ROOF PLAN GENERAL NOTES

1. SEE ROOF PLANS FOR ROOF SLOPES


2. PROVIDE ICE AND WATER SHEILD FLASHING WHERE ROOF PITCH CHANGES, WHERE
ROOF INTERSECTS VERTICAL SURFACES, AT ALL ROOF EAVES, AND PER ROOFING
MANUFACTURER'S WRITTEN INSTRUCTIONS.
3. PROVIDE HIGH-TEMPERATURE UNDERLAYMENT FOR ENTIRETY OF ALL METAL
2 ROOF AREAS.
______________________
4. PROVIDED GABLE END TRUSSES AT ALL GABLE END CONDITIONS AND AT ALL
A3.10
VERTICAL DRAFTSTOP LOCATIONS ABOVE AND IN LINE WITH DEMISING WALLS.
5. ROOF SHINGLES TO BE MINIMUM CLASS B. VERIFY SHINGLE INSTALLATION
38'-7 1/8"
REQUIREMENTS WITH CHINGLE MANUFACTURER'S WRITTEN INSTRUCTIONS FOR
PRODUCT TYPE AND APPLICATIONS.
1'-0" O.H. 27'-7 3/4" 1'-0" O.H. 12'-2 1/4" 2'-1 1/8" 67'-9 3/4" 2'-1 1/8" O.H. 34'-6" 2'-0" O.H.
6. ALL ROOF SHINGLES ARE TO OVERHANG DROP EDGES AT EAVES AND RAKES A PROJECT # : 122154
MINIMUM OF 1/2".
D.S. D.S. D.S. 13'-4 1/4" 7. PROVIDED 22"x30" RATED ATTIC ACCESS HATCH, 1-HOUR, WITH LOCK. FIELD DRAWN BY: KU, RB, PG
5" 5"

3'-0 1/2" O.H.


D.S. 1'-6" VERIFY LOCATIONS; SEE PLANS FOR BASIS OF DESIGN.

5"
JS

2'-0" O.H.
8. DIMENSIONS SHOWN ON ROOF PLAN ARE FROM FACE OF STUDS TO ENDS OF ROOF CHECKED BY:

6'-0" O.H.
D.S. E23 E20
1'-6" D.S. D.S. 1'-6" TRUSSES.

2'-0 1/2" O.H.


18'-0" SOFFIT VENT D.S.
15'-0" SOFFIT VENT 9. PROVIDE 3" CONTINUOUS ALUMINUM SOFFIT VENTS. VENTS MUST PROVIDE
12.7 SQ.IN. OF OPEN AREA PER LINEAR FOOT MINIMUM.
10. INSULATION BAFFLES SHALL BE INSTALLED IN SUCH A MANNER AS TO RESTRICT

8" / 12"

8" / 12"
INSULATION FROM BLOCKING THE NATURAL VENTILATION OF THE ROOF.

11'-0"
8" / 12" 6'-0" SOFFIT VENT 19'-0" SOFFIT VENT 19'-0" SOFFIT VENT 6'-0" SOFFIT VENT

8" / 12"
18'-0" SOFFIT VENT
11. PROVIDE KICK-OUT FLASHING WHERE ROOF INTERSECTS SIDEWALL.
12. PROVIDE 5" PREFINISHED ALUMINUM OGEE STYLE GUTTERS, TYP. WITH 5"
PREFINISHED ALUMINUM ROUND DOWNSPOUTS. QUANTITY AND LOCATION TO BE
8" / 12" DRAFTSTOPPING; TYP. DESIGN-BUILD. DOWNSPOUTS SHOWN IN PLAN ARE FOR REFERENCE ONLY.
D.S.

DRAFTSTOPPING; TYP.
ROOF FLASHING NOTES
8" / 12"

34'-11 1/2"

15'-0" SOFFIT VENT


32'-5 1/2"

EQ
1. PROVIDE 'D STYLE' METAL DRIP EDGE (COLOR TO MATCH FASCIA) AT ALL ROOF
EAVES AND RAKES - PER IBC 1507.2.9.3

23'-0"
2. PROVIDE A MULTI-STEP FLASHING SYSTEM AT ALL WALL/ROOF INTERSECTIONS

4" / 12"
E25
5"

(EXAMPLE - CHEEK WALLS, CHIMNEYS, DORMERS, ETC)


AREA A-1 AREA A-2 AREA A-3 AREA A-4 3. EXTEND EAVE SELF-ADHERING WATERPROOFING UNDERLAYMENT A MINIMUM OF
24" UP THE ROOF SLOPE BEYOND THE INTERIOR FACE OF EXTERIOR WALL.
4. 'WEATHER LAP' METAL FLASHING JOINTS A MINIMUM OF 2"
5. LAP SELF-ADHERING WATERPROOFING PIECES A MINIMUM OF 6".
30'-0" RIDGE VENT

6. ANY ROOFS WITH SLOPES BETWEEN 2/12 AND 4/12 ARE TO BE COMPLETELY

25'-0" RIDGE VENT


UNDERLAIDS WITH SELF-ADHERING WATERPROOFING UNDERLAYMENT.
7. APRON FLASHING AT FRONT CORNERS OF WALL/ROOF INTERFACES ARE TO BE 3060 Peachtree Rd. N.W.

74'-0"
74'-0"
62'-0"

68'-0"
E25
3
______________________
D.S. D.S. SHOP MADE, RIVETED, AND SEALED Suite 600
A3.10 4 8. WHERE BOTTOM OF DORMER WINDOWS ARE LESS THAN 6" ABOVE THE ROOF,
______________________
Atlanta, GA 30305
A3.10 WINDOWS ARE TO HAVE PAN / APRON FLASHING.
1'-3 5/8" 8'-6" RIDGE VENT 2'-10" 16'-0" RIDGE VENT 10'-0" 16'-0" RIDGE VENT 7'-3" 8'-6" RIDGE VENT 8" / 12" 9. PROVIDE MEMBRANE COUNTER FLASHING AT ALL METAL FLASHING CONDITIONS.
3'-0 1/2" O.H. 10. PROVIDE 72" WIDE SELF-ADHERING WATERPROOFING UNDERLAYMENT FROM T 404 365 7600

%8,/',1*7<3($%/'*6 
AREA A-5 AREA A-6 EDGE OF ROOF UP THE VALLEY FOR A MINIMUM OF 10' IN SHADED AND NORTH
8" / 12" E25
2'-11 1/2" 8" / 12" ROOF LOCATIONS.
8" / 12"
www.nilesbolton.com
727$/HD$77,&$&&(66

23'-0"
5"

D.S.

4" / 12"
ROOF LEGEND

15'-0" SOFFIT VENT


No. Description Date
GMP SET 01/16/23

EQ
31'-6 1/2"
32'-0 1/2"

CONSTRUCTION SET 2/17/23 1


RIDGE VENT (EXHAUST) PROVIDING 18 S.I. PER LINEAR FOOT 1 REVISION 1 5/1/23
8" / 12"

NET FREE AREA MIN. SEE DETAIL 1/A4.37 2 REVISION 2 06/23/23


3 REVISION 3 08/02/23
18'-0" SOFFIT VENT

8" / 12" D.S. OFF-RIDGE VENT (EXHAUST) PROVIDING 150 S.I. NET FREE
ORV
AREA MIN. SEE DETAIL 8/A4.37
ATTIC ACCESS PANEL; TYP.
8" / 12"
8" / 12"

8" / 12"
ATTIC ACCESS PANEL; TYP.

11'-0"
8" / 12"

SOFFIT VENT (INTAKE) PROVIDING 12.7 S.I. PER SF NET FREE


6'-0" SOFFIT VENT 19'-0" SOFFIT VENT 19'-0" SOFFIT VENT 6'-0" SOFFIT VENT AREA MIN.

2'-11 1/2" O.H.


15'-0" SOFFIT VENT
6'-0" O.H.

