Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

This article has been accepted for publication in a future issue of this journal, but has not been

fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2018.2890548, IEEE
Transactions on Smart Grid
1

Active Power Flow Control


Between DC Microgrids
Umamaheswararao Vuyyuru, Student Member, IEEE, Suman Maiti, Member, IEEE,
Chandan Chakraborty, Fellow, IEEE,

Abstract—The interconnection of dc microgrids may help to D1 Duty ratio of full bridge dc-dc converter
address the problems associated with uncertainty of renewable r1 , r2 Transmission line resistances
energy generation systems. In this paper, a Load Flow Con- Ld Total leakage inductance referred to primary side of
verter (LFC) is proposed which interconnects two adjacent dc
microgrids and controls bidirectional power flow between them. the transformer in DAB
The LFC needs to regulate power by applying and controlling Vtp , Vts Voltages across primary and secondary of trans-
a voltage in between two dc grids. Generation of this series- former respectively
voltage, if done by using the same grids, will be of immense N2
n Turns ratio of transformer (i.e. N1
)
advantage. Therefore, a new concept of input-parallel and output- VLd Voltage across inductor
series connection is proposed. The LFC is formed with a Dual
Active Bridge (DAB) followed by a full-bridge dc-dc converter. Vc Control signal for Full bridge dc-dc converter
It injects dynamic voltage in series with the transmission line Zin ,Zo Impedances seen at input and output sides of DAB
to control power flow between the dc grids. The required power
rating of the LFC is fairly low compared to the power transmitted
between dc grids and also it does not require any external power I. I NTRODUCTION
source for operation. The proposed configuration is simulated
in MATLAB/OPAL-RT based real-time simulation platform. A
scaled-down version of the system (at 30V level) is developed
in the laboratory to experimentally validate the concept. The
T HE remotely located rural areas in several countries do
not have access to electric supply from the utility grid.
As Renewable Energy Sources (RES) are usually dispersed,
results show the effectiveness of the LFC for interconnection of Distributed Generation (DG) becomes an attractive solution for
dc microgrids. meeting the energy demand in such areas [1]. By connecting
Index Terms—DC Microgrids, Load Flow Converter (LFC), DGs (e.g. solar, wind, fuel cell etc.) with local loads and
Dual Active Bridge (DAB), DC Power Flow Controller. energy storage, a microgrid is formed. Microgrid is a local
grid, which can be seen as an independent system with the
capability to operate in either grid-connected or islanded mode
NOMENCLATURE
[2]. Microgrids can be classified into two categories: ac and
V1 , V2 Voltages of dc microgrid-1 and 2 respectively dc depending on the type of operating voltage [3]. The dc mi-
V3 Voltage at node A (Input voltage of LFC) crogrid is becoming more attractive compared to its ac counter
V4 Voltage at node C part due to higher efficiency, simple interface to many types
Vk Output voltage of LFC of RES and Energy Storage Systems (ESS), better control
Vo Output voltage of DAB over consumer electronics, fewer ac/dc and dc/ac conversion
Pt Transmitted Power at node C (V4 *I2 ) stages, absence of reactive power and frequency related issues
PGi Total generation power at bus-i [4]. The general structure of islanded dc microgrid is shown
Pgi Net power (flowing through transmission line) at bus-i in Fig.1. The DGs are connected to a common bus through
PLi Total load power at bus-i power electronic converters to control the dc bus voltage [5].
Pin Input power of LFC The implementation and control of a single dc microgrid
Po Output power of LFC system is easy, but over the time an optimal control of dc grid
Pdo Output power of DAB may become sub-optimal due to expansion of the network.
I1 , I2 Line currents at bus-1 and bus-2 respectively Interconnection among the dc microgrids is found beneficial
I3 Input current of LFC due to the following reasons [6], [7]
PBi Output power of battery connected at ith microgrid • The impact of power variation from RES due to weather
PP V i Output power of PV connected at ith microgrid conditions is reduced. This is because, the excess of
PLi Load power connected at ith microgrid power in one grid may be transferred to the other grid
πD Phase-shift of DAB (in radian) and vice versa.
• Energy storage requirement is less as power balance may
U.Vuyyuru is with School of Energy Science and Engineering, Indian
Institute of Technology Kharagpur, India. take place within the grids.
S.Maiti and C.Chakraborty are with Department of Electrical Engineering, • Operational cost is reduced.
Indian Institute of Technology Kharagpur, India. • Reliability is increased.
Corresponding author e-mail: umamahesh271@gmail.com.
Manuscript received April 22, 2018; revised September 15, November 8, The above advantages lead to interconnection of two or
2018; accepted December 8, 2018. more dc microgrids to support each other by exchanging

1949-3053 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2018.2890548, IEEE
Transactions on Smart Grid
2

