Professional Documents
Culture Documents
Power Swing in Systems With Inverter-Based ResourcesPart II Impact On Protection Systems
Power Swing in Systems With Inverter-Based ResourcesPart II Impact On Protection Systems
This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3382843
Abstract—After introducing and analytically proving the dis- guidance for future IBR interconnection standards, parameter
tinctive dynamics associated with power swing of inverter-based tuning of inverter controllers, determining appropriate proce-
resources (IBRs) in Part I, Part II of this paper investigates the dures for the power swing detection component of relays, and
implications of such dynamics for power system protection. The
paper sheds light on some of the major consequences of IBRs’ the potential need for modifying these elements.
unique power swing patterns. The study employs theoretical The power swing frequency is directly reflected in the rate of
analysis and detailed PSCAD/EMTDC simulation models to change of apparent impedance, which is the primary param-
unveil the shortcomings of the conventional wisdom regarding eter examined by practical power swing detection methods
the power swing characteristics of IBRs. The paper offers new
discussed in [7], [8], [9], [10]. This poses several critical
insights into the operation of transmission line relays during
power swing conditions. This part of the study is supported by questions:
extensive testing of commercial relays. The findings of this paper 1) How can the dynamic model developed in Part I of the
will provide guidance for future IBR interconnection standards,
paper be utilized to derive analytical expressions that
the design of inverter control schemes, the power swing detection
methods used by relays, and the appropriate relay settings. describe the rate of change of impedance measured by
relays in systems with IBRs?
Index Terms—Inverter-based resources (IBRs), large-signal
disturbances, power swing, transmission line relays.
2) How can these expressions be employed to analytically
investigate the performance of power swing blocking
schemes of transmission line relays?
3) Do the behaviors of real-world, commercial relays repli-
I. I NTRODUCTION cate the findings from this paper?
4) What would be the system-wide implications of any
P ART I of this paper developed a novel state-space model
to analyze the power swing characteristics of systems
with inverter-based resources (IBRs) and synchronous ma-
potential relay malfunction caused by the IBRs’ uncon-
ventional power swing characteristics?
chines (SMs) [1]. The paper identified and mathematically 5) How can the power swing-related issues in systems with
represented the specific elements of an IBR control system IBRs be mitigated?
and the corresponding inverter parameters that affect power Each of the following five sections presents an answer to
swings after a fault. As a consequence, the developed model one of these questions.
enables assessing the combined impact of IBRs and SMs
on active power oscillations following a fault. This impact
analysis includes the range of frequency components in the II. R ATE OF C HANGE OF I MPEDANCE IN
voltage angle variations under different system conditions, G RIDS WITH IBR S
along with the origin of each component.
The first principle used by transmission line relays to
To ensure system stability after large-signal disturbances,
detect power swings is that the slow rotor dynamics of SMs
it is crucial to accurately distinguish between stable power
result in relatively small rates of impedance change for power
swings and faults [2]. For this purpose, transmission line relays
swings, whereas faults cause sudden changes in the apparent
primarily assess the swing frequency. The prevailing notion in
impedance seen by the relay [7], [8], [9], [10], [11]. To
the available literature is that the decrease in system inertia
determine the impact of IBRs on this approach, this section
caused by IBRs can raise the swing frequency and potentially
investigates the rate of change of impedance in grids with
hinder the reliable detection of power swing conditions by
IBRs. The following analysis shows how the dynamics of
relays [3], [4], [5], [6]. Part II of this paper will investigate if
voltage angle at IBR and SM buses—which were determined
the heightened swing frequency resulting from reduced system
by the state-space model in [1]—can be used to derive closed-
inertia poses the primary challenge for power swing detection
form relations for the rate of impedance change at any location
of line relays in systems with IBRs, or if there are other
in the system. These relations will form the basis for analyzing
aspects of the IBRs’ dynamics that could adversely affect these
the impact of IBRs on power swing detection techniques.
relays in a more significant manner. The findings will provide
To determine the rate of change of impedance, consider the
This work was supported by the Khalifa University of Science and transmission line in Fig. 1, which connects two subgrids that
Technology under Grant CIRA-2020-013. include a mixture of IBRs and SMs. In this figure, |Vx |̸ δx
The authors are with the Department of Electrical and Computer En-
gineering, University of Toronto, Toronto, ON M5S 3G4, Canada (email: and |Vy |̸ δy denote the voltages at buses x and y, respectively;
ma.nasr@mail.utoronto.ca; hooshyar@ece.utoronto.ca). Ix−y is the current flowing through the line; and Zx−y is
Authorized licensed use limited to: Universität Leipzig. Downloaded on March 29,2024 at 07:24:26 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3382843
seen by the relay, as in (6). in [1] and can be obtained using (38) and (40) in [1].
Therefore, all the parameters on the right side of (10) are
d h ∂ ih d i
known. The voltage angles of all the buses are in vector
ℜ{Zapp (t)} = ℜ{Zapp (t)} ∆δ(t) . (6)
dt ∂∆δ(t) dt Vn = [|V1 |̸ δ1 . . . |Vn |̸ δn ]T on the left side of (10). The
Calculating the partial derivative of the real part of Zapp (t) voltage angles calculated using (38) and (40) in [1] and
with respect to ∆δ(t) in (5) and substituting the result into (10) can be plugged into (7) to derive the rate of change of
(6) yield impedance measured by a relay.