2'-11 1/2" O.H.


2'-0" O.H.

18'-0" SOFFIT VENT D.S. 4" DIA. PREFINISHED ALUMINUM


DOWNSPOUT LOCATION
D.S.
5" PREFINISHED ALUMINUM
5"

E20 D.S. 1'-6" D.S. E23 23'-6" 23'-6" D.S. GUTTER


5" D.S. 2
D.S. E23 D.S.5" D.S. 13'-4 1/4" X:XX DIRECTION OF ROOF SLOPE-
1'-5 1/2" SEE GENERAL NOTES

OUTSIDE FACE OF STUD


OUTSIDE FACE OF STUD BELOW
BELOW, TYPICAL. This drawing, as an instrument of service, is and shall
1 remain the property of the Architects and shall not
______________________
142'-4" 1-HOUR RATED ATTIC DRAFTSTOPPING PER WINDER, GEORGIA
A3.10 be reproduced, published or used in any way without
CODE OF ORDINANCES SEC 9-61. SEE 6/A7.30 FOR DETAILS. the permission of the Architect.

DRAFTSTOPPING DOOR, SEE DETAILS 11/A7.30


1 ROOF PLAN- BUILDING A
A1.14 1/8" = 1'-0"
4'-0" WIDE 5/8" PLYWOOD WALKWAY, INSTALL OVER RAISED
BOTTOM CHORD OF TRUSS IN CORRIDORS; SEE DETAIL 17/A7.30

THE GATEWAY AT UNIVERSITY APARTMENTS


1-HOUR RATED ATTIC ACCESS HATCH,FIELD VERIFY
LOCATION, SEE DETAIL 11/A7.30

ICE AND WATER SHIELD


SEE NOTE 2 ON THIS PAGE
2

PROVIDE CRICKET AT CORNERS AS NEEDED.

0 EXCHANGE BOULEVARD

TPA RESIDENTIAL GROUP


WINDER, GEORGA 30620
AIR HANDLING UNIT

NATURAL VENTILATION CALCULATIONS ROOF AREA PLAN ALL BUILDINGS OR INFORMATION SHOWN OR REFERENCED
OTHER THAN WHAT IS INDICATED ON THE ARCHITECTURAL
COVER SHEET IS FOR REFERENCE ONLY

1B 2B 3B

CODE- NATURAL VENTILATION ATTIC/ROOF 1/300 - BLDG TYPE A


4C 5A 6B 7A
VENTILATION 1
WT REQUIRED VENTILATION PROVIDED GRAND TOTALS
SOFFIT RIDGE % OF VENT CLUB 8C 9B 10A
TOTAL REQ. SOFFIT VENT RIDGE VENT # OFF OFF RIDGE/SIDE AREA AT 3'-0" TOTAL VENT
VENT: AREA (SF) x SOFFIT AREA (12.7 SI/LF RIDGE AREA (18 RIDGE/SIDE WALL VENT AREA BELOW RIDGE PROVIDED
NAME AREA (SF) 1/300 x 144 (SI) LENGTH (FT) NFA) LENGTH (FT) SI/LF NFA) WALL VENTS (144 SI) AREA (SI) CHECK Comments AREA A-1 AREA A-2 AREA A-3 AREA A-4
11A 12A
2,993 1,735 1,724 2,719
ALL BUILDINGS OTHER THAN WHAT IS SHOWN
AREA A-1 2993.23 SF 1437 in² 72'-0" 914 in² 30'-0" 540 in² 0 0 in² 37% 1454 in² 1 BLDG A ON THE COVER SHEET FOR REFERENCE ONLY
AREA A-2 1735.46 SF 833 in² 60'-0" 762 in² 16'-0" 288 in² 0 0 in² 27% 1050 in² 1 BLDG A
AREA A-6 SHEET TITLE:
AREA A-3 1724.32 SF 828 in² 60'-0" 762 in² 16'-0" 288 in² 0 0 in² 27% 1050 in² 1 BLDG A AREA A-5
AREA A-4 2719.12 SF 1305 in² 60'-0" 762 in² 25'-0" 450 in² 2 288 in² 49% 1500 in² 1 BLDG A 752
746
ROOF PLAN-
AREA A-5 752.30 SF 361 in² 12'-0" 152 in² 8'-6" 153 in² 1 144 in² 66% 449 in² 1 BLDG A
BUILDING TYPE A

RELEASED FOR CONSTRUCTION


AREA A-6 745.91 SF 358 in² 12'-0" 152 in² 8'-6" 153 in² 1 144 in² 66% 449 in² 1 BLDG A
TYPICAL
SHEET NUMBER:
NOTE: SEE ELEVATIONS FOR GABLE VENT LOCATIONS.
1
BASIS OF DESIGN PLUMBING CALCULATIONS FOR DOWNSPOUTS:
PER 2018 IPC SECTION 1106.1 THE 100 YEAR HOURLY RAINFALL RATE IS 3.5".
PER 2018 IPC SECTION 1106.3 THE VERTICAL LEADER SIZING BASIS OF DESIGN IS 3 1/2"x4", WITH A 192 GPM CAPACITY.
192 GPM/.0364 (GPM PER 1 SF WITH A RAINFALL RATE OF 3.5 INCHES PER HOUR) = 5,275 SF COVERAGE PER DOWNSPOUT.
A1.14
PROJECT TRUE
2 AREA PLAN- ATTIC NATURAL VENTILATION PLAN - BLDG TYPE A NORTH NORTH
A1.14 1" = 20'-0" 02/17/23
ROOF PLAN GENERAL NOTES
1 1. SEE ROOF PLANS FOR ROOF SLOPES
______________________

A3.20 2. PROVIDE ICE AND WATER SHEILD FLASHING WHERE ROOF PITCH CHANGES, WHERE
ROOF INTERSECTS VERTICAL SURFACES, AT ALL ROOF EAVES, AND PER ROOFING
MANUFACTURER'S WRITTEN INSTRUCTIONS.
145'-0" 3. PROVIDE HIGH-TEMPERATURE UNDERLAYMENT FOR ENTIRETY OF ALL METAL
ROOF AREAS.
2'-0" O.H. 141'-0" 2'-0" O.H.
4. PROVIDED GABLE END TRUSSES AT ALL GABLE END CONDITIONS AND AT ALL
4" 4" VERTICAL DRAFTSTOP LOCATIONS ABOVE AND IN LINE WITH DEMISING WALLS.
5. ROOF SHINGLES TO BE MINIMUM CLASS B. VERIFY SHINGLE INSTALLATION
D.S. 12'-1 1/4" 11'-10 3/4" 11'-10 3/4" 12'-1 1/4" D.S. REQUIREMENTS WITH CHINGLE MANUFACTURER'S WRITTEN INSTRUCTIONS FOR
PRODUCT TYPE AND APPLICATIONS.
6. ALL ROOF SHINGLES ARE TO OVERHANG DROP EDGES AT EAVES AND RAKES A PROJECT # : 122154
15'-0" SOFFIT VENT D.S. D.S. E23 D.S. 15'-0" SOFFIT VENT MINIMUM OF 1/2".

3'-0" O.H.
7. PROVIDED 22"x30" RATED ATTIC ACCESS HATCH, 1-HOUR, WITH LOCK. FIELD DRAWN BY: KU, RB, PG

3'-0" O.H.
VERIFY LOCATIONS; SEE PLANS FOR BASIS OF DESIGN.
JS

10'-10 7/8"
8. DIMENSIONS SHOWN ON ROOF PLAN ARE FROM FACE OF STUDS TO ENDS OF ROOF CHECKED BY:
6'-0" SOFFIT VENT 18'-0" SOFFIT VENT 18'-0" SOFFIT VENT 6'-0" SOFFIT VENT

10'-6"
TRUSSES.