dc transformer operates at a high frequency (100kHz), is used


to control the power flow between dc microgrid and dc bus
of interlinking converter. It works in open loop scheme to
replace the conventional bulky transformer for bus voltage
matching and galvanic isolation. In [27], Dual Active Bridge
(DAB) based isolated dc-dc converter is proposed for power
flow control application by maintaining both input and output
grid voltages within the limits. For increasing the power
flow between microgrids, a modular-isolated bidirectional dc-
Fig. 1. The general structure of islanded dc microgrid
dc converter is presented in [28]. In the aforesaid literature,
power electronic converters are connected in such a way
that both input and output of the converter handle rated
voltage of the microgrids. As a consequence, the power rating
surplus power from one grid to other grid. However, the flow of the converter will be same as the amount of power to
of power in dc cable depends simply on the cable resistance be transferred between microgrids. This eventually demands
and voltage difference between both ends of the cable. In [8], higher rating of the PFC. In [29], a Controlled Series Current
the dc microgrids are interconnected which is named as dc Compensator (CSCC) technique introduced between dc micro-
microgrid cluster. A hierarchical control for such system is grids for control of power flow between them. Depending on
proposed to control the power flow among the dc mcirogrids the direction of power flow, CSCC can inject regulated voltage
according to the ratings of their local energy storage. In with appropriate polarity (positive or negative) in series with
[9], [10], a distributed control system is proposed to adjust the line. This type of series connection can reduce the power
the voltage set points of individual microgrids and control handled by the PFCs. However, CSCC requires external dc
the power flow among the interconnected microgrids. Due to power source for the operation which is a drawback of the
the coupled control feature, the control flexibility of power concept. In [30], a Series Voltage Regulator (SVR) is presented
transfer will be influenced and also plug-and-play feature of dc for voltage drop compensation in radial dc distribution system,
microgrids cannot be ensured, which means the scalability of a without using any external power source. But, this topology
microgrid-cluster will be reduced [11]. Moreover, if one grid is cannot be used for this application as it cannot provide output
connected to multiple grids, the power flow on each connected voltage with both polarities. In [31], the Floating Bidirectional
link cannot be controlled independently by adjustment of Power Flow Controller (F-BPFC) is proposed. However, differ-
the bus voltages. Beside this, the power flow between one ence in voltage levels among dc microgrids is not considered
grid to other grid is not possible if the two microgrids stay and an external isolated dc-dc converter is used to validate the
at same voltage level, which is obvious. Therefore, power concept of power flow between microgrids.
flow controllers (PFCs) are required for interconnection of In this paper, a new concept to implement the LFC is
two or more dc mcrogrids with different/same dc voltage proposed. The idea is basically to go for an input-parallel
levels [12]. The issues related to power flow control is also and output-series configuration that will allow generation of
observed when the ac microgrids are interconnected. In [13], controlled voltage in between two dc grids such that power
a distributed coordination control framework is introduced to flow can be easily regulated. Such unique configuration can
handle the load sharing between ac multi-bus microgrids. In optimize power-rating of the LFC and eliminate the need of
[14], the oscillatory modes in a multi-microgrid system caused any external source.
by various parameters, such as interconnecting line length, The high gain dc-dc converter is the building block of
droop gain, exciter gain and governor gain are studied. LFC. Various high-gain dc-dc converters are reviewed in [32].
The PFCs are power electronics based devices capable of Among them, Dual Active Bridge (DAB) is chosen for this
controlling dc power between two neighboring dc grids. In application as it can provide isolation between input and
[15], thyristor based bidirectional resonant dc-dc converter is output, high efficiency, and has moderate power rating. LFC
proposed for interconnection of high-power dc sources with is composed of a DAB and a full-bridge dc-dc converter. DAB
high stepping ratio voltages. In [16]–[19], a non-isolated buck- (first stage of the configuration) provides unipolar dc voltage
boost topology is used for power flow control between grids with a step-down ratio, decided by the transformer. The output
with different voltage levels. But, for dc microgrids of the voltage of DAB is always maintained at its reference value
same level of nominal voltage, step-up as-well-as step-down during the operation. The full-bridge dc-dc converter (second
capabilities are required due to power fluctuation and parasitic stage of the configuration) regulates the output voltage as per
line resistance [20]. In [21]–[24], two cascaded bidirectional requirement and is capable to change the polarity of the output
buck-boost converters are used to control the power flow voltage. The proposed LFC can also support bi-directional
between dc microgrids. Here power-flow is possible between power flow which is a prerequisite for some particular cases
grids by controlling duty ratios of two back-to-back converters. (e.g. in case of power flow control between different voltage
The isolated dc-dc converters are ideal for specific application levels of dc microgrids).
where galvanic isolation between dc microgrids are required This paper is organized in seven sections. Section-I in-
and for interconnecting dc grids of different capacity (eg., troduced the need of interconnection of dc microgrids and
microgrid and nanogrid) [25]. In [26], Bidirectional resonant associated literature review. The connection diagram of LFC

1949-3053 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2018.2890548, IEEE
Transactions on Smart Grid
3

the total loads connected at the microgrids are represented


by PL1 and PL2 . The need of two or more dc microgrids
interconnection is already explained in Section I. The input
side of the LFC is connected across the grid with terminals
A and B. The output side is connected in series with the
transmission line. According to the connection diagram, the
output of LFC experiences lower voltage (Vk ) associated to
line-drop and rated line current (I2 ), whereas the input of
LFC faces rated dc grid voltage (V3 ) and lower current (I3 ).
Therefore, the required input power to LFC for realizing power
flow control between dc grids is expressed as follows.
Pin = V3 I3 (1)
For ideal conditions, neglecting converter losses, the input
Fig. 2. (a) Connection diagram of LFC (b) Equivalent circuit of system under
consideration power is equal to output power of LFC. So, it can be written
as
Vk I2 = V3 I3 (2)

B. Theoretical analysis of power flow


The equivalent circuit diagram of the complete system
considering power flow from grid-1 to grid-2 is shown in Fig.2
(b). Here Pg1 is the net power received from grid-1, Pg2 is the
net power transferred to grid-2. LFC can be seen by the rest
of the network as a variable resistive load [33], represented
as R3 which is a function of average output voltage (Vk ) and
current (I2 ) of LFC. The variable resistor R3 can also act as
negative load during operation of LFC. From the equivalent
circuit, power transferred through the transmission line at node
voltage V4 (i.e. Pt ) can be expressed as:
Pt = V4 I2 (3)
According to Fig.2 (b),
V4 − V2 V1 − V3 V3
I2 = = I1 − I3 = − (4)
r2 r1 R3
V4 = V2 + I2 r2 (5)
Fig. 3. Transmitted power Vs. LFC output voltage and power: (a) r1 = 0.5Ω
and r2 = 0.5Ω, (b) r1 = 0.1Ω and r2 = 0.1Ω V3 = V4 − Vk (6)
η(V4 − Vk )2
R3 = (7)
and its theoretical analysis for power flow control between Vk I2
dc grids are presented in Section-II. Section-III describes where V1 , V2 are the voltages of grid-1 and grid-2 respectively,
the proposed configuration and its operation along with the r1 , r2 are half of the transmission line resistances, V3 and I3
control. The design of controller parameters are presented in are the input voltage and current of LFC respectively, Vk and
Section-IV. Section-V and VI provide the real time simulation I2 are the output voltage and current of LFC respectively, V4
(using OPAL-RT) and experimental results (on down scale lab- is the node voltage just after LFC, I1 , I2 are the grid currents
oratory prototype) under various operating conditions. Finally, with the reference polarities as shown in Fig.2 (b), and η is
Section-VII concludes the work. efficiency of the LFC. Based on (3), (4), (5), (6) and (7) the
transmitted power through the line at node V4 is written as:
II. C ONNECTION DIAGRAM AND THEORETICAL ANALYSIS
OF LFC FOR POWER FLOW CONTROL
1
A. Connection diagram Pt = [V2 η(V1 − V4 ) + (ηV2 − 2I2 r2 )]
r1 η
Considering power flow control between two dc microgrids r1
+ 2 [(V1 − V4 )2 + (V4 − Vk )2 + 2V1 Vk − V42 ]
as an example, Fig.2 (a) shows the single line diagram of two r2
dc microgrids and their interconnection using LFC. The total Vk I2
+ 2 [V2 I2 r2 r1 − η(V4 − Vk )(V2 r1 + 2V1 r2 )]
generation available at microgrid-1 (bus-1) and microgrid-2 η (V4 − Vk )2 r1
(bus-2) are represented as PG1 and PG2 respectively. Similarly, (8)

1949-3053 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2018.2890548, IEEE
Transactions on Smart Grid
4

