b e c o n s i d e re d f o r e l e c t r i c a l w o r k a n d d e s i g n .
Especially the power cable and circuit breaker should be selected in accordance with that. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions. 3. Power factor could vary less than ±1% according to the operating conditions.
4 . S o u n d p re s s u re l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e a n e c h o i c ro o m s b y I S O 3 7 4 5 s t a n d a rd . 4 . S o u n d p re s s u re l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e a n e c h o i c ro o m s b y I S O 3 7 4 5 s t a n d a rd .
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard. Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation. Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions : 5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero. Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination. 6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%. The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)
029 / 030
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION

MULTI V 5 MULTI V 5
ARUN240LTE5 / ARUN260LTE5 ARUN221LTE5 / ARUN241LTE5

HP 24 26 HP 22' 24'
Combination Unit ARUN240LTE5 ARUN260LTE5 Combination Unit ARUN221LTE5 ARUN241LTE5
Model Name Model Name
Independent Unit ARUN240LTE5 ARUN260LTE5 ARUN120LTE5 ARUN120LTE5
Independent Unit
ARUN100LTE5 ARUN120LTE5
kW 67.2 72.8
Cooling (Rated) kW 61.6 67.2
Btu/h 229,300 248,400 Cooling (Rated)
Capacity Btu/h 210,100 229,200
kW 74.3 74.3 Capacity
Heating (Rated) kW 69.3 75.6
Btu/h 253,400 253,400 Heating (Rated)
Btu/h 236,500 258,000
Cooling (Rated) kW 16.76 19.41
Input Cooling (Rated) kW 13.60 15.81
Heating (Rated) kW 18.85 19.49 Input
Heating (Rated) kW 13.80 16.12
EER (Rated) 4.01 3.75
EER (Rated) 4.53 4.25
COP (Rated) 3.94 3.81
COP (Rated) 5.01 4.69
Power Factor Rated - 0.93 0.93
Power Factor Rated - 0.93 0.93
Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Exterior Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray
RAL code NL503K / NA507K NL503K / NA507K Exterior
RAL code NL503K / NA507K NL503K / NA507K
Heat Exchanger Wide Louver Plus Wide Louver Plus
Heat Exchanger Wide Louver Plus Wide Louver Plus
Compressor Motor Output x Number W x No. 5,300 x 2 5,300 x 2
Compressor Motor Output x Number W x No. 5,300 x 2 5,300 x 2
Type Propeller fan Propeller fan
Type Propeller fan Propeller fan
Motor Output x Number W 900 x 2 900 x 2
Motor Output x Number W (1,200 x 1) + (1,200 x 1) (1,200 x 1) + (1,200 x 1)
m 3 /min 320 x 1 320 x 1
Air Flow Rate (High) m 3 /min (240 x 1) + (240 x 1) (240 x 1) + (240 x 1)
Fan ft3 /min 11,301 x 1 11,301 x 1 Air Flow Rate (High)
Fan ft3 /min (8,476 x 1) + (8,476 x 1) (8,476 x 1) + (8,476 x 1)
External Static Pressure (Max, Pa) 80 80
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Discharge Side / Top TOP TOP
Pipe Liquid Pipe mm (inch) 15.88 (5/8) 19.05 (3/4)
Connections Pipe Liquid Pipe mm (inch) 15.88 (5/8) 15.88 (5/8)
Gas Pipe mm (inch) 34.9 (1-3/8) 34.9 (1-3/8)
Connections Gas Pipe mm (inch) 28.58 (1-1/8) 34.9 (1-3/8)
Dimensions (W x H x D) mm x No. (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1
Dimensions (W x H x D) mm x No. (930 x 1,690 x 760) x 2 (930 x 1,690 x 760) x 2
kg 283 x 1 283 x 1
Net Weight kg 199 x 2 199 x 2
lbs 624 × 1 624 × 1 Net Weight
lbs 439 × 2 439 × 2
Sound Cooling dB(A) 65.0 65.0
Pressure Level Sound Cooling dB(A) 61.5 62.0
Heating dB(A) 67.0 67.0
Pressure Level Heating dB(A) 62.5 63.0
mm 2 x No.
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
(VCTF-SB) mm 2 x No.
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Refrigerant name R410A R410A (VCTF-SB)
kg 16.0 16.0 Refrigerant name R410A R410A
Precharged Amount
Refrigerant in factory lbs 35.3 35.3 Precharged Amount kg 10.0 + 10.0 10.0 + 10.0
Refrigerant in factory lbs 22.0 + 22.0 22.0 + 22.0
t-CO 2 eq 33.4 33.4
Control Electronic Expansion Valve Electronic Expansion Valve t-CO 2 eq 41.8 41.8
3, 380-415, 50 3, 380-415, 50 Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply Ø, V, Hz 3, 380-415, 50 3, 380-415, 50
3, 380, 60 3, 380, 60 Power Supply Ø, V, Hz
Number of maximum connectable indoor units 39 (61) 42 (64) 3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 35 (44) 39 (48)

Note Note
1. Due to our policy of innovation some specifications may be changed without notification. 1. Due to our policy of innovation some specifications may be changed without notification.
2 . W i r i n g c a b l e s i z e m u s t c o m p l y w i t h t h e a p p l i c a b l e l o c a l a n d n a t i o n a l c o d e s . A n d “ E l e c t r i c c h a r a c t e r i s t i c s ” c h a p t e r s h o u l d b e c o n s i d e re d f o r e l e c t r i c a l w o r k a n d d e s i g n . 2 . W i r i n g c a b l e s i z e m u s t c o m p l y w i t h t h e a p p l i c a b l e l o c a l a n d n a t i o n a l c o d e s . A n d “ E l e c t r i c c h a r a c t e r i s t i c s ” c h a p t e r s h o u l d b e c o n s i d e re d f o r e l e c t r i c a l w o r k a n d d e s i g n .
Especially the power cable and circuit breaker should be selected in accordance with that. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions. 3. Power factor could vary less than ±1% according to the operating conditions.
4 . S o u n d p re s s u re l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e a n e c h o i c ro o m s b y I S O 3 7 4 5 s t a n d a rd . 4 . S o u n d p re s s u re l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e a n e c h o i c ro o m s b y I S O 3 7 4 5 s t a n d a rd .
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard. Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation. Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions : 5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero. Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination. 6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%. The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)