8" / 12"
8" / 12"
9. PROVIDE 3" CONTINUOUS ALUMINUM SOFFIT VENTS. VENTS MUST PROVIDE
12.7 SQ.IN. OF OPEN AREA PER LINEAR FOOT MINIMUM.
10. INSULATION BAFFLES SHALL BE INSTALLED IN SUCH A MANNER AS TO RESTRICT
D.S.
INSULATION FROM BLOCKING THE NATURAL VENTILATION OF THE ROOF.
11. PROVIDE KICK-OUT FLASHING WHERE ROOF INTERSECTS SIDEWALL.
D.S.

4" / 12"
12. PROVIDE 5" PREFINISHED ALUMINUM OGEE STYLE GUTTERS, TYP. WITH 5"

15'-0" SOFFIT VENT

15'-0" SOFFIT VENT


PREFINISHED ALUMINUM ROUND DOWNSPOUTS. QUANTITY AND LOCATION TO BE
DESIGN-BUILD. DOWNSPOUTS SHOWN IN PLAN ARE FOR REFERENCE ONLY.

ROOF FLASHING NOTES


AREA B-1 AREA B-5 AREA B-2 AREA B-3 AREA B-6 AREA B-4 1. PROVIDE 'D STYLE' METAL DRIP EDGE (COLOR TO MATCH FASCIA) AT ALL ROOF
EAVES AND RAKES - PER IBC 1507.2.9.3

11'-3 1/4"
8" / 12" 8" / 12" 2. PROVIDE A MULTI-STEP FLASHING SYSTEM AT ALL WALL/ROOF INTERSECTIONS
8" / 12" 8" / 12"
(EXAMPLE - CHEEK WALLS, CHIMNEYS, DORMERS, ETC)

30'-0" RIDGE VENT

30'-0" RIDGE VENT


3. EXTEND EAVE SELF-ADHERING WATERPROOFING UNDERLAYMENT A MINIMUM OF
8'-6" RIDGE VENT 22'-0" RIDGE VENT 22'-0" RIDGE VENT 8'-6" RIDGE VENT E23 24" UP THE ROOF SLOPE BEYOND THE INTERIOR FACE OF EXTERIOR WALL.
E23
74'-0"

68'-0"

68'-0"

74'-0"
3 4 4. 'WEATHER LAP' METAL FLASHING JOINTS A MINIMUM OF 2"
______________________ ______________________

A3.20 A3.20 5. LAP SELF-ADHERING WATERPROOFING PIECES A MINIMUM OF 6".


D.S. D.S.

%8,/',1*7<3(%%/'*6 
6. ANY ROOFS WITH SLOPES BETWEEN 2/12 AND 4/12 ARE TO BE COMPLETELY
UNDERLAIDS WITH SELF-ADHERING WATERPROOFING UNDERLAYMENT.

11'-3 3/4"
11'-3 1/2"

7. APRON FLASHING AT FRONT CORNERS OF WALL/ROOF INTERFACES ARE TO BE 3060 Peachtree Rd. N.W.
727$/HD$77,&$&&(66 8.
SHOP MADE, RIVETED, AND SEALED
WHERE BOTTOM OF DORMER WINDOWS ARE LESS THAN 6" ABOVE THE ROOF,
Suite 600
Atlanta, GA 30305
WINDOWS ARE TO HAVE PAN / APRON FLASHING.
9. PROVIDE MEMBRANE COUNTER FLASHING AT ALL METAL FLASHING CONDITIONS.
10. PROVIDE 72" WIDE SELF-ADHERING WATERPROOFING UNDERLAYMENT FROM T 404 365 7600
EDGE OF ROOF UP THE VALLEY FOR A MINIMUM OF 10' IN SHADED AND NORTH
ROOF LOCATIONS.
www.nilesbolton.com
15'-0" SOFFIT VENT

15'-0" SOFFIT VENT


ATTIC ACCESS PANEL; TYP.

ROOF LEGEND No. Description Date

4" / 12"
DRAFTSTOPPING; TYP. GMP SET 01/16/23
CONSTRUCTION SET 2/17/23 1
D.S.
RIDGE VENT (EXHAUST) PROVIDING 18 S.I. PER LINEAR FOOT 1 REVISION 1 5/1/23
D.S.
NET FREE AREA MIN. SEE DETAIL 1/A4.37 2 REVISION 2 06/23/23

10'-10 15/16"
8" / 12"
3 REVISION 3 08/02/23
8" / 12"
10'-6"

OFF-RIDGE VENT (EXHAUST) PROVIDING 150 S.I. NET FREE


ORV
3'-0" O.H.

3'-0" O.H.
AREA MIN. SEE DETAIL 8/A4.37
6'-0" SOFFIT VENT 18'-0" SOFFIT VENT 18'-0" SOFFIT VENT 6'-0" SOFFIT VENT
15'-0" SOFFIT VENT 15'-0" SOFFIT VENT
SOFFIT VENT (INTAKE) PROVIDING 12.7 S.I. PER SF NET FREE
AREA MIN.

D.S. D.S. E23 D.S.


D.S. D.S. D.S. 4" DIA. PREFINISHED ALUMINUM
OUTSIDE FACE OF STUD E20
4" 1'-0" 24'-0" 24'-0" 1'-0" 4" DOWNSPOUT LOCATION
BELOW, TYPICAL.
5" PREFINISHED ALUMINUM
2'-0" O.H. 141'-0" 2'-0" O.H. GUTTER
2
X:XX DIRECTION OF ROOF SLOPE-
145'-0" SEE GENERAL NOTES

2
______________________
OUTSIDE FACE OF STUD BELOW
A3.20 This drawing, as an instrument of service, is and shall
remain the property of the Architects and shall not
1-HOUR RATED ATTIC DRAFTSTOPPING PER WINDER, GEORGIA be reproduced, published or used in any way without
1 ROOF PLAN- BUILDING B CODE OF ORDINANCES SEC 9-61. SEE 6/A7.30 FOR DETAILS. the permission of the Architect.

A1.22 1/8" = 1'-0"


DRAFTSTOPPING DOOR, SEE DETAILS 11/A7.30

2
4'-0" WIDE 5/8" PLYWOOD WALKWAY, INSTALL OVER RAISED
BOTTOM CHORD OF TRUSS IN CORRIDORS; SEE DETAIL 17/A7.30

THE GATEWAY AT UNIVERSITY APARTMENTS


1-HOUR RATED ATTIC ACCESS HATCH,FIELD VERIFY
LOCATION, SEE DETAIL 11/A7.30

ICE AND WATER SHIELD


SEE NOTE 2 ON THIS PAGE

PROVIDE CRICKET AT CORNERS AS NEEDED.

0 EXCHANGE BOULEVARD

TPA RESIDENTIAL GROUP


WINDER, GEORGA 30620
AIR HANDLING UNIT

NATURAL VENTILATION CALCULATIONS ROOF AREA PLAN ALL BUILDINGS OR INFORMATION SHOWN OR REFERENCED
OTHER THAN WHAT IS INDICATED ON THE ARCHITECTURAL
COVER SHEET IS FOR REFERENCE ONLY

1B 2B 3B

4C 5A 6B 7A
CODE- NATURAL VENTILATION ATTIC/ROOF 1/300 - BLDG TYPE E

VENTILATION
WT REQUIRED VENTILATION PROVIDED GRAND TOTALS CLUB 8C 9B 10A

SOFFIT RIDGE % OF VENT


TOTAL REQ. SOFFIT VENT RIDGE VENT # OFF OFF RIDGE/SIDE AREA AT 3'-0" TOTAL VENT
AREA B-1 AREA B-2 AREA B-3 AREA B-4 11A 12A
VENT: AREA (SF) x SOFFIT AREA (12.7 SI/LF RIDGE AREA (18 RIDGE/SIDE WALL VENT AREA BELOW RIDGE PROVIDED
NAME AREA (SF) 1/300 x 144 (SI) LENGTH (FT) NFA) LENGTH (FT) SI/LF NFA) WALL VENTS (144 SI) AREA (SI) CHECK Comments 2,724 1,725 1,725 2,724 ALL BUILDINGS OTHER THAN WHAT IS SHOWN
ON THE COVER SHEET FOR REFERENCE ONLY