" # It is worth noting that the oscillations associated with the
d −Xx−y 1 hd i
inverters’ outer control loops, including the dc-link voltage
ℜ{Zapp (t)} = · ∆δ(t) . (7)
dt 4 sin2 ∆δ(t) dt control loop discussed in [1], fall under the category of
2
low-frequency oscillations [14]. During such oscillations, the
The equation presented above is of a generic nature, thereby voltage and current waveforms are still dominated by the
making it applicable to any grid, regardless of the generation fundamental-frequency component. Therefore, modeling the
type involved. This equation shows that the rate of change electrical network using quasi-static phasors, as in (8) to
Authorized licensed use limited to: Universität Leipzig. Downloaded on March 29,2024 at 07:24:26 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3382843
Authorized licensed use limited to: Universität Leipzig. Downloaded on March 29,2024 at 07:24:26 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3382843
6 12 14a 6 12 14a
150 MW 150 MW
SM 4a 100 km SM 4a
100 km
14b
R12-6 150 MW R12-6 150 MW
Fig. 3. Area highlighted in Fig. 2 when IBRs replace the SM 4 units in: (a) Scenario 1; (b) Scenario 2; (c) Scenario 3; and (d) Scenario 4.
time difference shown in Fig. 4(e) for Scenario 4. Although the frequency of the SMs’ rotor oscillations intensi-
Figs. 5(b)-(d) indicate that once the 13 Hz swings subside fies due to the reduced inertia resulting from the replacement
around t = 2.25 s, the dominant frequency components of SMs with IBRs, the frequency range of the SMs’ rotor
transition to lower-frequency swings driven by the slower rotor oscillations in Figs. 4(b)-(d) remains within the commonly
dynamics of the SMs. Since the total inertia of the generation recognized 0.2 ∼ 2.5 Hz band for stable swing frequency of
behind bus 12 is determined based on the sum of the inertia SMs [15]. More importantly, this frequency range stays well
constants of the individual machines connected to this bus below the 7 Hz maximum frequency supported by the power
[17], reducing the number of SMs connected to bus 12 results swing detection elements of commercial relays [8], [9], [16].
in a decrease in the total inertia of the generation at this bus.
Reducing the inertia amplifies the swing frequency of the SMs
[18]. As a result, the frequency of the SMs’ rotor oscillations B. Rate of Change of Impedance
increases from 1/0.961 = 1.04 Hz in Fig. 4(a) (where the This subsection investigates the impact of the increase in
total inertia behind bus 12 reaches its maximum value of 8 the swing frequency discussed above on the rate of change of
s) to 1/0.731 = 1.37 Hz in Fig. 4(d) (where the total inertia apparent impedance seen by relay R12−6 in Fig. 3 after line
behind bus 12 is only 2 s). The potential increase in the swing 12-13 is tripped. Zones 1 and 2 of the phase distance element
frequency discussed in [3], [4], [5], [6] corresponds to this of this relay protect 80% and 120% of line 12-6, respectively.
specific increase, not the one explained in the previous two This relay uses the concentric characteristics delay to detect
paragraphs. Even if 95% of the generation at bus 12 becomes power swings [7], [8], [9], [10]. This technique measures
inverter-based, and the inertia of the SMs for the remaining the time it takes for the impedance locus to pass through
5% of the generation is H = 1 s (which is the minimum a zone delimited by two impedance characteristics, referred
practical value for SM inertia [19]), the swing frequency will to as the outer and middle characteristics [7]. If the elapsed
be only 2.5 Hz after the initial 13 Hz oscillations die out. time exceeds a certain threshold, such as 30 ms [10], the
The above finding also aligns with the simulation results in relay detects a power swing condition and blocks the distance
[3], where the swing frequency of SMs increases from 0.63 elements. The settings of the concentric technique for R12−6
Hz to only 0.77 Hz when the inertia of all the SMs is halved. are presented in Appendix A.
Authorized licensed use limited to: Universität Leipzig. Downloaded on March 29,2024 at 07:24:26 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3382843
Normalized amplitude Normalized amplitude Normalized amplitude Normalized amplitude Normalized amplitude
1
of oscillation
0.5
∆ t = 0.961 s
0
(a) (a)
1
of oscillation
0.5
∆ t = 0.078 s ∆ t = 0.882 s
0
(b) (b)
1
of oscillation
0.5
∆ t = 0.078 s ∆ t = 0.775 s
0
(c) (c)
1
of oscillation
0.5
∆ t = 0.078 s ∆ t = 0.731 s
0
(d) (d)
1
of oscillation
0.5
∆ t = 0.078 s
0
(e) (e)
Fig. 4. Phase angle difference between the voltages of buses 12 and 6, Fig. 5. STFT of δ12 − δ6 curves in Fig. 4 for: (a) the base scenario; (b)
calculated using (10) based on (38) and (40) in [1] for: (a) the base scenario; Scenario 1; (c) Scenario 2; (d) Scenario 3; and (e) Scenario 4.
(b) Scenario 1; (c) Scenario 2; (d) Scenario 3; and (e) Scenario 4.
The difference between the right blinders of the outer and rates depicted in Fig. 6, the following two-step methodology
middle characteristics of the concentric method used by R12−6 is pursued: (i) the vertical axes in Fig. 6 are scaled to convert
is about 7 Ω in Appendix A. Therefore, the objective is to the unit of the rate of change of impedance from Ω/s, as given
determine if the rate at which the impedance changes during by (7), to Ω/(30 ms). This rescaling aligns the measurement
the discussed power swing scenarios is high enough to cause scale with the time window pertinent to this analysis; and (ii)
the impedance to traverse the 7 Ω distance between the two the moving average of the solid-line curves in Fig. 6 is calcu-
blinders in less than 30 ms, leading to erroneous detection of a lated over a 30 ms window to calculate the above-mentioned
fault by R12−6 . To calculate the instantaneous rate of change integral. The average curves are shown as dashed lines in Fig.
of impedance, the voltage angles shown in Fig. 4 are plugged 6. This two-step process allows for easy determination of the
into (7), yielding the solid-line curves depicted in Fig. 6. To impedance variation over the preceding 30 ms at any given
determine whether the impedance trajectory crosses the critical point in time. For instance, for the base scenario, Fig. 6(a)
distance of 7 Ω between the power swing blinders in less illustrates that within the first 30 ms following the fault (i.e.,
than or more than 30 ms, the integral of these instantaneous from t = 2.075 to t = 2.105 s), the impedance measured
rates should be computed over a 30 ms period; i.e., the solid- by R12−6 decreases by only 2.14 Ω. This value is reliably
line curves in Fig. 6, in their original form, do not directly below 7 Ω, enabling the successful detection of a power swing
determine whether the impedance locus passes through the condition by the relay in the base scenario.