031 / 032
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION

MULTI V 5 MULTI V 5
ARUN261LTE5 / ARUN280LTE5 ARUN340LTE5 / ARUN360LTE5
ARUN300LTE5 / ARUN320LTE5 ARUN380LTE5 / ARUN400LTE5

HP 26' 28 30 32 HP 34 36 38 40
Combination Unit ARUN261LTE5 ARUN280LTE5 ARUN300LTE5 ARUN320LTE5 Combination Unit ARUN340LTE5 ARUN360LTE5 ARUN380LTE5 ARUN400LTE5
Model Name ARUN140LTE5 ARUN160LTE5 ARUN180LTE5 ARUN200LTE5 Model Name ARUN220LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
Independent Unit Independent Unit
ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN140LTE5 ARUN160LTE5
kW 72.8 78.4 84.0 89.6 kW 95.2 100.8 106.4 112.0
Cooling (Rated) Cooling (Rated)
Btu/h 248,400 267,500 286,600 305,700 Btu/h 324,800 343,900 363,100 382,200
Capacity Capacity
kW 81.9 88.2 94.5 100.8 kW 107.1 112.1 118.4 124.7
Heating (Rated) Heating (Rated)
Btu/h 279,500 301,000 322,500 344,000 Btu/h 365,500 382,400 403,900 425,400
Cooling (Rated) kW 17.02 18.70 18.86 20.21 Cooling (Rated) kW 22.75 24.66 25.87 27.55
Input Input
Heating (Rated) kW 17.84 19.65 20.12 23.58 Heating (Rated) kW 25.60 26.91 28.62 30.43
EER (Rated) 4.28 4.19 4.45 4.43 EER (Rated) 4.18 4.09 4.11 4.06
COP (Rated) 4.59 4.49 4.70 4.28 COP (Rated) 4.18 4.16 4.13 4.10
Power Factor Rated - 0.93 0.93 0.93 0.93 Power Factor Rated - 0.93 0.93 0.93 0.93
Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Exterior Exterior
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507 NL503K / NA507K
Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus
Compressor Motor Output x Number W x No. 5,300 x 2 5,300 x 2 (5,300 x 2) + (4,200 x 1 ) (5,300 x 2) + (4,200 x 1) Compressor Motor Output x Number W x No. 5,300 x 3 5,300 x 3 5,300 x 3 5,300 x 3
Type Propeller fan Propeller fan Propeller fan Propeller fan Type Propeller fan Propeller fan Propeller fan Propeller fan
Motor Output x Number W (900 x 2) + (1,200 x 1) (900 x 2) + (1,200 x 1 ) (900 x 2) + (1,200 x 1) (900 x 2) + (1,200 x 1) Motor Output x Number W (900 x 2) + (1,200 x 1) (900 x 2) + (1,200 x 1) 900 x 4 900 x 4
m 3 /min (320 x 1) + (240 x 1) (320 x 1) + (240 x 1 ) (320 x 1) + (240 x 1) (320 x 1) + (240 x 1) m 3 /min (320 x 1) + (240 x 1) (320 x 1) + (240 x 1) 320 x 2 320 x 2
Air Flow Rate (High) Air Flow Rate (High)
Fan ft3 /min (11,301 x 1) + (8,476 x 1) (11,301 x 1) + (8,476 x 1) (11,301 x 1) + (8,476 x 1) (11,301 x 1) + (8,476 x 1) Fan ft3 /min (11,301 x 1) + (8,476 x 1) (11,301 x 1) + (8,476 x 1) 11,301 x 2 11,301 x 2
External Static Pressure (Max, Pa) 80 80 80 80 External Static Pressure (Max, Pa) 80 80 80 80
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP TOP TOP Discharge Side / Top TOP TOP TOP TOP
Pipe Liquid Pipe mm (inch) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) Pipe Liquid Pipe mm (inch) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Connections Gas Pipe mm (inch) 34.9 (1-3/8) 34.9 (1-3/8) 34.9 (1-3/8) 34.9 (1-3/8) Connections Gas Pipe mm (inch) 34.9 (1-3/8) 41.3 (1-5/8) 41.3 (1-5/8) 41.3 (1-5/8)
(1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1
Dimensions (W x H x D) mm x No. Dimensions (W x H x D) mm x No. (1,240 x1,690 x 760) x 2 (1,240 x1,690 x 760) x 2
+ (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1
kg (221 x 1) + (199 x 1) (221 x 1) + (199 x 1) (261 x 1) + (199 x 1) (281 x 1) + (199 x 1) kg (281 x 1) + (199 x 1) (283 x 1) + (199 x 1) (283 x 1) + (221 x 1) (283 x 1) + (221 x 1)
Net Weight Net Weight
lbs (487 × 1) + (439 × 1) (487 × 1) + (439 × 1) (575 × 1) + (439 × 1) (619 × 1) + (439 × 1) lbs (619 × 1) + (439 × 1) (624 × 1) + (439 × 1) (624 × 1) + (487 × 1) (624 × 1) + (487 × 1)
Sound Cooling dB(A) 62.5 62.8 63.1 63.8 Sound Cooling dB(A) 65.6 66.0 66.2 66.3
Pressure Level Heating dB(A) 63.5 63.8 64.1 65.8 Pressure Level Heating dB(A) 66.6 67.8 68.0 68.1
mm 2 x No. mm 2 x No.
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
(VCTF-SB) (VCTF-SB)
Refrigerant name R410A R410A R410A R410A Refrigerant name R410A R410A R410A R410A
Precharged Amount kg 13.0 + 10.0 13.0 + 10.0 13.0 + 10.0 14.0 + 10.0 Precharged Amount kg 14.0 + 10.0 16.0 + 10.0 16.0 + 13.0 16.0 + 13.0
Refrigerant in factory lbs 28.7 + 22.0 28.7 + 22.0 28.7 + 22.0 30.9 + 22.0 Refrigerant in factory lbs 30.9 + 22.0 35.3 + 22.0 35.3 + 28.7 35.3 + 28.7
t-CO 2 eq 48.0 48.0 48.0 50.1 t-CO 2 eq 50.1 54.3 60.5 60.5
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50
Power Supply Ø, V, Hz Power Supply Ø, V, Hz
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 42 (52) 45 (56) 49 (60) 52 (64) Number of maximum connectable indoor units 55 (64) 58 (64) 61 (64) 64