Power flow from grid-2 to grid-1 can be obtained by polarity in series with the transmission line under steady state
negating the expression of Pt . Using (8), the output voltage of as well as transient conditions.
LFC (Vk ) and power handled by it are plotted with respect to
power transferred (Pt ) from one grid to another grid, as shown B. Operation and control of DAB
in Fig.3. In practical dc microgrids, the dc bus voltage may
vary within ±5% of its rated voltage which may be due to A DAB is an isolated bidirectional dc-dc converter, having
uncertainty in renewable energy generation and load power two full-bridge dc/ac converters and a High Frequency (HF)
balancing etc,. Accordingly, here three different operating transformer as shown in Fig.4. The HF transformer provides
modes are considered (i.e. Mode-I: V1 = 380V, V2 = 380V , the voltage matching of two sides with different voltage levels
Mode-II: V1 = 380V, V2 = 400V , Mode-III: V1 = 400V, V2 = and galvanic isolation. It is important to mention that the
380V ) for analysis of power flow control between two dc energy stored in the decoupled inductor (Ld ) is sufficient
microgrids. Fig.3 shows theoretical results for power flow to realize Zero Voltage Switching (ZVS) of all the switches.
control with two different transmission line resistances (r1 The magnitude and direction of inductor current (ILd ) can
and r2 ) [23], [34]. Form Fig.3 (a) and (b), it is observed that be varied by adjusting the phase shift between Vtp and Vts
power handled by the LFC (i.e. Po = Vk × I2 ) depends on the of bridges, which can control the direction of power flow in
following parameters. DAB. The detailed steady-state analysis of DAB is available
in [37], [38]. The power transferred by the DAB is:
• Transmission line resistance between dc microgrids.
• DC bus voltage levels. V3 Vo Ts (D − D2 )
Pdo =< Ido > Vo = Iinb Vo = (9)
• The magnitude of power to be transfered from one grid 2nLd
to other. Where V3 and Vo are the input and output voltages of DAB
One more observation from these figures is that the power respectively, TS is the switching time period, D is a variable
handled by the LFC need to be bidirectional, particularly in for control of phase shift between transformer primary and
case-2 and case-3 (see in Fig.3 (a) and (b)). In Mode-I (same secondary voltage (phase-shift = πD), n is the winding turns
grid voltages), the transmitted power is zero. The LFC voltage ratio of transformer. Maximum power will be transferred from
output is zero, compared to other two modes which is obvious. primary to secondary or vice versa when D = ±0.5.
Power handled by the LFC (Po =Vk ×I2 ) is less in Mode-II and The control for DAB, consists of two control loops which
Mode-III (different grid voltages), when power is transfered are outer voltage loop and inner current loop. The main
from higher voltage grid to lower voltage grid (Fig.3 (a) and purpose of this control is to maintain required power flow
(b)). Similarly the Power handled by the LFC (Po =Vk × I2 ) through the LFC keeping the output of DAB (i.e. Vo ) constant.
is more, when power is transfered from lower voltage grid to The difference between the reference and actual values of Vo
higher voltage grid. However, in the overall operation of power (where e = Vo∗ − Vo ) is fed to a Proportional-Integral (PI)
flow control, power handled by the LFC is fairly less (<10%) type voltage controller which generates reference (i.e. I3∗ ) for
compared to the power transmitted between grids (Fig.3 (a) the inner current loop. The actual input current of the DAB
and (b)). is then compared with reference value and the error is passed
to the current controller with transfer function Gci3 . Note that
III. C ONFIGURATION , O PERATION AND C ONTROL OF LFC only the integral controller is enough for the inner current
A. Topology loop. The inner current loop generates desired phase shift
πD. Here D is varying from -0.5 to 0.5. The control keeps
The proposed topology of LFC is shown in Fig.4. The output voltage of DAB (i.e. Vo ) constant irrespective of the
LFC comprises of a DAB followed by a full-bridge dc-dc variation of load, as well as the input voltage of DAB (i.e.
converter. The two bridges (primary and secondary) in DAB V3 ). The gains of controllers are chosen in such a way that
are operated to generate high-frequency square-wave voltage at the bandwidth of outer voltage loop is 10 times lesser than
the transformer terminals. The phase shift between two square- the inner current loop. The design of various controllers are
waves can be adjusted to control power flow from V3 to Vo presented in Section-IV.
or vice versa. Power flow always happens from the bridge
generating leading square-wave to the other bridge [35]. The
first stage of LFC (i.e. DAB) is operated in power control C. Operation and control of full bridge dc-dc converter
mode and its output voltage (Vo ) is always maintained to its The full bridge dc-dc converter is used to generate ad-
reference value under the variation of output current (Iinb ) and justable voltage for desired voltage regulation. The switching
input voltage (V3 ). The output of DAB is connected to input of signals for T9 , T10 , T11 and T12 are generated through the
second stage converter (i.e. full bridge dc-dc converter). Full comparison of triangular carrier signal and control signal (Vc )
bridge dc-dc converter is operated in voltage control mode [36]. The polarity of the output voltage can be changed from
with unipolar modulation [36] to generate an adjustable dc +Vk to -Vk and vice versa by changing the sign of the control
voltage (Vk ). So, based on the power reference command, signal (i.e. from +Vc to -Vc ). Note that the switches T9 , T12
the required amount of voltage with suitable polarity can and T10 , T11 are operated as a pair. The gate pulses for T9 and
be generated across output of full bridge dc-dc converter. T12 are inverse of T10 and T11 with appropriate dead time. An
The proposed configuration regulates power flow between LC filter is used at the output of dc-dc converter for filtering
dc microgrids by adding controlled voltage with appropriate out the ripples from the output voltage. The magnitude of Vrs

1949-3053 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2018.2890548, IEEE
Transactions on Smart Grid
5

Fig. 4. The overall system with LFC

is changing from +Vo to -Vo based on switching operation and


ILo is the current flowing through the filter inductor. The LFC
output voltage (Vk ) and output current (Ik ) are the average
values of Vrs and ILo respectively.
The control of full-bridge dc-dc converter, consists of power
controller (Gcp ) and voltage controller (Gcvc ) are shown in
Fig.4. The objective of these controllers is to adjust output Fig. 5. The control block diagram for DAB operation
voltage of LFC (Vk ) with required magnitude and polarity. The
reference power (i.e. Pt∗ ) to be transferred between microgrids  
1
compared to actual power (Pt = V4 × I2 ). The error is given Mid Zo n + Zin Miv
v̂o
to a Proportional-Integral (PI) controller (Gcp ) which gives a Gvod = = 2 (12)
reference for voltage controller (Gcvc ). The voltage reference dˆ 1 − Zin Zo Miv
is generated through the following equation. Ts 2 Vo Ts
where Miv = 2nLd (D −D ), Mid = 2nLd (1−2D), Zin =
rs (1+src1 C1 ) ro (1+src2 C2 ) 1+sC1 rc1
Vk∗ = (Pt∗ − Pt )Gcp . (10) 1+sC1 (rc1 +rs ) , Zo = 1+sC2 (rc2 +ro ) , Min = 1+sC1 (rc1 +rs )