power swing region within the 30 ms time delay. For Scenarios 1 and 2, the amplitude of the 13 Hz oscil-
To enhance the visual comprehension of the instantaneous lations added by the IBRs to the curves in Figs. 4(b)-(c) is
Authorized licensed use limited to: Universität Leipzig. Downloaded on March 29,2024 at 07:24:26 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3382843
Authorized licensed use limited to: Universität Leipzig. Downloaded on March 29,2024 at 07:24:26 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3382843
tic
tic
tic
aracteris
aracteris
aracteris
40 40 40
istic
istic
istic
tic
tic
tic
character
character
character
30 30 30
aracteris
aracteris
aracteris
Outer ch
Outer ch
Outer ch
Zone 2 Zone 2
Inner ch
Inner ch
Zone 2 2.165 s
Middle
Middle
Middle
10 2.114 s 10 2.097 s 10
Zone 1 Zone 1 Zone 1 2.098 s
tic
tic
aracteris
aracteris
40 40
istic
istic
tic
tic
character
character
30 30
aracteris
aracteris
Outer ch
Outer ch
Zone 2 Zone 2
Inner ch
Middle
Middle
10 Zone 1 10 Zone 1
Fig. 7. Impedance measured by the distance element of R12−6 in: (a) the base scenario; (b) Scenario 1; (c) Scenario 2; (d) Scenario 3; and (e) Scenario 4.
with the results obtained using theoretical analysis in Fig. IV. P ERFORMANCE E VALUATION OF
5(e), which indicates the maximum amplitude for the 13 Hz R EAL -W ORLD R ELAYS
oscillations, and Fig. 6(e), which illustrates an impedance
change rate exceeding −21 Ω/(30 ms). The 8 ms travel time is We conducted extensive laboratory experiments using com-
less than the minimum half-a-cycle setting allowed by certain mercial relays from various manufacturers to validate the
commercial relays, such as [8], for the power swing blocking aforementioned findings. Consistent results were obtained
time delay of the concentric technique. Although some other across all of these relays, irrespective of the manufacturer. This
manufacturers’ relays allow for a shorter time delay, they still section presents the outcomes obtained from two off-the-shelf
advise against reducing this delay below 30 ms [10]. relays, referred to as Commercial Relay 1 and Commercial
Note that the increased swing frequency resulting from Relay 2. These relays were updated with the latest firmware
reduced inertia, as discussed in [3], [4], [5], [6], and the last as of February 2024. The voltage and current waveforms of
paragraph of Section III-A, does not contribute to the failure PSCAD/EMTDC simulations, captured at the R12−6 location
to detect power swings in Scenarios 3 and 4. This increase in Figs. 2 and 3, were recorded as common format for transient
in swing frequency merely requires considering the actual data exchange (COMTRADE) files [21]. The relay test set
system inertia when determining the settings of the concentric detailed in [22] was used to supply these input COMTRADE
method. Moreover, as shown in Section III-A, this increase files to the relays.
is small enough to keep the required changes in the relay Fig. 8 illustrates the relay recordings, which are distinct
settings within the setting ranges commonly used in conven- from the recordings at the terminals of IBRs and SMs; this
tional systems. By contrast, the high-frequency component distinction is elaborated at the end of this section. These
introduced to the voltage angle oscillations by the inverter recordings show the currents on the secondary side of the
control system renders the first principle of the relays’ power current transformer (CT), voltages on the secondary side of the
swing detection methods ineffective. Consequently, addressing voltage transformer (VT), and the relay word bits, for the base
this issue requires more than just minor adjustments to the scenario. Word bits POWER SWING OUTER and X7ABC
relay settings. in Figs. 8(c)-(d) pick up when the impedance locus enters
Authorized licensed use limited to: Universität Leipzig. Downloaded on March 29,2024 at 07:24:26 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3382843
Current (A)
locus enters the middle characteristic; and word bits POWER
2
SWING BLOCK and OSB in Figs. 8(c)-(d) are asserted to 0
logical 1 and latched for 0.5 s if the relay detects a power -2
swing condition. PH DIST Z1 OP and Z1P in Figs. 8(c)-(d)
denote the operation of the zone-1 phase distance elements of 2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675
Time (s)
these relays (the former stays latched until the reset condition (a)
Voltage (V)
is met or the element is blocked by the power swing blocking 100
function of the relay); and TRIPBUS 1 OP and TRIP word 0
bits in Figs. 8(c)-(d) show the relays’ trip signals.
-100
The difference between the pick-up times of the outer and
middle characteristics in Figs. 8(c)-(d) is in the range of 80- 2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675
Time (s)
100 ms. Thus, both of these relays successfully detect a power (b)
POWER SWING OUTER
swing condition in the base scenario. This prevents the zone-1 POWER SWING MIDDLE
POWER SWING BLOCK
distance element from operating, and neither of these relays PH DIST Z1 OP
trip in this scenario. This outcome aligns with the theoretical TRIPBUS 1 OP
2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675
analysis depicted in Fig. 6(a) and the simulation results shown Time (s)
in Fig. 7(a). A similar consistency between the results of (c)
X7ABC
Section III and the operation of commercial relays is observed X6ABC
for Scenarios 1 and 2 as well. Figs. 9 and 10 show that OSB
Z1P
both relays can effectively detect a power swing condition, TRIP
2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675
preventing the operation of their distance elements.
Time (s)
In Scenario 3, Fig. 7(d) demonstrates that the impedance (d)
traverses the area between the outer and middle characteristics
Fig. 8. COMTRADE recordings of commercial relays for the base scenario
twice, both within a cycle, before entering the relay’s zone 1. of Fig. 2: (a) CT secondary currents; (b) VT secondary voltages; (c) Word
Testing of commercial relays produced the same result. Figs. bits of Commercial Relay 1; and (d) Word bits of Commercial Relay 2.
11(c)-(d) show that the middle characteristic picks up twice,
both less than a cycle after the outer characteristic is activated.