Note Note
1. Due to our policy of innovation some specifications may be changed without notification. 1. Due to our policy of innovation some specifications may be changed without notification.
2 . W i r i n g c a b l e s i z e m u s t c o m p l y w i t h t h e a p p l i c a b l e l o c a l a n d n a t i o n a l c o d e s . A n d “ E l e c t r i c c h a r a c t e r i s t i c s ” c h a p t e r s h o u l d b e c o n s i d e re d f o r e l e c t r i c a l w o r k a n d d e s i g n . 2 . W i r i n g c a b l e s i z e m u s t c o m p l y w i t h t h e a p p l i c a b l e l o c a l a n d n a t i o n a l c o d e s . A n d “ E l e c t r i c c h a r a c t e r i s t i c s ” c h a p t e r s h o u l d b e c o n s i d e re d f o r e l e c t r i c a l w o r k a n d d e s i g n .
Especially the power cable and circuit breaker should be selected in accordance with that. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions. 3. Power factor could vary less than ±1% according to the operating conditions.
4 . S o u n d p re s s u re l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e a n e c h o i c ro o m s b y I S O 3 7 4 5 s t a n d a rd . 4 . S o u n d p re s s u re l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e a n e c h o i c ro o m s b y I S O 3 7 4 5 s t a n d a rd .
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard. Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation. Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions : 5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero. Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination. 6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%. The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)

033 / 034
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION

MULTI V 5 MULTI V 5
ARUN420LTE5 / ARUN440LTE5 ARUN500LTE5 / ARUN520LTE5
ARUN460LTE5 / ARUN480LTE5 ARUN540LTE5 / ARUN560LTE5

HP 42 44 46 48 HP 50 52 54 56
Combination Unit ARUN420LTE5 ARUN440LTE5 ARUN460LTE5 ARUN480LTE5 Combination Unit ARUN500LTE5 ARUN520LTE5 ARUN540LTE5 ARUN560LTE5
Model Name ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 Model Name ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
Independent Unit Independent Unit ARUN140LTE5 ARUN160LTE5 ARUN180LTE5 ARUN200LTE5
ARUN180LTE5 ARUN200LTE5 ARUN220LTE5 ARUN240LTE5
ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5
kW 117.6 123.2 128.8 134.4
Cooling (Rated) kW 140.0 145.6 151.2 156.8
Btu/h 401,300 420,400 439,500 458,600 Cooling (Rated)
Capacity Btu/h 477,700 496,800 515,900 535,000
kW 131.0 137.3 143.6 148.5 Capacity
Heating (Rated) kW 156.2 162.5 168.8 175.1
Btu/h 446,900 468,400 489,900 506,800 Heating (Rated)
Btu/h 532,900 554,400 575,900 597,400
Cooling (Rated) kW 27.71 29.07 31.60 33.52 Cooling (Rated) kW 33.78 35.46 35.62 36.97
Input Input
Heating (Rated) kW 30.91 34.36 36.39 37.69 Heating (Rated) kW 36.68 38.49 38.97 42.42
EER (Rated) 4.24 4.24 4.08 4.01 EER (Rated) 4.14 4.11 4.24 4.24
COP (Rated) 4.24 3.99 3.94 3.94 COP (Rated) 4.26 4.22 4.33 4.13
Power Factor Rated - 0.93 0.93 0.93 0.93 Power Factor Rated - 0.93 0.93 0.93 0.93
Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Exterior Exterior
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K
Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus
Compressor Motor Output x Number W x No. (5,300 x 3) + (4,200 x 1) 5,300 x 4 5,300 x 4 5,300 x 4 Compressor Motor Output x Number W x No. 5,300 x 4 5,300 x 4 (5,300 x 4) + (4,200 x 1) 5,300 x 5
Type Propeller fan Propeller fan Propeller fan Propeller fan Type Propeller fan Propeller fan Propeller fan Propeller fan
Motor Output x Number W 900 x 4 900 x 4 900 x 4 900 x 4 Motor Output x Number W (900 x 4) + (1,200 x 1) (900 x 4) + (1,200 x 1) (900 x 4) + (1,200 x 1) (900 x 4) + (1,200 x 1)
m 3 /min (320 x 2) + (240 x 1) (320 x 2) + (240 x 1) (320 x 2) + (240 x 1) (320 x 2) + (240 x 1)
m 3 /min 320 x 2 320 x 2 320 x 2 320 x 2 Air Flow Rate (High)
Air Flow Rate (High) Fan ft3 /min (11,301 x 2) + (8,476 x 1) (11,301 x 2) + (8,476 x 1) (11,301 x 2) + (8,476 x 1 ) (11,301 x 2) + (8,476 x 1)
Fan ft3 /min 11,301 x 2 11,301 x 2 11,301 x 2 11,301 x 2
External Static Pressure (Max, Pa) 80 80 80 80
External Static Pressure (Max, Pa) 80 80 80 80
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP TOP TOP
Discharge Side / Top TOP TOP TOP TOP
Pipe Liquid Pipe mm (inch) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Pipe Liquid Pipe mm (inch) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) Connections Gas Pipe mm (inch) 41.3 (1-5/8) 41.3 (1-5/8) 41.3 (1-5/8) 41.3 (1-5/8)
Connections Gas Pipe mm (inch) 41.3 (1-5/8) 41.3 (1-5/8) 41.3 (1-5/8) 41.3 (1-5/8) (1,240 x 1,690 x 760) x 2 (1,240 x 1,690 x 760) x 2 (1,240 x 1,690 x 760) x 2 (1,240 x 1,690 x 760) x 2
Dimensions (W x H x D) mm x No.
Dimensions (W x H x D) mm x No. (1,240 x1,690 x 760) x 2 (1,240 x1,690 x 760) x 2 (608 × 1) + (604 × 1) 608 × 2 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1
kg (283 x 1) + (261 x 1) (283 x 1) + (281 x 1) (283 x 1) + (281 x 1) 283 x 2 (283 x 1) + (221 x 1) + (283 x 1) + (221 x 1) + (283 x 1) + (261 x 1) + (283 x 1) + (281 x 1) +
Net Weight kg
(199 x 1) (199 x 1) (199 x 1) (199 x 1)
lbs (624 × 1) + (575 × 1) (624 × 1) + (619 × 1) (624 x 1) + (619 x 1) 624 x 2 Net Weight
(624 × 1) + (487 × 1) + (624 × 1) + (487 × 1) + (624 × 1) + (575 × 1) + (624 × 1) + (619 × 1) +
Sound Cooling dB(A) 66.5 66.8 67.8 68.0 lbs
(439 × 1) (439 × 1) (439 × 1) (439 × 1)
Pressure Level Heating dB(A) 68.2 68.9 69.3 70.0 Cooling dB(A) 67.0 67.1 67.2 67.4
Sound
mm 2 x No. Pressure Level Heating dB(A) 68.6 68.7 68.8 69.5
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
(VCTF-SB)
mm 2 x No.
Refrigerant name R410A R410A R410A R410A Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
(VCTF-SB)
Precharged Amount kg 16.0 + 13.0 16.0 + 14.0 16.0 + 14.0 16.0 + 16.0 Refrigerant name R410A R410A R410A R410A
Refrigerant in factory lbs 35.3 + 28.7 35.3 + 30.9 35.3 + 30.9 35.3 + 35.3 Precharged Amount kg 16.0 + 13.0 + 10.0 16.0 + 13.0 + 10.0 16.0 + 13.0 + 10.0 16.0 + 14.0 + 10.0
t-CO 2 eq 60.5 62.6 62.6 66.8 Refrigerant in factory lbs 35.3 + 28.7 + 22.0 35.3 + 28.7 + 22.0 35.3 + 28.7 + 22.0 35.3 + 30.9 + 22.0
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve t-CO 2 eq 81.4 81.4 81.4 83.5
3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Power Supply Ø, V, Hz 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 Power Supply Ø, V, Hz
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 64 64 64 64
Number of maximum connectable indoor units 64 64 64 64