AREA B-1 2723.73 SF 1307 in² 60'-0" 762 in² 30'-0" 540 in² 1 144 in² 47% 1446 in² 1 BLDG B AREA B-5 AREA B-6 SHEET TITLE:
AREA B-2 1725.00 SF 828 in² 36'-0" 457 in² 22'-0" 396 in² 0 0 in² 46% 853 in² 1 BLDG B 577 584
AREA B-3 1725.00 SF 828 in² 36'-0" 457 in² 22'-0" 396 in² 0 0 in² 46% 853 in² 1 BLDG B
ROOF PLAN-

RELEASED FOR CONSTRUCTION


AREA B-4 2723.73 SF 1307 in² 60'-0" 762 in² 30'-0" 540 in² 1 144 in² 47% 1446 in² 1 BLDG B
AREA B-5 577.13 SF 277 in² 12'-0" 152 in² 8'-6" 153 in² 1 144 in² 66% 449 in² 1 BLDG B BUILDING TYPE B
AREA B-6 583.59 SF 280 in² 12'-0" 152 in² 8'-6" 153 in² 1 144 in² 66% 449 in² 1 BLDG B

SHEET NUMBER:
NOTE: SEE ELEVATIONS FOR GABLE VENT LOCATIONS.
1
BASIS OF DESIGN PLUMBING CALCULATIONS FOR DOWNSPOUTS:
PER 2018 IPC SECTION 1106.1 THE 100 YEAR HOURLY RAINFALL RATE IS 3.5".
PER 2018 IPC SECTION 1106.3 THE VERTICAL LEADER SIZING BASIS OF DESIGN IS 3 1/2"x4", WITH A 192 GPM CAPACITY.
192 GPM/.0364 (GPM PER 1 SF WITH A RAINFALL RATE OF 3.5 INCHES PER HOUR) = 5,275 SF COVERAGE PER DOWNSPOUT.
A1.22
PROJECT TRUE
2 1
AREA PLAN- ATTIC NATURAL VENTILATION PLAN - BLDG TYPE B NORTH NORTH
A1.22 1" = 20'-0" 02/17/23
ROOF PLAN GENERAL NOTES
1. SEE ROOF PLANS FOR ROOF SLOPES
1
______________________ 2. PROVIDE ICE AND WATER SHEILD FLASHING WHERE ROOF PITCH CHANGES, WHERE
A3.30 ROOF INTERSECTS VERTICAL SURFACES, AT ALL ROOF EAVES, AND PER ROOFING
MANUFACTURER'S WRITTEN INSTRUCTIONS.
3. PROVIDE HIGH-TEMPERATURE UNDERLAYMENT FOR ENTIRETY OF ALL METAL
137'-11 1/2" ROOF AREAS.
11 1/4" 136'-1 5/8" 10 5/8" 4. PROVIDED GABLE END TRUSSES AT ALL GABLE END CONDITIONS AND AT ALL
VERTICAL DRAFTSTOP LOCATIONS ABOVE AND IN LINE WITH DEMISING WALLS.
5" 5" 23'-6" 23'-6" 5" 5" 5. ROOF SHINGLES TO BE MINIMUM CLASS B. VERIFY SHINGLE INSTALLATION
D.S. D.S. E23 REQUIREMENTS WITH CHINGLE MANUFACTURER'S WRITTEN INSTRUCTIONS FOR
D.S. D.S.
D.S. D.S. D.S. PRODUCT TYPE AND APPLICATIONS.
D.S.
6. ALL ROOF SHINGLES ARE TO OVERHANG DROP EDGES AT EAVES AND RAKES A PROJECT # : 122154
MINIMUM OF 1/2".

11 1/4"

11 1/8"
16'-0" SOFFIT VENT 16'-0" SOFFIT VENT D.S.
7. PROVIDED 22"x30" RATED ATTIC ACCESS HATCH, 1-HOUR, WITH LOCK. FIELD DRAWN BY: KU, RB, PG
VERIFY LOCATIONS; SEE PLANS FOR BASIS OF DESIGN.

8" / 12"
24'-6" SOFFIT VENT 24'-6" SOFFIT VENT 4'-0" SOFFIT VENT

8" / 12"
8" / 12" 8" / 12" 8. DIMENSIONS SHOWN ON ROOF PLAN ARE FROM FACE OF STUDS TO ENDS OF ROOF CHECKED BY: JS

8" / 12"
7'-0" SOFFIT VENT 4'-0" SOFFIT VENT 7'-0" SOFFIT VENT TRUSSES.

8" / 12"
9. PROVIDE 3" CONTINUOUS ALUMINUM SOFFIT VENTS. VENTS MUST PROVIDE
12.7 SQ.IN. OF OPEN AREA PER LINEAR FOOT MINIMUM.
8" / 12" 8" / 12" 10. INSULATION BAFFLES SHALL BE INSTALLED IN SUCH A MANNER AS TO RESTRICT
DRAFTSTOPPING; TYP. INSULATION FROM BLOCKING THE NATURAL VENTILATION OF THE ROOF.
11. PROVIDE KICK-OUT FLASHING WHERE ROOF INTERSECTS SIDEWALL.

8" / 12"
12. PROVIDE 5" PREFINISHED ALUMINUM OGEE STYLE GUTTERS, TYP. WITH 5"

8" / 12"
PREFINISHED ALUMINUM ROUND DOWNSPOUTS. QUANTITY AND LOCATION TO BE
DESIGN-BUILD. DOWNSPOUTS SHOWN IN PLAN ARE FOR REFERENCE ONLY.

10" / 12"
D.S. 10" / 12"
D.S.
ROOF FLASHING NOTES

4" / 12"
AREA C-1 AREA C-5 AREA C-1 AREA C-6
AREA C-2 AREA C-3 1. PROVIDE 'D STYLE' METAL DRIP EDGE (COLOR TO MATCH FASCIA) AT ALL ROOF
EAVES AND RAKES - PER IBC 1507.2.9.3

20'-0" SOFFIT VENT


2. PROVIDE A MULTI-STEP FLASHING SYSTEM AT ALL WALL/ROOF INTERSECTIONS

25'-0" RIDGE VENT


D.S.

20'-0" SOFFIT VENT


30'-0" RIDGE VENT
(EXAMPLE - CHEEK WALLS, CHIMNEYS, DORMERS, ETC)
4
______________________ 3. EXTEND EAVE SELF-ADHERING WATERPROOFING UNDERLAYMENT A MINIMUM OF
A3.30 24" UP THE ROOF SLOPE BEYOND THE INTERIOR FACE OF EXTERIOR WALL.
68'-10"

68'-10"
70'-10"

70'-10"
10" / 12"
E23
E20
%8,/',1*7<3(&%/'*6  10" / 12" E23 4.
5.
'WEATHER LAP' METAL FLASHING JOINTS A MINIMUM OF 2"
LAP SELF-ADHERING WATERPROOFING PIECES A MINIMUM OF 6".

