A1.22 - ROOF PLAN - BUILDING TYPE B Rev.1 Markup
A1.22 - ROOF PLAN - BUILDING TYPE B Rev.1 Markup
A3.20 2. PROVIDE ICE AND WATER SHEILD FLASHING WHERE ROOF PITCH CHANGES, WHERE
ROOF INTERSECTS VERTICAL SURFACES, AT ALL ROOF EAVES, AND PER ROOFING
MANUFACTURER'S WRITTEN INSTRUCTIONS.
145'-0" 3. PROVIDE HIGH-TEMPERATURE UNDERLAYMENT FOR ENTIRETY OF ALL METAL
ROOF AREAS.
2'-0" O.H. 141'-0" 2'-0" O.H.
4. PROVIDED GABLE END TRUSSES AT ALL GABLE END CONDITIONS AND AT ALL
4" 4" VERTICAL DRAFTSTOP LOCATIONS ABOVE AND IN LINE WITH DEMISING WALLS.
5. ROOF SHINGLES TO BE MINIMUM CLASS B. VERIFY SHINGLE INSTALLATION
D.S. 12'-1 1/4" 11'-10 3/4" 11'-10 3/4" 12'-1 1/4" D.S. REQUIREMENTS WITH CHINGLE MANUFACTURER'S WRITTEN INSTRUCTIONS FOR
PRODUCT TYPE AND APPLICATIONS.
6. ALL ROOF SHINGLES ARE TO OVERHANG DROP EDGES AT EAVES AND RAKES A PROJECT # : 122154
15'-0" SOFFIT VENT D.S. D.S. E23 D.S. 15'-0" SOFFIT VENT MINIMUM OF 1/2".
3'-0" O.H.
7. PROVIDED 22"x30" RATED ATTIC ACCESS HATCH, 1-HOUR, WITH LOCK. FIELD DRAWN BY: KU, RB, PG
3'-0" O.H.
VERIFY LOCATIONS; SEE PLANS FOR BASIS OF DESIGN.
JS
10'-10 7/8"
8. DIMENSIONS SHOWN ON ROOF PLAN ARE FROM FACE OF STUDS TO ENDS OF ROOF CHECKED BY:
6'-0" SOFFIT VENT 18'-0" SOFFIT VENT 18'-0" SOFFIT VENT 6'-0" SOFFIT VENT
10'-6"
TRUSSES.
8" / 12"
8" / 12"
9. PROVIDE 3" CONTINUOUS ALUMINUM SOFFIT VENTS. VENTS MUST PROVIDE
12.7 SQ.IN. OF OPEN AREA PER LINEAR FOOT MINIMUM.
10. INSULATION BAFFLES SHALL BE INSTALLED IN SUCH A MANNER AS TO RESTRICT
D.S.
INSULATION FROM BLOCKING THE NATURAL VENTILATION OF THE ROOF.
11. PROVIDE KICK-OUT FLASHING WHERE ROOF INTERSECTS SIDEWALL.
D.S.
4" / 12"
12. PROVIDE 5" PREFINISHED ALUMINUM OGEE STYLE GUTTERS, TYP. WITH 5"
11'-3 1/4"
8" / 12" 8" / 12" 2. PROVIDE A MULTI-STEP FLASHING SYSTEM AT ALL WALL/ROOF INTERSECTIONS
8" / 12" 8" / 12"
(EXAMPLE - CHEEK WALLS, CHIMNEYS, DORMERS, ETC)
68'-0"
68'-0"
74'-0"
3 4 4. 'WEATHER LAP' METAL FLASHING JOINTS A MINIMUM OF 2"
______________________ ______________________
11'-3 3/4"
11'-3 1/2"
7. APRON FLASHING AT FRONT CORNERS OF WALL/ROOF INTERFACES ARE TO BE 3060 Peachtree Rd. N.W.
SHOP MADE, RIVETED, AND SEALED Suite 600
8. WHERE BOTTOM OF DORMER WINDOWS ARE LESS THAN 6" ABOVE THE ROOF,
Atlanta, GA 30305
WINDOWS ARE TO HAVE PAN / APRON FLASHING.