Note Note
1. Due to our policy of innovation some specifications may be changed without notification. 1. Due to our policy of innovation some specifications may be changed without notification.
2 . W i r i n g c a b l e s i z e m u s t c o m p l y w i t h t h e a p p l i c a b l e l o c a l a n d n a t i o n a l c o d e s . A n d “ E l e c t r i c c h a r a c t e r i s t i c s ” c h a p t e r s h o u l d b e c o n s i d e re d f o r e l e c t r i c a l w o r k a n d d e s i g n . 2 . W i r i n g c a b l e s i z e m u s t c o m p l y w i t h t h e a p p l i c a b l e l o c a l a n d n a t i o n a l c o d e s . A n d “ E l e c t r i c c h a r a c t e r i s t i c s ” c h a p t e r s h o u l d b e c o n s i d e re d f o r e l e c t r i c a l w o r k a n d d e s i g n .
Especially the power cable and circuit breaker should be selected in accordance with that. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions. 3. Power factor could vary less than ±1% according to the operating conditions.
4 . S o u n d p re s s u re l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e a n e c h o i c ro o m s b y I S O 3 7 4 5 s t a n d a rd . 4 . S o u n d p re s s u re l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e a n e c h o i c ro o m s b y I S O 3 7 4 5 s t a n d a rd .
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard. Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation. Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions : 5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero. Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination. 6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%. The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)

035 / 036
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION

MULTI V 5 MULTI V 5
ARUN580LTE5 / ARUN600LTE5 ARUN660LTE5 / ARUN680LTE5
ARUN620LTE5 / ARUN640LTE5 ARUN700LTE5 / ARUN720LTE5