727$/HD$77,&$&&(66
3 8'-0" RIDGE VENT 24'-0" RIDGE VENT 9 1/2" 24'-0" RIDGE VENT 1'-9 1/8"
8'-0" RIDGE VENT 6. ANY ROOFS WITH SLOPES BETWEEN 2/12 AND 4/12 ARE TO BE COMPLETELY
______________________
UNDERLAIDS WITH SELF-ADHERING WATERPROOFING UNDERLAYMENT.
A3.30 3060 Peachtree Rd. N.W.
7. APRON FLASHING AT FRONT CORNERS OF WALL/ROOF INTERFACES ARE TO BE
SHOP MADE, RIVETED, AND SEALED Suite 600

4" / 12"
8. WHERE BOTTOM OF DORMER WINDOWS ARE LESS THAN 6" ABOVE THE ROOF,
Atlanta, GA 30305
WINDOWS ARE TO HAVE PAN / APRON FLASHING.
9. PROVIDE MEMBRANE COUNTER FLASHING AT ALL METAL FLASHING CONDITIONS.
10. PROVIDE 72" WIDE SELF-ADHERING WATERPROOFING UNDERLAYMENT FROM T 404 365 7600
EDGE OF ROOF UP THE VALLEY FOR A MINIMUM OF 10' IN SHADED AND NORTH
D.S. ROOF LOCATIONS.
D.S.
www.nilesbolton.com

8" / 12"
ATTIC ACCESS PANELS; TYP.
8" / 12"

ROOF LEGEND No. Description


GMP SET
Date
01/16/23
CONSTRUCTION SET 2/17/23 1
8" / 12"
8" / 12"

8" / 12"
8" / 12" RIDGE VENT (EXHAUST) PROVIDING 18 S.I. PER LINEAR FOOT 1 REVISION 1 5/1/23
8" / 12"
8" / 12" NET FREE AREA MIN. SEE DETAIL 1/A4.37 2 REVISION 2 06/23/23

8" / 12"
8" / 12"

3 REVISION 3 08/02/23
7'-0" SOFFIT VENT 4'-0" SOFFIT VENT 24'-6" SOFFIT VENT 24'-6" SOFFIT VENT 4'-0" SOFFIT VENT 7'-0" SOFFIT VENT OFF-RIDGE VENT (EXHAUST) PROVIDING 150 S.I. NET FREE
1'-0 3/4"

1'-0 3/4"
ORV
16'-0" SOFFIT VENT AREA MIN. SEE DETAIL 8/A4.37
16'-0" SOFFIT VENT

D.S. D.S.
SOFFIT VENT (INTAKE) PROVIDING 12.7 S.I. PER SF NET FREE
AREA MIN.
5" D.S. 5" D.S. 23'-6" D.S. 23'-6" D.S.
D.S. E23 D.S. D.S. 5"
5"
OUTSIDE FACE OF STUD D.S. 4" DIA. PREFINISHED ALUMINUM
1'-0" 135'-11 1/2" 1'-0"
BELOW, TYPICAL. DOWNSPOUT LOCATION
138'-0 1/2" 5" PREFINISHED ALUMINUM
GUTTER
2
2
______________________ X:XX DIRECTION OF ROOF SLOPE-
A3.30 SEE GENERAL NOTES

OUTSIDE FACE OF STUD BELOW


This drawing, as an instrument of service, is and shall
remain the property of the Architects and shall not
1-HOUR RATED ATTIC DRAFTSTOPPING PER WINDER, GEORGIA be reproduced, published or used in any way without
CODE OF ORDINANCES SEC 9-61. SEE 6/A7.30 FOR DETAILS. the permission of the Architect.

DRAFTSTOPPING DOOR, SEE DETAILS 11/A7.30


2
1 ROOF PLAN- BUILDING C
4'-0" WIDE 5/8" PLYWOOD WALKWAY, INSTALL OVER RAISED
A1.33 1/8" = 1'-0"
BOTTOM CHORD OF TRUSS IN CORRIDORS; SEE DETAIL 17/A7.30

THE GATEWAY AT UNIVERSITY APARTMENTS


1-HOUR RATED ATTIC ACCESS HATCH,FIELD VERIFY
LOCATION, SEE DETAIL 11/A7.30

ICE AND WATER SHIELD


SEE NOTE 2 ON THIS PAGE

PROVIDE CRICKET AT CORNERS AS NEEDED.

0 EXCHANGE BOULEVARD

TPA RESIDENTIAL GROUP


WINDER, GEORGA 30620
AIR HANDLING UNIT

2
3

NATURAL VENTILATION CALCULATIONS ROOF AREA PLAN ALL BUILDINGS OR INFORMATION SHOWN OR REFERENCED
OTHER THAN WHAT IS INDICATED ON THE ARCHITECTURAL
COVER SHEET IS FOR REFERENCE ONLY

1B 2B 3B

4C 5A 6B 7A
CODE- NATURAL VENTILATION ATTIC/ROOF 1/300 - BLDG TYPE C

VENTILATION
CLUB 8C 9B
WT REQUIRED VENTILATION PROVIDED GRAND TOTALS 10A

SOFFIT RIDGE AREA C-2 AREA C-3


% OF VENT
TOTAL REQ. SOFFIT VENT RIDGE VENT # OFF OFF RIDGE/SIDE AREA AT 3'-0" TOTAL VENT 1,721 1,721
11A 12A
VENT: AREA (SF) x SOFFIT AREA (12.7 SI/LF RIDGE AREA (18 RIDGE/SIDE WALL VENT AREA BELOW RIDGE PROVIDED
NAME AREA (SF) 1/300 x 144 (SI) LENGTH (FT) NFA) LENGTH (FT) SI/LF NFA) WALL VENTS (144 SI) AREA (SI) CHECK Comments AREA C-5
AREA C-1 AREA C-4 ALL BUILDINGS OTHER THAN WHAT IS SHOWN

2,114 758 AREA C-6 2,111


ON THE COVER SHEET FOR REFERENCE ONLY

751
AREA C-1 2723.75 SF 1307 in² 66'-0" 838 in² 30'-0" 540 in² 0 0 in² 39% 1378 in² 1 BLDG C SHEET TITLE:
AREA C-2 2172.92 SF 1043 in² 49'-0" 622 in² 24'-0" 432 in² 0 0 in² 41% 1054 in² 1 BLDG C
AREA C-3 2172.92 SF 1043 in² 49'-0" 622 in² 24'-0" 432 in² 0 0 in² 41% 1054 in² 1 BLDG C
1 ROOF PLAN-
BUILDING TYPE C

RELEASED FOR CONSTRUCTION


AREA C-4 2723.71 SF 1307 in² 66'-0" 838 in² 30'-0" 540 in² 0 0 in² 39% 1378 in² 1 BLDG C
AREA C-5 757.78 SF 364 in² 8'-0" 102 in² 8'-0" 144 in² 1 144 in² 74% 390 in² 1 BLDG C
AREA C-6 751.34 SF 361 in² 8'-0" 102 in² 8'-0" 144 in² 1 144 in² 74% 390 in² 1 BLDG C TYPICAL
SHEET NUMBER:

NOTE: SEE ELEVATIONS FOR GABLE VENT LOCATIONS.

BASIS OF DESIGN PLUMBING CALCULATIONS FOR DOWNSPOUTS:


1
A1.33
PER 2018 IPC SECTION 1106.1 THE 100 YEAR HOURLY RAINFALL RATE IS 3.5". 2 AREA PLAN- ATTIC NATURAL VENTILATION PLAN - BLDG TYPE C PROJECT TRUE
PER 2018 IPC SECTION 1106.3 THE VERTICAL LEADER SIZING BASIS OF DESIGN IS 3 1/2"x4", WITH A 192 GPM CAPACITY. NORTH NORTH
A1.33 1" = 20'-0"
192 GPM/.0364 (GPM PER 1 SF WITH A RAINFALL RATE OF 3.5 INCHES PER HOUR) = 5,275 SF COVERAGE PER DOWNSPOUT. 02/17/23
RCP GENERAL NOTES
1. CEILINGS ARE PART OF A RATED FLOOR/CEILING ASSEMBLY. SEE AREAS TO RECEIVE 14. LIGHTING CONTROL COVER PLATES SHALL BE WHITE AT GWB CEILINGS, SOFFITS AND
CEILING UNLESS NOTED OTHERWISE. CEILING MOUNTED FABRIC WRAPPED PANEL LOCATIONS, U.N.O.