Consequently, both relays in Figs. 11(c)-(d) fail to detect the a violation of the IBRs’ 1.5 pu current limit considered in
power swing condition. As a result, the impedance enters √ (which is equivalent to a combined total of 1.5 ×
this study
zone 1, causing both PH DIST Z1 OP and Z1P to activate 600/( 3 × 230) = 2260 A). This can be further verified in
in Figs. 11(c)-(d). Consequently, both relays erroneously trip Fig. 14, where the current of each individual inverter within the
line 12-6. Figs. 12(c)-(d) illustrate a similar relay malfunction IBR plants connected to bus 12 remains below the inverters’
in Scenario 4, where the middle characteristic picks up only 1.5 pu current limit not only during the fault (i.e., from t = 2
8 ms after the outer characteristic is activated. The relay fails to t = 2.075 s) but also during the power swing condition
to detect the power swing condition, while PH DIST Z1 OP from t = 2.075 s onwards.
and Z1P are asserted, resulting in the tripping of line 12-6. In addition, the temporary overvoltage condition immedi-
As mentioned at the beginning of this section, the currents ately after the fault clearance in Fig. 13(b) is due to the reactive
shown in Fig. 12(a) are the currents measured at the location current injection of the IBRs during the fault, as per [23].
of relay R12−6 , not at the terminal of the IBRs connected to This overvoltage is normal in IBR systems during post-fault
bus 12. In addition, the currents in Fig. 12(a) are the currents conditions [24]. This temporary overvoltage condition does not
on the secondary side of the CT connected to relay R12−6 . As cause any overvoltage tripping since it is mitigated by surge
discussed in Appendix A, the CT ratio for this relay is 600:1. arrestors within the IBR plant facility [25].
The CT nominal tap for this relay is determined based on the
rated current of line 12-6. Due to the load connected to bus V. S YSTEM -W IDE I MPACTS
12 and the presence of line 12-13 during normal conditions, The last two sections demonstrated that the control system
the rated current of line 12-6 is less than half of the IBRs’ dynamics of the IBRs prevented relay R12−6 from detecting
total current injected to bus 12. Before the fault, line 12-6 stable power swings. As a result, 500 MW of generation
transmits only half of the total power exported from bus 12. transmitted through line 12-6 was lost. This section examines
Therefore, since the total rated current
√ of the IBR generation the significance of this issue and its system-wide impacts for
outflowing from bus 12 is 500/( 3 × 230) = 1255 A, the the grid shown in Figs. 2 and 3. This system is based on the
nominal current through line 12-6 is about 600 A, which is 1 CIGRE high-voltage benchmark, derived from an actual North
A on the secondary side of the CT connected to relay R12−6 . American system [26]. The significant imbalance between
The above indicates that the increased current magnitude in the generation and load caused by the aforementioned relay
Fig. 12(a), whose zoomed-in view is displayed in Fig. 13(a), malfunction has a severe impact on the frequencies of SMs 1-3
is due to the overloading of line 12-6 after the tripping of in the system. Fig. 15(a) demonstrates that following the fault,
line 12-13 at t = 2.075 s. This increase does not indicate the frequencies of these SMs decrease to 57.33 Hz before their
Authorized licensed use limited to: Universität Leipzig. Downloaded on March 29,2024 at 07:24:26 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3382843
Current (A)
Current (A)
2 2
0 0
-2 -2
2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675 2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675
Time (s) Time (s)
(a) (a)
Voltage (V)
Voltage (V)
100 100
0 0
-100 -100
2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675 2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675
Time (s) Time (s)
(b) (b)
POWER SWING OUTER POWER SWING OUTER
POWER SWING MIDDLE POWER SWING MIDDLE
POWER SWING BLOCK POWER SWING BLOCK
PH DIST Z1 OP PH DIST Z1 OP
TRIPBUS 1 OP TRIPBUS 1 OP
2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675
2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675 Time (s)
Time (s) (c)
(c)
X7ABC
X7ABC X6ABC
X6ABC OSB
OSB Z1P
Z1P TRIP
TRIP
2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675
2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675 Time (s)
Time (s) (d)
(d)
Fig. 9. COMTRADE recordings of commercial relays for Scenario 1 of Fig. Fig. 11. COMTRADE recordings of commercial relays for Scenario 3 of Fig.
3(a): (a) CT secondary currents; (b) VT secondary voltages; (c) Word bits of 3(c): (a) CT secondary currents; (b) VT secondary voltages; (c) Word bits of
Commercial Relay 1; and (d) Word bits of Commercial Relay 2. Commercial Relay 1; and (d) Word bits of Commercial Relay 2.
Current (A)
Current (A)
2 2
0 0
-2 -2
2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675 2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675
Time (s) Time (s)
(a) (a)
Voltage (V)
Voltage (V)
100 100
0 0
-100 -100
2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675 2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675
Time (s) Time (s)
(b) (b)
POWER SWING OUTER POWER SWING OUTER
POWER SWING MIDDLE POWER SWING MIDDLE
POWER SWING BLOCK POWER SWING BLOCK
PH DIST Z1 OP PH DIST Z1 OP
TRIPBUS 1 OP TRIPBUS 1 OP
2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675
2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675 Time (s)
Time (s) (c)
(c)
X7ABC X7ABC
X6ABC X6ABC
OSB OSB
Z1P Z1P
TRIP TRIP
2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675 2.075 2.275 2.475 2.675 2.875 3.075 3.275 3.475 3.675
Time (s) Time (s)
(d) (d)
Magnified in Fig. 13
Fig. 10. COMTRADE recordings of commercial relays for Scenario 2 of Fig. Fig. 12. COMTRADE recordings of commercial relays for Scenario 4 of Fig.
3(b): (a) CT secondary currents; (b) VT secondary voltages; (c) Word bits of 3(d): (a) CT secondary currents; (b) VT secondary voltages; (c) Word bits of
Commercial Relay 1; and (d) Word bits of Commercial Relay 2. Commercial Relay 1; and (d) Word bits of Commercial Relay 2.
speed governors begin to respond. This frequency falls well all SMs in the grid may trip. To prevent cascade tripping, Fig.
below the under-frequency trip curve of the NERC Standard 15(b) illustrates that shedding 500 MW of the load at bus 6 in
PRC-006-2 [27]. Consequently, without appropriate measures, Fig. 2—which is equivalent to approximately 25% of the total
Authorized licensed use limited to: Universität Leipzig. Downloaded on March 29,2024 at 07:24:26 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3382843
10
Current (A)
4
2
0
-2
-4
2.025 2.075 2.125 2.175 2.225 2.275 2.325
Time (s)
(a)
Voltage (V)
200
100
0
-100 Fig. 14. Instantaneous currents of each individual inverter within the IBR
-200 plants connected to bus 12 before, during, and after the fault of Fig. 12.