Where Pt∗ can be in both polarities (i.e. either +ve or -ve) Using equations (11) and (12), the DAB input-current to
based on power flow requirement. If the reference power is output-voltage transfer function (Gvoi3 ) may be written as
+ve, that means the power is transfered from grid-1 (bus-1) to follows.
grid-2 (bus-2). Similarly in the reverse power flow, the polarity v̂o v̂o dˆ
Gvoi3 = = (13)
of Pt∗ is -ve. î3 dˆ î3
The actual output voltage of LFC (Vk ) is then compared With the help of above transfer functions, the control block
to the reference value which is generated from Gcp . The diagram of DAB is shown in Fig.5.
error is formed in between the reference and actual output The closed loop transfer function between I3∗ and I3 can be
voltage (i.e. e = Vk∗ − Vk ) which is fed to a PI controller expressed as
(Gcvc ). Voltage controller provides the control signal (i.e. Vc ) I3 Ti
to generate PWM signals for switches T9 to T12 . Gi = ∗ = (14)
I3 1 + Ti
where Ti = Gci3 Gi3d Hi3 .
IV. D ESIGN OF C ONTROLLER PARAMETERS The Kii of the current controller (Gci3 ) is designed to set
1
the gain-cross-over frequency at 10 times of the switching fre-
A. Controller gains of DAB
quency. With the help of MATLAB toolbox, Kii is calculated
The control signal (d) ˆ to input-current (î3 ) transfer-function as 0.03.
(Gi3d ) and control signal (d) ˆ to output-voltage (v̂o ) transfer- The transfer function between Vo and Vo∗ can be expressed
function (Gvod ) of DAB can be written as follows [39]. as follows.
Vo Tv1
  Gv1 = ∗ = (15)
Min Mid 1 + n Zo Miv Vo 1 + Tv1
î3
Gi3d = = (11) where Tv1 = Gi
Hi3 Gcvo Gvoi3 Hvo .
2
dˆ 1 − Zin Zo Miv

1949-3053 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2018.2890548, IEEE
Transactions on Smart Grid
6

the bandwidth of the voltage loop should be 10 times lower


than the switching frequency. Considering this, Kpk and Kik
can be calculated as 0.1 and 0.01, respectively.
The closed loop transfer function between Pt and Pt∗ can
be expressed as follows.
Pt Tp
Fig. 6. The control block diagram for full bridge dc-dc converter operation Gp = ∗ = (23)
Pt 1 + Tp
Gv2
where Tp = H Gcp Gptvk Hpt
The gains of the voltage controller (i.e. Kpv , Kiv of Gcvo ) vk
The gains of power controller (i.e. Kpp , Kip of Gcp ) are
are selected in such a way that the bandwidth of the outer selected in such a way that the bandwidth of the outer voltage
voltage loop should be 10 times lower than the inner current loop should be 30 times lower than the inner current loop.
loop. Considering this, Kpv and Kiv is calculated as 1.9 and Considering this, Kpp and Kip is calculated as 0.01 and 0.035,
10.1, respectively. respectively.

B. Controller gains of full bridge dc-dc converter C. Stability analysis


The control block diagram of full bridge dc-dc converter is The stability of the complete system with the presence of
shown in Fig.6. The control signal (v̂c ) to output-voltage (v̂k ) LFC is performed in this section. The stability analysis is
transfer-function (Gvkvc ) is written as follows [40]. carried out using state space model of the system. Fig.7 shows
v̂k (XRo )Vo the simplified equivalent representation of the system with the
Gvkvc = = (16) following assumptions.
vˆc (XRo ) + Y (X + Ro )
• Total resistance of the distribution line is referred to grid-
Where X = resr + sC1 o , Y = rLo + sLo , Ro is the
2 side.
load resistance. Small-signal representation of the transmitted
• Output filter inductance (Lo ) of LFC is included within
power between dc microgrids (p̂t ) can be expressed as a
the line inductance value.
function of (v̂k ), (v̂4 ) and (î2 ) as (17),
• Inductor (L1 ) represents the input inductance of source.
• The losses of the LFC are neglected.
p̂t = K1 v̂4 + K2 î2 + K3 v̂k (17)
Based on these assumptions, an overall state space model of
where small-signal variables are denoted with hats. K1 , K2 the system is derived which is expressed through the flowing
and K3 are the gains evaluated at steady-state operating point equations.
and given by,
ẋ = Ax + Bu (24)
V2 2r2 V1 2r2 (V4 + Vk )
K1 = + − (18) y = Cx + Du
r1 r1 r12
where x is the state vector, u is the input vector, y is the output
V2 Vk 2r2 V1 Vk 2I2 Vk2 r2 2r2 Vk
K2 = + − 2 − vector, and A, B, C, D are the state-space matrices which are
η(V4 + Vk ) ηr1 (V4 + Vk ) η (V4 + Vk )2 ηr1 expressed as follows.
(19)
 T
V 2 I2 2r2 V1 I2 2I 2 Vk r2 2r2 I2 x = Vk ILo Vo I3 (25)
K3 = + − 2 2 −
η(V4 + Vk ) ηr1 (V4 + Vk ) η (V4 + Vk )2 ηr1 
u = V1 V2
T
(26)
V2 2V1 r2 2r2 (V4 + Vk )
+ + − (20) 
y = Vk iLo Vo i3 I1 I2
T
(27)
r1 r12 r12
 −1 1
Using (17) transmitted power (p̂t ) to output voltage (v̂k ) 0 0

r12 Co Co
transfer-function (Gptvk ) is expressed in (21) by considering −1 2D1 −1
 L 0 Lo 0
v̂4 = 0 and î2 = 0. A= o
− 2D1 −1 0
 (28)
2r12 C2 0 0
−1
p̂t V2 I2 2r2 V1 I2 2I 2 Vk r2 0 0 nL1 0
Gptvk = = + − 2 2
v̂k η(V4 + Vk ) ηr1 (V4 + Vk ) η (V4 + Vk )2  −1 1

r12 Co r12 Co
2r2 I2 V2 2V1 r2 2r2 (V4 + Vk ) 0 0
− + + − (21)
 
ηr1 r1 2
r1 r12 B =  Ts (D−D2 )
 
(29)
2D1 −1 2D1 −1 
 2nLd C2 − 2r12 C2 2r12 C2 
The closed loop transfer function between Vk and Vk∗ can 1
0
L1
be expressed as:    
1 0 0 0 0 0
Vk Tv2
Gv2 = = (22)  0 1 0 0  0 0 
Vk∗ 1 + Tv2 
0 0 1