2. SEE ELECTRICAL DRAWINGS FOR ALL SMOKE AND HEAT DETECTOR LOCATIONS AND 15. ALL LIGHTING TO BE 3500K COLOR TEMPERATURE.
EMERGENCY EGRESS LIGHTING.
16. CEILING MOUNTED ELECTRICAL DEVICES SHALL BEAR UL LABEL AND FREE OF DEFECTS.
3. ALL FIXTURES, INTERIOR AND EXTERIOR, TO BE BUG RESISTANT.
17. SUBSTITUTIONS SHALL NOT BE MADE WITHOUT WRITTEN APPROVAL BY OWNER. THESE
4. ALL FIXTURES TO BE EXTERIOR FIXTURES. SHALL BE PROVIDED TO RECEIVE THE ARCHITECT'S APPROVAL IN REGARDS TO CUT SHEETS
AND SHOP DRAWINGS SUBMITTED TO THE ARCHITECT FOR APPROVAL.
PROJECT # : 122154
5. ALL FIXTURES WITHOUT DIMENSIONAL NOTATION ARE TO BE EQUALLY SPACED WITHIN
THE ROOM BASED ON THE NUMBER OF INDICATED FIXTURES. 18. DIMENSIONS OF FIXTURES, DEVICES, ETC. ARE TO CENTERLINE OF FIXTURE, U.O.N.
DRAWN BY: Author
19. ALL EXPOSED OPEN TO STRUCTURE, MECHANICAL, DUCTWORK/GRILLES, SPRINKER
6. SEE REFLECTED CEILING PLAN FOR CEILING FINISHES. ALL SOFFITS/DRYWALL AND CHECKED BY: Checker
EXPOSED CEILING PAINT TO BE P-03 FLAT U.O.N. PIPES, HANGERS, CABLE TRAYS, CEILING SUPPORTS, ETC TO BE PAINTED P-1, U.O.N.

6. FIXTURE TYPES ARE AS NOTED ON LIGHTING SCHEDULE/SPECIFICATIONS. 20. CONTRACTOR TO COORDINATE FIRE SPRINKLER AND FIRE ALARM DEVICE LOCATIONS
WITH ARCHITECT PRIOR TO SUBMITTING FOR PERMIT. WHERE APPLICABLE CENTER
7. CONTRACTOR TO LOCATE SPRINKLERS AS REQUIRED FOR COMPLIANCE WITH ALL SPRINKLER HEADS IN CEILING TILE. ALIGN SPEAKERS, SMOKE DETECTORS, MOTION SENSORS
APPLICABLE FEDERAL, STATE, AND LOCAL BUILDING/FIRE CODES. AND RELATED CEILING MOUNTED DEVICES WITH LIGHTING FIXTURE CENTERLINES AND
CENTER OF CEILING TILE. LOCATE HVAC DIFFUSERS IN GWB CEILINGS AS SHOW ON
8. FLUSH SPRINKLER HEAD COVERS ARE TO HAVE FACTORY PAINTED WHITE CAPS, U.O.N. ARCHITECTURAL RCP.
REFER TO RCP NOTES FOR CUSTOM CAP COLORS AND LOCATION. LOCATE SPRINKLER HEAD
IN CENTER OF TILE, AS APPLICABLE. 21. CEILING GRID TO BE CENTERED IN ROOMS AS SHOWN ON PLAN, TYP.

9. THE CONTRACTOR IS RESPONSIBLE FOR COMPLIANCE WITH DRAWINGS' PLACEMENT OF 22. ALL ACT CEILINGS TO BE 9'-0", U.N.O.
ALL DUCTWORK, PLUMBING LINES, AND SPRINKLER LINES PRIOR TO INSTALLATION OF LIGHT
FIXTURES AS SHOWN ON CONSTRUCTION DOCUMENTS. CONTRACTOR WILL NOTIFY THE 23. ALL GYP CEILINGS TO BE 9'-0", U.N.O.
DESIGNER IMMEDIATELY UPON DISCOVERY OF ANY FIELD CONDITIONS, WHICH WILL PROHIBIT
INSTALLATION OF FIXTURES AS SHOWN OR REQUIRED CHANGE TO HEIGHT OF CEILING. 24. REFER TO ENGINEERING DRAWINGS FOR SWITCHING, CIRCUIT, LOADS, HVAC
REQUIREMENTS AND FIREPLACE VENTILATION DETAILS.
10. IF REQUIRED PROVIDE FLUSH DRYWALL TYPE ACCESS PANEL W/ CONCEALED FRAME AT
ALL NON RATED LOCATIONS. PAINT TO MATCH THE SURFACES ON WHICH THEY OCCUR. 25. ALL SWITCH COVERPLATES TO BE LOCATED PER PROVIDED DETAILS. TWO OR MORE
ADJACENT SWITCHES ARE TO BE GANGED WITH A COMMON FACEPLATE, IF THEY CANNOT BE
11. ALL GYPSUM BOARD CEILING SURFACES TO BE PAINTED FLAT FINISH INCLUDING GANGED THEY SHALL BE INSTALLED WITH MINIMUM DISTANCE BETWEEN DEVICES. FINISH TO
DIFFUSERS AND GRILLS, UNLESS NOTED OTHERWISE. BE WHITE, UNLESS NOTED OTHERWISE.

12.SUBMIT CUTSHEETS OF ALL LIGHTING FIXTURES FOR DESIGNER APPROVAL PRIOR TO 26. COORDINATE WITH DESIGNER SIZE AND LOCATION OF ALL ACCESS PANELS REQUIRED FOR
ORDER PLACEMENT/INSTALLATION. A NON-ACCESSIBLE CEILING.
1
______________________

A3.03 3060 Peachtree Rd. N.W.


13. LOCATE EXIT SIGNS VERTICALLY ABOVE THE FINISH FLOOR TO INSURE SIGHT LINES ARE 27. ALL GWB CEILINGS TO HAVE A LEVEL 5 FINISH. COORDINATE WITH DESIGNER IF
18'-8" 18'-8" EXPANSION JOINTS ARE NEEDED SO THEY CAN BE INCORPORATED INTO THE DESIGN. Suite 600
NOT BLOCKED BY LIGHT FIXTURES, BEAMS, SOFFITS, DROPPED CEILINGS, DUCTWORK,
CONDUIT, PIPING AND RELATED OVERHEAD WORK. Atlanta, GA 30305
28. COORDINATE WITH DESIGNER IN FIELD EXACT LOCATION AND MOUNTING HEIGHT OF
PENDANT LIGHTING.
T 404 365 7600
29. PROVIDE 2" WHITE LINEAR CEILING MOUNTED SLOT DIFFUSERS/RETURNS THROUGHOUT
AMENITY AREAS. SEE ENGINEER'S DRAWINGS FOR EXACT SPECIFICATION, SIZE AND www.nilesbolton.com
LOCATION. 2" MIN.

No. Description Date


CONSTRUCTION SET 2/17/23 1
B ADDENDUM 2 3/15/23

10'-11"
1 REVISION 1 5/1/23
54'-0" 2 REVISION 2 06/23/23
FIBER CEMENT BULKHEAD (TYPICAL) 3 REVISION 3 08/02/23
E24 E20 E23 E24 5 IFC RECONCILIATION 9/20/23
E07
6 OWNER CHANGES 10/25/23
9 ASI 03 02/15/24
9
RCP SYMBOL LEGEND
LIGHT FIXTURE SCHEDULE PROVIDED ON SHEET A2.00 FOR CLUBHOUSE / BUILDING 100.