2.025 2.075 2.125 2.175 2.225 2.275 2.325
Time (s)
(b)
POWER SWING OUTER 57.33 Hz
POWER SWING MIDDLE
POWER SWING BLOCK
PH DIST Z1 OP
TRIPBUS 1 OP
2.025 2.075 2.125 2.175 2.225 2.275 2.325
Time (s)
(c)
X7ABC (a)
X6ABC
OSB
Z1P 58.53 Hz
TRIP
2.025 2.075 2.125 2.175 2.225 2.275 2.325
Time (s)
(d)
Under-frequency load shedding begins
Fig. 13. Zoomed-in view of Fig. 12: (a) CT secondary currents; (b) VT
secondary voltages; (c) Word bits of Commercial Relay 1; and (d) Word bits
of Commercial Relay 2.
(b)
system load—can mitigate the decline in frequency and limit Fig. 15. Frequency of SMs 1-3 after the loss of 500 MW of power transmitted
by line 12-6: (a) if no under-frequency load shedding scheme is implemented;
it to 58.53 Hz. The prevention of such system-wide major and (b) if an under-frequency load shedding scheme is implemented.
disturbances requires adequate awareness of the power swing
characteristics of IBRs.
VI. D ISCUSSION The above demonstrates that the primary focus in [23]
A. Regulatory Frameworks and Fault Recovery of IBRs is to mitigate the oscillations of IBRs in weak grids by
imposing a ramp limit on IBRs’ active power. By contrast, the
The phenomenon investigated in this paper occurs following priority in [28] is given to the swift recovery of IBRs’ active
the clearance of a fault. The requirements for the operation power, explicitly prohibiting ramp limitations. The NERC
of IBRs after the fault clearance are not consistent across recommendation in [28] is consistent with Section 10.2.3.3
all recent regulatory frameworks, such as the IEEE Standard of the VDE grid code as well [29]. This section discusses
2800-2022 [23], and the more recent NERC recommendations how adherence to each of these requirements influences the
in [28], most notably in power swing behavior of IBRs and explores how to combine
1) Subclause 7.2.2.6 of [23], where it is mentioned “The the advantages of both approaches while avoiding the power
active power recovery time shall be configurable within swing-related issues identified in this paper.
a range between 1 s and 10 s. The default active power Consider Scenario 4, illustrated in Fig. 3(d), as the worst-
recovery time is 1 s; however, in weak grids, in order case scenario, where the sources connected to bus 12 are
to reduce oscillatory behavior of the IBR plant upon entirely inverter-based. Fig. 16(a) depicts the active power
fault recovery and maintain system stability, it may be transmitted through line 12-6 before, during, and after the fault
desirable to reduce the average rate of active power in this scenario. As discussed in [1], the IBRs’ active power is
recovery in consultation with the TS owner;” and regulated by the dc-link voltage control loop shown in Fig. 2
2) Recommendation 4.d of [28], where it is mentioned of [1] before and after the fault. This structure, including the
“Coordinate with inverter manufacturers and power proportional-integral (PI) compensator, is well established in
plant controller manufacturers to ensure that facility the inverter control literature [30], [31], [32]. The post-fault
control modes, fault ride through modes and parameters, oscillations of the power curve in Fig. 16(a) are consistent with
and protections are set and coordinated according to those of the voltage angle curve in Fig. 4(e), leading to the
the following principles: Facility output returns to pre- relay malfunction and incorrect tripping of line 12-6. Having
disturbance active power levels as soon as possible said that, the power curve in Fig. 16(a) does comply with the
without any artificial ramp rate limit or delay imposed recommendations in [28] regarding the fast recovery of active
by the power plant controller.” power following a fault. Fig. 16(b) shows the active power
Authorized licensed use limited to: Universität Leipzig. Downloaded on March 29,2024 at 07:24:26 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3382843
11
Authorized licensed use limited to: Universität Leipzig. Downloaded on March 29,2024 at 07:24:26 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3382843
12
Closed-loop pole {s} for the zone-1 distance element, cannot dynamically adapt
Open-loop pole 40 to weather variations. As a consequence, the five scenarios
Open-loop zero
20 depicted in Figs. 2 and 3 should not be necessarily seen as
{s} five different systems each with its own settings for R12−6 .
-2000 -1500 -1000 -500 Instead, the single-line diagrams in these figures can represent
-20
five potential generation mixes for a single system with one
-40 set of settings for R12−6 .
For the condition shown in Fig. 3(d), a time delay for zone 1
Fig. 17. Root locus plot of the open-loop transfer function of the dc-link
voltage control loop with the proposed lead filter.
of R12−6 does not impact the stability of the generation units
connected to bus 12. However, consider a scenario where the
power of the IBRs reduces by 25%, necessitating the dispatch
Magnitude (dB)
(a)
-90
operation time and the time it takes for the impedance to
-120 enter zone 1 after the fault inception, suppose that the faulted
-150 Phase margin = 73.5 line, i.e., line 12-13, is removed from the system in 100
ms (which does not represent the worst-case scenario for the
-180 breaker opening time). Fig. 20 shows the measurements at the
10 2 3 4 5
10 0 10 1 10 10 10
Frequency (rad/s) terminal of the SM connected to bus 14a in Fig. 3(c). The SM
(b) undergoes transient instability as a result of the additional time
delay added to the zone-1 distance element. However, if the
Fig. 18. Bode plot of the open-loop transfer function of the dc-link voltage
control loop with the proposed lead filter: (a) Magnitude and (b) Phase.
fault is cleared in 75 ms (as demonstrated in the case studies
presented earlier), the SM can successfully recover from the
fault, as shown in Fig. 21.
