Professional Documents
Culture Documents
Do & Donts BMS
Do & Donts BMS
Bengaluru, Karnataka.
DON’TS
• Do not over cool the room; do not leave the temperature set point to minimum.
• Prevent direct sunlight into the room by using curtains, awning, sun shade, etc.
• Do not open windows or doors for a long time while the unit is running.
• Do not put heating apparatus too close to the thermostat it will also increase the room’s heat
load, causing insufficient cooling.
• Do not step on or do not put heavy loads on VAV. So that it can be damaged and the duct
joints may leak.
• Make sure the VCD dampers nearby the VAVs should not be modulated manually after the
Air Balancing completion, doing so will affect the VAVs to supply insufficient air flow.
• Do not pull out the power cord when the power is on.
• Do not pull out the VAQ communication cables in absence of our technician.
• Do not pull out the VAV to thermostat communication cables in absence of HVAC technician
DOs
• Make sure there are no dust particles flowing through the Duct to VAV, those dust particles
may stuck in VAV Flow sensor & VAV will not be able to give sufficient air flow as per the
design.
• There should not be any air flow leakage; this would affect the VAVs to supply insufficient air flow.
• Set the temperature set point as per the design Min/Max for optimum comfort.
• Make sure the VAVs are always in ON condition & all the cable are properly connected
(Power cable, VAV to VAV communication cable & thermostat cables).
• VFD should always run the AHU fan speed as per the design CFM of that particular AHU.
Running the VFD below the required speed may affect the VAVs to supply insufficient air flow.
And running the VFD above the required speed may damage the VAV flow sensors & its
damper.
• VAVs should always run on UPS power supply only. In case of raw power, the VAVs
controllers & thermostat might get shot circuit if any fluctuations happen.
Dos
• Please provide the UPS power to the DDC Panels, Giving raw power may shot circuit the
DDC Controllers
• If any fault LED found on any of the Controllers & Integrators, please do contact our team.
(Please refer Escalation Matrix)
Don’ts
• Do not open the sensor cover or its case for any cleaning purpose or checking purpose.
• Do not switch off the power of any of the DDC panel from outside panel or inside the panel.
• Do not remove or unplug any of the cables including power & communication cables from
DDC Panel, BMS Panel as well as any of the sensors.
• Do not unplug any cables from BMS IO Controllers inside the DDC Panel.
• Do not unplug the RJ45 Network cable from any of the integrator or network Hub.
• Removal of cables & reconnecting the cables incorrectly will mal function the whole BMS
software system.
• Check for incorrect type of screws or missing screws at the cabinet front cover.