9. PROVIDE MEMBRANE COUNTER FLASHING AT ALL METAL FLASHING CONDITIONS.
10. PROVIDE 72" WIDE SELF-ADHERING WATERPROOFING UNDERLAYMENT FROM T 404 365 7600
EDGE OF ROOF UP THE VALLEY FOR A MINIMUM OF 10' IN SHADED AND NORTH
ROOF LOCATIONS.
www.nilesbolton.com
15'-0" SOFFIT VENT
4" / 12"
DRAFTSTOPPING; TYP. GMP SET 01/16/23
CONSTRUCTION SET 2/17/23 1
D.S.
RIDGE VENT (EXHAUST) PROVIDING 18 S.I. PER LINEAR FOOT 1 REVISION 1 5/1/23
D.S.
NET FREE AREA MIN. SEE DETAIL 1/A4.37 2 REVISION 2 06/23/23
10'-10 15/16"
8" / 12"
3 REVISION 3 08/02/23
8" / 12"
10'-6"
3'-0" O.H.
AREA MIN. SEE DETAIL 8/A4.37
6'-0" SOFFIT VENT 18'-0" SOFFIT VENT 18'-0" SOFFIT VENT 6'-0" SOFFIT VENT
15'-0" SOFFIT VENT 15'-0" SOFFIT VENT
SOFFIT VENT (INTAKE) PROVIDING 12.7 S.I. PER SF NET FREE
AREA MIN.
2
______________________
OUTSIDE FACE OF STUD BELOW
A3.20 This drawing, as an instrument of service, is and shall
remain the property of the Architects and shall not
1-HOUR RATED ATTIC DRAFTSTOPPING PER WINDER, GEORGIA be reproduced, published or used in any way without
1 ROOF PLAN- BUILDING B CODE OF ORDINANCES SEC 9-61. SEE 6/A7.30 FOR DETAILS. the permission of the Architect.
2
4'-0" WIDE 5/8" PLYWOOD WALKWAY, INSTALL OVER RAISED
BOTTOM CHORD OF TRUSS IN CORRIDORS; SEE DETAIL 17/A7.30
0 EXCHANGE BOULEVARD
NATURAL VENTILATION CALCULATIONS ROOF AREA PLAN ALL BUILDINGS OR INFORMATION SHOWN OR REFERENCED
OTHER THAN WHAT IS INDICATED ON THE ARCHITECTURAL
COVER SHEET IS FOR REFERENCE ONLY
1B 2B 3B
4C 5A 6B 7A
CODE- NATURAL VENTILATION ATTIC/ROOF 1/300 - BLDG TYPE E
VENTILATION
WT REQUIRED VENTILATION PROVIDED GRAND TOTALS CLUB 8C 9B 10A
AREA B-1 2723.73 SF 1307 in² 60'-0" 762 in² 30'-0" 540 in² 1 144 in² 47% 1446 in² 1 BLDG B AREA B-5 AREA B-6 SHEET TITLE:
AREA B-2 1725.00 SF 828 in² 36'-0" 457 in² 22'-0" 396 in² 0 0 in² 46% 853 in² 1 BLDG B 577 584
AREA B-3 1725.00 SF 828 in² 36'-0" 457 in² 22'-0" 396 in² 0 0 in² 46% 853 in² 1 BLDG B
ROOF PLAN-
SHEET NUMBER:
NOTE: SEE ELEVATIONS FOR GABLE VENT LOCATIONS.
1
BASIS OF DESIGN PLUMBING CALCULATIONS FOR DOWNSPOUTS:
PER 2018 IPC SECTION 1106.1 THE 100 YEAR HOURLY RAINFALL RATE IS 3.5".
PER 2018 IPC SECTION 1106.3 THE VERTICAL LEADER SIZING BASIS OF DESIGN IS 3 1/2"x4", WITH A 192 GPM CAPACITY.
192 GPM/.0364 (GPM PER 1 SF WITH A RAINFALL RATE OF 3.5 INCHES PER HOUR) = 5,275 SF COVERAGE PER DOWNSPOUT.
A1.22
PROJECT TRUE
2 1
AREA PLAN- ATTIC NATURAL VENTILATION PLAN - BLDG TYPE B NORTH NORTH
A1.22 1" = 20'-0" 02/17/23