ATTIC ACCESS PANEL

10" / 12"
CEILING MOUNTED DOUBLE TIER CHANDELIER LIGHT FIXTURE
0$,/3$9,/,21HD$77,&$&&(66
17'-0"

19'-0"
This drawing, as an instrument of service, is and shall
remain the property of the Architects and shall not
14'-0" 3'-0"

10" / 12"
be reproduced, published or used in any way without
CEILING FAN the permission of the Architect.
3'-0" 14'-0"
RIDGE VENT
RIDGE VENT

PENDANT LIGHTS

THE GATEWAY AT UNIVERSITY APARTMENTS


SURFACE MOUNT DOWNLIGHT FIXTURE
2'-0"

ROUND SUSPENDED PENDANT


12'-0" E24 42'-0" E24

WALL MOUNTED HORIZONTAL

HIGHPOINT DEVELOPMENT
0 EXCHANGE BOULEVARD
WINDER, GEORGIA 30620
2 ROOF PLAN- MAIL PAVILION LINEAR MOUNT
A1.81 1/4" = 1'-0"

LINEAR MOUNT

BL02 BL02 BL02 BL02 BL02

B05

CL CL CL CL
2 5/8" 7'-0 1/2" 6'-5" 7'-4" 4'-6 1/8"

CL CL 3
5'-9 1/4" 7'-9 1/4" EQ EQ
2
EQ

1'-9"

L01 L01 L01 L01


EQ

POOL EQ
ATTIC ACCESS DOOR EQUIPMENT
CL

ALL BUILDINGS OR INFORMATION SHOWN OR REFERENCED


4'-0" 9'-0" OTHER THAN WHAT IS INDICATED ON THE ARCHITECTURAL
MAIL & COVER SHEET IS FOR REFERENCE ONLY

PACKAGE PARCEL
6'-0 1/2"

ROOM B04 B04


CL

CL

GYP 9'-0" 1B 2B 3B

L01 L01 L01 L01


4C 5A 6B 7A
Sim
CL
EQ

EQ

10
___________________________________
__________________________
EQ

A7.30
4'-3 3/4"

CLUB 8C 9B 10A

11A 12A

HATCHED AREA FOR REFERENCE ONLY


BL02 BL02 BL02
SHEET TITLE:
2 5/8" 7'-0 1/2" 6'-5" 7'-4" 4'-6 1/8"
MAIL PAVILION
PLANS AND

RELEASED FOR CONSTRUCTION


CL CL CL CL

ELEVATIONS
SHEET NUMBER:

1
A1.81
RCP-MAIL PAVILION - LEVEL 1
1/4" = 1'-0"
A1.81
02/17/23
CODE- NATURAL VENTILATION ATTIC/ROOF 1/300 - B100
ROOF PLAN GENERAL NOTES
VENTILATION
ROOF AREA REQUIRED VENTILATION PROVIDED GRAND TOTALS
SOFFIT RIDGE 1. SEE ROOF PLANS FOR ROOF SLOPES
% OF VENT
2. PROVIDE ICE AND WATER SHEILD FLASHING WHERE ROOF PITCH CHANGES, WHERE
TOTAL REQ. SOFFIT VENT RIDGE VENT # OFF OFF RIDGE/SIDE AREA AT 3'-0" TOTAL VENT
ROOF INTERSECTS VERTICAL SURFACES, AT ALL ROOF EAVES, AND PER ROOFING
VENT: AREA (SF) x SOFFIT AREA (5 SI/LF RIDGE AREA (18 SI/LF RIDGE/SIDE WALL VENT AREA BELOW RIDGE PROVIDED
MANUFACTURER'S WRITTEN INSTRUCTIONS.
NAME AREA (SF) 1/300 x 144 (SI) LENGTH (FT) NFA) LENGTH (FT) NFA) WALL VENTS (144 SI) AREA (SI)
3. PROVIDE HIGH-TEMPERATURE UNDERLAYMENT FOR ENTIRETY OF ALL METAL
ROOF AREAS.
100-AREA 1 1974.47 SF 948 in² 106'-0" 530 in² 30'-0" 540 in² 3 432 in² 65% 1502 in² 4. PROVIDED GABLE END TRUSSES AT ALL GABLE END CONDITIONS AND AT ALL
100-AREA 2 2543.62 SF 1221 in² 152'-0" 760 in² 30'-0" 540 in² 4 576 in² 59% 1876 in² VERTICAL DRAFTSTOP LOCATIONS ABOVE AND IN LINE WITH DEMISING WALLS.
100-AREA 3 2042.83 SF 981 in² 112'-0" 560 in² 30'-0" 540 in² 3 432 in² 63% 1532 in² 5. ROOF SHINGLES TO BE MINIMUM CLASS B. VERIFY SHINGLE INSTALLATION
100-AREA 4 708.12 SF 340 in² 88'-0" 440 in² 0" 0 in² 0 0 in² 0% 440 in² REQUIREMENTS WITH CHINGLE MANUFACTURER'S WRITTEN INSTRUCTIONS FOR
100-AREA 5 675.62 SF 324 in² 72'-0" 360 in² 0" 0 in² 0 0 in² 0% 360 in² PRODUCT TYPE AND APPLICATIONS.
6. ALL ROOF SHINGLES ARE TO OVERHANG DROP EDGES AT EAVES AND RAKES A PROJECT # : 122154
MINIMUM OF 1/2".
1 NOTE: SEE RCP PLANS ON A2.00A THRU A2.00C FOR ADDITIONAL REFERENCES FOR SOFFIT VENT LOCATIONS AND LENGTHS.
______________________

A3.00 SEE ELEVATIONS FOR GABLE VENT LOCATIONS.


7. PROVIDED 22"x30" RATED ATTIC ACCESS HATCH, 1-HOUR, WITH LOCK. FIELD DRAWN BY: KU, CS
VERIFY LOCATIONS; SEE PLANS FOR BASIS OF DESIGN.
BASIS OF DESIGN PLUMBING CALCULATIONS FOR DOWNSPOUTS:
8. DIMENSIONS SHOWN ON ROOF PLAN ARE FROM FACE OF STUDS TO ENDS OF ROOF CHECKED BY: JS
TRUSSES.
PER 2018 IPC SECTION 1106.1 THE 100 YEAR HOURLY RAINFALL RATE IS 3.5".
9. PROVIDE 3" CONTINUOUS ALUMINUM SOFFIT VENTS. VENTS MUST PROVIDE
PER 2018 IPC SECTION 1106.3 THE VERTICAL LEADER SIZING BASIS OF DESIGN IS 3 1/2"x4", WITH A 192 GPM CAPACITY.
12.7 SQ.IN. OF OPEN AREA PER LINEAR FOOT MINIMUM.
192 GPM/.0364 (GPM PER 1 SF WITH A RAINFALL RATE OF 3.5 INCHES PER HOUR) = 5,275 SF COVERAGE PER DOWNSPOUT.
10. INSULATION BAFFLES SHALL BE INSTALLED IN SUCH A MANNER AS TO RESTRICT
INSULATION FROM BLOCKING THE NATURAL VENTILATION OF THE ROOF.
11. PROVIDE KICK-OUT FLASHING WHERE ROOF INTERSECTS SIDEWALL.
12. PROVIDE 5" PREFINISHED ALUMINUM OGEE STYLE GUTTERS, TYP. WITH 5"
PREFINISHED ALUMINUM ROUND DOWNSPOUTS. QUANTITY AND LOCATION TO BE
DESIGN-BUILD. DOWNSPOUTS SHOWN IN PLAN ARE FOR REFERENCE ONLY.
55'-8 5/8" 18'-8" 52'-8 3/4"

A3.02
______________________ 3'-0" 7'-4" 7'-10 1/4" 20'-0"
ASPHALT SHINGLE ROOF
ASPHALT SHINGLE ROOF
14'-0" 10'-2 5/8" 8'-0" 1'-2 1/4" ROOF FLASHING NOTES
2
SOFFIT VENT SOFFIT VENT SOFFIT VENT SOFFIT VENT
1. PROVIDE 'D STYLE' METAL DRIP EDGE (COLOR TO MATCH FASCIA) AT ALL ROOF
EAVES AND RAKES - PER IBC 1507.2.9.3

6'-2 1/8"
2. PROVIDE A MULTI-STEP FLASHING SYSTEM AT ALL WALL/ROOF INTERSECTIONS

5'-8"
(EXAMPLE - CHEEK WALLS, CHIMNEYS, DORMERS, ETC)
3. EXTEND EAVE SELF-ADHERING WATERPROOFING UNDERLAYMENT A MINIMUM OF
34'-0 7/8" 24" UP THE ROOF SLOPE BEYOND THE INTERIOR FACE OF EXTERIOR WALL.

