Professional Documents
Culture Documents
Optimization of An Industrial Air Compressor System
Optimization of An Industrial Air Compressor System
6 2013
Optimization of an
Industrial Air Compressor System
Bei Zhang, Mingsheng Liu, Yunhua Li, Lixia Wu
ABSTRACT
INTRODUCTION
METHODOLOGY
Fundamentals
For air compressors, the mechanical power consumption rate for ac-
tual processes can be estimated by Equation (1) below.
(1)
Test Groups
From Table 1, it can be found that the compressed air system in the
site consisted of air compressors of three different models. During the
walk-through, it was known that under part-load conditions one of the
seven air compressors running alone can satisfy the load. When the load
increased and the pressure setpoint could not be maintained, another air
compressor of the same size and type would be chosen to run in com-
bination with the one online. Due to the system configuration, running
55
air compressors of the same model facilitated the starting process since
less system checking was involved. So the air compressors with the same
model were grouped together when testing the performance of their com-
bined running. If a single air compressor could not satisfy the load, one of
the same model would be started and the two would run as a group.
To compare the performance of different compressors, six tests were
conducted which is presented in Table 2.
. .
E = Q/W (2)
Data Collection
To cover more load condition, a whole week’s data were logged for
all the tests with the consumed electrical power using kilowatt meters and
compressed air delivered using the site air flow meter which was built
in recent years. The intake air temperature of the online compressor was
trended with temperature loggers. During the trending, data were col-
lected every five minutes for each logger.
Data Handling
Grp#1 and Grp#2 use reciprocating air compressors. Grp#1 utilizes
a five-step (0, 25, 50, 75, 100 percent) design, and Grp#2 uses a three-step
(0, 50, 100 percent) control design. The air compressors in Grp#3 are de-
signed with start/stop control. The compressors switch between loading
to unloading to maintain the system (compressed air tank) pressure set-
point of 100 psi. The actual system pressure varied from 96 psi (loading
setpoint) to 110 psi (unloading setpoint) and the power consumed fluctu-
ated accordingly. Therefore, extreme low power data were logged during
the unloading process even when the compressed air flor rate delivered
by the system was in normal range. This yielded a false high efficiency
value. To reduce this error, extraneous values were eliminated. A moving
average, using 15-minute cycles, was instituted to smooth data fluctuation
for both the air flow rate and electrical power. Then the efficiency was ob-
tained from Equation (2) by substituting the moving average result of air
flow rate and electrical power.
AC#1, AC#6, Grp#2, Grp#1, and Grp#3. Since the load during the test
of AC#5 is very low (less than 1200 cfm), the efficiency line for AC#5
disappears after the load is higher than 1200 cfm. It crosses with line of
AC#2, indicating that AC#5 shows lower efficiency than AC#2 when load
is higher than the crossing point which is about 1200 cfm. Further tests
should be done to verify this. The conclusion is that when the system air
59
Figure 10. Efficiency and load for all the test groups
60 Energy Engineering Vol. 110, No. 6 2013
Saving Calculation
To estimate the annual savings, the average air demand profile was
tested during different months, and is shown in Table 3 which gives the
time the system operated under different load ranges, and which repre-
sents the plant’s one-year load profile. Results showed that a whole year
2) Air compressors run more efficiently under higher load. Much bet-
ter linear regression relationship can be obtained if the tests covered
the load condition of a wider range.
NOMENCLATURE
E
. = efficiency, cfm/kW
. = compressed air delivered, cfm
𝑄
. = input electrical power, kW
𝑊
𝑊𝑚 = compressor power consumption
.
𝑚𝑎 = air mass flow rate
𝑅𝑎 = ideal gas constant of air
Ti = intake (or inlet) air temperature
𝑙 = empirical parameter
𝑃𝑖 = inlet air pressure
𝑃𝑜 = outlet air pressure
Acknowledgements
The authors appreciate the support of Mrs. Jingrong Wang, Mr. Lou-
is Thomas, and Jay M. Schubert from Omaha Public Power District. The
cooperation and assistance from building managers, engineers, and op-
erators is gratefully acknowledged.
64 Energy Engineering Vol. 110, No. 6 2013
Reference
[1] U.S. Department of Energy, 2003. Improving compressed air system performance, a
source book for industry.
[2] Van Ormer, Hank. 1995. Optimize your plant’s compressed air system. Chemical Engi-
neering Progress, 91(2):35-39
[3] Foss, R. Scot. 2005. Optimizing the compressed air system. Energy Engineering,
102(1):49-60
[4] Sheckler, Mark S. 2007. Assessment of a Compressed air system. Energy Engineering,
104(1):13-22
[5] Dalgleish, A.Z. & L.J. Grobler. 2006. Energy management opportunities on a com-
pressed air system in a packaging facility. Energy Engineering, 103(4):42-52
————————————————————————————————
ABOUT THE AUTHORS
Bei Zhang is a Ph.D. student and a research assistant of architectural
engineering at the University of Nebraska Lincoln. Her research interests
are energy efficiency of building mechanical systems including system
control strategy, system optimization, and system commissioning etc. She
can be contacted at: bzhang@unomaha.edu