HP 58 60 62 64 HP 66 68 70 72
Combination Unit ARUN580LTE5 ARUN600LTE5 ARUN620LTE5 ARUN640LTE5 Combination Unit ARUN660LTE5 ARUN680LTE5 ARUN700LTE5 ARUN720LTE5
Model Name ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 Model Name ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
Independent Unit ARUN220LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 Independent Unit ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
ARUN120LTE5 ARUN120LTE5 ARUN140LTE5 ARUN160LTE5 ARUN180LTE5 ARUN200LTE5 ARUN220LTE5 ARUN240LTE5
kW 162.4 168.0 173.6 179.2 kW 184.8 190.4 196.0 201.6
Cooling (Rated) Cooling (Rated)
Btu/h 554,100 573,200 592,400 611,500 Btu/h 630,600 649,700 668,800 687,900
Capacity Capacity
kW 181.4 186.3 192.6 198.9 kW 205.2 211.5 217.8 222.8
Heating (Rated) Heating (Rated)
Btu/h 618,900 635,800 657,300 678,800 Btu/h 700,300 721,800 743,300 760,200
Cooling (Rated) kW 39.51 41.42 42.63 44.31 Cooling (Rated) kW 44.47 45.82 48.36 50.27
Input
Heating (Rated) kW 44.45 45.75 47.47 49.28 Input
Heating (Rated) kW 49.76 53.21 55.24 56.54
EER (Rated) 4.11 4.06 4.07 4.04
EER (Rated) 4.16 4.16 4.05 4.01
COP (Rated) 4.08 4.07 4.06 4.04
COP (Rated) 4.12 3.97 3.94 3.94
Power Factor Rated - 0.93 0.93 0.93 0.93
Power Factor Rated - 0.93 0.93 0.93 0.93
Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Exterior Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K Exterior
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K
Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus
Compressor Motor Output x Number W x No. 5,300 x 5 5,300 x 5 5,300 x 5 5,300 x 5 Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus
Type Propeller fan Propeller fan Propeller fan Propeller fan Compressor Motor Output x Number W x No. (5,300 x 5) + (4,200 x 1) 5,300 x 6 5,300 x 6 5,300 x 6
Motor Output x Number W (900 x 4) + (1,200 x 1) (900 x 4) + (1,200 x 1) 900 x 6 900 x 6 Type Propeller fan Propeller fan Propeller fan Propeller fan
m 3 /min (320 x 2) + (240 x 1) (320 x 2) + (240 x 1) 320 x 3 320 x 3 Motor Output x Number W 900 x 6 900 x 6 900 x 6 900 x 6
Air Flow Rate (High)
Fan ft3 /min (11,301 x 2) + (8,476 x 1) (11,301 x 2) + (8,476 x 1) 11,301 x 3 11,301 x 3 m 3 /min 320 x 3 320 x 3 320 x 3 320 x 3
Air Flow Rate (High)
External Static Pressure (Max, Pa) 80 80 80 80 Fan ft3 /min 11,301 x 3 11,301 x 3 11,301 x 3 11,301 x 3
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER External Static Pressure (Max, Pa) 80 80 80 80
Discharge Side / Top TOP TOP TOP TOP Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Pipe Liquid Pipe mm (inch) 19.05 (3/4) 19.05 (3/4) 22.2 (7/8) 22.2 (7/8) Discharge Side / Top TOP TOP TOP TOP
Connections Gas Pipe mm (inch) 41.3 (1-5/8) 41.3 (1-5/8) 44.5 (1-3/4) 44.5 (1-3/4)
Pipe Liquid Pipe mm (inch) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8)
(1,240 x 1,690 x 760) x 2 (1,240 x 1,690 x 760) x 2 Connections Gas Pipe mm (inch) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
Dimensions (W x H x D) mm x No. (1,240 x1,690 x 760) x 3 (1,240 x1,690 x 760) x 3
+ (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1
Dimensions (W x H x D) mm x No. (1,240 x1,690 x 760) x 3 (1,240 x1,690 x 760) x 3 (1,240 x1,690 x 760) x 3 (1,240 x1,690 x 760) x 3
(283 x 1) + (281 x 1) +
kg (283 x 2) + (199 x 1) (283 x 2) + (221 x 1) (283 x 2) + (221 x 1) kg (283 x 2) + (261 x 1) (283 x 2) + (281 x 1) (283 x 2) + (281 x 1) 283 x 3
(199 x 1)
Net Weight Net Weight
(624 × 1) + (619 × 1) + lbs (624 × 2) + (575 × 1) (624 × 2) + (619 × 1) (624 × 2) + (619 × 1) 624 × 3
lbs (624 × 2) + (439 × 1) (624 × 2) + (487 × 1) (624 × 2) + (487 × 1)
(439 × 1)
Sound Cooling dB(A) 68.8 69.0 69.6 69.8
Sound Cooling dB(A) 68.3 68.5 68.6 68.7 Pressure Level Heating dB(A) 70.6 71.1 71.3 71.8
Pressure Level Heating dB(A) 69.8 70.4 70.5 70.6
mm 2 x No.
mm 2 x No. Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C (VCTF-SB)
(VCTF-SB)
Refrigerant name R410A R410A R410A R410A
Refrigerant name R410A R410A R410A R410A
Precharged Amount kg 16.0 + 16.0 + 13.0 16.0 + 16.0 + 14.0 16.0 + 16.0 + 14.0 16.0 + 16.0 + 16.0
Precharged Amount kg 16.0 + 14.0 + 10.0 16.0 + 16.0 + 10.0 16.0 + 16.0 + 13.0 16.0 + 16.0 + 13.0
Refrigerant in factory lbs 35.3 + 35.3 + 28.7 35.3 + 35.3 + 30.9 35.3 + 35.3 + 30.9 35.3 + 35.3 + 35.3
Refrigerant in factory lbs 35.3 + 30.9 + 22.0 35.3 + 35.3 + 22.0 35.3 + 35.3 + 28.7 35.3 + 35.3 + 28.7
t-CO 2 eq 83.5 87.7 93.9 93.9 t-CO 2 eq 93.9 96.0 96.0 100.2
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50
Power Supply Ø, V, Hz Power Supply Ø, V, Hz
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 64 64 64 64 Number of maximum connectable indoor units 64 64 64 64

Note Note
1. Due to our policy of innovation some specifications may be changed without notification. 1. Due to our policy of innovation some specifications may be changed without notification.
2 . W i r i n g c a b l e s i z e m u s t c o m p l y w i t h t h e a p p l i c a b l e l o c a l a n d n a t i o n a l c o d e s . A n d “ E l e c t r i c c h a r a c t e r i s t i c s ” c h a p t e r s h o u l d b e c o n s i d e re d f o r e l e c t r i c a l w o r k a n d d e s i g n . 2 . W i r i n g c a b l e s i z e m u s t c o m p l y w i t h t h e a p p l i c a b l e l o c a l a n d n a t i o n a l c o d e s . A n d “ E l e c t r i c c h a r a c t e r i s t i c s ” c h a p t e r s h o u l d b e c o n s i d e re d f o r e l e c t r i c a l w o r k a n d d e s i g n .
Especially the power cable and circuit breaker should be selected in accordance with that. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions. 3. Power factor could vary less than ±1% according to the operating conditions.
4 . S o u n d p re s s u re l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e a n e c h o i c ro o m s b y I S O 3 7 4 5 s t a n d a rd . 4 . S o u n d p re s s u re l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e a n e c h o i c ro o m s b y I S O 3 7 4 5 s t a n d a rd .
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard. Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation. Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions : 5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero. Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination. 6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%. The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)

037 / 038
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION

MULTI V 5 MULTI V 5
ARUN740LTE5 / ARUN760LTE5 ARUN820LTE5 / ARUN840LTE5
ARUN780LTE5 / ARUN800LTE5 ARUN860LTE5 / ARUN880LTE5