The above shows the need for caution when introducing
Magnitude (dB)
100
time delays to the operation of distance elements: Depending
50 on the system configuration, this delay may solve one problem
0 while creating another. It should be noted that the scenario
-50 illustrated in Fig. 20 is only one example of problematic
-100 scenarios for delayed operation of zone 1. Even if all sources
10 0 10 1 10 2 10 3 10 4 10 5 behind the relay are inverter-based, delaying zone 1 could
Frequency (rad/s) potentially affect the stability of SMs in other parts of the
Phase (degree)
VII. C ONCLUSION
to direct tie-lines of IBRs; these findings are actually mostly
applicable to large transmission corridors of systems with Using the dynamic model developed in Part I, Part II of
high penetration of IBRs. Consequently, reducing the speed this paper analyzed the rate of change of impedance measured
of distance relays can compromise the system stability when by transmission line relays during power swings in systems
the source on one end of a transmission corridor is a mix of with IBRs. The findings revealed that the dc-link voltage
SMs and IBRs. For such systems, the generation mix varies control dynamics of IBRs can significantly amplify the rate
with weather conditions and the availability of renewable of impedance change, surpassing the high rate of impedance
energy sources. However, relay settings, including time delays change caused by the low inertia of IBR systems. These rapid
Authorized licensed use limited to: Universität Leipzig. Downloaded on March 29,2024 at 07:24:26 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3382843
13
A. Outer Characteristic
(a) The blinders of the outer characteristic should be set below
the impedance associated with the maximum line loading,
multiplied by a safety factor [10]. To this end, first consider
the 600 MW total generation behind bus 12 in Fig. 2. Given
the 100 MW load connected to the same bus, the total power
transmitted through lines 12-6 and 12-13 is 500 MW. The
maximum line loading for line 12-6 occurs when line 12-13
(b)
is out of service, i.e., when the entire 500 MW is transmitted
through line 12-6. For this emergency loading condition, the
Fig. 20. Measurements at bus 14a of the system of Fig. 3(c) when the
operation of the zone-1 distance element of the relay that protects line 12-13
impedance measured by relay R12−6 is calculated using the
is delayed by 50 ms and the fault is cleared in 100 ms: (a) Instantaneous relation in (12) [11].
currents; and (b) Instantaneous voltages. 2
Sbase Vbase CTR
Zload =
Pline Sbase VTR
2
100 [MVA] 230 [kV] 600
= . .
500 [MW] 100 [MVA] 2090.90
= 30.36 Ω. (12)
Based on the above load impedance and considering a 0.9
(a) safety factor [10], the right blinder of the outer characteristic
is set to
Right blinder = (0.9)(30.36)
= 27.32 Ω. (13)
The left blinder is set to the negative of the right blinder,
as recommended in [10]. In addition, the settings for the top
(i.e., forward reach) and bottom (i.e., reverse reach) of the
(b)
outer characteristic are, respectively, chosen as 45.91 Ω and
Fig. 21. Measurements at bus 14a of the system of Fig. 3(c) when the fault is −28.26 Ω, which fall within the range recommended in [37],
cleared in 75 ms: (a) Instantaneous currents; and (b) Instantaneous voltages.
that is, at least two to three times the distance element’s reach.
Authorized licensed use limited to: Universität Leipzig. Downloaded on March 29,2024 at 07:24:26 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3382843
14
ms. However, as discussed in [10] and elaborated further in the reactance reach of zone 1 is set to 80% of the reactance
[37], this time delay is system-specific and depends largely of line 12-6 in Fig. 2; i.e.,
on the oscillation frequency during power swings. Therefore,
the recommended 30 ms threshold should be checked with rch 600
X1 = (0.8)(47.87)
the system’s oscillation frequency to ensure it is neither too 2090.90
short nor too long. The relation for determining this time delay = 10.99 Ω. (16)
based on the swing frequency is given by (14) [37].
Therefore, based on the guideline in [10], R1rch can be as high
δmid − δout
Time delay = fnom , (14) as 3 × 10.99 = 32.97 Ω. In addition, as shown in (12), the
360fs load impedance associated with the maximum line loading for
where δmid and δout are the middle and outer blinder power line 12-6 in Fig. 2 is 30.36 Ω. Therefore, to avoid interference
angles, respectively, in degrees; fnom is the system’s nominal with the load impedance, the upper limit for R1rch should be
frequency in Hz; and fs is the swing frequency in Hz. The 30.36 Ω. Setting R1rch to this upper limit, however, brings
time delay obtained using (14) is expressed in cycles. The about two challenges: (i) the power swing blinders cannot be
method for obtaining δmid and δout is outlined in [37]. Based placed between the distance zone characteristic and the load
on this method and the blinder values calculated in the last two region; and (ii) the phase angle errors in the polarizing current
subsections, δmid and δout are 72.31° and 61.81°, respectively. of the distance elements are not accounted for.
Extensive transient stability analysis performed on the sys- To address the challenges discussed above, we follow the
tem of Fig. 2 reveals that the highest oscillation frequency of guideline in [38] and recalculate R1rch . To make the relay
the voltage angle at bus 12 relative to bus 6 is approximately robust against phase angle errors in the polarizing current,
1 Hz during the most severe stable power swing for this R1rch should satisfy the inequality in (17) [38].
system. This frequency increases to about 5 Hz during unstable
power swings. Therefore, since the triple-blinder scheme used R1rch,pu < [(1 − X1rch,pu )/(θerr × π/180)]. (17)
to detect power swings in Fig. 7 decouples the power swing
blocking and the out-of-step tripping functions of the relay In this equation, R1rch,pu and X1rch,pu are, respectively, the
[36], the frequency of the most severe stable power swing is resistive and reactance reaches of the zone-1 quadrilateral
used to determine the power swing blocking time delay [10]. distance element, expressed in per-unit of line reactance;
Thus, based on (14), the power swing blocking time delay is and θerr is the phase angle error in the polarizing current.
calculated as Considering an error as large as θerr = 8° [38] and plugging
X1rch,pu = 0.8 pu in (17) result in an upper limit of 1.43 pu for
72.31 − 61.81
Time delay = 60 = 1.75 cycles. (15) R1rch,pu , which is equivalent to 1.43 × (10.99/0.8) = 19.65 Ω.