0
 
& D =  0 0
  
where Tv2 = Gcvc Gvkvc Hvk . C=  (30)
 0 0 0 1  0 0 
−1 
 1   1 
The gains of voltage controller (i.e. Kpk , Kik of Gcvc ) in r 0 0 0 r r
12 12 12
full bridge buck dc-dc converter are selected in such a way that −1 −1 1
r12 0 0 0 r12 r12

1949-3053 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2018.2890548, IEEE
Transactions on Smart Grid
7

Fig. 7. Equivalent representation of the total system

Fig. 9. OPAL-RT system architecture

Four eigenvalues are obtained from A matrix, out of which


two are found to be dominant. Fig.8 shows the variation of
these dominant pole locations with respect to r12 , D1 and
Lo . It is important to note that poles remain always in the
left half plane confirming that the introduction of LFC does
not make the system unstable. Increasing the magnitude of Lo
moves the pole to further left enhancing stability (although in
practice this makes the LFC more bulky). The performance of
the system with the variation of D1 is explained as follows. At
D1 =0.5, the LFC output is zero. In practice, at this point, the
DAB operates at a very light load condition supplying only
the losses invoking stability issues. This is also reflected here
with one pole approaching to origin. Identical behavior of the
poles is observed when D1 varies from 0.5 to 1 as expected.

V. R EAL - TIME (OPAL-RT) R ESULTS


Two dc microgrids at 380V level connected through a
transmission line resistance of 1Ω is considered for real-
time (OPAL-RT) simulation study. Fig.9 shows the real-time
simulation test bed used in this work. The proposed system
is first modeled in MATLAB integrated with OPAL-RT. Then
Fig. 8. Movement of pole locations: (a) Variation of LFC output voltage in it is compiled with RT-LAB to run as an effective platform
terms of duty ratio (D1 ) from 0 to 1, (b) Variation of line resistance (r12 ) for developing and testing real-time operation of the system
from 0.1Ω to 1Ω, (c) Variation of filter inductance (Lo ) from 0.1mH to 10mH
under consideration. The parameters corresponding to Fig.4
are: V1 =V2 =380V±5% (which are assumed as dc microgrids),

1949-3053 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2018.2890548, IEEE
Transactions on Smart Grid
8

Fig. 10. Power flow in microgrids operating at same bus voltages (V1 =380V and V2 =380V): Vo -DAB output voltage (50V/div), Vk -LFC output voltage
(20V/div), I1 -Current from the bus-1 (25A/div), I2 -Current entered to the bus-2 (25A/div), V1 -Voltage at bus-1, V3 -Node voltage at DAB input, V4 -Node
voltage just after LFC, V2 -Voltage at bus-2 (70V/div)

as per requirements. Current from the bus-1 (I1 ) is negative


and current entered to the bus-2 (I2 ) is positive upto point-
X, that indicates power in the transmission line is flowing
from bus-1 to bus-2. After the point-X, both currents (I1
and I2 ) are reversed for change of direction of power flow.
It clearly indicates that the direction of power flow can be
controlled by controlling the magnitude and polarity of Vk .
The corresponding terminal voltages V1 , V3 , V4 and V2 are
shown in Fig.10. The flow of power at terminal voltage V4
(i.e. Pt = V4 I2 ) is equal to 10kW in both directions of
power flow. It indicates that the desired power flow control
is possible irrespective of voltage magnitudes at two buses.
Moreover, power handled by the LFC (i.e. Po = Vk I2 ) is
less (nearly 10%) compared to power transfered between two
microgrids. The pictorial representation of power flow between
buses are shown in Fig.11. The power drawn from bus-1 is
Fig. 11. Power flow for case-1: (a): Power flow from Bus-1 to Bus-2 (before more compared to the power entered to bus-2 because of losses
point-X), (b) Power flow from Bus-2 to Bus-1 (in between point X and Y) in the transmission line and LFC as observed in Fig.11 (a). The
reverse situation is shown in Fig.11 (b). In both directions of
r1 =r2 =0.5Ω, V3 (input of DAB) =380V±10%, Vo (output power flow control, the LFC output voltage polarity is changed
of DAB) =110V±1%, Po (rated power of LFC) =1kW and to maintain the power flow at node V4 to its reference value
switching frequency=5kHz. The details of real-time simulator i.e. 10kW.
are given in TABLE I. The results are presented for the
following cases. B. Case-2: Power flow control at different grid voltages
In a actual dc microgrids, the bus voltage can vary between
A. Case-1: Power flow control at same voltage ±5% of rated voltage, because the output fluctuations of
The real-time simulation is carried out for step change in renewable energy sources. So, it is important to consider the
power command, where Pt is changed in steps from +10kW voltage difference among dc microgrids. The Fig.12 (a) and (b)
to -10kW and vice-versa in every 5 sec. The system response show power flow control and system response with different
for V1 =380V and V2 =380V is shown in Fig.10. The point bus voltage levels. Since the bus voltage levels are different,
X (at 3sec) and Y (at 8sec) indicate the sudden change the magnitudes of Vk is changed to control the same amount of
of power flow direction from bus-1 to bus-2 (from +10kW power-flow between grids compared to case-1. Fig.12 (a) and
to -10kW ) and bus-2 to bus-1 (from -10kW to +10kW ) (b) show the power handled by LFC (i.e. Po = Vk I2 ) is less
respectively. The output voltage of DAB (Vo ) is held constant when power is transferred from higher voltage bus to lower
(at ≈110V) irrespective of power flow direction. The output voltage bus (e.g. before point-X in Fig.12 (a)). On the contrary,
voltage of the LFC (Vk ) changes its polarity and magnitude power handled by LFC is more when power is transferred from

1949-3053 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2018.2890548, IEEE
Transactions on Smart Grid
9

Fig. 12. Power flow in microgrids operating at different bus voltages ((a) V1 =380V, V2 =400V and (b) V1 =400V, V2 =380V): Vo -DAB output voltage (50V/div),
Vk -LFC output voltage (20V/div), I1 -Current from the bus-1 (25A/div), I2 -Current entered to the bus-2 (25A/div), V1 -Voltage at bus-1, V3 -Node voltage at
DAB input, V4 -Node voltage just after LFC, V2 -Voltage at bus-2 (70V/div)