HP 74 76 78 80 HP 82 84 86 88
Combination Unit ARUN740LTE5 ARUN760LTE5 ARUN780LTE5 ARUN800LTE5 Combination Unit ARUN820LTE5 ARUN840LTE5 ARUN860LTE5 ARUN880LTE5
ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
Model Name ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 Model Name ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
Independent Unit Independent Unit
ARUN140LTE5 ARUN160LTE5 ARUN180LTE5 ARUN200LTE5 ARUN220LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN140LTE5 ARUN160LTE5
kW 207.2 212.8 218.4 224.0 kW 229.6 235.2 240.8 246.4
Cooling (Rated) Cooling (Rated)
Btu/h 707,000 726,100 745,200 764,300 Btu/h 783,400 802,500 821,700 840,800
Capacity Capacity
kW 230.4 236.7 243.0 249.3 kW 255.6 260.6 266.9 273.2
Heating (Rated) Heating (Rated)
Btu/h 786,300 807,800 829,300 850,800 Btu/h 872,300 889,200 910,700 932,200
Cooling (Rated) kW 50.54 52.22 52.38 53.73 Cooling (Rated) kW 56.27 58.18 59.39 61.07
Input Input
Heating (Rated) kW 55.53 57.34 57.82 61.27 Heating (Rated) kW 63.30 64.60 66.32 68.13
EER (Rated) 4.10 4.08 4.17 4.17 EER (Rated) 4.08 4.04 4.05 4.03
COP (Rated) 4.15 4.13 4.20 4.07 COP (Rated) 4.04 4.03 4.02 4.01
Power Factor Rated - 0.93 0.93 0.93 0.93 Power Factor Rated - 0.93 0.93 0.93 0.93
Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Exterior Exterior
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K
Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus
Compressor Motor Output x Number W x No. 5,300 x 6 5,300 x 6 (5,300 x 6) + (4,200 x 1) 5,300 x 7 Compressor Motor Output x Number W x No. 5,300 x 7 5,300 x 7 5,300 x 7 5,300 x 7
Type Propeller fan Propeller fan Propeller fan Propeller fan Type Propeller fan Propeller fan Propeller fan Propeller fan
Motor Output x Number W (900 x 6) + (1,200 x 1) (900 x 6) + (1,200 x 1) (900 x 6) + (1,200 x 1) (900 x 6) + (1,200 x 1) Motor Output x Number W (900 x 6) + (1,200 x 1) (900 x 6) + (1,200 x 1) 900 x 8 900 x 8
m 3 /min (320 x 3) + (240 x 1) (320 x 3) + (240 x 1) (320 x 3) + (240 x 1) (320 x 3) + (240 x 1) m 3 /min (320 x 3) + (240 x 1) (320 x 3) + (240 x 1) 320 x 4 320 x 4
Air Flow Rate (High) Air Flow Rate (High)
Fan ft3 /min (11,301 x 3) + (8,476 x 1) (11,301 x 3) + (8,476 x 1) (11,301 x 3) + (8,476 x 1) (11,301 x 3) + (8,476 x 1) Fan ft3 /min (11,301 x 3) + (8,476 x 1) (11,301 x 3) + (8,476 x 1) 11,301 x 4 11,301 x 4
External Static Pressure (Max, Pa) 80 80 80 80 External Static Pressure (Max, Pa) 80 80 80 80
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP TOP TOP Discharge Side / Top TOP TOP TOP TOP
Pipe Liquid Pipe mm (inch) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) Pipe Liquid Pipe mm (inch) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8)
Connections Gas Pipe mm (inch) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) Connections Gas Pipe mm (inch) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
(1,240 x 1,690 x 760) x 3 (1,240 x 1,690 x 760) x 3 (1,240 x 1,690 x 760) x 3 (1,240 x 1,690 x 760) x 3 (1,240 x 1,690 x 760) x 3 (1,240 x 1,690 x 760) x 3
Dimensions (W x H x D) mm x No. Dimensions (W x H x D) mm x No. (1,240 x1,690 x 760) x 4 (1,240 x1,690 x 760) x 4
+ (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1
kg (283 x 2) + (221 x 1) + (199 x 1) (283 x 2) + (221 x 1) + (199 x 1) (283 x 2) + (261 x 1) + (199 x 1) (283 x 2) + (281 x 1) + (199 x 1) kg (283 x 2) + (281 x 1) + (199 x 1) (283 x 3) + (199 x 1) (283 x 3) + (221 x 1) (283 x 3) + (221 x 1)
Net Weight Net Weight
lbs (624 × 2) + (487 × 1) + (439 × 1) (624 × 2) + (487 × 1) + (439 × 1) (624 × 2) + (575 × 1) + (439 × 1) (624 × 2) + (619 × 1) + (439 × 1) lbs (624 × 2) + (619 × 1) + (439 × 1) (624 × 3) + (439 × 1) (624 × 3) + (487 × 1) (624 × 3) + (487 × 1)
Sound Cooling dB(A) 69.1 69.2 69.2 69.4 Sound Cooling dB(A) 70.0 70.1 70.2 70.3
Pressure Level Heating dB(A) 70.9 70.9 71.0 71.4 Pressure Level Heating dB(A) 71.6 72.1 72.1 72.2
mm 2 x No. mm 2 x No.
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
(VCTF-SB) (VCTF-SB)
Refrigerant name R410A R410A R410A R410A Refrigerant name R410A R410A R410A R410A
Precharged Amount kg 16.0 + 16.0 + 13.0 + 10.0 16.0 + 16.0 + 13.0 + 10.0 16.0 + 16.0 + 13.0 + 10.0 16.0 + 16.0 + 14.0 + 10.0 Precharged Amount kg 16.0 + 16.0 + 14.0 + 10.0 16.0 + 16.0 + 16.0 + 10.0 16.0 + 16.0 + 16.0 + 13.0 16.0 + 16.0 + 16.0 + 13.0
Refrigerant in factory lbs 35.3 + 35.3 + 28.7 + 22.0 35.3 + 35.3 + 28.7 + 22.0 35.3 + 35.3 + 28.7 + 22.0 35.3 + 35.3 + 30.9 + 22.0 Refrigerant in factory lbs 35.3 + 35.3 + 30.9 + 22.0 35.3 + 35.3 + 35.3 + 22.0 35.3 + 35.3 + 35.3 + 28.7 35.3 + 35.3 + 35.3 + 28.7
t-CO 2 eq 114.8 114.8 114.8 116.9 t-CO 2 eq 116.9 121.1 127.3 127.3
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50
Power Supply Ø, V, Hz Power Supply Ø, V, Hz
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 64 64 64 64 Number of maximum connectable indoor units 64 64 64 64