360 (1) Considering an additional 1 Ω safety margin, we set the
This time delay corresponds to 29.16 ms, which is approx- resistive reach of zone 1 of the distance elements in Fig. 7
imately the same as the 30 ms threshold recommended in to 18.65 Ω. This number is about 60% of the 30.36 Ω upper
[10]. Therefore, the power swing blocking time delay of relay limit suggested by [10], thereby addressing the two challenges
R12−6 is set to 30 ms. It should be noted that although the discussed above.
procedure outlined above closely follows multiple industry
practices and guidelines, reducing the chosen time delay any
further is not always effective for improving the power swing B. Zone-2 Resistive Reach
detection near IBRs, as discussed in Section III-B.
To configure the resistive reach for zone 2 of the distance
characteristics illustrated in Fig. 7, one strategy involves
A PPENDIX B adhering to the guideline presented in [20], which recommends
S ETTINGS C ALCULATIONS FOR THE coordinating the resistive reaches of zones 1 and 2 considering
R ESISTIVE R EACH OF R12−6 the infeed currents, hence different resistive reach settings
across these zones. Meanwhile, since zone 2 is also considered
This appendix outlines the procedure adopted to set the susceptible to inadvertent operation during power swings [11],
resistive reaches of the distance zones depicted in Fig. 7. we follow the zone overlapping practice recommended in [9],
in which the resistive reach parameters are set uniformly across
all zones. This would reduce the resistive reach of zone 2
A. Zone-1 Resistive Reach
for a given zone-1 characteristic, thereby making the passage
The setting guideline in [10] recommends to set the resistive of apparent impedance through zone 2 during power swings
reach for both the ground and phase elements of the relay as less likely. This approach is also adopted in [10], where the
high as possible without interfering with the load impedance. default settings for the resistive reaches of zones 1 and 2 of the
Meanwhile, this guideline recommends that the resistive reach quadrilateral characteristics are identical (whereas the default
for the zone-1 phase distance element, denoted in this paper settings for the reactance reaches of zone 1 and 2 in [10]
by R1rch , should be limited to three times the reactance reach are different). Therefore, the resistive reach for zone 2 of the
of zone 1, denoted by X1rch . As discussed in Section III-B, distance characteristics in Fig. 7 is similarly set to 18.65 Ω.
Authorized licensed use limited to: Universität Leipzig. Downloaded on March 29,2024 at 07:24:26 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3382843
15
ACKNOWLEDGMENT [24] Odessa Disturbance, Joint NERC and Texas RE Staff Report. NERC, At-
lanta, United States, 2021. [Online]. Available: https://bit.ly/46hHw45.
The authors gratefully acknowledge the contributions of [25] Reliability Guideline: BPS-Connected Inverter-Based Resource Perfor-
Dr. Manish Patel of Southern Company, Atlanta, GA, for his mance. NERC, Atlanta, United States, 2018. [Online]. Available:
valuable insights and discussions throughout this study. https://bit.ly/3tl4gS4.
[26] K. Strunz et al., Benchmark Systems for Network Integration of Renew-
able and Distributed Energy Resources. CIGRE, TF C6.04, Apr. 2014.
R EFERENCES [27] Standard PRC-006-2 — Automatic Underfrequency Load Shedding.
NERC Std. PRC-006-2, 2015.
[1] M. A. Nasr and A. Hooshyar, “Power swing in systems with inverter- [28] Industry Recommendation: Inverter-Based Resource Performance Is-
based resources—Part I: Dynamic model development,” IEEE Trans. sues. NERC, Atlanta, United States, 2023. [Online]. Available:
Power Del., In press, 2024. https://bit.ly/42OhK5k.
[2] Protection System Response to Power Swings. System Protection and [29] Technical requirements for the connection and operation of customer
Control Subcommittee, NERC, Atlanta, United States, Aug. 2013. installations to the high voltage network (TAR high voltage). VDE-AR-
[3] Impact of Inverter Based Generation on Bulk Power System Dynamics N 4120:2018-11, 2018.
and Short-Circuit Performance. IEEE/NERC Task Force on Short- [30] R. Teodorescu, M. Liserre, and P. Rodriguez, “Ac voltage and dc voltage
Circuit and System Performance Impact of Inverter Based Generation, control,” in Grid Converters for Photovoltaic and Wind Power Systems,
Tech. Rep. PES-TR68, Jul. 2018. [Online]. Available: https://bit.ly/ ch. 9, pp. 210–219, John Wiley & Sons, Ltd, 1st ed., 2011.
3PKE8ZS. [31] A. Sangwongwanich, A. Abdelhakim, Y. Yang, and K. Zhou, “Control
[4] A. Haddadi, I. Kocar, U. Karaagac, H. Gras, and E. Farantatos, “Impact of single-phase and three-phase dc/ac converters,” in Control of Power
of wind generation on power swing protection,” IEEE Trans. Power Del., Electronic Converters and Systems, ch. 6, pp. 153–173, Academic Press,
vol. 34, pp. 1118–1128, Jun. 2019. 1st ed., 2018.
[5] Impact of High Penetration of Inverter-based Generation on System [32] S. Bacha, I. Munteanu, and A. Iuliana Bratcu, “Design of the outer
Inertia of Networks. CIGRE, Working Group C2/C4, Oct. 2021. loop (voltage) controller,” in Power Electronic Converters Modeling and
[6] Electromagnetic transient simulation models for large-scale system Control, ch. 9, pp. 283–284, Springer, 1st ed., 2014.
impact studies in power systems having a high penetration of inverter- [33] K. Ogata, “Transient and steady-state response analyses,” in Modern
connected generation. CIGRE, Working Group C4.56, Sep. 2022. Control Engineering, ch. 5, pp. 218–225, Prentice Hall, 5th ed., 2010.
[Online]. Available: https://bit.ly/3FjsXRu. [34] R. Chowdhury and N. Fischer, “Transmission line protection for systems
[7] D60 Line Distance Protection System: Instruction Manual. GE, with inverter-based resources—Part II: Solutions,” IEEE Trans. Power
Markham, Canada, Jun. 2023. [Online]. Available: https://bit.ly/ Del., vol. 36, pp. 2426–2433, Aug. 2021.
