Nizamsagar - Illumination Clarification - 24.05.2024
Nizamsagar - Illumination Clarification - 24.05.2024
Nizamsagar - Illumination Clarification - 24.05.2024
Dear Sir,
With reference to TSGENCO Letter referred in sr. no. 2 above, please find our point wise reply as
below:
Sr.
TSGENCO comment Voith replies
No.
Control circuit Schematic drawing for space heater control panel shall be submitted
drawing for space separately.
1 heaters and No separate circuit diagram is prepared for illumination. As a standard
illumination is not practice, we will follow the installation as per our submitted Generator
provided wiring illumination drawing no. 2GSV00-0000-10139074.
Temperature sensor
Please be informed that Temperature sensor are already provided at sr. no.
for auto ON/OFF
7.1.1 in Gen instrument list (doc no. 2GSV00-0000-10119097 Rev A)
2 operation of space
submitted via Transmittal no. VHN/NZSR_TRANS-000071 dated
heaters are not
24.12.2021. Please refer the same.
provided
We hope that above clarification will suffice the purpose. We hereby request you to kindly provide
approval on Generator wiring illumination drawing no. 2GSV00-0000-10139074 at the earliest.
Yours faithfully,
For Voith Hydro Private Limited