8" / 12"

8" / 12"

SOFFIT VENT
8" / 12"

8" / 12"
4. 'WEATHER LAP' METAL FLASHING JOINTS A MINIMUM OF 2"

7'-0"
5. LAP SELF-ADHERING WATERPROOFING PIECES A MINIMUM OF 6".
3
______________________
6. ANY ROOFS WITH SLOPES BETWEEN 2/12 AND 4/12 ARE TO BE COMPLETELY
A3.02 UNDERLAIDS WITH SELF-ADHERING WATERPROOFING UNDERLAYMENT.
3'-5 3/4" 7'-0" 3'-6 1/2" 2'-0" 10'-0" 10'-0" 10'-9" 10'-0" 2'-0" 2'-0 3/16" 10'-0" 9'-4 3/8" 10'-0" 10'-0" 1'-11 13/16" 3060 Peachtree Rd. N.W.
7. APRON FLASHING AT FRONT CORNERS OF WALL/ROOF INTERFACES ARE TO BE
12'-11 3/8"
SOFFIT VENT RIDGE VENT RIDGE VENT RIDGE VENT RIDGE VENT RIDGE VENT RIDGE VENT SHOP MADE, RIVETED, AND SEALED Suite 600
8. WHERE BOTTOM OF DORMER WINDOWS ARE LESS THAN 6" ABOVE THE ROOF,
CENTER D.S. ON SOFFIT VENT Atlanta, GA 30305
WINDOWS ARE TO HAVE PAN / APRON FLASHING.

25'-11 3/4"
STRUCTURAL POST; ATTIC DRAFTSTOP

36'-8"

36'-8"
4 9. PROVIDE MEMBRANE COUNTER FLASHING AT ALL METAL FLASHING CONDITIONS.
SEE ELEVATIONS;

1/4":12" MIN
______________________

T 404 365 7600


4'-1 1/8"

10. PROVIDE 72" WIDE SELF-ADHERING WATERPROOFING UNDERLAYMENT FROM

4'-2 1/4"
4'-6 3/8"

A3.02

2'-0"
TYPICAL AT POSTS AND D.S.
1'-4 1/4"

EDGE OF ROOF UP THE VALLEY FOR A MINIMUM OF 10' IN SHADED AND NORTH
D.S. AREA A-3 AREA A-1 ROOF LOCATIONS.
www.nilesbolton.com

8" / 12"
SOFFIT VENT

8" / 12"

8" / 12"
8" / 12"

8" / 12"

SOFFIT VENT
8'-0"
7'-0"

RIDGE VENT

8" / 12" 8" / 12"


ROOF LEGEND
19'-7 3/4"

No. Description Date

7'-0"
12'-10 1/4"
10'-0"

RIDGE VENT
&/8%+286(HD$77,&$&&(66 GMP SET 01/16/23
3'-0" 7'-4" 7'-10 1/4" 20'-0" CONSTRUCTION SET 2/17/23
RIDGE VENT (EXHAUST) PROVIDING 18 S.I. PER LINEAR FOOT B ADDENDUM 2 3/15/23

8" / 12"
SOFFIT VENT SOFFIT VENT

4'-6 1/8"
NET FREE AREA MIN. SEE DETAIL 1/A4.37 1 REVISION 1 5/1/23

5'-8"
2 REVISION 2 06/23/23
TPO ROOF
OFF-RIDGE VENT (EXHAUST) PROVIDING 150 S.I. NET FREE
ORV
AREA MIN. SEE DETAIL 8/A4.37

2" / 12"
14'-0" 10'-2 5/8" 8'-0" 1'-2 1/4"
2'-0"
5'-2 3/8"

5'-2 3/8"

AREA A-4 ATTIC DRAFTSTOP ATTIC DRAFTSTOP


D.S. SOFFIT VENT SOFFIT VENT
SOFFIT VENT (INTAKE) PROVIDING 12.7 S.I. PER SF NET FREE
AREA MIN.
RIDGE VENT
10'-0"

D.S. D.S.
49'-8 5/8"
D.S. 4" DIA. PREFINISHED ALUMINUM
SEE RCP FOR 3'-5 1/2" DOWNSPOUT LOCATION
SOFFIT VENT

SOFFIT VENT

SOFFIT VENT ASPHALT SHINGLE ROOF - FULL ICE AND WATER


14'-0"

14'-0"

DIMENSIONS IN SHIELD REQUIRED BENEATH SHINGLES 5" PREFINISHED ALUMINUM


D.S. GUTTER
THIS ZONE 2" / 12"
8" / 12" 8" / 12" X:XX DIRECTION OF ROOF SLOPE-
71'-10 7/8"
35'-2 3/8"

SEE GENERAL NOTES


30'-5 1/8"

AREA A-5
AREA A-2 OUTSIDE FACE OF STUD BELOW
2 This drawing, as an instrument of service, is and shall
______________________
1 remain the property of the Architects and shall not
A3.01 ______________________ 1-HOUR RATED ATTIC DRAFTSTOPPING PER WINDER, GEORGIA be reproduced, published or used in any way without
A3.01 CODE OF ORDINANCES SEC 9-61. SEE 6/A7.30 FOR DETAILS. the permission of the Architect.
2
______________________
RIDGE VENT

A3.00
DRAFTSTOPPING DOOR, SEE DETAILS 11/A7.30
10'-0"

ASPHALT SHINGLE ROOF - FULL


ICE AND WATER SHIELD REQUIRED
UNDER SHINGLES
4'-0" WIDE 5/8" PLYWOOD WALKWAY, INSTALL OVER RAISED
BOTTOM CHORD OF TRUSS IN CORRIDORS; SEE DETAIL 17/A7.30
D.S. D.S.
2'-0"
3'-1"

3'-1"

THE GATEWAY AT UNIVERSITY APARTMENTS


CENTER D.S. ON
STRUCTURAL POST; 1-HOUR RATED ATTIC ACCESS HATCH,FIELD VERIFY
SEE ELEVATIONS; TYPICAL LOCATION, SEE DETAIL 11/A7.30
AT POSTS AND D.S.
SOFFIT VENT

SOFFIT VENT
RIDGE VENT
19'-7 3/4"

14'-0"

14'-0"

ICE AND WATER SHIELD


10'-0"

8" / 12" 8" / 12" SEE NOTE 2 ON THIS PAGE

PROVIDE CRICKET AT CORNERS AS NEEDED.


1'-2 3/4"

0 EXCHANGE BOULEVARD

TPA RESIDENTIAL GROUP


WINDER, GEORGA 30620
3'-6 3/4"

3'-6 3/4"
5'-3"

D.S. ASPHALT SHINGLE ROOF

ATTIC ACCESS AIR HANDLING UNIT


9'-5 1/8" 34'-0 7/8" PANEL; TYP 9'-3 1/8"

1
______________________

A3.02

1B 2B 3B

4C 5A 6B 7A

CLUB 8C 9B 10A

11A 12A

HATCHED AREA FOR REFERENCE ONLY

SHEET TITLE:

ROOF PLAN-

RELEASED FOR CONSTRUCTION


1
CLUBHOUSE
ROOF PLAN- BUILDING 100
A1.01 1/8" = 1'-0"
SHEET NUMBER:

CLUBHOUSE REVISIONS INCORPORATED PER OWNER REQUEST.


SIZE OF CLUBHOUSE REDUCED.
A1.01
02/17/23