3mucHXR. [35] B. Kasztenny and R. Chowdhury, “Security criterion for distance zone
[8] Instruction Manual for SEL-411L Advanced Line Differential Protection, 1 applications in high SIR systems with CCVTs,” in Proceedings of
Automation, and Control System. SEL, Pullman, United States, Dec. the 76th Annual Georgia Tech Protective Relaying Conference,, Atlanta,
2022. [Online]. Available: https://selinc.com/products/411L/docs/. GA, USA, May 2023.
[9] SIPROTEC 5, Distance Protection, 7SA82-V9.5: Manual. Siemens, [36] P. Annamdevula, A. Thurman, M. Thompson, B. Smyth, and D. Tziou-
Germany, Apr. 2023. [Online]. Available: https://sie.ag/44MKLPU. varas, “Simplifying PRC-026 compliance with practical solutions you
[10] Line Distance Protection REL670 Application Manual. ABB, Vasteras, least expect,” in 2021 74th Annual Georgia Tech Protective Relaying
Sweden, Jul. 2022. [Online]. Available: https://bit.ly/3Q1sIRH. Conference, Aug. 2021.
[11] Power swing and out-of-step considerations on transmission lines. IEEE [37] J. Mooney and N. Fischer, “Application guidelines for power swing
Power System Relaying and Control Committee (PSRC) Working Group detection on transmission systems,” in 42nd Annual Minnesota Power
WG-D6, Jul. 2005. [Online]. Available: https:bit.ly/3kQx8xI. Systems Conference, Saint Paul, MN, USA, Nov. 2006.
[12] J. Machowski, Z. Lubosny, J. W. Bialek, and J. R. Bumby, “Electrome- [38] B. Kasztenny, “Settings considerations for distance elements in line
chanical dynamics - Large disturbances,” in Power System Dynamics: protection applications,” 74th Annual Conference for Protective Relay
Stability and Control, ch. 6, pp. 229–283, John Wiley & Sons Ltd., Engineers, Texas, TX, USA, Mar. 2021.
3rd ed., 2020.
[13] H. Saadat, “Bus admittance matrix,” in Power System Analysis, ch. 6, Mohamad-Amin Nasr is currently working toward
pp. 190–195, PSA Publishing LLC, 1st ed., 1999. the Ph.D. degree in electrical engineering with the
[14] N. Hatziargyriou et al., “Definition and classification of power system Department of Electrical and Computer Engineering,
stability – Revisited & extended,” IEEE Trans. Power Syst., vol. 36, University of Toronto, Toronto, ON, Canada. He
pp. 3271–3281, Jul. 2021. received the M.Sc. (Hons.) degree in electrical engi-
[15] J. Machowski, Z. Lubosny, J. W. Bialek, and J. R. Bumby, “Electrome- neering from Amirkabir University of Technology
chanical dynamics - Small disturbances,” in Power System Dynamics: (Tehran Polytechnic), Tehran, Iran, in 2019. Mr.
Stability and Control, ch. 5, pp. 195–228, John Wiley & Sons Ltd., Nasr was recognized as an outstanding reviewer of
3rd ed., 2020. the IEEE T RANSACTIONS ON P OWER D ELIVERY
[16] G. Ziegler, “Mode of operation,” in Numerical Distance Protection: in 2021. His current research interests include power
Principles and Applications, ch. 3, p. 66, Erlangen, Germany: Publicis system dynamics and protection in the presence of
Publishing, 4th ed., 2011. inverter-based resources.
[17] E. W. Kimbark, “Solution of networks,” in Power System Stability,
Volume I, ch. 3, pp. 111–112, IEEE Press, 1st ed., 1995. Ali Hooshyar (Senior Member, IEEE) is currently
[18] J. D. Glover, M. S. Sarma, and T. J. Overbye, “Numerical integration a Canada Research Chair in Electric Power Systems
of the swing equation,” in Power System Analysis and Design, ch. 11, with the Department of Electrical and Computer
pp. 608–613, Cengage Learning, 5th ed., 2012. Engineering at the University of Toronto, Toronto,
[19] N. Tleis, “Typical data of power system equipment,” in Power Systems ON, Canada. His research interests include dynam-
Modelling and Fault Analysis: Theory and Practice, Appendix A.2, ics, control, and protection of renewable energy
pp. 608–618, Newnes, 1st ed., 2008. systems. Dr. Hooshyar is an Editor of the IEEE
[20] C. Henville and R. Chowdhury, “Coordination of resistive reach of T RANSACTIONS ON S MART G RID, IEEE T RANS -
phase and ground distance elements,” in Proceedings of the 48th Annual ACTIONS ON P OWER D ELIVERY , and IEEE P OWER
Western Protective Relay Conference, Spokane, WA, USA, Oct. 2021. E NGINEERING L ETTERS. He was the Guest Editor-
[21] IEEE/IEC Measuring relays and protection equipment – Part 24: in-Chief of the Special Issue of the IEEE T RANS -
Common format for transient data exchange (COMTRADE) for power ACTIONS ON P OWER D ELIVERY on “Resilience-Oriented Protection, Control,
systems. IEEE Std. C37.111-2013 (IEC 60255-24 Edition 2.0 2013-04), and Monitoring Systems for Power Grids.” Dr. Hooshyar was the Guest
2013. Editor of the IEEE E LECTRIFICATION M AGAZINE for the Special Issue on
[22] CMC 356 User Manual. Omicron Electronics Corporation, 2020. “Microgrid Protection and Control.” He is also an Associate Editor for the
[Online]. Available: https://bit.ly/3NVZdjo. Wiley Encyclopedia of Electrical and Electronics Engineering. Dr. Hooshyar
[23] IEEE Standard for Interconnection and Interoperability of Inverter- chairs Working Group C45 of the IEEE Power Systems Relaying and Control
Based Resources (IBR) Interconnecting with Associated Transmission Committee on short-circuit modeling and protection of power systems with
Electric Power Systems. IEEE Std. 2800-2022, 2022. high penetration of inverter-based resources.
Authorized licensed use limited to: Universität Leipzig. Downloaded on March 29,2024 at 07:24:26 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.