Note Note
1. Due to our policy of innovation some specifications may be changed without notification. 1. Due to our policy of innovation some specifications may be changed without notification.
2 . W i r i n g c a b l e s i z e m u s t c o m p l y w i t h t h e a p p l i c a b l e l o c a l a n d n a t i o n a l c o d e s . A n d “ E l e c t r i c c h a r a c t e r i s t i c s ” c h a p t e r s h o u l d b e c o n s i d e re d f o r e l e c t r i c a l w o r k a n d d e s i g n . 2 . W i r i n g c a b l e s i z e m u s t c o m p l y w i t h t h e a p p l i c a b l e l o c a l a n d n a t i o n a l c o d e s . A n d “ E l e c t r i c c h a r a c t e r i s t i c s ” c h a p t e r s h o u l d b e c o n s i d e re d f o r e l e c t r i c a l w o r k a n d d e s i g n .
Especially the power cable and circuit breaker should be selected in accordance with that. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions. 3. Power factor could vary less than ±1% according to the operating conditions.
4 . S o u n d p re s s u re l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e a n e c h o i c ro o m s b y I S O 3 7 4 5 s t a n d a rd . 4 . S o u n d p re s s u re l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e a n e c h o i c ro o m s b y I S O 3 7 4 5 s t a n d a rd .
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard. Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation. Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions : 5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero. Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination. 6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%. The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)

039 / 040
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION

MULTI V 5 NOTE
ARUN900LTE5 / ARUN920LTE5
ARUN940LTE5 / ARUN960LTE5

HP 90 92 94 96
Combination Unit ARUN900LTE5 ARUN920LTE5 ARUN940LTE5 ARUN960LTE5
ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
Model Name ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
Independent Unit
ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
ARUN180LTE5 ARUN200LTE5 ARUN220LTE5 ARUN240LTE5
kW 252.0 257.6 263.2 268.8
Cooling (Rated)
Btu/h 859,900 879,000 898,100 917,200
Capacity
kW 279.5 285.8 292.1 297.0
Heating (Rated)
Btu/h 953,700 975,200 996,700 1,013,600
Cooling (Rated) kW 61.23 62.58 65.12 67.03
Input
Heating (Rated) kW 68.60 72.06 74.08 75.39
EER (Rated) 4.12 4.12 4.04 4.01
COP (Rated) 4.07 3.97 3.94 3.94
Power Factor Rated - 0.93 0.93 0.93 0.93
Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Exterior
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K
Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus
Compressor Motor Output x Number W x No. (5,300 x 7) + (4,200 x 1) 5,300 x 8 5,300 x 8 5,300 x 8
Type Propeller fan Propeller fan Propeller fan Propeller fan
Motor Output x Number W 900 x 8 900 x 8 900 x 8 900 x 8
m 3 /min 320 x 4 320 x 4 320 x 4 320 x 4
Air Flow Rate (High)
Fan ft3 /min 11,301 x 4 11,301 x 4 11,301 x 4 11,301 x 4
External Static Pressure (Max, Pa) 80 80 80 80
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP TOP TOP
Pipe Liquid Pipe mm (inch) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8)
Connections Gas Pipe mm (inch) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
Dimensions (W x H x D) mm x No. (1,240 x1,690 x 760) x 4 (1,240 x1,690 x 760) x 4 (1,240 x1,690 x 760) x 4 (1,240 x1,690 x 760) x 4
kg (283 x 3) + (261 x 1) (283 x 3) + (281 x 1) (283 x 3) + (281 x 1) 283 x 4
Net Weight
lbs (624 × 3) + (575 × 1) (624 × 3) + (619 × 1) (624 × 3) + (619 × 1) 624 × 4
Sound Cooling dB(A) 70.3 70.4 70.9 71.0
Pressure Level Heating dB(A) 72.2 72.5 72.7 73.0
mm 2 x No.
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
(VCTF-SB)
Refrigerant name R410A R410A R410A R410A
Precharged Amount kg 16.0 + 16.0 + 16.0 + 13.0 16.0 + 16.0 + 16.0 + 14.0 16.0 + 16.0 + 16.0 + 14.0 16.0 + 16.0 + 16.0 + 16.0
Refrigerant in factory lbs 35.3 + 35.3 + 35.3 + 28.7 35.3 + 35.3 + 35.3 + 30.9 35.3 + 35.3 + 35.3 + 30.9 35.3 + 35.3 + 35.3 + 35.3
t-CO 2 eq 127.3 129.4 129.4 133.6
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50
Power Supply Ø, V, Hz
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 64 64 64 64

Note
1. Due to our policy of innovation some specifications may be changed without notification.
2 . W i r i n g c a b l e s i z e m u s t c o m p l y w i t h t h e a p p l i c a b l e l o c a l a n d n a t i o n a l c o d e s . A n d “ E l e c t r i c c h a r a c t e r i s t i c s ” c h a p t e r s h o u l d b e c o n s i d e re d f o r e l e c t r i c a l w o r k a n d d e s i g n .
Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions.
4 . S o u n d p re s s u re l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e a n e c h o i c ro o m s b y I S O 3 7 4 5 s t a n d a rd .
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)

041 / 042
OUTDOOR UNITS _ MULTI V 5 _ TECHNICAL DATA

Field Wiring Field Wiring


Outdoor Voltage range(V)
Power supply Frequency Outdoor The below System is representative Multi V 5 System.
Outdoor Indoor Power supply
(3Ø 4wires) Actual combination of outdoor unit may be different by product line-up of region.
[Outdoor Unit] 60Hz 380 220 (3Ø 4wires)
(Main Switch)
R S T N 50Hz 380-415 220-240 (Main Switch) [Master] [Slave1] [Slave2] [Slave3]
Switch R S T N

Switch
Fuse
Indoor Fuse
Power supply Indoor
(1Ø 2wires) Power supply
L N (1Ø 2wires)
Power Line
(4 Wires Cable) L N
Power Line
Fuse Power Line
(2 Wires Cable)
(4 Wires Cable)
Communication Line Fuse Power Line
(2 Wires Cable) (2 Wires Cable)
Communication Line
(2 Wires Cable)

Pull Box Pull Box Pull Box


(Installer option) (Installer option) (Installer option)
Pull Box Pull Box Pull Box
(Installer option) (Installer option) (Installer option)

Power Line Power Line Power Line Power Line


(2 Wires Cable) (2 Wires Cable) (2 Wires Cable) (2 Wires Cable)

Power Line Power Line Power Line Power Line Voltage range(V)
(2 Wires Cable) (2 Wires Cable) (2 Wires Cable) (2 Wires Cable) Frequency
Outdoor Indoor
Communication Line
(3 Wires Cable)
60Hz 380 220
[Indoor Units] 50Hz 380-415 220-240
Communication Line
(3 Wires Cable)