Fig. 13. DC microgrids with PV, BESS and LFC

TABLE I
REAL-TIME (OPAL-RT) S IMULATOR PARAMETERS

parameter description
Type of simulation Real-Time
Time-step 35us Fig. 14. Power flow control between dc microgrids with three different
Operating System Linux based RedhatOS Operating Points (OPs): Ch-1:Vk -LFC output voltage (20V/div), Ch-2:V1 -
simulator OP5607 (RCP/HIL vitex7 FPGA processor) Grid-1 voltage, Ch-3:V2 -Grid-2 voltage, Ch-4:Pt -Power transfered through
the line

lower voltage bus to higher voltage bus (e.g. in between point C. Case-3: Power flow control between dc microgrids with PV
X and Y in Fig.12 (a)). During operation of LFC, the output and BESS
voltage of DAB (Vo ) is held constant (at ≈110V) irrespective So far DGs are replaced by voltage sources to investigate
of power flow direction. power transfer issues. Now a microgrid is considered with

1949-3053 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2018.2890548, IEEE
Transactions on Smart Grid
10

Fig. 15. Photographic view of the experimental prototype

Fig. 16. Performance under sudden change in power flow direction (V1 =30V,
PV, BESS and internal loads. This is shown in Fig.13. The V2 =30V): Ch-1:I1 -Current from the bus-1 (5A/div), Ch-2:I2 -Current entered
proposed LFC is successfully working under such circum- to the bus-2 (5A/div) , Ch-3:Vk -LFC output voltage (5V/div), Ch-4:Vo -DAB
output voltage (10V/div)
stances and the results are shown in Fig.14 for three different
Operating Points (OPs). In OP-1, PV at bus-1 is operated
at MPPT and generates 4 kW power (PP V 1 ). The load is transformer have 12-turns and 6-turns, respectively. Remaining
consuming 6 kW (PL2 ) and the difference power is supplied parameters of the hardware are as follows: C1 =4700µF, 450V,
by the BESS. Similarly, at bus-2, PV is operated at MPPT C2 =4700µF, 450V, Co =32µF, 100V, Lo =0.5mH, 10A and the
and generates 4 kW power. The load is 3 kW and the surplus switching frequency is 10kHz. Entire control is implemented
power is absorbed by the BESS. By this way, the voltage in a OPAL-RT/OP5607 (RCP/HIL vertex-7 FPGA processor
of both the buses are maintained at their rated value. Hence and I/O expansion unit).
power through the LFC is zero as shown in Fig.14 (Ch-4).
The corresponding output voltage of LFC (Vk ), grid-1 voltage
(V1 ) and grid-2 voltage (V2 ) are shown in Fig.14. B. Power flow in microgrids operating at same bus voltage
In OP-2, The load connected at bus-1 (PL1 ) is suddenly Fig. 16 shows the waveforms when the power flow com-
reduced to 1kW and PV output power is kept constant. The mand is changed from +100W to -100W at the same bus
load connected at bus-2 (i.e. PL2 ) is suddenly increased to voltage level. The dirction of currents for I1 (Fig.16 (Ch-
7kW and PV output power is almost constant. The power 1)) and I2 (Fig.16 (Ch-2)) changes based on the power flow
generation is more compared to load power at grid-1 (Ppv1 > command. It clearly indicates that the magnitude of current
PL1 + PB1 ) and the reverse situation has happened at grid-2 from bus-1 (I1 =4.5A) is more compared to current entered
(Ppv1 + PB1 < PL1 ). In this situation, the difference power into bus-2 (I2 =3A) during positive power flow command (i.e.
available at bus-1 can be transferred to bus-2 through LFC from bus-1 to bus-2). This is because, the extra power drawn
to match the load and generation at both of the buses. The from bus-1 includes losses of LFC and line. The magnitudes
corresponding results are shown in Fig.14. of these currents will be reversed during negative power flow
Reverse situation of OP-2 is considered in OP-3, where power command, i.e. from bus-2 to bus-1. The LFC output voltage
transfer is taken place from bus-2 to bus-1. The corresponding (Fig.16 (Ch-3)) is changing its polarity to transfer the required
results are presented in Fig.14. power flow between the dc-grids in appropriate direction. Note
that DAB output voltage (Fig.16 (Ch-4)) is maintained to its
VI. E XPERIMENTAL RESULTS reference value irrespective of power flow direction. These
waveforms clearly indicate the effectiveness of the proposed
A. Prototype description
LFC in power flow control between two dc microgrids.
The prototype of the experimental system is shown in
Fig.15. The dc microgrids are formed with the help of 30V
dc regulated power supply and a variable resistance of 10Ω, C. Power flow in microgrids operating at different bus volt-
6.5A. Microgrid-1 and Microgrid-2 are connected at bus- ages
1 and bus-2 respectively. Two 0.5Ω (300W) resistances are Fig.17 and 18 show the waveforms when the power flow
connected between the buses which represents equivalent command is changed from -70W to +70W at different oper-
resistance of the transmission line. Semikron make half-bridge ating conditions. In first condition, the bus voltages are set
IGBT module (SKM74GB12T4) is used to form DAB and at V1 =27V and V2 =30V corresponding to Fig.17. The reverse
dc-dc converter of the power circuit. The transformer and situation is considered for Fig.18, where V1 =30V and V2 =27V.
decoupled inductor are made with Ferrite core (N-87) of It is observed that the output voltage of LFC (Ch-3 of Fig.17
size ETD-59. The primary and secondary windings of the and 18) is more when the power is transfered from lower

1949-3053 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2018.2890548, IEEE
Transactions on Smart Grid
11

through real-time simulation and experimental prototype. The


proposed concept using LFC makes the power flow simple and
efficient at different voltage levels of grids and expected to be
very popular in future.

ACKNOWLEDGMENT
The authors acknowledge the support from Department of
Science and Technology (DST), Govt. of India and Engineer-
ing and Physical Research Council (EPSRC), UK through the
project Reliable and Efficient System for Community Energy
Solution (RESCUES/EP/K03619X/1).