[Indoor Units]
WARNING

Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage, WARNING
Communication disorder by noise effect and motor current leakage (without connection to pipe).
When the total capacity is over than 68Hp, do not use single power source for connecting series units.
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from
The First terminal block could be burnt out.
the power supply.
If individual power supply is necessary for each indoor unit, IPM (Independent Power Module) should
be applied at each indoor unit. (optional)
When the power source is supplied to Each outdoor unit individually.
• Install the main switch that can interrupt all the power sources in an integrated manner because this Outdoor
The below System is representative Multi V 5 System.
system consists of the equipment utilizing the multiple power sources. Power supply
Actual combination of outdoor unit may be different by product line-up of region.
(3Ø 4wires)
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on [Master] [Slave1] [Slave2] [Slave3]
(Main Switch)
and off while the product is operating, attach a reversed phase protection circuit locally. R S T N R S T N R S T N R S T N

Running the product in reversed phase may break the compressor and other parts. Switch Switch Switch Switch

Fuse Fuse Fuse Fuse


Indoor
Power supply
Between Indoor and Master Outdoor unit
(1Ø 2wires)
L N
Master
SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
Outdoor Unit Fuse Power Line
(2 Wires Cable)
Power Line Communication Line
(4 Wires Cable) (2 Wires Cable)

Pull Box Pull Box Pull Box


(Installer option) (Installer option) (Installer option)
3 4 3 4 3 4

Power Line Power Line Power Line Power Line


Voltage range(V) (2 Wires Cable) (2 Wires Cable) (2 Wires Cable) (2 Wires Cable)
Frequency
Outdoor Indoor
60Hz 380 220
The GND terminal at the main PCB is a ‘-’ terminal for day contact, it is Communication Line
50Hz 380-415 220-240
not the point to make ground connection. (3 Wires Cable)

[Indoor Units]

043 / 044
OUTDOOR UNITS _ MULTI V 5 _ TECHNICAL DATA

Field Wiring Electric Characteristics

WARNING

• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from
the power supply.
If individual power supply is necessary for each indoor unit, IPM (Independent Power Module) should
be applied at each indoor unit. (optional)
• Install the main switch that can interrupt all the power sources in an integrated manner because this
system consists of the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on
and off while the product is operating, attach a reversed phase protection circuit locally. WARNING
Running the product in reversed phase may break the compressor and other parts.

Between Indoor and Master Outdoor unit

SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
Master
SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
Master
Outdoor Unit Outdoor unit

3 4 3 4 3 4 SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
Slave1 CAUTION
Outdoor Unit

Slave2
SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
Outdoor Unit

The GND terminal at the main PCB is a ‘-’ terminal for dry contact. It is not the point to
make ground connection.
• Make sure that terminal number of master and slave outdoor units are

Example Connection of Communication Cable


• Connection of communication cable must be installed • Abnormal operation can be caused by communication
like below figure between indoor unit to outdoor unit. defect, when connection of communication cable is
installed like below figure.

045 / 046
OUTDOOR UNITS _ MULTI V 5 _ TECHNICAL DATA

Electric Characteristics Electric Characteristics


[Unit : mm] [Unit : mm]

047 / 048
[Unit : mm]
Gravity point Dimensions
OUTDOOR UNITS _ MULTI V 5 _ TECHNICAL DATA

ARUN080LTE5 / ARUN100LTE5 / ARUN120LTE5

[mm(inch)]
System Heat Recovery Heat Pump
Liquid Low Pressure High Pressure Liquid Gas
HP
pipe Gas pipe Gas pipe pipe pipe

8 Ø 9.52 (3/8) Ø 19.05 (3/4) Ø 15.88 (5/8) Ø 9.52 (3/8) Ø 19.05 (3/4)
10 Ø 9.52 (3/8) Ø 22.2 (7/8) Ø 19.05 (3/4) Ø 9.52 (3/8) Ø 22.2 (7/8)

12 Ø 12.7 (1/2) Ø 28.58 (1-1/8) Ø 19.05 (3/4) Ø 12.7 (1/2) Ø 28.58 (1-1/8)
[Unit : mm]
Dimensions
OUTDOOR UNITS _ MULTI V 5 _ TECHNICAL DATA

ARUN220LTE5 / ARUN240LTE5 / ARUN260LTE5

[mm(inch)]
System Heat Recovery Heat Pump
Liquid Low Pressure High Pressure Liquid Gas
HP
ARUN140LTE5 / ARUN160LTE5 / ARUN180LTE5 / ARUN200LTE5

pipe Gas pipe Gas pipe pipe pipe

14~16 Ø 12.7 (1/2) Ø 28.58 (1-1/8) Ø 22.2 (7/8) Ø 12.7 (1/2) Ø 28.58 (1-1/8)
18~20 Ø 15.88 (5/8) Ø 28.58 (1-1/8) Ø 22.2 (7/8) Ø 15.88 (5/8) Ø 28.58 (1-1/8)

22 Ø 15.88 (5/8) Ø 28.58(1-1/8) Ø 28.58 (1-1/8) Ø 15.88 (5/8) Ø 28.58 (1-1/8)


24 Ø 15.88 (5/8) Ø 34.9(1-3/8) Ø 28.58 (1-1/8) Ø 15.88 (5/8) Ø 34.9 (1-3/8)

26~34 Ø 19.05 (3/4) Ø 34.9 (1-3/8) Ø 28.58 (1-1/8) Ø 19.05 (3/4) Ø 34.9 (1-3/8)
36~40 Ø 19.05 (3/4) Ø 41.3 (1-5/8) Ø 28.58 (1-1/8) Ø 19.05 (3/4) Ø 41.3 (1-5/8)

42~60 Ø 19.05 (3/4) Ø 41.3 (1-5/8) Ø 34.9 (1-3/8) Ø 19.05 (3/4) Ø 41.3 (1-5/8)

62~64 Ø 22.2 (7/8) Ø 44.5 (1-3/4) Ø 41.3 (1-5/8) Ø 22.2 (7/8) Ø 44.5 (1-3/4)

66~96 Ø 22.2 (7/8) Ø 53.98 (2-1/8) Ø 44.5 (1-3/4) Ø 22.2 (7/8) Ø 53.98 (2-1/8)
049 / 050