R EFERENCES
[1] M. Nouni, S. Mullick, and T. Kandpal, “Providing electricity access to
remote areas in india: An approach towards identifying potential areas
for decentralized electricity supply,” Renewable and Sustainable Energy
Fig. 17. Performance under sudden change in power flow direction (V1 =27V, Reviews, vol. 12, no. 5, pp. 1187–1220, 2008.
V2 =30V): Ch-1:I1 -Current from the bus-1 (5A/div), Ch-2:I2 -Current entered [2] L. Che, X. Zhang, M. Shahidehpour, A. Alabdulwahab, and A. Abusor-
to the bus-2 (5A/div), Ch-3:Vk -LFC output voltage (10V/div), Ch-4:V4 - rah, “Optimal interconnection planning of community microgrids with
Voltage after LFC (20V/div) renewable energy sources,” IEEE Transactions on Smart Grid, vol. 8,
no. 3, pp. 1054–1063, 2017.
[3] D. Wu, F. Tang, T. Dragicevic, J. M. Guerrero, and J. C. Vasquez,
“Coordinated control based on bus-signaling and virtual inertia for
islanded dc microgrids,” IEEE Transactions on Smart Grid, vol. 6, no. 6,
pp. 2627–2638, 2015.
[4] A. Werth, N. Kitamura, and K. Tanaka, “Conceptual study for open
energy systems: distributed energy network using interconnected dc
nanogrids,” IEEE Transactions on Smart Grid, vol. 6, no. 4, pp. 1621–
1630, 2015.
[5] Y. Ito, Y. Zhongqing, and H. Akagi, “Dc microgrid based distribution
power generation system,” in Power Electronics and Motion Control
Conference, 2004. IPEMC 2004. The 4th International, vol. 3. IEEE,
2004, pp. 1740–1745.
[6] M. Lee, W. Choi, H. Kim, and B.-H. Cho, “Operation schemes of
interconnected dc microgrids through an isolated bi-directional dc-dc
converter,” in Applied Power Electronics Conference and Exposition
(APEC), 2015 IEEE. IEEE, 2015, pp. 2940–2945.
[7] S. Parhizi, H. Lotfi, A. Khodaei, and S. Bahramirad, “State of the art in
research on microgrids: A review,” IEEE Access, vol. 3, pp. 890–925,
2015.
[8] Q. Shafiee, T. Dragičević, J. C. Vasquez, and J. M. Guerrero, “Hierar-
chical control for multiple dc-microgrids clusters,” IEEE Transactions
on Energy Conversion, vol. 29, no. 4, pp. 922–933, 2014.
[9] S. Moayedi and A. Davoudi, “Distributed tertiary control of dc microgrid
Fig. 18. Performance under sudden change in power flow direction (V1 =30V, clusters,” IEEE Transactions on Power Electronics, vol. 31, no. 2, pp.
V2 =27V): Ch-1:I1 -Current from the bus-1 (5A/div), Ch-2:I2 -Current entered 1717–1733, 2016.
to the bus-2 (5A/div), Ch-3:Vk -LFC output voltage (10V/div), Ch-4:V4 - [10] V. Nasirian, S. Moayedi, A. Davoudi, and F. L. Lewis, “Distributed
Voltage after LFC (10V/div) cooperative control of dc microgrids,” IEEE Transactions on Power
Electronics, vol. 30, no. 4, pp. 2288–2303, 2015.
[11] X. Li, L. Guo, Y. Li, C. Hong, Y. Zhang, Z. Guo, D. Huang, and
C. Wang, “Flexible interlinking and coordinated power control of
voltage bus to higher voltage bus. The node voltage after LFC multiple dc microgrids clusters,” IEEE Transactions on Sustainable
(i.e. V4 ) is also shown in Fig. 17 and 18 (Ch-4) which is Energy, vol. 9, no. 2, pp. 904–915, 2018.
changing according to the power flow command. [12] K. Rouzbehi, J. I. Candela, A. Luna, G. B. Gharehpetian, and P. Ro-
driguez, “Flexible control of power flow in multi terminal dc grids using
dc–dc converter,” IEEE Journal of Emerging and Selected Topics in
VII. C ONCLUSION Power Electronics, vol. 4, no. 3, pp. 1135–1144, 2016.
[13] D. Shi, X. Chen, Z. Wang, X. Zhang, Z. Yu, X. Wang, and D. Bian, “A
A novel power flow scheme to control power transfer distributed cooperative control framework for synchronized reconnection
between two dc microgrids using Load Flow Converter (LFC) of a multi-bus microgrid,” IEEE Transactions on Smart Grid, vol. 9,
no. 6, pp. 6646 – 6655, 2018.
is presented in this paper. Topologically, this is a cascading of [14] A. Aderibole, H. Zeineldin, and M. Al Hosani, “A critical assessment
Dual Active Bridge (DAB) and a full bridge dc/dc converter of oscillatory modes in multi-microgrids comprising of synchronous and
connected in input-shunt and output-series mode. The dc/dc inverter based distributed generation,” IEEE Transactions on Smart Grid,
2018 (early access).
converter can generate both positive and negative voltages [15] D. Jovcic, “Bidirectional, high-power dc transformer,” IEEE transactions
and is therefore capable of controlling power flow in both on Power Delivery, vol. 24, no. 4, pp. 2276–2283, 2009.
directions. The power rating of the LFC is found very low [16] M. Kumar, S. C. Srivastava, S. N. Singh, and M. Ramamoorty, “De-
velopment of a control strategy for interconnection of islanded direct
(approximately 10%) compared to the power transfer between current microgrids,” IET Renewable Power Generation, vol. 9, no. 3,
the grids. The performance of LFC is extensively checked pp. 284–296, 2014.

1949-3053 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2018.2890548, IEEE
Transactions on Smart Grid
12

[17] A. P. Tahim, D. J. Pagano, M. L. Heldwein, and E. Ponce, “Control of [38] R. Naayagi, A. J. Forsyth, and R. Shuttleworth, “High-power bidirec-
interconnected power electronic converters in dc distribution systems,” tional dc–dc converter for aerospace applications,” IEEE Transactions
in Power Electronics Conference (COBEP), 2011 Brazilian. IEEE, on Power Electronics, vol. 27, no. 11, pp. 4366–4379, 2012.
2011, pp. 269–274. [39] M. Evzelman, M. M. U. Rehman, K. Hathaway, R. Zane, D. Costinett,
[18] M. Mahmoodi, R. Noroozian, G. B. Gharehpetian, and M. Abedi, “A and D. Maksimovic, “Active balancing system for electric vehicles with
suitable power transfer control system for interconnection converter of incorporated low-voltage bus,” IEEE Transactions on Power Electronics,
dc microgrids,” in International Conference on Renewable Energies and vol. 31, no. 11, pp. 7887–7895, 2016.
Power Quality (ICREPQ), 2008, pp. 12–14. [40] R. W. Erickson and D. Maksimovic, Fundamentals of Power Electronics.
[19] M. Farhadi, A. Mohamed, and O. Mohammed, “Connectivity and Springer Science & Business Media, 2007.
bidirectional energy transfer in dc microgrid featuring different voltage
characteristics,” in Green Technologies Conference, 2013 IEEE. IEEE,
2013, pp. 244–249.
[20] J. Ma, M. Zhu, X. Cai, and Y. W. Li, “Configuration and operation
of dc microgrid cluster linked through dc-dc converter,” in Industrial
Electronics and Applications (ICIEA), 2016 IEEE 11th Conference on. Umamaheswararao Vuyyuru (S’16) received his
IEEE, 2016, pp. 2565–2570. B.Tech degree in Electrical and Electronics Engi-
[21] A. Berasain, J. Lopez, E. Gubia, H. Piquet, and L. Marroyo, “Power neering from Jawaharlal Nehru Technological Uni-
control between two dc buses for on-board systems network stability versity, Kakinada and M. Tech Degree in Electrical
support,” in Industrial Electronics, 2009. IECON’09. 35th Annual Con- Engineering with specialization in Power Electronics
ference of IEEE. IEEE, 2009, pp. 2575–2580. from National Institute of Technology Tiruchirap-
[22] D. Jovcic, M. Hajian, H. Zhang, and G. Asplund, “Power flow control in palli, India, in the year 2009 and 2012 respectively.
dc transmission grids using mechanical and semiconductor based dc/dc From June 2012 to May 2015, he has served as a
devices,” in 10th IET International Conference on. AC and DC Power assistant professor in GVP college of Engineering,
Transmission (ACDC 2012). IET, 2012, pp. 1–6. India. He is pursuing his Ph.D in School of Energy
[23] K. Natori, H. Obara, K. Yoshikawa, B. C. Hiu, and Y. Sato, “Flexible Science and Engineering, Indian Institute of Tech-
power flow control for next-generation multi-terminal dc power net- nology Kharagpur, India. His research interests include DC microgrids and
work,” in Energy Conversion Congress and Exposition (ECCE), 2014 power electronic converters.
IEEE. IEEE, 2014, pp. 778–784.
[24] Y. Takahashi, K. Natori, and Y. Sato, “A multi-terminal power flow
control method for next-generation dc power network,” in Energy
Conversion Congress and Exposition (ECCE), 2015 IEEE. IEEE, 2015,
pp. 6223–6230.
[25] S. Konar and A. Ghosh, “Interconnection of islanded dc microgrids,” in Suman Maiti (M’10) received his BE degree from
Power and Energy Engineering Conference (APPEEC), 2015 IEEE PES Jalpaiguri Govt. Engineering College in 2002, Mas-
Asia-Pacific. IEEE, 2015, pp. 1–5. ter degree from IIEST Shibpur in 2004, and PhD
[26] J. Huang, J. Xiao, C. Wen, P. Wang, and A. Zhang, “Implementation of degree from Indian Institute of Technology Kharag-
bidirectional resonant dc transformer in hybrid ac/dc micro-grid,” IEEE pur in 2009. All the degrees are in Electrical Engi-
Transactions on Smart Grid, 2017 (early access). neering. Since 2009, he had been working with the
[27] A. S. Morais and L. A. Lopes, “Interlink converters in dc nanogrids Research and Development (R&D) group of ABB
and its effect in power sharing using distributed control,” in Power (India) Ltd. as an Associate Scientist. In 2014, he
Electronics for Distributed Generation Systems (PEDG), 2016 IEEE 7th joined in the department of Electrical Engineering,
International Symposium on. IEEE, 2016, pp. 1–7. Indian Institute of Technology Kharagpur as an
[28] R. Haghmaram, F. Sedaghati, and R. Ghafarpour, “Power exchange Assistant Professor. His research interests include
among microgrids using modular-isolated bidirectional dc–dc converter,” topology evaluation and control of multilevel converters for high power
Electrical Engineering, vol. 99, no. 1, pp. 441–454, 2017. applications, AC/DC microgrids, Renewable energy integration and related
[29] A. Mohamed and O. Mohammed, “Power flow control in dc distribution issues.
systems,” in North American Power Symposium (NAPS), 2010. IEEE,
2010, pp. 1–7.
[30] V. Umamaheswararao, J. George, S. Maiti, and C. Chakraborty, “Dy-
namic voltage compensation using series voltage regulator for dc-
microgid,” in Industrial Electronics Society, IECON 2016-42nd Annual
Conference of the IEEE. IEEE, 2016, pp. 2271–2276. Chandan Chakraborty (S’92-M’97-SM’01-F’15)
[31] T. Tanaka, Y. Takahashi, K. Natori, and Y. Sato, “High-efficiency received the B.E. and M.E. degrees in electrical en-
floating bidirectional power flow controller for next-generation dc power gineering from Jadavpur University, Kolkata, India,
network,” IEEJ Journal of Industry Applications, vol. 7, no. 1, pp. 29– in 1987 and 1989, respectively, and the Ph.D degrees
34, 2018. from the Indian Institute of Technology Kharagpur,
[32] D. S. Segaran, “Dynamic modelling and control of dual active bridge India and Mie University, Tsu, Japan, in 1997 and
bi-directional dc-dc converters for smart grid applications,” Ph.D. disser- 2000, respectively. He is currently a Professor with
tation, School of Electrical and Computer Engineering (SECE), RMIT the Department of Electrical Engineering, Indian
University., February 7 2013. Institute of Technology Kharagpur. His research
[33] H. Mohsenian-Rad and A. Davoudi, “Towards building an optimal interest includes power converters, motor drives,
demand response framework for dc distribution networks,” IEEE Trans- electric vehicles, and renewable energy.
actions on Smart Grid, vol. 5, no. 5, pp. 2626–2634, 2014. Dr.Chakraborty was awarded the JSPS Fellowship to work at the University
[34] Y. Mi, H. Zhang, Y. Fu, C. Wang, P. C. Loh, and P. Wang, “Intelligent of Tokyo during 20002002. He has received the Bimal Bose award in power
power sharing of dc isolated microgrid based on fuzzy sliding mode electronics in 2006 from the IETE (India). He has regularly contributed to
droop control,” IEEE Transactions on Smart Grid, 2018. IES conferences such as IECON, ISIE, and ICIT as general chair/technical
[35] M. Kheraluwala, R. W. Gascoigne, D. M. Divan, and E. D. Baumann, program chair/track chair. He is an ADCOM Member of the IEEE Industrial
“Performance characterization of a high-power dual active bridge dc- Electronics Society. He is a co Editor-in-Chief of IEEE TRANSACTIONS ON
to-dc converter,” IEEE Transactions on Industry Applications, vol. 28, INDUSTRIAL ELECTRONICS, an associate editor of IEEE INDUSTRIAL
no. 6, pp. 1294–1301, 1992. ELECTRONICS MAGAZINE and an Editor of the IEEE TRANSACTIONS
[36] N. Mohan and T. M. Undeland, Power Electronics: Converters, Appli- ON SUSTAINABLE ENERGY. He is also an editor of IEEE POWER ENGI-
cations, and design. John Wiley & Sons, 2007. NEERING LETTERS. He is the Founding Editor-in-Chief of IE Technology
News (ITeN), a web-only publication for IEEE Industrial Electronics Society.
[37] C. Mi, H. Bai, C. Wang, and S. Gargies, “Operation, design and
He is a Fellow of the Indian National Academy of Engineering (INAE).
control of dual h-bridge-based isolated bidirectional dc–dc converter,”
IET Power Electronics, vol. 1, no. 4, pp. 507–517, 2008.

1949-3053 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

You might also like